Section 105.20 Storage and Wholesaling of Class "C" (Common) Fireworks
IllinoisRegulations
Ask Donna
How this section applies to your facts.
Illinois Administrative Code › Title 41 FIRE PROTECTION › CHAPTER I: OFFICE OF THE STATE FIRE MARSHAL › Part 105 FIREWORKS › Section 105.20 Storage and Wholesaling of Class "C" (Common) Fireworks
Text
Section 105
Section 105.20 Storage and
Wholesaling of Class "C" (Common) Fireworks
These Rules and Regulations
shall apply to both existing and new facilities, except as specifically
provided for herein.
a) Definitions
1) Class "C" or "Common Fireworks" are those
so defined:
Class "C" of Common fireworks are fireworks devices
designed primarily to produce visible effects by combustion. Some small
devices designed to produce audible effects are also included in this class.
The types, sizes and amount of pyrotechnic contents of these devices are
limited as enumerated in this paragraph. No component, of any device listed in
this paragraph, which produces or is intended to produce an audible effect
shall contain pyrotechnic composition in excess of two grains in weight; nor
any metal, glass or brittle plastic fragments. Common fireworks must be in a
finished state exclusive of mere ornamentation as supplied to the trade and
must be so constructed and packed that loose pyrotechnic composition will not
be present in packages in transportation or storage.
2) "Storage": shall mean net weight quantities of 100
lbs. or more of Class "C" fireworks.
3) "Net weight": Shall mean the weight of the finished
product, the display packaging, and the first or smallest unit shipping
container.
4) "Inhabited building": For the purpose of this section
means a building or structure regularly used in whole or in part as a place of
human habitation. The term inhabited building shall also mean any church,
school, store, passenger station, airport terminal, and any other structure
where people are accustomed to congregate or assemble, but excluding any
building used for the manufacture, transportation, and storage of fireworks.
b) All storage of Class "C" fireworks in quantities of
100 lbs
or in part as a place of
human habitation. The term inhabited building shall also mean any church,
school, store, passenger station, airport terminal, and any other structure
where people are accustomed to congregate or assemble, but excluding any
building used for the manufacture, transportation, and storage of fireworks.
b) All storage of Class "C" fireworks in quantities of
100 lbs. or more, net weight, shall conform to the distances, type height of
construction, and fire protection systems requirements of Tables #1 and #2, of
these Rules and Regulations.
c) Existing structures used for the storage of 100 lbs. or more
(net weight) of Class "C" fireworks which cannot be brought into
compliance with the distance or type of construction requirements of Table #1
may continue in use by compliance with the following provisions:
1) Exterior walls shall be of two-hour fire resistive
construction. Two-hour fire resistive construction shall be as defined in
National Fire Protection Association #220, Types of Building Construction, 1980
Edition, Chapter 2, Para. 2-1. There is no specification as to materials
required provided that performance criteria are met.
2) All portions of the structure used for the storage of Class
"C" fireworks shall be protected by an automatic sprinkler system,
installed and maintained in accordance with National Fire Protection
Association #13, Installation of Sprinkler Systems, 1980 Edition.
3) The entire structure has a standard fire alarm system
installed to consist of the following:
A) Automatic detection consisting of smoke detectors where
appropriate, heat detectors in areas where smoke detection cannot be used.
B) Manual pull stations on each floor and at all exits.
C) The system connected to the fire department or other approved
central station as required in the Illinois Rules and Regulations for Fire
Prevention and Safety
onsist of the following:
A) Automatic detection consisting of smoke detectors where
appropriate, heat detectors in areas where smoke detection cannot be used.
B) Manual pull stations on each floor and at all exits.
C) The system connected to the fire department or other approved
central station as required in the Illinois Rules and Regulations for Fire
Prevention and Safety.
4) Such existing structure has no storage of Class "C"
fireworks above the second floor or below the first floor.
