RETAIL HYDROGEN FUELING REGULATIONS

ColoradoRegulations

Ask Donna

How this section applies to your facts.

Code of Colorado Regulations › 1100 Department of Labor and Employment › 1101 Division of Oil and Public Safety › 7 CCR 1101-17

This text was captured on Aug 14, 2026. It is a snapshot, not a live feed, so check the official code before relying on it.

Text

1

DEPARTMENT OF LABOR AND EMPLOYMENT

Division of Oil and Public Safety

RETAIL HYDROGEN FUELING REGULATIONS

7 CCR 1101-17

[Editor’s Notes follow the text of the rules at the end of this CCR Document.]

_________________________________________________________________________

ARTICLE 1

GENERAL PROVISIONS

Section 1-1

Basis and Purpose

The basis and purpose of these regulations is to set forth minimum standards for the design, construction,

location, installation and operation of retail hydrogen fueling facilities, which are reasonably necessary for

the protection of the health, welfare and safety of the public and persons using such materials.

Section 1-2

Technical Rationale

The technical requirements of these regulations are based on generally-accepted national and

international codes and standards governing the minimum levels of acceptability for inspections,

specifications, shipment notification, record keeping, labeling of containers, use of meters or mechanical

devices for measurement, submittal of installation plans and minimum standards for the design,

construction, location, installation and operation of retail hydrogen systems.

Section 1-3

Statutory Authority

These regulations are created pursuant to 8-20-102 of the Colorado Revised Statutes.

Section 1-4

Effective Date

These regulations shall be effective on January 1, 2017.

Section 1-5

Codes and Standards incorporated by reference

The following codes are incorporated by reference.

(a)

NFPA 2, Hydrogen Technologies Code, 2016 edition.

(b)

NFPA 55, Compressed Gases and Cryogenic Fluids Code, 2016 edition.

(c)

NFPA 30-A, Code for Motor Fuel Dispensing Facilities & Repair Garages , 2012 edition.(d) NIST

Handbook 44 Specifications, Tolerances, and Other Technical Requirements for Weighing and

Measuring Devices, 2016 edition.

(e)

NIST Handbook 130, Uniform Laws and Regulations in the Areas of Legal Metrology and Engine

Fuel Quality, 2016 edition.

(f)

SAE J 2601, Fueling Protocols for Light Duty Gaseous Hydrogen Surface Vehicles, 2014 edition.

sing Facilities & Repair Garages , 2012 edition.(d) NIST

Handbook 44 Specifications, Tolerances, and Other Technical Requirements for Weighing and

Measuring Devices, 2016 edition.

(e)

NIST Handbook 130, Uniform Laws and Regulations in the Areas of Legal Metrology and Engine

Fuel Quality, 2016 edition.

(f)

SAE J 2601, Fueling Protocols for Light Duty Gaseous Hydrogen Surface Vehicles, 2014 edition.

(g)

SAE J 2719, Hydrogen Fuel Quality for Fuel Cell Vehicles, 2015 edition.

Code of Colorado Regulations

Secretary of State

State of Colorado

CODE OF COLORADO REGULATIONS

7 CCR 1101-17

Division of Oil and Public Safety

2

Section 1-5-2 Inspection of incorporated codes

Interested parties may inspect the referenced incorporated materials by contacting the Division at 633

17th Street, Suite 500, Denver, CO 80202.

Section 1-5-3 Later amendments not included

These regulations do not include later amendments to or editions of the incorporated material.

Section 1-6

Definitions

Terms in these regulations shall have the same meaning as those found in Title 8, Article 20 of the

Colorado Revised Statutes. In addition, unless the context otherwise requires:

ASME – Means the American Society of Mechanical Engineers (ASME).

ASTM International – Formerly the American Society for Testing and Materials (ASTM).

California Type Evaluation Program (CTEP) - Means the evaluation program administered by

the California Department of Food and Agriculture, Division of Measurement Standards.

Condemned – Means a condemned container assembly and piping system which is

determined by a state inspector to be so unsafe that further use is prohibited until it is

satisfactorily repaired or replaced.

Container Assembly – Includes ASME containers, commonly known as tanks or cylinders.

CRS – Means the Colorado Revised Statutes.

Delivery – Means delivery of hydrogen to a hydrogen fueling facility by means of truck transport

or connected pipeline

nd piping system which is

determined by a state inspector to be so unsafe that further use is prohibited until it is

satisfactorily repaired or replaced.

