§ 431.97 Energy efficiency standards and their compliance dates.

FederalRegulations

Ask Donna

How this section applies to your facts.

Title 10 CFR: Energy › Chapter II: DEPARTMENT OF ENERGY › Part 431: ENERGY EFFICIENCY PROGRAM FOR CERTAIN COMMERCIAL AND INDUSTRIAL EQUIPMENT › Subpart F: Commercial Air Conditioners and Heat Pumps › § 431.97: § 431.97 Energy efficiency standards and their compliance dates.

This text was captured on Aug 14, 2026. It is a snapshot, not a live feed, so check the official code before relying on it.

Text

(a) All basic models of commercial package air conditioning and heating equipment must be tested for performance using the applicable DOE test procedure in § 431.96, be compliant with the applicable standards set forth in paragraphs (b) through (i) of this section, and be certified to the Department under 10 CFR part 429.

(b) Each air-cooled commercial package air conditioning and heating equipment (excluding air-cooled equipment with cooling capacity less than 65,000 Btu/h and double-duct air conditioners or heat pumps) manufactured on or after January 1, 2023, and before January 1, 2029, must meet the applicable minimum energy efficiency standard level(s) set forth in table 1 to this paragraph (b). Each air-cooled commercial package air conditioning and heating equipment (excluding air-cooled equipment with cooling capacity less than 65,000 Btu/h and double-duct air conditioners or heat pumps) manufactured on or after January 1, 2029, must meet the applicable minimum energy efficiency standard level(s) set forth in table 2 to this paragraph (b). Each water-cooled commercial package air conditioning and heating equipment manufactured on or after the compliance date listed in table 3 to this paragraph (b) must meet the applicable minimum energy efficiency standard level(s) set forth in table 3. Each evaporatively-cooled commercial air conditioning and heating equipment manufactured on or after the compliance date listed in table 4 to this paragraph (b) must meet the applicable minimum energy efficiency standard level(s) set forth in table 4. Each double-duct air conditioner or heat pump manufactured on or after January 1, 2010, must meet the applicable minimum energy efficiency standard level(s) set forth in table 5 to this paragraph (b)

ng and heating equipment manufactured on or after the compliance date listed in table 4 to this paragraph (b) must meet the applicable minimum energy efficiency standard level(s) set forth in table 4. Each double-duct air conditioner or heat pump manufactured on or after January 1, 2010, must meet the applicable minimum energy efficiency standard level(s) set forth in table 5 to this paragraph (b).

Table 1 to Paragraph (

b

)—Minimum Efficiency Standards for Air-Cooled Commercial Package Air Conditioning and Heating Equipment With a Cooling Capacity Greater Than or Equal to 65,000 Btu/

h

(Excluding Double-Duct Air-Conditioners and Heat Pumps)

Cooling capacity

Subcategory

Supplementary heating type

Minimum

efficiency

1

Compliance date: equipment

manufactured

starting on . . .

Air-Cooled Commercial Package Air Conditioning and Heating Equipment With a Cooling Capacity Greater Than or Equal to 65,000 Btu/h (Excluding Double-Duct Air Conditioners and Heat Pumps)

≥65,000 Btu/h and <135,000 Btu/h

AC

Electric Resistance Heating or No Heating

IEER = 14.8

January 1, 2023.

≥65,000 Btu/h and <135,000 Btu/h

AC

All Other Types of Heating

IEER = 14.6

January 1, 2023.

≥65,000 Btu/h and <135,000 Btu/h

HP

Electric Resistance Heating or No Heating

IEER = 14.1

COP = 3.4

January 1, 2023.

≥65,000 Btu/h and <135,000 Btu/h

HP

All Other Types of Heating

IEER = 13.9

COP = 3.4

January 1, 2023.

≥135,000 Btu/h and <240,000 Btu/h

AC

Electric Resistance Heating or No Heating

IEER = 14.2

January 1, 2023.

≥135,000 Btu/h and <240,000 Btu/h

AC

All Other Types of Heating

IEER = 14.0

January 1, 2023.

≥135,000 Btu/h and <240,000 Btu/h

HP

Electric Resistance Heating or No Heating

IEER = 13.5

COP = 3.3

January 1, 2023.

≥135,000 Btu/h and <240,000 Btu/h

HP

All Other Types of Heating

IEER = 13.3

COP = 3.3

January 1, 2023.

≥240,000 Btu/h and <760,000 Btu/h

AC

Electric Resistance Heating or No Heating

IEER = 13.2

January 1, 2023.

≥240,000 Btu/h and <760,000 Btu/h

AC

All Other Types of Heating

IEER = 13.0

January 1, 2023

240,000 Btu/h

HP

Electric Resistance Heating or No Heating

IEER = 13.5

COP = 3.3

January 1, 2023.

≥135,000 Btu/h and <240,000 Btu/h

HP

All Other Types of Heating

IEER = 13.3

COP = 3.3

January 1, 2023.

≥240,000 Btu/h and <760,000 Btu/h

AC

Electric Resistance Heating or No Heating

IEER = 13.2

January 1, 2023.

≥240,000 Btu/h and <760,000 Btu/h

AC

All Other Types of Heating

IEER = 13.0

January 1, 2023.

≥240,000 Btu/h and <760,000 Btu/h

HP

Electric Resistance Heating or No Heating

IEER = 12.5

COP = 3.2

January 1, 2023.

≥240,000 Btu/h and <760,000 Btu/h

HP

All Other Types of Heating

IEER = 12.3

COP = 3.2

January 1, 2023.

1

See section 3 of appendix A to this subpart for the test conditions upon which the COP standards are based.

