Section 466.20 Definitions
IllinoisRegulations
Ask Donna
How this section applies to your facts.
Illinois Administrative Code › Title 83 PUBLIC UTILITIES › CHAPTER I: ILLINOIS COMMERCE COMMISSION › Part 466 ELECTRIC INTERCONNECTION OF DISTRIBUTED ENERGY RESOURCES FACILITIES › Section 466.20 Definitions
Text
Section 466.20 Definitions
Terms defined in Section 16-102 of the Public Utilities Act
[220 ILCS 5] shall have the same meaning for purposes of this Part as they have
under Section 16-102 of the Act, unless further defined in this Part. The
following words and terms, when used in this Part, have the following meanings
unless the context indicates otherwise:
"Act" means the Public
Utilities Act [220 ILCS 5].
"Adverse system impact"
means a negative effect that compromises the safety or reliability of the
electric distribution system or materially affects the quality of electric
service provided by the electric distribution company (EDC) to other customers.
"Affected system" means
an electric system not owned or operated by the electric distribution company
reviewing the interconnection request that could suffer an adverse system
impact from the proposed interconnection.
"Applicant" means a
person (or entity) who has submitted an interconnection request to interconnect
a distributed energy resources facility to an EDC's electric distribution
system.
"Area network" means a
type of electric distribution system served by multiple transformers
interconnected in an electrical network circuit, generally used in large,
densely populated metropolitan areas.
"Business day" means
Monday through Friday, excluding State and federal holidays.
"Calendar day" means any
day, including Saturdays, Sundays and State and federal holidays.
"Certificate of completion"
means a certificate, in a form approved by the Commission, that contains
information about the interconnection equipment to be used, its installation
and local inspections (see Appendix B).
"Commissioning test"
means tests applied to a distributed energy resources facility by the applicant
after construction is completed to verify that the facility does not create
adverse system impacts and performs to the submitted specifications
by the Commission, that contains
information about the interconnection equipment to be used, its installation
and local inspections (see Appendix B).
"Commissioning test"
means tests applied to a distributed energy resources facility by the applicant
after construction is completed to verify that the facility does not create
adverse system impacts and performs to the submitted specifications. At a
minimum, the scope of the commissioning tests performed shall include the
commissioning test specified in Institute of Electrical and Electronics Engineers,
Inc. (IEEE) Standard 1547 Section 5.4 "Commissioning tests".
"Contingent upgrades"
means proposed interconnection facilities or distribution system upgrades,
identified during interconnection studies for an applicant's interconnection
request, that are the responsibility of an interconnection request earlier in
the queue than the subject application for interconnection. The identified
contingent upgrades are required in order for the applicant's proposed
interconnection request to receive permission to operate and, if delayed or not
built by the earlier-queued interconnection request, could cause a need for
restudies of the interconnection request and may become the responsibility of
the applicant's interconnection request.
"Distributed energy resources
facility" or "DER" facility means the equipment used by an
interconnection customer to generate or store electricity that operates in
parallel with the electric distribution system. A DER facility may include,
but is not limited to, an electric generator or energy storage system, a prime
mover, and the interconnection equipment required to safely interconnect with
the electric distribution system or local electric power system.
"Distribution upgrade"
means a required addition or modification to the electric distribution system
to accommodate the interconnection of the DER facility. Distribution upgrades
do not include interconnection facilities
energy storage system, a prime
mover, and the interconnection equipment required to safely interconnect with
the electric distribution system or local electric power system.
"Distribution upgrade"
means a required addition or modification to the electric distribution system
to accommodate the interconnection of the DER facility. Distribution upgrades
do not include interconnection facilities.
"Draw-out type circuit
breaker" means a switching device capable of making, carrying and breaking
currents under normal and abnormal circuit conditions such as those of a short
circuit. A draw-out circuit breaker can be physically removed from its
enclosure creating a visible break in the circuit. The draw-out circuit
breaker shall be capable of being locked in the open, drawn-out position.
"Earlier in the queue"
means that an interconnection request relative to another interconnection
request retains the rights to use any available distribution system capacity
first and may be interconnected first.
"Electric distribution
company" (EDC) means any electric utility subject to the jurisdiction of
the Commission.