5) In storage facilities of 300 square feet or more, at least two
means of egress, remote from each other, are provided. The need for additional
means of egress shall be determined by applying the 1981 Edition, Life Safety
Code, National Fire Protection Association #101, Chapter 5.
d) The owner/operator of each storage and sales facility for
Class "C" fireworks shall keep a record of all transactions and
operations, involving fireworks for five (5) years. Such records shall show
quantities (net weight) sold or shipped, in and out; such records shall be made
available to authorized representatives of the Office of the State Fire
Marshal.
e) Storage buildings containing Class "C" fireworks
shall be separated from other buildings, magazines, and fireworks plant
building in accordance with Table #2.
f) Storage buildings for Class "C" fireworks shall be
vented, or in the alternative, shall be constructed in such a manner that
venting will occur by yielding of weaker parts of the structure under pressure
generated by burning fireworks.
g) All storage buildings shall be equipped with locking means for
all openings.
h) All doors shall open outward, and all exits must be clearly
marked. Aisles and exit doors should be kept free of any obstructions
alternative, shall be constructed in such a manner that
venting will occur by yielding of weaker parts of the structure under pressure
generated by burning fireworks.
g) All storage buildings shall be equipped with locking means for
all openings.
h) All doors shall open outward, and all exits must be clearly
marked. Aisles and exit doors should be kept free of any obstructions.
i) Only dust-ignition proof type electrical fixtures shall be
used, and wiring shall comply with Section 502-4 (b) of National Fire
Protection Association #70, the National Electrical Code, 1981 Edition. No
wall receptacles are permitted; all light fixtures must have guards.
j) An outside master electrical switch shall be provided at each
storage building where electricity is used. This switch must be placed in the
OFF position when the last person leaves the premises daily. This switch may
be secured with an approved locking device; such master switch shall not
control the operation of any alarm systems for the building.
k) Storage Building Operations
1) When operations are being conducted in storage buildings, a
competent person shall be in charge at all times. Such person shall be at
least eighteen (18) years of age and shall be held responsible for the
enforcement of all safety precautions.
2) Doors and other openings shall be kept locked, except during
hours of operation.
3) Safety rules covering the operations of storage buildings
shall be posted.
4) Containers shall be piled in a stable manner and height of
storage, aisle width, and all other provisions of National Fire Protection
Association #13, Installation of Sprinkler Systems, 1980, and National Fire
Protection Association #231, Indoor General Storage, 1979 Edition, shall be
adhered to
.
3) Safety rules covering the operations of storage buildings
shall be posted.
4) Containers shall be piled in a stable manner and height of
storage, aisle width, and all other provisions of National Fire Protection
Association #13, Installation of Sprinkler Systems, 1980, and National Fire
Protection Association #231, Indoor General Storage, 1979 Edition, shall be
adhered to.
5) Class "C" fireworks shall be stored in their
original packaging and in unopened cases or cartons so as to take advantage of
the insulation provided by such packaging; provided, however, unpackaged
fireworks which have been returned may be temporarily retained in bins for
re-packaging.
6) Tools used for opening containers of Class "C"
fireworks shall be constructed of non-sparking material, except that metal
slitters may be used for opening fiberboard containers.
7) Storage buildings shall be regularly swept, kept clean, dry,
free of grit, paper, empty used packages and rubbish. Brooms and other
cleaning utensils shall not have any spark-producing metal parts. Sweepings
shall be properly disposed of.
8) When storage buildings need interior repairs, all fireworks
shall be removed therefrom and the interior cleaned.
9) In making exterior storage building repairs, when there is a
possibility of causing sparks or fire, the fireworks shall be removed from the
storage building.
10) Fireworks removed from a storage building under repair shall
either be placed in another storage building or placed a safe distance from the
storage building where they shall be properly guarded and protected until
repairs have been completed. Upon completion of repairs, the fireworks shall
be properly returned to the storage building.
l) Miscellaneous Safety Precautions
1) Smoking, matches, open flames, spark producing devices and
firearms shall not be permitted inside storage buildings
d a safe distance from the
storage building where they shall be properly guarded and protected until
repairs have been completed. Upon completion of repairs, the fireworks shall
be properly returned to the storage building.
l) Miscellaneous Safety Precautions
1) Smoking, matches, open flames, spark producing devices and
firearms shall not be permitted inside storage buildings. Smoking, matches,
open flames, spark producing devices and firearms shall not be permitted within
25 feet of storage buildings. Existing storage facilities with a property line
less than 25 feet to the nearest portion of the building shall not permit such
prohibited material in the area between the property line and the building.
2) The land surrounding storage buildings shall be kept clear of
brush, dried grass, leaves, and similar combustibles for a distance of at least
twenty-five (25) feet, except for such existing facilities as cannot meet the
distance requirements of Table #1.