Table 2 to Paragraph (

b

)—Updated Minimum Efficiency Standards for Air-Cooled Commercial Package Air Conditioning and Heating Equipment With a Cooling Capacity Greater Than or Equal to 65,000 Btu/

h

(Excluding Double-Duct Air Conditioners and Heat Pumps)

Cooling capacity

Subcategory

Supplementary heating type

Minimum efficiency

Compliance date: equipment

manufactured

starting on . . .

Air-Cooled Commercial Package Air Conditioning and Heating Equipment With a Cooling Capacity Greater Than or Equal to 65,000 Btu/h (Excluding Double-Duct Air Conditioners and Heat Pumps)

≥65,000 Btu/h and <135,000 Btu/h

AC

Electric Resistance Heating or No Heating

IVEC = 14.3

January 1, 2029.

≥65,000 Btu/h and <135,000 Btu/h

AC

All Other Types of Heating

IVEC = 13.8

January 1, 2029.

≥65,000 Btu/h and <135,000 Btu/h

HP

All Types of Heating

IVEC = 13.4

IVHE = 6.2

January 1, 2029.

≥135,000 Btu/h and <240,000 Btu/h

AC

Electric Resistance Heating or No Heating

IVEC = 13.8

January 1, 2029.

≥135,000 Btu/h and <240,000 Btu/h

AC

All Other Types of Heating

IVEC = 13.3

January 1, 2029.

≥135,000 Btu/h and <240,000 Btu/h

HP

All Types of Heating

IVEC = 13.1

IVHE = 6.0

January 1, 2029.

≥240,000 Btu/h and <760,000 Btu/h

AC

Electric Resistance Heating or No Heating

IVEC = 12.9

January 1, 2029

000 Btu/h and <240,000 Btu/h

AC

Electric Resistance Heating or No Heating

IVEC = 13.8

January 1, 2029.

≥135,000 Btu/h and <240,000 Btu/h

AC

All Other Types of Heating

IVEC = 13.3

January 1, 2029.

≥135,000 Btu/h and <240,000 Btu/h

HP

All Types of Heating

IVEC = 13.1

IVHE = 6.0

January 1, 2029.

≥240,000 Btu/h and <760,000 Btu/h

AC

Electric Resistance Heating or No Heating

IVEC = 12.9

January 1, 2029.

≥240,000 Btu/h and <760,000 Btu/h

AC

All Other Types of Heating

IVEC = 12.2

January 1, 2029.

≥240,000 Btu/h and <760,000 Btu/h

HP

All Types of Heating

IVEC = 12.1

IVHE = 5.8

January 1, 2029.

Table 3 to Paragraph (

b

)—Minimum Cooling Efficiency Standards for Water-Cooled Commercial Package Air Conditioning Equipment

Cooling capacity

Supplementary heating type

Minimum efficiency

Compliance date: equipment

manufactured

starting on . . .

Water-Cooled Commercial Package Air Conditioning Equipment

<65,000 Btu/h

All

EER = 12.1

October 29, 2003.

≥65,000 Btu/h and <135,000 Btu/h

No Heating or Electric Resistance Heating

EER = 12.1

June 1, 2013.

≥65,000 Btu/h and <135,000 Btu/h

All Other Types of Heating

EER = 11.9

June 1, 2013.

≥135,000 Btu/h and <240,000 Btu/h

No Heating or Electric Resistance Heating

EER = 12.5

June 1, 2014.

≥135,000 Btu/h and <240,000 Btu/h

All Other Types of Heating

EER = 12.3

June 1, 2014.

≥240,000 Btu/h and <760,000 Btu/h

No Heating or Electric Resistance Heating

EER = 12.4

June 1, 2014.

≥240,000 Btu/h and <760,000 Btu/h

All Other Types of Heating

EER = 12.2

June 1, 2014.

Table 4 to Paragraph (

b

)—Minimum Cooling Efficiency Standards for Evaporatively-Cooled Commercial Package Air Conditioning Equipment

Cooling capacity

Supplementary heating type

Minimum efficiency

Compliance date: equipment

manufactured

starting on . . .

Evaporatively-Cooled Commercial Package Air Conditioning Equipment

<65,000 Btu/h

All

EER = 12.1

October 29, 2003.

≥65,000 Btu/h and <135,000 Btu/h

No Heating or Electric Resistance Heating

EER = 12.1

June 1, 2013

Evaporatively-Cooled Commercial Package Air Conditioning Equipment

Cooling capacity

Supplementary heating type

Minimum efficiency

Compliance date: equipment

manufactured

starting on . . .

Evaporatively-Cooled Commercial Package Air Conditioning Equipment

<65,000 Btu/h

All

EER = 12.1

October 29, 2003.

≥65,000 Btu/h and <135,000 Btu/h

No Heating or Electric Resistance Heating

EER = 12.1

June 1, 2013.

≥65,000 Btu/h and <135,000 Btu/h

All Other Types of Heating

EER = 11.9

June 1, 2013.

≥135,000 Btu/h and <240,000 Btu/h

No Heating or Electric Resistance Heating

EER = 12.0

June 1, 2014.

≥135,000 Btu/h and <240,000 Btu/h

All Other Types of Heating

EER = 11.8

June 1, 2014.

≥240,000 Btu/h and <760,000 Btu/h

No Heating or Electric Resistance Heating

EER = 11.9

June 1, 2014.

≥240,000 Btu/h and <760,000 Btu/h

All Other Types of Heating

EER = 11.7

June 1, 2014.