"Electric distribution system"
means the facilities and equipment owned and operated by the EDC and used to
transmit electricity to ultimate usage points such as homes and industries from
interchanges with higher voltage transmission networks that transport bulk
power over longer distances. The voltage levels at which electric distribution
systems operate differ among areas, but generally operate at less than 100
kilovolts (kV) of electricity. "Electric distribution system"
excludes facilities under the operational control of the regional transmission
organization (RTO) that would otherwise be classified as distribution.
"Energy storage system" (ESS)
means a mechanical, electrical, or electrochemical means to store and release
electrical energy, and its associated electrical inversion device and control
functions
) of electricity. "Electric distribution system"
excludes facilities under the operational control of the regional transmission
organization (RTO) that would otherwise be classified as distribution.
"Energy storage system" (ESS)
means a mechanical, electrical, or electrochemical means to store and release
electrical energy, and its associated electrical inversion device and control
functions.
"Export capacity" means
the nameplate capacity in kilovolt amperes (kVA) of a DER facility except where
that capacity is limited by an acceptable means as identified in Section
466.75.
"Fault current" is the
electrical current that flows through a circuit during an electrical fault
condition. A fault condition occurs when one or more electrical conductors
contact ground or each other. Types of faults include phase to ground,
double-phase to ground, three-phase to ground, phase-to-phase, and three-phase.
Often, a fault current is several times larger in magnitude than the current
that normally flows through a circuit.
"Host load" means the
electrical power registered by the EDC during the prior 12-month period at the
customer meter to which the proposed DER facility is to be interconnected.
"IEEE" is the Institute
of Electrical and Electronics Engineers, Inc., 3 Park Avenue, New York NY
10016-5997 (http://www.ieee.org).
"IEEE C37.90" is the
IEEE Standard C 37.90 (2005), "IEEE Standard for Relays and Relay Systems
Associated with Electric Power Apparatus".
This
incorporation does not include any later amendments or editions.
"IEEE C37.90.1" is the
IEEE Standard C37.90.1 (2012), "IEEE Standard for Surge Withstand
Capability (SWC) Tests for Relays and Relay Systems Associated with Electric
Power Apparatus".
This incorporation does not
include any later amendments or editions.
"IEEE C37.90.2" is the
IEEE Standard C37.90.2 (2004), "IEEE Standard for Withstand Capability of
Relay Systems to Radiated Electromagnetic Interference from Transceivers"
tandard C37.90.1 (2012), "IEEE Standard for Surge Withstand
Capability (SWC) Tests for Relays and Relay Systems Associated with Electric
Power Apparatus".
This incorporation does not
include any later amendments or editions.
"IEEE C37.90.2" is the
IEEE Standard C37.90.2 (2004), "IEEE Standard for Withstand Capability of
Relay Systems to Radiated Electromagnetic Interference from Transceivers".
This incorporation does not include any later
amendments or editions.
"IEEE C62.92.6" is the
IEEE Standard C62.92.6 (2017), "IEEE Guide for Application of Neutral
Grounding in Electrical Utility Systems, Part VI--Systems Supplied by Current-Regulated
Sources". This incorporation does not include any later amendments or
editions.
"IEEE Standard 519-2014"
is the IEEE Standard 519-2014 "IEEE Recommended Practice and Requirements
for Harmonic Control in Electric Power Systems". This incorporation does
not include any later amendments or editions.
"IEEE Standard 1547" is
the IEEE Standard 1547 (2003) "Standard for Interconnecting Distributed
Resources with Electric Power Systems". This incorporation does not
include any later amendments or editions.
"IEEE Standard 1547.1"
is the IEEE Standard 1547.1 (2005) "Conformance Test Procedures for
Equipment Interconnecting Distributed Resources with Electric Power Systems."
This incorporation does not include any later amendments or editions.
"Inadvertent
export" means the unpermitted, unscheduled, and uncompensated export of
real power from a DER facility and exported across the point of interconnection
to the EDC's distribution system.
"Interconnection customer"
means a person or entity that interconnects, or seeks to interconnect, a DER
facility to an electric distribution system
es not include any later amendments or editions.
"Inadvertent
export" means the unpermitted, unscheduled, and uncompensated export of
real power from a DER facility and exported across the point of interconnection
to the EDC's distribution system.
"Interconnection customer"
means a person or entity that interconnects, or seeks to interconnect, a DER
facility to an electric distribution system.
