Section 220.70 Grounding

IllinoisRegulations

Ask Donna

How this section applies to your facts.

Illinois Administrative Code › Title 62 MINING › CHAPTER I: DEPARTMENT OF NATURAL RESOURCES › Part 220 SURFACE INSTALLATION HEALTH AND SAFETY › Section 220.70 Grounding

This text was captured on Aug 14, 2026. It is a snapshot, not a live feed, so check the official code before relying on it.

Text

Section 220

Section 220.70  Grounding

a)         Grounding, metallic shielding, armors, conduit enclosing power

conductors, metallic frames, casings, and other metallic enclosures of electric

equipment and circuits.

Metallic shieldings, armors, conduits enclosing power

conductors, metallic frames, casings, and other metallic enclosures of electric

equipment and circuits that can become "alive" through failure of

insulation or by contact with energized parts shall be grounded by methods

approved by an authorized representative of the Department.

b)         Approved grounding methods; three (3)-phase systems.

1)         Resistance Grounded Systems.  A grounding circuit consisting

of a grounding wire that meets the requirements of Section 220.70(f),

originating at the grounded side of the grounding resistor, shall extend along

with the power conductors and serve as the grounding conductor for all metallic

shielding, armors, conduit enclosing power conductors, metallic frames,

casings, and other metallic enclosures of electric equipment and circuits that

receive power from the circuit.  The grounding resistor shall be located at the

power source.  The grounded side of the grounding resistor shall be connected

to a low resistance ground field.

2)         Solidly Grounded Systems.  The grounded point of three

(3)-phase systems shall be grounded to a low resistance ground field and to the

cases of the source transformers.  A grounding circuit that meets the

requirements of Section 220.70(b)(1) shall originate at the grounded point of

the circuit and extend along with the power conductors and serve as a grounding

circuit for the frames, casings, and other metallic enclosures of all circuits

and equipment receiving power from that circuit.  The grounded point shall be

located at the power source

ce transformers.  A grounding circuit that meets the

requirements of Section 220.70(b)(1) shall originate at the grounded point of

the circuit and extend along with the power conductors and serve as a grounding

circuit for the frames, casings, and other metallic enclosures of all circuits

and equipment receiving power from that circuit.  The grounded point shall be

located at the power source.  In three (3)-phase, four (4)-wire systems in

which the neutral is a power conductor, the neutral shall also be grounded to a

low resistance ground field at the service entrance to building or at the

utilization locations.

3)         Ungrounded Systems.  A grounding circuit, consisting of a

grounding conductor that meets the requirements of Section 220.70(i) and

originating at the grounded case or frame of the power source, shall extend

along with the power conductors and serve as the grounding conductor for all

metallic casings and other metallic enclosures of electrical equipment and

circuits receiving power from that circuit.  The grounded case or frame of the

power source shall be connected to a low resistance ground field.

c)         Grounding method; single-phase system.

Single phase systems shall be grounded in such manner so that

the minimum amount of voltage will exist between the ungrounded conductors and

earth.  A conductor that meets the requirements of Section 220.70(i) shall

originate at the grounded point in the circuit and extend along with the power

conductors and serve as a grounding medium for the frames of all equipment

receiving power from that circuit and such conductor shall also be grounded to

a low resistance ground field at the service entrance or utilization points.

d)         Grounding methods; direct-current systems.

1)         Direct-current systems having one (1) grounded polarity.  In

direct-current systems having one polarity grounded to a low resistance ground

field the grounded feeder wire or track rail shall be approved grounding medium

conductor shall also be grounded to

a low resistance ground field at the service entrance or utilization points.

d)         Grounding methods; direct-current systems.

1)         Direct-current systems having one (1) grounded polarity.  In

direct-current systems having one polarity grounded to a low resistance ground

field the grounded feeder wire or track rail shall be approved grounding medium.

A grounding circuit meeting the requirements of Section 220.70(f) shall

originate at the grounded feeder wire or tract rail and extend along with the

power conductors and serve as a grounding conductor for the frames, casing, and

metallic enclosures of all circuits and equipment receiving power from that

credit.