Table 5 to Paragraph (

b

)—Minimum Efficiency Standards for Double-Duct Air Conditioners or Heat Pumps

Cooling capacity

Subcategory

Supplementary heating type

Minimum

efficiency

1

Compliance date: equipment

manufactured

starting on . . .

Double-Duct Air Conditioners or Heat Pumps

≥65,000 Btu/h and <135,000 Btu/h

AC

Electric Resistance Heating or No Heating

EER = 11.2

January 1, 2010.

≥65,000 Btu/h and <135,000 Btu/h

AC

All Other Types of Heating

EER = 11.0

January 1, 2010.

≥65,000 Btu/h and <135,000 Btu/h

HP

Electric Resistance Heating or No Heating

EER = 11.0

COP = 3.3

January 1, 2010.

≥65,000 Btu/h and <135,000 Btu/h

HP

All Other Types of Heating

EER = 10.8

COP = 3.3

January 1, 2010.

≥135,000 Btu/h and <240,000 Btu/h

AC

Electric Resistance Heating or No Heating

EER = 11.0

January 1, 2010.

≥135,000 Btu/h and <240,000 Btu/h

AC

All Other Types of Heating

EER = 10.8

January 1, 2010.

≥135,000 Btu/h and <240,000 Btu/h

HP

Electric Resistance Heating or No Heating

EER = 10.6

COP = 3.2

January 1, 2010.

≥135,000 Btu/h and <240,000 Btu/h

HP

All Other Types of Heating

EER = 10.4

COP = 3.2

January 1, 2010

nd <240,000 Btu/h

AC

Electric Resistance Heating or No Heating

EER = 11.0

January 1, 2010.

≥135,000 Btu/h and <240,000 Btu/h

AC

All Other Types of Heating

EER = 10.8

January 1, 2010.

≥135,000 Btu/h and <240,000 Btu/h

HP

Electric Resistance Heating or No Heating

EER = 10.6

COP = 3.2

January 1, 2010.

≥135,000 Btu/h and <240,000 Btu/h

HP

All Other Types of Heating

EER = 10.4

COP = 3.2

January 1, 2010.

≥240,000 Btu/h and <300,000 Btu/h

AC

Electric Resistance Heating or No Heating

EER = 10.0

January 1, 2010.

≥240,000 Btu/h and <300,000 Btu/h

AC

All Other Types of Heating

EER = 9.8

January 1, 2010.

≥240,000 Btu/h and <300,000 Btu/h

HP

Electric Resistance Heating or No Heating

EER = 9.5

COP = 3.2

January 1, 2010.

≥240,000 Btu/h and <300,000 Btu/h

HP

All Other Types of Heating

EER = 9.3

COP = 3.2

January 1, 2010.

1

See section 3 of appendix A to this subpart for the test conditions upon which the COP standards are based.

(c) Each water-source heat pump manufactured starting on the compliance date listed in table 6 to this paragraph (c) must meet the applicable minimum energy efficiency standard level(s) set forth in this paragraph (c).

Table 6 to Paragraph (

c

)—Minimum Efficiency Standards for Water-Source Heat Pumps (Water-to-Air, Water-Loop)

Cooling capacity

Minimum efficiency

Compliance date: equipment

manufactured starting on . . .

Water-Source Heat Pumps (Water-to-Air, Water-Loop)

<17,000 Btu/h

EER = 12.2

COP = 4.3

October 9, 2015.

≥17,000 Btu/h and <65,000 Btu/h

EER = 13.0

COP = 4.3

October 9, 2015.

≥65,000 Btu/h and <135,000 Btu/h

EER = 13.0

COP = 4.3

October 9, 2015.

andards for Water-Source Heat Pumps (Water-to-Air, Water-Loop)

Cooling capacity

Minimum efficiency

Compliance date: equipment

manufactured starting on . . .

Water-Source Heat Pumps (Water-to-Air, Water-Loop)

<17,000 Btu/h

EER = 12.2

COP = 4.3

October 9, 2015.

≥17,000 Btu/h and <65,000 Btu/h

EER = 13.0

COP = 4.3

October 9, 2015.

≥65,000 Btu/h and <135,000 Btu/h

EER = 13.0

COP = 4.3

October 9, 2015.

(d) Each non-standard size packaged terminal air conditioner (PTAC) and packaged terminal heat pump (PTHP) manufactured on or after October 7, 2010, must meet the applicable minimum energy efficiency standard level(s) set forth in table 7 to this paragraph (d). Each standard size PTAC manufactured on or after October 8, 2012, and before January 1, 2017, must meet the applicable minimum energy efficiency standard level(s) set forth in table 7. Each standard size PTHP manufactured on or after October 8, 2012, must meet the applicable minimum energy efficiency standard level(s) set forth in table 7. Each standard size PTAC manufactured on or after January 1, 2017, must meet the applicable minimum energy efficiency standard level(s) set forth in table 8 to this paragraph (d).

Table 7 to Paragraph (

d

)—Minimum Efficiency Standards for PTAC and PTHP

Equipment type

Category

Cooling capacity

Minimum efficiency

Compliance date: products

manufactured on

and after . . .

PTAC

Standard Size

<7,000 Btu/h

EER = 11.7

October 8, 2012.

2

≥7,000 Btu/h and ≤15,000 Btu/h

EER = 13.8−(0.3 × Cap

1

)

October 8, 2012.

2

>15,000 Btu/h

EER = 9.3

October 8, 2012.

2

Non-Standard Size

<7,000 Btu/h

EER = 9.4

October 7, 2010.

≥7,000 Btu/h and ≤15,000 Btu/h

EER = 10.9−(0.213 × Cap

1

)

October 7, 2010.

