DEPARTMENT OF TRANSPORTATION

Research and Special Programs Administration

49 CFR Part 192

[Docket No. PS-118; Amendment 192-80]

RIN 2137-AB97

Excess Flow Valve--Performance Standards

AGENCY: Research and Special Programs Administration, (RSPA), DOT.

ACTION: Final rule; response to petition for reconsideration.

-----------------------------------------------------------------------

SUMMARY: This action concerns a petition from the American Gas

Association (AGA) to reconsider and clarify certain provisions of the

excess flow valve (EFV) performance standards regulations. AGA's

request to clarify the rule by deleting language in the regulation

concerning sizing of the EFV and locating the EFV beyond the hard

surface is granted because some operators are apparently

misinterpreting this language. AGA's request to delete the recommended

installation standards from the performance standards rule and include

them in the notification rulemaking is denied because such standards

are applicable to an EFV's safe and reliable operation. AGA's request

to allow an operator to determine how to identify the presence of an

EFV in the service line is denied because the final rule already allows

the operator this flexibility.

EFFECTIVE DATE: February 18, 1997.

FOR FURTHER INFORMATION CONTACT: Mike Israni (202) 366-4571, regarding

this final rule or the Dockets Unit, (202) 366-5046, regarding copies

of this final rule or other material in the docket.

SUPPLEMENTARY INFORMATION:

Background

On June 20, 1996 (61 FR 31449), RSPA published regulations (49 CFR

192.381) prescribing performance standards for EFVs used to protect

single-residence service lines. In a petition for reconsideration and

request for clarification dated July 17, 1996, AGA asked RSPA to

reconsider several provisions of this final rule on EFV performance

standards. On July 30, 1996, OPS and AGA met to discuss the issues in

the petition.

AGA Petition for Reconsideration

I. AGA contended that the marking requirement (Sec. 192.381(c)) and

recommendations concerning where to locate the EFV (Sec. 192.381(d))

and whether to install an EFV in certain circumstances

(Sec. 192.381(e)) are installation standards and should not have been

included in the final rule on EFV performance standards. AGA maintained

that these requirements should have been included in RSPA's notice of

proposed rulemaking on EFV customer notification (61 FR 33476; June 27,

1996), and subject to notice and comment.

Response: RSPA disagrees that the marking requirement and the

recommendations on locating and installing an EFV are misplaced and

were not subject to notice and comment. RSPA established the EFV

performance standards as minimum requirements for an EFV to perform

safely and reliably when installed in a gas piping system. The marking

requirement and the recommendations on locating and installing an EFV

were included in the rule because RSPA considers them integral to an

EFV's performance.

RSPA recommended the circumstances in which an operator should not

install an EFV and where the operator should locate the EFV to address

concerns raised during the EFV rulemaking process. Because these

recommendations addressed comments that were made during the EFV

rulemaking process, although not specifically proposed, RSPA considered

them to be within the scope of the EFV rulemaking. To address

commenters' concern about placing an EFV in a system where contaminants

could cause a malfunction, RSPA included a recommendation that

operators consider this factor when installing an EFV. Similarly, to

address concerns about protecting the maximum length of service line,

as well as comments about logistical and economic difficulties in

installing or removing an EFV beneath a hard surface, RSPA recommended

that an operator locate the EFV beyond the hard surface and as near the

gas supply main as practical. Both recommended standards affect an

EFV's operation and reliability, and are better suited to the

performance standards rule than the notification rulemaking. The

proposed notification rule proposes to require operators to notify

customers about the availability, safety benefits, and cost associated

with EFV installation, issues not related to an EFV's operation.

The requirement to identify the presence of an EFV in a service

line by marking or other means is intended to alert personnel servicing

the line to its presence. Although not technically a performance

standard, the requirement is better placed in the performance standards

rule because it helps to ensure that a service line with an EFV is

properly serviced.

Accordingly, for the reasons discussed, RSPA does not adopt AGA's

suggestion to amend the final rule by deleting these sections. However,

AGA's additional concerns about the recommendation to locate an EFV

beyond the hard surface are addressed in section III of this document.

II. AGA requested RSPA to clarify the requirement to mark, or

otherwise identify, the presence of an EFV in a service line

(Sec. 192.381(c)). AGA expressed concern that marking would notify the

public of the valve's existence to the detriment of the public's

safety. AGA suggested that RSPA amend this requirement to allow each

operator to determine the method to identify the presence of an EFV in

the service line.