Container Assembly – Includes ASME containers, commonly known as tanks or cylinders.

CRS – Means the Colorado Revised Statutes.

Delivery – Means delivery of hydrogen to a hydrogen fueling facility by means of truck transport

or connected pipeline.

Division – Means the Division of Oil and Public Safety, which is the regulatory agency of the

Colorado Department of Labor and Employment having jurisdiction over retail natural gas

systems per the provisions of CRS 8-20-102 (3).

Existing Installation – Includes any hydrogen container assembly and piping system at a retail

hydrogen fueling facility that has been placed into service prior to the effective date of

these regulations or has received its initial inspection by a state inspector.

Hydrogen Fuel – A fuel composed of molecular hydrogen intended for use in motor vehicles.

Hydrogen Fueling Facility – Means a facility that has a hydrogen fueling system which is used

for motor vehicle fueling.

Hydrogen Fueling System – Means a hydrogen storage container assembly, associated piping

and dispenser(s) which is used for motor vehicle fueling.

Incident – Means a reportable accident, as defined by this regulation.

National Board – Means the National Board of Boiler and Pressure Vessel Inspectors.

National Type Evaluation Program (NTEP) - Means the evaluation program administered by

the National Conference on Weights and Measures.

CODE OF COLORADO REGULATIONS

7 CCR 1101-17

Division of Oil and Public Safety

used for motor vehicle fueling.

Incident – Means a reportable accident, as defined by this regulation.

National Board – Means the National Board of Boiler and Pressure Vessel Inspectors.

National Type Evaluation Program (NTEP) - Means the evaluation program administered by

the National Conference on Weights and Measures.

CODE OF COLORADO REGULATIONS

7 CCR 1101-17

Division of Oil and Public Safety

3

New Installation – Means any hydrogen container assembly, associated piping or dispenser(s)

at a hydrogen fueling facility that has been placed into service after the effective date of

these regulations or has not received its initial inspection by a state inspector.

NFPA – Means the National Fire Protection Association.

NIST– Means the National Institute of Standards and Technology.

Piping System – Means pipes, tubing, hose and flexible connectors with valves and fittings

made into complete systems for conveying hydrogen from one point to another within a

retail hydrogen fueling facility.

Proved – Means the act of having verified the accuracy of meters used to measure fuel and

petroleum products using a prover.

Prover – Means a calibrated volumetric receiver or mechanical device traceable to NIST

standards.

Registered Serviceperson – Means any individual who for hire, award, commission or any other

payment of any kind installs, services, repairs or reconditions a commercial weighing or

measuring device and who voluntarily registers with the Division.

Registered Service Agency (RSA) – Means any agency, firm, company or corporation that for

hire, award, commission or any other payment of any kind installs, services, repairs or

reconditions a commercial weighing or measuring device and that voluntarily registers

with the Division. Under agency registration, identification of individual servicepersons

shall be required.

Retail – Means the sale of hydrogen at a hydrogen fueling facility, in small or individual quantities

for use as a motor fuel by the purchaser

r any other payment of any kind installs, services, repairs or

reconditions a commercial weighing or measuring device and that voluntarily registers

with the Division. Under agency registration, identification of individual servicepersons

shall be required.

Retail – Means the sale of hydrogen at a hydrogen fueling facility, in small or individual quantities

for use as a motor fuel by the purchaser.

State Inspector – Means a person who is employed or authorized by the Division to perform

inspections of retail hydrogen fueling facilities.

Section 1-7

Applicability

The regulations contained herein shall apply to the installation and operation of all retail hydrogen fueling

facilities.

Section 1-8

Condemning a Hydrogen Container Assembly and Piping System

(a)

Conditions which a state inspector may determine to be unsafe include: bypassed safety controls,

inoperative relief valves, any leak from a hydrogen fueling system, missing nameplate or

markings, or any other condition deemed by a state inspector to be unsafe based on codes

incorporated by this regulation. A hydrogen fueling system that meets any condition described

above may be condemned by a state inspector.

(b)

The owner or user must shut down the condemned hydrogen fueling system as directed by a

state inspector. If neither the owner nor user is available, a state inspector will take necessary

means to have the system safely shut down.

(c)

A state inspector will affix a notice to a condemned hydrogen fueling system stating that it has

been condemned and may not be used until satisfactory repairs are made, as determined by a re-

inspection by a state inspector or other person authorized by the Division.