>15,000 Btu/h

EER = 7.7

October 7, 2010.

PTHP

Standard Size

<7,000 Btu/h

EER = 11.9

COP = 3.3

October 8, 2012.

≥7,000 Btu/h and ≤15,000 Btu/h

EER = 14.0−(0.3 × Cap

1

)

COP = 3.7−(0.052 × Cap

1

)

October 8, 2012.

>15,000 Btu/h

EER = 9.5

COP = 2.9

October 8, 2012.

Non-Standard Size

<7,000 Btu/h

EER = 9.3

COP = 2.7

October 7, 2010

0 Btu/h and ≤15,000 Btu/h

EER = 10.9−(0.213 × Cap

1

)

October 7, 2010.

>15,000 Btu/h

EER = 7.7

October 7, 2010.

PTHP

Standard Size

<7,000 Btu/h

EER = 11.9

COP = 3.3

October 8, 2012.

≥7,000 Btu/h and ≤15,000 Btu/h

EER = 14.0−(0.3 × Cap

1

)

COP = 3.7−(0.052 × Cap

1

)

October 8, 2012.

>15,000 Btu/h

EER = 9.5

COP = 2.9

October 8, 2012.

Non-Standard Size

<7,000 Btu/h

EER = 9.3

COP = 2.7

October 7, 2010.

≥7,000 Btu/h and ≤15,000 Btu/h

EER = 10.8−(0.213 × Cap

1

)

COP = 2.9−(0.026 × Cap

1

)

October 7, 2010.

>15,000 Btu/h

EER = 7.6

COP = 2.5

October 7, 2010.

1

“Cap” means cooling capacity in thousand Btu/h at 95 °F outdoor dry-bulb temperature.

2

And manufactured before January 1, 2017. See table 8 to this paragraph (d) for updated efficiency standards that apply to this category of equipment manufactured on and after January 1, 2017.

Table 8 to Paragraph (

d

)—Updated Minimum Efficiency Standards for PTAC

Equipment type

Category

Cooling capacity

Minimum efficiency

Compliance date: products

manufactured on

and after . . .

PTAC

Standard Size

<7,000 Btu/h

EER = 11.9

January 1, 2017.

≥7,000 Btu/h and ≤15,000 Btu/h

EER = 14.0−(0.3 × Cap

1

)

January 1, 2017.

>15,000 Btu/h

EER = 9.5

January 1, 2017.

1

“Cap” means cooling capacity in thousand Btu/h at 95 °F outdoor dry-bulb temperature.

(e)(1) Each single package vertical air conditioner and single package vertical heat pump manufactured on or after January 1, 2010, but before October 9, 2015 (for models ≥65,000 Btu/h and <135,000 Btu/h), or October 9, 2016 (for models ≥135,000 Btu/h and <240,000 Btu/h), must meet the applicable minimum energy conservation standard level(s) set forth in this paragraph (e)(1).

Table 9 to Paragraph (

e

)(1)—Minimum Efficiency Standards for Single Package Vertical Air Conditioners and Single Package Vertical Heat Pumps

Equipment type

Cooling capacity

Sub-

category

Efficiency level

Compliance date: products

manufactured on and after . .

000 Btu/h and <240,000 Btu/h), must meet the applicable minimum energy conservation standard level(s) set forth in this paragraph (e)(1).

Table 9 to Paragraph (

e

)(1)—Minimum Efficiency Standards for Single Package Vertical Air Conditioners and Single Package Vertical Heat Pumps

Equipment type

Cooling capacity

Sub-

category

Efficiency level

Compliance date: products

manufactured on and after . . .

Single package vertical air conditioners and single package vertical heat pumps, single-phase and three-phase

<65,000 Btu/h

AC

HP

EER = 9.0

EER = 9.0

COP = 3.0

January 1, 2010.

January 1, 2010.

Single package vertical air conditioners and single package vertical heat pumps

≥65,000 Btu/h and <135,000 Btu/h

AC

HP

EER = 8.9

EER = 8.9

COP = 3.0

January 1, 2010.

January 1, 2010.

Single package vertical air conditioners and single package vertical heat pumps

≥135,000 Btu/h and <240,000 Btu/h

AC

HP

EER = 8.6

EER = 8.6

COP = 2.9

January 1, 2010.

January 1, 2010.

(2) Each single package vertical air conditioner and single package vertical heat pump manufactured on and after October 9, 2015 (for models ≥65,000 Btu/h and <135,000 Btu/h), or October 9, 2016 (for models ≥135,000 Btu/h and <240,000 Btu/h), but before September 23, 2019, must meet the applicable minimum energy conservation standard level(s) set forth in this paragraph (e)(2).

Table 10 to Paragraph (

e

)(2)—Minimum Efficiency Standards for Single Package Vertical Air Conditioners and Single Package Vertical Heat Pumps

Equipment type

Cooling capacity

Sub-

category

Efficiency level

Compliance date: products

manufactured on and after . . .

Single package vertical air conditioners and single package vertical heat pumps, single-phase and three-phase

<65,000 Btu/h

AC

HP

EER = 9.0

EER = 9.0

COP = 3.0

January 1, 2010.

January 1, 2010.

Single package vertical air conditioners and single package vertical heat pumps

≥65,000 Btu/h and <135,000 Btu/h

AC

HP

EER = 10.0

EER = 10.0

COP = 3.0

October 9, 2015.

October 9, 2015

red on and after . . .

Single package vertical air conditioners and single package vertical heat pumps, single-phase and three-phase

<65,000 Btu/h

AC

HP

EER = 9.0

EER = 9.0

COP = 3.0

January 1, 2010.