2)         Direct current systems having a grounded neutral point.  The

grounded neutral point shall be the approved grounding medium.  A grounding

circuit meeting the requirements of Section 220.70(f) originate at the grounded

neutral point and extend along with the power conductors and serve as a

grounding conductor for the frames, casings, and metallic enclosures of all

circuits and equipment receiving power from that circuit.

3)         Ungrounded direct-current circuits.  In ungrounded

direct-current circuits the grounded frame or casing of the power source shall

be the approved grounding medium.  In the event the power source is a

direct-current generator, the frame of the generator power source is a direct-current

generator, the frame of the generator shall be connected to a low resistance

ground field.  A grounding circuit meeting the requirements of Section

220.70(f) shall originate at the grounded frame or casing of the power source

and extend along with the power conductors and serve as a grounding conductor

for the frames, casings, and metallic enclosures of all circuits and equipment

receiving power from that circuit.

e)         Low resistance ground field; interpretation

ground field.  A grounding circuit meeting the requirements of Section

220.70(f) shall originate at the grounded frame or casing of the power source

and extend along with the power conductors and serve as a grounding conductor

for the frames, casings, and metallic enclosures of all circuits and equipment

receiving power from that circuit.

e)         Low resistance ground field; interpretation.

1)         A low resistance ground field as referred to in Section 220.90

of this Part is interpreted to mean:  made electrodes, buried metallic piping

system, metal building framework, well or borehole casing, steel piling, and

other underground metal structures installed for purpose other than grounding

which have a resistance to ground of not more than five (5) OHMS.  Grounding

fields shall be measured at the time of installation and at least annually

thereafter to insure a sufficiently low resistance ground field has been

established and is being maintained and such measurements shall be recorded and

kept at the installation.

2)         An authorized representative of the Department may allow

higher resistance to ground values if an investigation has revealed that such

greater values of resistance will not pose a hazard to the miners.

f)         Grounding wires; capacity.

Where grounding wires are used to ground metallic shielding,

armors, conduits, frames, casings, and other metallic enclosures, such

grounding wires will be approved if:

1)         Where the power conductor used is No.  6 A.W.G., or larger,

the cross-sectional area of the grounding wire is at least one-half (½) the

cross-sectional area of the power conductor; or

2)         Where the power conductor used is less than No.  6 A.W.G., the

cross-sectional area of the grounding wire is equal to the cross-sectional area

of the power conductor.

g)         Protection other than grounding.

Methods other than grounding which provide no less effective

protection may be permitted by the Department or its authorized

representative

al area of the power conductor; or

2)         Where the power conductor used is less than No.  6 A.W.G., the

cross-sectional area of the grounding wire is equal to the cross-sectional area

of the power conductor.

g)         Protection other than grounding.

Methods other than grounding which provide no less effective

protection may be permitted by the Department or its authorized

representative.  Such methods shall not be used unless so approved.

h)         Grounding circuit; criteria.

The grounding circuit for equipment and conductor enclosures

shall:

1)         Be permanent and continuous;

2)         Have ample current-carrying capacity to conduct safely any

currents liable to be imposed on it; and

3)         Have impedance sufficiently low to facilitate the operation of

the ground overcurrent devices in the circuit during fault conditions.

i)          Approved grounding conductors.

Any of the following conductors when properly installed shall

be acceptable for grounding equipment to the ground field:

1)         A properly-sized copper or other corrosion-resistant conductor

which meets the requirements of Section 220.70(f);

2)         Rigid metal conduit;

3)         Electrical metallic tubing; and

4)         The structural metal frame of buildings.

j)          Use of grounding connectors.

If ground wires are attached to grounded power conductors,

separate clamps, suitable for such purpose, shall be used and installed to

provide a solid connection.

k)         Guy wire; grounding.

Guy wires from poles supporting power lines shall be securely

connected to the system ground or be provided with insulators installed near

the pole end.