"Interconnection equipment"
means a group of components or an integrated system owned and operated by the
interconnection customer that connects an electric generator with a local
electric power system, as that term is defined in Section 3.1.6.2 of IEEE
Standard 1547, or with the electric distribution system. Interconnection
equipment is all interface equipment including switchgear, protective devices,
inverters or other interface devices. Interconnection equipment may be
installed as part of an integrated equipment package that includes a generator
or other electric source.
"Interconnection facilities"
means facilities and equipment required by the EDC to accommodate the
interconnection of a DER facility. After installation, interconnection
facilities become part of the electric distribution system. Collectively,
interconnection facilities include all facilities and equipment between the DER
facility's interconnection equipment and the point of interconnection,
including any modifications, additions, or upgrades necessary to physically and
electrically interconnect the DER facility to the electric distribution system.
Interconnection facilities are sole use facilities and do not include
distribution upgrades.
"Interconnection request"
means an applicant's request, in a form approved by the Commission, for
interconnection of a new DER facility or to change the capacity or other operating
characteristics of an existing DER facility already interconnected with the
electric distribution system.
"Interconnection
study" is any study described in Section 466.120
and do not include
distribution upgrades.
"Interconnection request"
means an applicant's request, in a form approved by the Commission, for
interconnection of a new DER facility or to change the capacity or other operating
characteristics of an existing DER facility already interconnected with the
electric distribution system.
"Interconnection
study" is any study described in Section 466.120.
"Lab-certified" means a
designation that the interconnection equipment meets the requirements set forth
in Section 466.70.
"Like-kind modification"
means a modification to interconnection equipment such that the installed
interconnection equipment has analogous certification, size, ratings,
impedances, efficiencies, and operating capabilities.
"Limited export" means
the exporting capability of a DER facility whose generating capacity is limited
below the nameplate capacity by the use of a configuration or operating mode as
described in Section 466.75.
"Line section" is that
portion of an electric distribution system connected to an interconnection
customer's site, bounded by automatic sectionalizing devices or the end of the
distribution line.
"Local electric power system"
means facilities that deliver electric power to a load that is contained
entirely within a single premises or group of premises. Local electric power
system has the same meaning as that term has as defined in Section 3.1.6.2 of
IEEE Standard 1547.
"Material
modification" has the meaning ascribed in Section 466.125.
"Minor system
modifications" means modifications to an EDC's Electric Distribution
System located between the service tap on the distribution circuit and the
meter serving the Interconnection Customer or other minor system changes that
the EDC estimates will entail less than 10 hours of work and $5,000 in
materials
rd 1547.
"Material
modification" has the meaning ascribed in Section 466.125.
"Minor system
modifications" means modifications to an EDC's Electric Distribution
System located between the service tap on the distribution circuit and the
meter serving the Interconnection Customer or other minor system changes that
the EDC estimates will entail less than 10 hours of work and $5,000 in
materials.
"Nameplate capacity" is
the maximum rated output in kVA of a generator, prime mover, energy storage
system, or other electric power production equipment under specific conditions
designated by the manufacturer and usually indicated on a nameplate physically
attached to the power production equipment.
"Nationally recognized
testing laboratory" or "NRTL" means a qualified private
organization that meets the requirements of the Occupational Safety and Health
Administration's (OSHA) regulations. See 29 CFR 1910.7 (February 18, 2020). This
incorporation does not include any later amendments or editions. NRTLs perform
independent safety testing and product certification. Each NRTL shall meet the
requirements as set forth by OSHA in its NRTL program.
"Non-export" or
"non-exporting" means that the DER facility is sized and designed,
such that no electrical energy other than inadvertent export allowed by Section
466.75 is transferred from the DER facility to the electric distribution
system.
"Operating profile"
means the manner in which the DER facility is designed to be operated, based on
the generating prime mover and operating characteristics, including any energy
storage system.
"Parallel operation" or "parallel"
means a DER facility that is connected electrically to the electric
distribution system for longer than 100 milliseconds.
"Point of interconnection"
or "POI" means the point where the DER facility is electrically
connected to the electric distribution system
ed on
the generating prime mover and operating characteristics, including any energy
storage system.
"Parallel operation" or "parallel"
means a DER facility that is connected electrically to the electric
distribution system for longer than 100 milliseconds.