January 1, 2010.

Single package vertical air conditioners and single package vertical heat pumps

≥65,000 Btu/h and <135,000 Btu/h

AC

HP

EER = 10.0

EER = 10.0

COP = 3.0

October 9, 2015.

October 9, 2015.

Single package vertical air conditioners and single package vertical heat pumps

≥135,000 Btu/h and <240,000 Btu/h

AC

HP

EER = 10.0

EER = 10.0

COP = 3.0

October 9, 2016.

October 9, 2016.

(3) Each single package vertical air conditioner and single package vertical heat pump manufactured on and after September 23, 2019, must meet the applicable minimum energy conservation standard level(s) set forth in this paragraph (e)(3).

Table 11 to Paragraph (

e

)(3)—Updated Minimum Efficiency Standards for Single Package Vertical Air Conditioners and Single Package Vertical Heat Pumps

Equipment type

Cooling capacity

Sub-

category

Efficiency level

Compliance date: products

manufactured on and after . . .

Single package vertical air conditioners and single package vertical heat pumps, single-phase and three-phase

<65,000 Btu/h

AC

HP

EER = 11.0

EER = 11.0

COP = 3.3

September 23, 2019.

September 23, 2019.

Single package vertical air conditioners and single package vertical heat pumps

≥65,000 Btu/h and <135,000 Btu/h

AC

HP

EER = 10.0

EER = 10.0

COP = 3.0

October 9, 2015.

October 9, 2015.

Single package vertical air conditioners and single package vertical heat pumps

≥135,000 Btu/h and <240,000 Btu/h

AC

HP

EER = 10.0

EER = 10.0

COP = 3.0

October 9, 2016.

October 9, 2016.

23, 2019.

September 23, 2019.

Single package vertical air conditioners and single package vertical heat pumps

≥65,000 Btu/h and <135,000 Btu/h

AC

HP

EER = 10.0

EER = 10.0

COP = 3.0

October 9, 2015.

October 9, 2015.

Single package vertical air conditioners and single package vertical heat pumps

≥135,000 Btu/h and <240,000 Btu/h

AC

HP

EER = 10.0

EER = 10.0

COP = 3.0

October 9, 2016.

October 9, 2016.

(f)(1) Each computer room air conditioner with a net sensible cooling capacity less than 65,000 Btu/h manufactured on or after October 29, 2012, and before May 28, 2024 and each computer room air conditioner with a net sensible cooling capacity greater than or equal to 65,000 Btu/h and less than 760,000 Btu/h manufactured on or after October 29, 2013, and before May 28, 2024 must meet the applicable minimum energy efficiency standard level(s) set forth in this paragraph (f)(1).

Table 12 to Paragraph

(f)(1)

—Minimum Efficiency Standards for Computer Room Air Conditioners

Equipment type

Net sensible cooling capacity

Minimum SCOP efficiency

Downflow

Upflow

Air-Cooled

<65,000 Btu/h

2.20

2.09

≥65,000 Btu/h and <240,000 Btu/h

2.10

1.99

≥240,000 Btu/h and <760,000 Btu/h

1.90

1.79

Water-Cooled

<65,000 Btu/h

2.60

2.49

≥65,000 Btu/h and <240,000 Btu/h

2.50

2.39

≥240,000 Btu/h and <760,000 Btu/h

2.40

2.29

Water-Cooled with Fluid Economizer

<65,000 Btu/h

2.55

2.44

≥65,000 Btu/h and <240,000 Btu/h

2.45

2.34

≥240,000 Btu/h and <760,000 Btu/h

2.35

2.24

Glycol-Cooled

<65,000 Btu/h

2.50

2.39

≥65,000 Btu/h and <240,000 Btu/h

2.15

2.04

≥240,000 Btu/h and <760,000 Btu/h

2.10

1.99

Glycol-Cooled with Fluid Economizer

<65,000 Btu/h

2.45

2.34

≥65,000 Btu/h and <240,000 Btu/h

2.10

1.99

≥240,000 Btu/h and <760,000 Btu/h

2.05

1.94

(2) Each computer room air conditioner manufactured on or after May 28, 2024, must meet the applicable minimum energy efficiency standard level(s) set forth in this paragraph (f)(2).

Table 13 to Paragraph

2.04

≥240,000 Btu/h and <760,000 Btu/h

2.10

1.99

Glycol-Cooled with Fluid Economizer

<65,000 Btu/h

2.45

2.34

≥65,000 Btu/h and <240,000 Btu/h

2.10

1.99

≥240,000 Btu/h and <760,000 Btu/h

2.05

1.94

(2) Each computer room air conditioner manufactured on or after May 28, 2024, must meet the applicable minimum energy efficiency standard level(s) set forth in this paragraph (f)(2).

