SECTION 403, HIGH-RISE BUILDINGS
MinnesotaRegulations
Ask Donna
How this section applies to your facts.
Minnesota Administrative Rules › DEPARTMENT OF LABOR AND INDUSTRY › Chapter 1305 › Part 1305.0403
Text
Subpart 1. IBC section 403.2.1.2. IBC section 403.2.1.2 is deleted in its entirety. Subp. 2. [Repealed, 39 SR 1605] Subp. 3. IBC section 403.4.8.3. IBC section 403.4.8.3 is amended to read as follows: 403.4.8.3 Standby power loads. The following are classified as standby power loads: 1. power and lighting for the fire command center required by Section 403.4.6; 2. ventilation and automatic fire detection equipment for smokeproof enclosures; and 3. passenger elevators serving occupied floors more than 75 feet (22, 860 mm) above the lowest level of fire department vehicle access.