Section 890.1200 Water Service Sizing
IllinoisRegulations
Ask Donna
How this section applies to your facts.
Illinois Administrative Code › Title 77 PUBLIC HEALTH › CHAPTER I: DEPARTMENT OF PUBLIC HEALTH › Part 890 ILLINOIS PLUMBING CODE › Section 890.1200 Water Service Sizing
Text
Section 890
Section 890.1200 Water
Service Sizing
a) Water Service Pipe Sizing. The water service pipe from the
street main (including the tap) to the water distribution system for the
building shall be sized in accordance with Appendix A, Tables M, N, O, P and
Q. Water service pipe and fittings shall be at least ¾ inch diameter. Plastic
water pipe shall be rated at a minimum of 160 psi at 73.4°F. If flushometers or
other devices requiring a high rate of water flow are used, the water service
pipe shall be designed and installed to provide this additional flow.
b) Demand Load. The calculation of the water service demand load
for a building shall be based on the total number and types of fixtures
installed in the building, assuming the simultaneous use of such fixtures.
c) Unused sections of water service or water distribution piping
("dead ends"), where the water in the piping may become stagnant, are
prohibited. A developed length of more than 2 feet shall be considered a dead
end.