Section 220.90 Low and Medium-Voltage Alternating Current Circuits

IllinoisRegulations

Ask Donna

How this section applies to your facts.

Illinois Administrative Code › Title 62 MINING › CHAPTER I: DEPARTMENT OF NATURAL RESOURCES › Part 220 SURFACE INSTALLATION HEALTH AND SAFETY › Section 220.90 Low and Medium-Voltage Alternating Current Circuits

This text was captured on Aug 14, 2026. It is a snapshot, not a live feed, so check the official code before relying on it.

Text

Section 220

Section 220.90  Low and

Medium-Voltage Alternating Current Circuits

a)         Low-voltage and medium-voltage circuits serving portable,

mobile and stationary, three (3)-phase alternating-current equipment;

protective devices.

1)         Low and medium-voltage circuits supplying power to portable or

mobile three (3)-phase alternating-current equipment shall be protected by

suitable circuit breakers of adequate interrupting capacity, which are properly

tested and maintained and equipped with devices to provide protection against

grounded phase, short circuit, and overload.

2)         Low and medium-voltage circuits supplying power to stationary

equipment shall be deenergized with the occurrence of an overload or, short

circuit, by a circuit breaker, or fuses of the correct type and capacity. Such

devices shall, in addition, on solidly grounded or resistance grounded systems

deenergize the circuit on the occurrence of a phase-to-ground fault.

Ungrounded low and medium-voltage circuits supplying power to stationary

equipment shall be provided with ground detectors to indicate visually the

presence of a grounded on any phase.  Other no less effective devices may be

approved by an authorized representative of the Department.

b)         Testing, examination, and maintenance of circuit breaker;

procedures.

1)         Circuit breakers and their auxiliary devices shall be tested

and examined at least once each month by a qualified person.

2)         In performing such tests, the circuit breaker auxiliaries or

control circuits shall be actuated in any manner which causes the circuit

breaker to open.  In the absence of auxiliaries or control circuits, the

breaker will be operated manually.  All components of the circuit breaker and

its auxiliary devices shall be visually examined and such repairs or

adjustments as are indicated by such tests and examinations shall be carried out

immediately.

c)         Testing, examination, and maintenance of circuit breakers;

record

uit

breaker to open.  In the absence of auxiliaries or control circuits, the

breaker will be operated manually.  All components of the circuit breaker and

its auxiliary devices shall be visually examined and such repairs or

adjustments as are indicated by such tests and examinations shall be carried out

immediately.

c)         Testing, examination, and maintenance of circuit breakers;

record.

The operator shall maintain a written record of each test,

examination, repair, or adjustment of all circuit breakers protecting low and

medium-voltage circuits serving three (3)-phase alternating-current equipment

and such record shall be kept in an approved book.

d)         Low-voltage and medium-voltage three (3)-phase circuits;

system grounding.

1)         Low-voltage and medium-voltage circuits supplying power to

portable or mobile three (3)-phase alternating-current equipment shall contain:

A)        Either a direct or derived neutral grounded through a suitable

resistor as the power source; or

B)        A grounding circuit originating at the grounded side of the

grounding resistor which extends along with the power conductors and serves as

a grounding conductor for the frames of all the electric equipment supplied

power from the circuit.

2)         Grounding resistors shall be connected to a low resistance

ground field, and shall be of an CHMIC value which limits the ground fault

current to no more than twenty-five (25) amperes.  Such grounding resistors

shall be rated for maximum fault current continuously and provide insulation

from ground for a voltage equal to the phase-to-phase voltage of the system.

e)         Grounding resistors; continuous current-rating.

The ground

fault current rating of grounding resistors shall meet the "extended time

rating" set forth in American Institute of Electrical Engineers Standard

No. 32.

f)         Low-voltage and medium-voltage ground check circuits.

Present

technology does not provide for a fail safe ground monitor system

-to-phase voltage of the system.

e)         Grounding resistors; continuous current-rating.

The ground

fault current rating of grounding resistors shall meet the "extended time

rating" set forth in American Institute of Electrical Engineers Standard

No. 32.

f)         Low-voltage and medium-voltage ground check circuits.

Present

technology does not provide for a fail safe ground monitor system.  In the

event such technology becomes available, The Mining Board has the authority to

adopt rules requiring such systems.

g)         Systems grounding.

Three

(3)-phase low-voltage and medium-voltage circuits of more than two hundred

forty (240) volts phase-to-phase extending to stationary equipment shall be

grounded in one of following ways:

1)         Solidly grounded through a direct or derived neutral;

2)         Contain a direct or derived neutral grounded through a

suitable resistor located at the power source; or

3)         Ungrounded Delta.

h)         Disconnecting devices.

Disconnecting

devices shall be installed at the beginning of each branch line supplying power

to each piece of portable or mobile equipment and shall provide visual evidence

that the power is disconnected.

i)          Connection of single-phase loads.

Single-phase

loads shall be connected phase-to-phase in resistance grounded systems.

j)          Qualified person.

An individual

is a qualified person within the meaning of this Section 220.90 of this Part,

if such person is a qualified person under Section 220.50(e) of this Part.