Table 13 to Paragraph

(f)(2)

—Updated Minimum Efficiency Standards for Floor-Mounted Computer Room Air Conditioners

Equipment type

Downflow and upflow ducted

Upflow non-ducted and horizontal flow

Net sensible cooling capacity

Minimum NSenCOP

efficiency

Net sensible cooling capacity

Minimum NSenCOP

efficiency

Downflow

Upflow ducted

Upflow

non-ducted

Horizontal flow

Air-Cooled

<80,000 Btu/h

2.70

2.67

<65,000 Btu/h

2.16

2.65

≥80,000 Btu/h and <295,000 Btu/h

2.58

2.55

≥65,000 Btu/h and <240,000 Btu/h

2.04

2.55

≥295,000 Btu/h and <930,000 Btu/h

2.36

2.33

≥240,000 Btu/h and <760,000 Btu/h

1.89

2.47

Air-Cooled with Fluid Economizer

<80,000 Btu/h

≥80,000 Btu/h and <295,000 Btu/h

2.70

2.58

2.67

2.55

<65,000 Btu/h

≥65,000 Btu/h and <240,000 Btu/h

2.09

1.99

2.65

2.55

≥295,000 Btu/h and <930,000 Btu/h

2.36

2.33

≥240,000 Btu/h and <760,000 Btu/h

1.81

2.47

Water-Cooled

<80,000 Btu/h

2.82

2.79

<65,000 Btu/h

2.43

2.79

≥80,000 Btu/h and <295,000 Btu/h

2.73

2.70

≥65,000 Btu/h and <240,000 Btu/h

2.32

2.68

≥295,000 Btu/h and <930,000 Btu/h

2.67

2.64

≥240,000 Btu/h and <760,000 Btu/h

2.20

2.60

Water-Cooled with Fluid Economizer

<80,000 Btu/h

≥80,000 Btu/h and <295,000 Btu/h

2.77

2.68

2.74

2.65

<65,000 Btu/h

≥65,000 Btu/h and <240,000 Btu/h

2.35

2.24

2.71

2.60

≥295,000 Btu/h and <930,000 Btu/h

2.61

2.58

≥240,000 Btu/h and <760,000 Btu/h

2.12

2.54

Glycol-Cooled

<80,000 Btu/h

2.56

2.53

<65,000 Btu/h

2.08

2.48

≥80,000 Btu/h and <295,000 Btu/h

2.24

2.21

≥65,000 Btu/h and <240,000 Btu/h

1.90

2.18

≥295,000 Btu/h and <930,000 Btu/h

2.21

2.18

≥240,000 Btu/h and <760,000 Btu/h

1.81

2.18

Glycol-Cooled with Fluid Economizer

<80,000 Btu/h

≥80,000 Btu/h and <295,000 Btu/h

2.5

tu/h and <930,000 Btu/h

2.61

2.58

≥240,000 Btu/h and <760,000 Btu/h

2.12

2.54

Glycol-Cooled

<80,000 Btu/h

2.56

2.53

<65,000 Btu/h

2.08

2.48

≥80,000 Btu/h and <295,000 Btu/h

2.24

2.21

≥65,000 Btu/h and <240,000 Btu/h

1.90

2.18

≥295,000 Btu/h and <930,000 Btu/h

2.21

2.18

≥240,000 Btu/h and <760,000 Btu/h

1.81

2.18

Glycol-Cooled with Fluid Economizer

<80,000 Btu/h

≥80,000 Btu/h and <295,000 Btu/h

2.51

2.19

2.48

2.16

<65,000 Btu/h

≥65,000 Btu/h and <240,000 Btu/h

2.00

1.82

2.44

2.10

≥295,000 Btu/h and <930,000 Btu/h

2.15

2.12

≥240,000 Btu/h and <760,000 Btu/h

1.73

2.10

Table 14 to Paragraph

(f)(2)

—Minimum Efficiency Standards for Ceiling-Mounted Computer Room Air Conditioners

Equipment type

Net sensible cooling capacity

Minimum NSenCOP

efficiency

Ducted

Non-ducted

Air-Cooled with Free Air Discharge Condenser

<29,000 Btu/h

2.05

2.08

≥29,000 Btu/h and <65,000 Btu/h

2.02

2.05

≥65,000 Btu/h and <760,000 Btu/h

1.92

1.94

Air-Cooled with Free Air Discharge Condenser and Fluid Economizer

<29,000 Btu/h

2.01

2.04

≥29,000 Btu/h and <65,000 Btu/h

1.97

2

≥65,000 Btu/h and <760,000 Btu/h

1.87

1.89

Air-Cooled with Ducted Condenser

<29,000 Btu/h

1.86

1.89

≥29,000 Btu/h and <65,000 Btu/h

1.83

1.86

≥65,000 Btu/h and <760,000 Btu/h

1.73

1.75

Air-Cooled with Fluid Economizer and Ducted Condenser

<29,000 Btu/h

1.82

1.85

≥29,000 Btu/h and <65,000 Btu/h

1.78

1.81

≥65,000 Btu/h and <760,000 Btu/h

1.68

1.7

Water-Cooled

<29,000 Btu/h

2.38

2.41

≥29,000 Btu/h and <65,000 Btu/h

2.28

2.31

≥65,000 Btu/h and <760,000 Btu/h

2.18

2.2

Water-Cooled with Fluid Economizer

<29,000 Btu/h

2.33

2.36

≥29,000 Btu/h and <65,000 Btu/h

2.23

2.26

≥65,000 Btu/h and <760,000 Btu/h

2.13

2.16

Glycol-Cooled

<29,000 Btu/h

1.97

2

≥29,000 Btu/h and <65,000 Btu/h

1.93

1.98

≥65,000 Btu/h and <760,000 Btu/h

1.78

1.81

Glycol-Cooled with Fluid Economizer

<29,000 Btu/h

1.92

1.95

≥29,000 Btu/h and <65,000 Btu/h

1.88

1.93

≥65,000 Btu/h and <760,000 Btu/h

1.73

1.76

oled with Fluid Economizer

<29,000 Btu/h

2.33

2.36

≥29,000 Btu/h and <65,000 Btu/h

2.23

2.26

≥65,000 Btu/h and <760,000 Btu/h

2.13

2.16

Glycol-Cooled

<29,000 Btu/h

1.97

2

≥29,000 Btu/h and <65,000 Btu/h

1.93

1.98

≥65,000 Btu/h and <760,000 Btu/h

1.78

1.81

Glycol-Cooled with Fluid Economizer

<29,000 Btu/h

1.92

1.95

≥29,000 Btu/h and <65,000 Btu/h

1.88

1.93

≥65,000 Btu/h and <760,000 Btu/h

1.73

1.76

(g)(1) Each variable refrigerant flow air conditioner or heat pump manufactured on or after the compliance date listed in table 15 to this paragraph (g)(1) and prior to January 1, 2024, must meet the applicable minimum energy efficiency standard level(s) set forth in this paragraph (g)(1).