CODE OF COLORADO REGULATIONS

7 CCR 1101-17

Division of Oil and Public Safety

4

ARTICLE 2

INSTALLATION AND REGISTRATION

No person may install, or cause to be installed, a new retail hydrogen fueling facility until:

(a)

An application, as described in Section 2-2 has been approved by the Division and an installation

permit has been issued by the Division;

r other person authorized by the Division.

CODE OF COLORADO REGULATIONS

7 CCR 1101-17

Division of Oil and Public Safety

4

ARTICLE 2

INSTALLATION AND REGISTRATION

No person may install, or cause to be installed, a new retail hydrogen fueling facility until:

(a)

An application, as described in Section 2-2 has been approved by the Division and an installation

permit has been issued by the Division;

(b)

The installation plan has been reported to the local Fire Department having jurisdiction; and

(c)

The application and inspection fee described in Section 2-2(a)(3) has been paid.

Section 2-1

General Requirements

(a)

All new retail hydrogen fueling facilities shall be operated and maintained in accordance with the

codes incorporated by this regulation, including any retroactive requirements adopted by the

Division at the time of installation.

(b)

All existing retail hydrogen fueling facilities shall be operated and maintained in accordance with

the edition of the incorporated codes that were in effect at the time of original construction.

(1)

If after inspection the Division determines that an existing situation presents an

unacceptable degree of risk, the Division shall be permitted to apply retroactively any

portion of the incorporated codes as deemed appropriate.

(c)

Local Authorities Having Jurisdiction, including Fire Departments and building code officials, may

adopt and enforce more stringent requirements than the minimum standards in these regulations.

These requirements may include, but are not limited to, the following:

(1)

Plan review and permitting for new hydrogen fueling facilities.

(2)

Access to hydrogen fueling facilities for the purpose of conducting inspections.

(3)

Delivery into containers located at hydrogen fueling facilities.

Section 2-2

Installation Permits

re stringent requirements than the minimum standards in these regulations.

These requirements may include, but are not limited to, the following:

(1)

Plan review and permitting for new hydrogen fueling facilities.

(2)

Access to hydrogen fueling facilities for the purpose of conducting inspections.

(3)

Delivery into containers located at hydrogen fueling facilities.

Section 2-2

Installation Permits

(a)

Plans for all new retail hydrogen fueling facilities shall be submitted to and approved by the

Division before construction of such facility begins.

(1)

Plans for the installation of new container assembly, associated piping or dispenser(s) at

existing retail hydrogen fueling facilities shall be submitted to the Division for approval

before construction of such installation begins.

(2)

Plans for change of service of existing hydrogen fueling facilities from non-retail to retail

service shall be submitted to the Division for approval before any such change of service

occurs.

(3)

For each installation plan submitted, the owner/operator must remit a fee of one thousand

dollars ($1,000) to the Division to cover the costs of the site plan review and installation

inspection.

(4)

It is not necessary to submit plans for the repair or replacement of existing equipment at

a permitted facility.

CODE OF COLORADO REGULATIONS

7 CCR 1101-17

Division of Oil and Public Safety

5

(b)

The permit procedures are as follows.

(1)

The permit application shall be submitted using an application form provided by the

Division.

(2)

The application shall include a plot plan containing all elements required by the Division.

(3)

The Division may deny the permit application if the proposed installation does not

conform to the requirements of the Colorado Revised Statutes, this regulation or any of

the codes incorporated by reference, or if the application is determined to be incomplete

or inaccurate.

(4)

Construction and installation of all associated equipment shall conform to the

incorporated codes in effect at the time of installation.

deny the permit application if the proposed installation does not

conform to the requirements of the Colorado Revised Statutes, this regulation or any of

the codes incorporated by reference, or if the application is determined to be incomplete

or inaccurate.

(4)

Construction and installation of all associated equipment shall conform to the

incorporated codes in effect at the time of installation.

(5)

The Division may revoke a permit if construction is not performed per the approved

permit or if the construction fails to meet operating or fire safety regulations established

by the Division or by the applicable incorporated codes.

(6)

An installation permit approved by the Division is automatically revoked if construction

does not begin within 6 months of approval unless a written request for an extension is

submitted to and approved by the Division.

Section 2-3

Annual Registration

(a)

Each owner/operator of a retail hydrogen fueling facility must register their facility with the

Division within 30 calendar days after the first day on which the facility begins storing hydrogen

fuel. This registration must be made on a form provided by the Division.