3) There shall be conspicuously posted signs with the words
"FIREWORKS – NO SMOKING" in letters not less than four inches high.
4) Heat-producing devices when used shall not be located within
the storage building, hear shall be provided through ducts, or piping. Entry
into the boiler/furnace room shall be from the outside. No openings into the
boiler/furnace room from the storage building shall be allowed. Ductwork shall
have smoke and fire dampers at each duct opening into the storage building.
5) Re-packaging of fireworks shall not be done in any facility
used for the storage of 500 or more pounds of Class "C" fireworks,
unless the re-packaging activity is separated from storage by two-hour fire
resistive construction. Only that amount of fireworks necessary for one days
re-packaging may be kept in the re-packaging room or area.
m) Quantity-Distance Separation Tables
Table 1
Re-packaging of fireworks shall not be done in any facility
used for the storage of 500 or more pounds of Class "C" fireworks,
unless the re-packaging activity is separated from storage by two-hour fire
resistive construction. Only that amount of fireworks necessary for one days
re-packaging may be kept in the re-packaging room or area.
m) Quantity-Distance Separation Tables
Table 1.
Minimum separation, and construction requirements of Class "C"
fireworks storage structures from inhabited buildings, passenger railways, and
public highways.
Net Wt. of Frwks.
Bldg.
Const.
Fire Alarms
Sprinklers
Distance
from Passing. Railways & Public Highways
Distance
From Inhabited Bldgs.
Class
C Frwks
Class
C Frwks
Pounds
Feet
Feet
100
Ord
Cons
N/A*
N/A
25
50
200
"
"
"
"
30
60
400
"
"
"
"
35
70
600
"
"
"
"
40
80
800
"
"
"
"
45
90
1,000
Ord
Cons
F.A.**
N/A
50
100
2,000
"
"
"
"
58
115
3,000
"
"
"
"
62
124
4,000
"
"
"
"
65
130
5,000
Non-Comb
F.A.
N/A
68
135
6,000
"
"
"
"
70
139
8,000
"
"
"
"
73
140
10,000
"
"
"
"
75
150
15,000
"
"
F.A.
Sprinklers
80
159
20,000
"
"
"
"
83
165
30,000
"
"
"
"
87
174
40,000
"
"
"
"
90
180
50,000
"
"
"
"
93
185
60,000
"
"
"
"
95
189
80,000
Fire-Res
F.A.
Sprinklers
98
195
100,000
"
"
"
"
100
200
150,000
"
"
"
"
105
209
200,000
"
"
"
"
108
215
250,000
"
"
"
"
110
220
*N/A Not
Applicable
**F.A. Fire
Alarm Systems
n) Minimum Separation Distances at Fireworks Manufacturing Plants
Net
Weight Fireworks
Distances
of Magazines and Storage Buildings from Nonprocess Buildings
Distance
Between Process Buildings and Between Process and Nonprocess Buildings
Pounds
Class
C Fireworks
Class
C Fireworks
100
Feet
Feet
200
400
30
37
600
30
37
800
30
37
1,000
30
37
2,000
30
37
3,000
30
37
4,000
35
48
5,000
38
60
6,000
42
67
8,000
50
78
10,000
54
82
1) For the purposes of applying the separation distances in Table
2 a process building includes a mixing building, any building in which
pyrotechnic or explosive composition is pressed or otherwise prepared for
finishing and assem
C Fireworks
100
Feet
Feet
200
400
30
37
600
30
37
800
30
37
1,000
30
37
2,000
30
37
3,000
30
37
4,000
35
48
5,000
38
60
6,000
42
67
8,000
50
78
10,000
54
82
1) For the purposes of applying the separation distances in Table
2 a process building includes a mixing building, any building in which
pyrotechnic or explosive composition is pressed or otherwise prepared for
finishing and assembling, and any finishing and assembling building. A
nonprocess building means office buildings, warehouses, and other fireworks
plant buildings where no fireworks or explosive compositions are processed or
stored.
2) Distances apply with or without barricades or screen-type
barricades.
3) Distances included are those between magazines, between
storage buildings, between magazines and storage buildings, between magazines
or storage buildings from process buildings and nonprocess buildings.
This is a copy of a public record, reproduced as it was published. It is not legal advice, and it may not be the version a court would rely on. Check the official source before you cite it.