Table 15 to Paragraph (

g

)(1)—Minimum Efficiency Standards for Variable Refrigerant Flow Multi-Split Air Conditioners and Heat Pumps

Equipment type

Cooling

capacity

Heating type

1

Efficiency level

Compliance date: equipment

manufactured

on and after . . .

VRF Multi-Split Air Conditioners (Air-Cooled)

≥65,000 Btu/h and <135,000 Btu/h

No Heating or Electric Resistance Heating

11.2 EER

January 1, 2010.

All Other Types of Heating

11.0 EER

January 1, 2010.

≥135,000 Btu/h and <240,000 Btu/h

No Heating or Electric Resistance Heating

11.0 EER

January 1, 2010.

All Other Types of Heating

10.8 EER

January 1, 2010.

≥240,000 Btu/h and <760,000 Btu/h

No Heating or Electric Resistance Heating

10.0 EER

January 1, 2010.

All Other Types of Heating

9.8 EER

January 1, 2010.

VRF Multi-Split Heat Pumps (Air-Cooled)

≥65,000 Btu/h and <135,000 Btu/h

No Heating or Electric Resistance Heating

11.0 EER, 3.3 COP

January 1, 2010.

All Other Types of Heating

10.8 EER, 3.3 COP

January 1, 2010.

≥135,000 Btu/h and <240,000 Btu/h

No Heating or Electric Resistance Heating

10.6 EER, 3.2 COP

January 1, 2010.

All Other Types of Heating

10.4 EER, 3.2 COP

January 1, 2010.

≥240,000 Btu/h and <760,000 Btu/h

No Heating or Electric Resistance Heating

9.5 EER, 3.2 COP

January 1, 2010.

All Other Types of Heating

9.3 EER, 3.2 COP

January 1, 2010

Other Types of Heating

10.8 EER, 3.3 COP

January 1, 2010.

≥135,000 Btu/h and <240,000 Btu/h

No Heating or Electric Resistance Heating

10.6 EER, 3.2 COP

January 1, 2010.

All Other Types of Heating

10.4 EER, 3.2 COP

January 1, 2010.

≥240,000 Btu/h and <760,000 Btu/h

No Heating or Electric Resistance Heating

9.5 EER, 3.2 COP

January 1, 2010.

All Other Types of Heating

9.3 EER, 3.2 COP

January 1, 2010.

VRF Multi-Split Heat Pumps (Water-Source)

<17,000 Btu/h

Without Heat Recovery

12.0 EER,

4.2 COP

October 29, 2012.

October 29, 2003.

With Heat Recovery

11.8 EER

4.2 COP

October 29, 2012.

October 29, 2003.

≥17,000 Btu/h and <65,000 Btu/h

All

12.0 EER, 4.2 COP

October 29, 2003.

≥65,000 Btu/h and <135,000 Btu/h

All

12.0 EER, 4.2 COP

October 29, 2003.

≥135,000 Btu/h and <760,000 Btu/h

Without Heat Recovery

10.0 EER, 3.9 COP

October 29, 2013.

With Heat Recovery

9.8 EER, 3.9 COP

October 29, 2013.

1

VRF multi-split heat pumps (air-cooled) with heat recovery fall under the category of “All Other Types of Heating” unless they also have electric resistance heating, in which case it falls under the category for “No Heating or Electric Resistance Heating.”

(2) Each variable refrigerant flow air conditioner or heat pump (except air-cooled systems with cooling capacity less than 65,000 Btu/h) manufactured on or after January 1, 2024, must meet the applicable minimum energy efficiency standard level(s) set forth in this paragraph (g)(2).

Table 16 to Paragraph (

g

)(2)—Updated Minimum Efficiency Standards for Variable Refrigerant Flow Multi-Split Air Conditioners and Heat Pumps

Equipment type

Size category

Heating type

Minimum efficiency

VRF Multi-Split Air Conditioners (Air-Cooled)

≥65,000 and <135,000 Btu/h

All

15.5 IEER.

≥135,000 and <240,000 Btu/h

All

14.9 IEER.

≥240,000 Btu/h and <760,000 Btu/h

All

13.9 IEER.

VRF Multi-Split Heat Pumps (Air-Cooled)

≥65,000 and <135,000 Btu/h

Heat Pump without Heat Recovery

14.6 IEER, 3.3 COP.

Heat Pump with Heat Recovery

14.4 IEER, 3.3 COP

nt type

Size category

Heating type

Minimum efficiency

VRF Multi-Split Air Conditioners (Air-Cooled)

≥65,000 and <135,000 Btu/h

All

15.5 IEER.

≥135,000 and <240,000 Btu/h

All

14.9 IEER.

≥240,000 Btu/h and <760,000 Btu/h

All

13.9 IEER.

VRF Multi-Split Heat Pumps (Air-Cooled)

