Section 890.1170 Potable Water Supply Tanks and Auxiliary Pressure Tanks
IllinoisRegulations
Ask Donna
How this section applies to your facts.
Illinois Administrative Code › Title 77 PUBLIC HEALTH › CHAPTER I: DEPARTMENT OF PUBLIC HEALTH › Part 890 ILLINOIS PLUMBING CODE › Section 890.1170 Potable Water Supply Tanks and Auxiliary Pressure Tanks
Text
Section 890
Section 890.1170 Potable
Water Supply Tanks and Auxiliary Pressure Tanks
a) Water Pressure. When the water pressure from the public water
supply main is insufficient during periods of peak flow or due to the building
height to supply all fixtures in accordance with Section 890.1210(c), the rate
of supply shall be supplemented by a gravity tank or auxiliary pressure
(booster) system. Auxiliary pressure systems shall not substitute for adequate
sizing of water distribution piping within the building.
b) Support. All water supply tanks shall be supported in
accordance with local building codes or authorities having jurisdiction.
c) Tank Supply Inlet and Outlet. The water supply inlet to the
tank shall have a minimum air gap of at least 6 inches. The supply outlet
shall be a minimum of 4 inches above the bottom of the tank.
d) Overflow For Water Supply Tanks. Overflow pipes for gravity
tanks shall be indirectly connected to the drainage system with an air gap of
at least 6 inches. Overflow pipes shall be full sized, unrestricted and
screened with 24-mesh per inch stainless steel or bronze screen.
e) Size of Overflow. Overflow drains for gravity water supply
tanks shall have an area of at least twice the size of the supply pipe.
f) Drains. Water supply tanks shall be provided with valved
drain lines located at their lowest point and shall discharge through an
indirect waste with an air gap of twice the diameter of the drain line. The
drain line and valve shall have no restrictions and need not exceed 2 inches in
diameter.
g) Gravity and Suction Tanks. Tanks used for potable water supply
or only to supply fire-fighting equipment shall be equipped with tight,
overlapping covers that are rodent and insect proof
nd shall discharge through an
indirect waste with an air gap of twice the diameter of the drain line. The
drain line and valve shall have no restrictions and need not exceed 2 inches in
diameter.
g) Gravity and Suction Tanks. Tanks used for potable water supply
or only to supply fire-fighting equipment shall be equipped with tight,
overlapping covers that are rodent and insect proof. The tanks shall be vented
with a return bend (turned down) pipe having an area at least ½ the area of the
tank outlet pipe, and the vent opening shall be covered with a stainless steel
or bronze screen of at least 24-mesh per inch.
h) Pressure Tanks. Pressure tanks used for supplying water to
the water distribution system, or only to supply standpipes for fire equipment,
shall be equipped with a vacuum relief valve located on top of the tank. An
air inlet of this device shall be covered with a stainless steel or bronze
screen of at least 24-mesh per inch. (See Section 890.1230(f).)