(b)

Each owner/operator of a retail hydrogen fueling facility shall renew their registration annually, on

or before the calendar date of the initial registration.

(c)

Each owner/operator of a retail hydrogen fueling facility shall pay a registration fee of $1,000 per

facility per year as authorized by CRS 8-20-102.

Section 2-4

Access Requirements

(a)

The Division may inspect a retail hydrogen fueling facility at any time during its construction.

Access shall be provided to the Division or its agent for such purpose upon request.

of the initial registration.

(c)

Each owner/operator of a retail hydrogen fueling facility shall pay a registration fee of $1,000 per

facility per year as authorized by CRS 8-20-102.

Section 2-4

Access Requirements

(a)

The Division may inspect a retail hydrogen fueling facility at any time during its construction.

Access shall be provided to the Division or its agent for such purpose upon request.

(b)

The Division may inspect a retail hydrogen fueling facility upon completion to verify compliance

with design, construction, location, installation and operation, dispensing and fuel quality

requirements in these regulations. Retail hydrogen fueling facility owners, hydrogen fueling

system owners and owners of locations where a retail hydrogen fueling system is installed shall

grant inspection access to the Division or its agent for such purpose upon request.

CODE OF COLORADO REGULATIONS

7 CCR 1101-17

Division of Oil and Public Safety

6

ARTICLE 3

DISPENSING AND FUEL QUALITY

Section 3-1

Retail Dispensing of Hydrogen

(a)

All retail dispensers of hydrogen used as a motor vehicle fuel shall be operated and maintained in

accordance with the applicable requirements of the codes incorporated by this regulation.

(b)

All retail dispensing of hydrogen into motor vehicles shall be in conformance with SAE J2601,

“Fueling Protocols for Light Duty Gaseous Hydrogen Surface Vehicles.”

Section 3-2

Retail Motor Fuel Dispensers Inspection and Testing

(a)

All retail motor fuel dispensers (RMFDs) shall be suitable for their intended use, properly

installed, accurate and maintained in that condition by their owner/operator.

(b)

All RMFDs shall have an active certificate of conformance (CC) from either the National Type

Evaluation Program (NTEP) or the California Type Evaluation Program (CTEP) prior to

installation or use for commercial purposes.

(c)

All RMFDs shall be capable of displaying delivered quantity in units of mass and all adjustments

and calibrations of RMFDs shall be made utilizing mass measurement standards.

All RMFDs shall have an active certificate of conformance (CC) from either the National Type

Evaluation Program (NTEP) or the California Type Evaluation Program (CTEP) prior to

installation or use for commercial purposes.

(c)

All RMFDs shall be capable of displaying delivered quantity in units of mass and all adjustments

and calibrations of RMFDs shall be made utilizing mass measurement standards.

(d)

The Division shall be notified when any new or remanufactured RMFD is placed in service at a

new or existing installation.

(1)

Notification shall be submitted using a placed in service report provided by the Division.

(e)

No owner/operator of any RMFD shall use the RMFD for the measurement of hydrogen unless it

has been proved in a manner acceptable to the Division and sealed as correct by a state

inspector or registered service agency (RSA).

(1)

All RMFDs shall be proved and sealed as correct on an annual basis by either a state

inspector or RSA.

(f)

Means shall be provided at the hydrogen fueling facility to return all hydrogen product used for

proving meters back to the storage equipment or the facility’s hydrogen vent system when

proving is completed.

(g)

If any RMFD fails to comply with any of the provisions of this regulation, a state inspector shall

seal it in such a manner as to prohibit its use and it shall remain sealed until it complies with all of

the provisions of this regulation.

(1)

When an RMFD is brought back into compliance with this regulation, it must be placed

back in service by a state inspector or RSA.

(h)

All RMFDs shall comply with the minimum standards as prescribed by the applicable sections of

the codes incorporated by this regulation except as modified or rejected by this regulation or by

the Division.

Section 3-3

Retail Motor Fuel Dispensers for Hydrogen

(a)

The symbol for hydrogen vehicle fuel shall be the capital letter “H” (the word “Hydrogen” may also

be used).

CODE OF COLORADO REGULATIONS

7 CCR 1101-17

Division of Oil and Public Safety

7

prescribed by the applicable sections of

the codes incorporated by this regulation except as modified or rejected by this regulation or by

the Division.

Section 3-3

Retail Motor Fuel Dispensers for Hydrogen

(a)

The symbol for hydrogen vehicle fuel shall be the capital letter “H” (the word “Hydrogen” may also

be used).