Response: By requiring an operator to mark or otherwise identify

the presence of an EFV in a service line, the final rule intended for

each operator to determine how to identify the presence of an EFV to

personnel servicing the line. The language in the rule left to the

operator's discretion whether to identify the EFV's presence by marking

the line, by indicating on maps and records, or by using some other

method. When, during the meeting, OPS explained that this language was

not intended to limit an operator, AGA agreed that further clarifying

language was not needed. Thus, we do not see any necessity for

modifying the rule.

III. The final rule (Sec. 192.381 (d)) recommended that an operator

locate an EFV beyond the hard surface and as near as practical to the

fitting connecting the service line to its source of gas supply. In its

petition AGA said that the language specifying that an EFV should be

located beyond the hard surface could increase the costs of

installation and reduce the safety benefits of EFVs. AGA explained that

under the three most common installation and replacement methods

(trenching, boring, insertion), an additional excavation or cutting and

resealing of the pipe would be needed to accommodate the requirement.

Furthermore, the effect of this requirement would be to install the EFV

further from the service line than necessary.

Response: RSPA intended in the final rule that if an EFV were

installed in a service line, it would be located as near the gas supply

main as practical. RSPA further recommended that the EFV be located

beyond the hard surface to alleviate concerns raised during the

rulemaking process that installing or removing an EFV under a hard

surface would result in increased installation or removal costs. To

avoid any confusion for the operator about where best to locate an EFV,

RSPA is deleting the language ``beyond the hard surface'' from the

rule.

RSPA continues to believe that if an EFV is installed, it is placed

as near the source of gas supply as practical to ensure the EFV

protects the maximum length of service line. Therefore, we are further

amending the section to clarify the original intent of the rule by

changing ``should locate'' to ``shall locate the EFV as near as

practical to the fitting connecting the service line to its source of

gas supply.'' The clarification continues to allow the operator to

decide if such an installation is practical.

IV. AGA argued in its petition that the language requiring that the

EFV be ``sized to close at * * *'' (Sec. 192.381(a)(3)(I)), has caused

confusion among operators. AGA explained that because sizing is usually

done by an engineer, not the manufacturer, an operator could not ensure

that the manufacturer had sized the valve correctly. AGA recommended

RSPA delete this language or clarify who bears responsibility for

ensuring the EFV is correctly sized.

Response: In RSPA's experience, the language concerning sizing

should not cause confusion. Nonetheless, to preclude this possibility,

RSPA is deleting the language ``[b]e sized to * * * '' from

Sec. 192.381(a)(3)(I).

Regulatory Analyses and Notices

Executive Order 12866 and DOT Regulatory Policies and Procedures

The Office of Management and Budget (OMB) does not consider this

final rule to be a significant regulatory action under section 3(f) of

Executive Order 12866. Therefore, OMB did not review this final rule.

Also, DOT does not consider this final rule to be significant under its

regulatory policies and procedures (44 FR 11034; February 26, 1979).

Because this final rule merely clarifies an existing rule, the economic

impact is too minimal to warrant an evaluation of costs and benefits.

However, an economic evaluation of the original final rule is available

for review in the docket.

Executive Order 12612

We analyzed this final rule under the principles and criteria in

Executive Order 12612 (``Federalism''). The final rule does not have

sufficient federalism impacts to warrant preparation of a federalism

assessment.

Regulatory Flexibility Act

I certify, under Section 605 of the Regulatory Flexibility Act,

that this final rule will not have a significant economic impact on a

substantial number of small entities.

Paperwork Reduction Act

This rule does not modify the paperwork burden that operators

already have. Therefore, a paperwork evaluation is unnecessary.

List of Subjects in 49 CFR Part 192

Natural gas, Pipeline safety, Reporting and record keeping

requirements.

RSPA amends 49 CFR part 192 as follows:

PART 192--[AMENDED]

1. The authority citation for part 192 continues to read as

follows:

Authority: 49 U.S.C. 5103, 60102, 60104, 60108, 60109, 60110,

60113, and 60118; 49 CFR 1.53.

2. Section 192.381 is amended by revising paragraphs (a)(3)(i), and

(d) to read as follows:

Sec. 192.381 Service lines: Excess flow valve performance standards.

(a) * * *

(3) At 10 psig:

(i) Close at, or not more than 50 percent above, the rated closure

flow rate specified by the manufacturer; and

* * * * *

(d) An operator shall locate an excess flow valve as near as

practical to the fitting connecting the service line to its source of

gas supply.

* * * * *

Issued in Washington, DC, on January 14, 1997.

Kelley S. Coyner,

Deputy Administrator.

[FR Doc. 97-1249 Filed 1-16-97; 8:45 am]

BILLING CODE 4910-60-P