Section 890.1180 Flushing/Disinfection of Potable Water System
IllinoisRegulations
Ask Donna
How this section applies to your facts.
Illinois Administrative Code › Title 77 PUBLIC HEALTH › CHAPTER I: DEPARTMENT OF PUBLIC HEALTH › Part 890 ILLINOIS PLUMBING CODE › Section 890.1180 Flushing/Disinfection of Potable Water System
Text
Section 890
Section 890.1180
Flushing/Disinfection of Potable Water System
New or repaired potable water
systems shall be flushed or disinfected prior to use as follows:
a) Chlorinated Water Supply. If the potable water supply serving
the water supply system is chlorinated, e.g., a community water system, the
water supply system, or appropriate repaired portion, shall be flushed with
clean, potable water until no dirty water appears at the point of outlet.
b) Non-Chlorinated Water Supply. The pipe system shall be
flushed with clean, potable water until no dirty water appears at the point of
outlet.
1) The system, or part of the system, shall be filled with a
chlorine solution containing at least 50 parts per million of chlorine and
shall be valved off and allowed to stand for 24 hours, or the system, or part of
the system, shall be filled with a chlorine solution containing at least 200
parts per million of chlorine and be allowed to stand for three hours.
2) Following the required contact (standing) time, the system
shall be flushed with clean, potable water until the chlorine level in the
water discharging from the system is within acceptable limits for potable
water, i.e., generally until the water has no detectable chlorine odor.
3) To ensure that the water supplied by the water system is safe
for drinking, a bacteriological examination of a water sample taken from the
water supply system shall be secured. This examination shall be performed by a
laboratory certified in accordance with 77 Ill. Adm. Code 465. The chlorine
residual in any water sample collected for examination shall not exceed 4 parts
per million (or 4 milligrams/liter) for a reliable laboratory result. If the
examination reveals that contamination still persists in the system, the
procedure for disinfection shall be repeated.