CODE OF COLORADO REGULATIONS

7 CCR 1101-17

Division of Oil and Public Safety

7

(b)

Each RMFD of hydrogen shall be labeled with the product identity shown in a conspicuous

location on the dispenser, using the symbol for hydrogen vehicle fuel (the capital letter “H” or the

word “Hydrogen”).

(c)

Hydrogen shall be labeled in accordance with 16 CFR 309, “FTC Labeling Alternative Fuels.”

(d)

NFPA labeling requirements also apply; refer to NFPA 2.

(e)

All Hydrogen kept, offered or available for sale or sold at retail as a vehicle fuel shall be in units of

mass (kilograms).

(f)

A computing dispenser must display the unit price in whole cents on the basis of price per

kilogram (e.g., $3.49 per kg, not $3.499 per kg).

(g)

The service pressure(s) of the dispenser must be conspicuously shown on the user interface bar

or the SI unit of pascal (Pa) (e.g., MPa).

Section 3-4

Street Sign Prices and Advertisements

(a)

The unit price must be in terms of price per kilogram in whole cents (e.g., $3.49 per kg, not

$3.499 per kg).

(b)

The sign or advertisement must include the service pressure (expressed in megapascals) at

which the dispenser(s) delivers hydrogen fuel (e.g., H35 or H70).

Section 3-5

Product Quality

(a)

Hydrogen Fuel shall meet the latest version of SAE J2719, “Hydrogen Fuel Quality for Fuel Cell

Vehicles.”

(b)

All equipment, including filters and strainers, used to prevent any foreign material, including

compressor oil or water, from being dispensed into a motor vehicle shall be periodically serviced

and maintained.

er(s) delivers hydrogen fuel (e.g., H35 or H70).

Section 3-5

Product Quality

(a)

Hydrogen Fuel shall meet the latest version of SAE J2719, “Hydrogen Fuel Quality for Fuel Cell

Vehicles.”

(b)

All equipment, including filters and strainers, used to prevent any foreign material, including

compressor oil or water, from being dispensed into a motor vehicle shall be periodically serviced

and maintained.

(c)

Any shipper of hydrogen fuel products to be used for retail motor fuel who ships such product into

the state of Colorado or ships hydrogen fuel products from one point within the state to another

point within the state shall make records of such shipments available to the Division upon

request.

ARTICLE 4

DELIVERY INTO RETAIL HYDROGEN SYSTEMS

No owner/operator of a retail hydrogen fueling facility shall allow hydrogen to be delivered into the

following:

(a)

An improperly-installed container assembly or piping system installed at a hydrogen fueling

facility.

(b)

A container installed at a hydrogen fueling facility that does not have a proper ASME nameplate.

CODE OF COLORADO REGULATIONS

7 CCR 1101-17

Division of Oil and Public Safety

8

ARTICLE 5

ACCIDENT REPORTS AND INVESTIGATIONS

Section 5-1

Reportable Accidents

(a)

Accidents, fires, explosions, injuries, damage to property or loss of life resulting from the storage

or dispensing of hydrogen at retail hydrogen fueling facilities shall be reported to the Division

within 24 hours after their occurrence.

(b)

Subsection (a) of this Section includes accidents resulting from the improper use or installation of

compression, storage and dispensing equipment or equipment failure at retail hydrogen fueling

facilities.

(1)

The Division may investigate such occurrences and shall maintain a written record of

findings, which shall be available for public examination.

Section 5-2

Reporting Requirements

rence.

(b)

Subsection (a) of this Section includes accidents resulting from the improper use or installation of

compression, storage and dispensing equipment or equipment failure at retail hydrogen fueling

facilities.

(1)

The Division may investigate such occurrences and shall maintain a written record of

findings, which shall be available for public examination.

Section 5-2

Reporting Requirements

(a)

The owner/operator or other representative of the retail hydrogen fueling facility is required to

notify the Division of an accident that meets any of the criteria of Section 5-1.

(b)

Accidents may be reported by telephone (303-318-8547), or email

(cdle_oil_inspection@state.co.us).

(c)

The accident report shall include, at minimum, the following information:

(1)

The names of the owner/operator and person making the report and their telephone

numbers.

(2)

The date, time and location of the accident.

(3)

The number of fatalities and personal injuries.

(4)

All other significant facts known by the person making the report that are relevant to the

cause of the accident or extent of the damages.