"Point of interconnection"
or "POI" means the point where the DER facility is electrically
connected to the electric distribution system. Point of interconnection has
the same meaning as the term "point of common coupling" defined in
Section 3.1.13 of IEEE Standard 1547.
"Power control system"
means systems or devices that electronically limit or control steady state
currents to a programmable limit.
"Power rating configuration
setting" means the as-configured value of the active or apparent power
ratings that is used as the rating within the DER facility.
"Primary line" means an
electric distribution system line operating at greater than 600 volts.
"Protective function"
means the specific type of protection, based on the ANSI Protection Device
Numbers and functional descriptions, that a utility-grade protective relay
provides against conditions that, if left uncorrected, could result in, but not
limited to, the following: harm to personnel, damage to equipment, loss of
safety or reliability, or operation outside pre-established parameters required
by the interconnection agreement.
"Queue position" means,
for each distribution circuit or line section, the order of a completed
interconnection request relative to all other pending completed interconnection
requests on that distribution circuit or line section. It is established by
the date that the EDC receives the completed interconnection request.
"Radial distribution circuit"
means a circuit configuration in which independent feeders branch out radially
from a common source of supply.
"Regional Transmission
Organization" or "RTO" means the independent systems operator
that administers and oversees the wholesale electricity markets in which the
State participates
by
the date that the EDC receives the completed interconnection request.
"Radial distribution circuit"
means a circuit configuration in which independent feeders branch out radially
from a common source of supply.
"Regional Transmission
Organization" or "RTO" means the independent systems operator
that administers and oversees the wholesale electricity markets in which the
State participates. In Illinois, the two RTOs are the Midcontinent Independent
System Operator, Inc. and PJM Interconnection, LLC.
"Scoping meeting" means
a meeting between representatives of the applicant and EDC conducted to discuss
interconnection issues and exchange relevant information.
"Secondary line" means
an electric distribution system line, or service line, operating at 600 volts
or less.
"Shared transformer"
means a transformer that supplies secondary voltage to more than one customer.
"Spot network" means a
type of electric distribution system that uses two or more inter-tied
transformers to supply an electrical network circuit. A spot network is
generally used to supply power to a single customer or a small group of
customers. Spot network has the same meaning as the term "spot network"
defined in Section 4.1.4 of IEEE Standard 1547.
"Standard DER interconnection
agreement" means a standard interconnection agreement applicable to
interconnection requests for DER facilities. (see Appendices A and D).
"UL Standard 1741" means
the standard titled "Inverters, Converters, Controllers and
Interconnection System Equipment for Use With Distributed Energy Resources
(January 28, 2010), Underwriters Laboratories Inc., 333 Pfingsten Road,
Northbrook IL 60062-2096. This incorporation does not include any later
amendments or editions
rconnection requests for DER facilities. (see Appendices A and D).
"UL Standard 1741" means
the standard titled "Inverters, Converters, Controllers and
Interconnection System Equipment for Use With Distributed Energy Resources
(January 28, 2010), Underwriters Laboratories Inc., 333 Pfingsten Road,
Northbrook IL 60062-2096. This incorporation does not include any later
amendments or editions.
"UL 1741 CRD for PCS"
means the Certification Requirement Decision for Power Control Systems for the standard
titled "Inverters, Converters, Controllers and Interconnection System
Equipment for Use With Distributed Energy Resources" (March 8, 2019),
Underwriters Laboratories Inc., 333 Pfingsten Road, Northbrook IL 60062-2096.
This incorporation does not include any later amendments or editions.
"Utility-grade protective
relay" means a protective relay system that works under a variety of
environmental and operational conditions and that includes:
Test plugs/switches for testing
the operation of the relay without unwiring or disassembly;
Targets to indicate relay
operation;
Ability to record and store fault
events; and
Conformance with
IEEE C37.90, IEEE C37.90.1 and IEEE C37.90.2.
"Witness test" means a
verification, either by an on-site observation or review of documents, that the
interconnection installation evaluation required by IEEE Standard 1547 Section
5.3 and the commissioning test required by IEEE Standard 1547 Section 5.4 have
been performed. For interconnection equipment that has not been lab-certified,
the witness test shall also include verification of the on-site design tests as
required by IEEE Standard 1547 Section 5.1 and verification of production tests
required by IEEE Standard 1547 Section 5.2. All verified tests are to be
performed in accordance with the test procedures specified by IEEE Standard
1547.1.