≥65,000 and <135,000 Btu/h

Heat Pump without Heat Recovery

14.6 IEER, 3.3 COP.

Heat Pump with Heat Recovery

14.4 IEER, 3.3 COP.

≥135,000 and <240,000 Btu/h

Heat Pump without Heat Recovery

Heat Pump with Heat Recovery

13.9 IEER, 3.2 COP.

13.7 IEER, 3.2 COP.

≥240,000 Btu/h and <760,000 Btu/h

Heat Pump without Heat Recovery

Heat Pump with Heat Recovery

12.7 IEER, 3.2 COP.

12.5 IEER, 3.2 COP.

VRF Multi-Split Heat Pumps (Water-Source)

<65,000 Btu/h

Heat Pump without Heat Recovery

Heat Pump with Heat Recovery

16.0 IEER, 4.3 COP.

15.8 IEER, 4.3 COP.

≥65,000 and <135,000 Btu/h

Heat Pump without Heat Recovery

Heat Pump with Heat Recovery

16.0 IEER, 4.3 COP.

15.8 IEER, 4.3 COP.

≥135,000 and <240,000 Btu/h

Heat Pump without Heat Recovery

Heat Pump with Heat Recovery

14.0 IEER, 4.0 COP.

13.8 IEER, 4.0 COP.

≥240,000 Btu/h and <760,000 Btu/h

Heat Pump without Heat Recovery

Heat Pump with Heat Recovery

12.0 IEER, 3.9 COP.

11.8 IEER, 3.9 COP.

(h) Each direct expansion-dedicated outdoor air system manufactured on or after the compliance date listed in table 17 to this paragraph (h) must meet the applicable minimum energy efficiency standard level(s) set forth in this paragraph (h).

Table 17 to Paragraph (

h

)—Minimum Efficiency Standards for Direct Expansion-Dedicated Outdoor Air Systems

Equipment

category

Subcategory

Efficiency level

Compliance date: equipment manufactured starting on . . .

Direct expansion-dedicated outdoor air systems

(AC)—Air-cooled without ventilation energy recovery systems

ISMRE2 = 3.8

May 1, 2024.

(AC w/VERS)—Air-cooled with ventilation energy recovery systems

ISMRE2 = 5.0

May 1, 2024.

(ASHP)—Air-source heat pumps without ventilation energy recovery systems

ISMRE2 = 3.8

ISCOP2 = 2.05

May 1, 2024

y level

Compliance date: equipment manufactured starting on . . .

Direct expansion-dedicated outdoor air systems

(AC)—Air-cooled without ventilation energy recovery systems

ISMRE2 = 3.8

May 1, 2024.

(AC w/VERS)—Air-cooled with ventilation energy recovery systems

ISMRE2 = 5.0

May 1, 2024.

(ASHP)—Air-source heat pumps without ventilation energy recovery systems

ISMRE2 = 3.8

ISCOP2 = 2.05

May 1, 2024.

(ASHP w/VERS)—Air-source heat pumps with ventilation energy recovery systems

ISMRE2 = 5.0

ISCOP2 = 3.20

May 1, 2024.

(WC)—Water-cooled without ventilation energy recovery systems

ISMRE2 = 4.7

May 1, 2024.

(WC w/VERS)—Water-cooled with ventilation energy recovery systems

ISMRE2 = 5.1

May 1, 2024.

(WSHP)—Water-source heat pumps without ventilation energy recovery systems

ISMRE2 = 3.8

ISCOP2 = 2.13

May 1, 2024.

(WSHP w/VERS)—Water-source heat pumps with ventilation energy recovery systems

ISMRE2 = 4.6

ISCOP2 = 4.04

May 1, 2024.

(i) Air-cooled, three-phase, commercial package air conditioning and heating equipment with a cooling capacity of less than 65,000 Btu/h and air-cooled, three-phase variable refrigerant flow multi-split air conditioning and heating equipment with a cooling capacity of less than 65,000 Btu/h manufactured on or after the compliance date listed in tables 18 and 19 to this paragraph (i) must meet the applicable minimum energy efficiency standard level(s) set forth in this paragraph (i).

Table 18 to Paragraph (

i

)—Minimum Efficiency Standards for Air-Cooled, Three-Phase, Commercial Package Air Conditioning and Heating Equipment With a Cooling Capacity of Less Than 65,000 Btu/

h

and Air-Cooled, Three-Phase, Small Variable Refrigerant Flow Multi-Split Air Conditioning and Heating Equipment With a Cooling Capacity of Less Than 65,000 Btu/

h

Equipment type

Cooling

capacity

Subcategory

Minimum efficiency

Compliance date: equipment

manufactured

starting on . . .

Commercial Package Air Conditioning Equipment

<65,000 Btu/h

Split-System

13.0 SEER

June 16, 2008

Than 65,000 Btu/

h

and Air-Cooled, Three-Phase, Small Variable Refrigerant Flow Multi-Split Air Conditioning and Heating Equipment With a Cooling Capacity of Less Than 65,000 Btu/

h

Equipment type

Cooling

capacity

Subcategory

Minimum efficiency

Compliance date: equipment

manufactured

starting on . . .

Commercial Package Air Conditioning Equipment

<65,000 Btu/h

Split-System

13.0 SEER

June 16, 2008.

1

Commercial Package Air Conditioning Equipment

<65,000 Btu/h

Single-Package

14.0 SEER

January 1, 2017.

1

Commercial Package Air Conditioning and Heating Equipment

<65,000 Btu/h

Split-System

14.0 SEER

8.2 HSPF

January 1, 2017.

1

Commercial Package Air Conditioning and Heating Equipment

<65,000 Btu/h

Single-Package

14.0 SEER

8.0 HSPF

January 1, 2017.

1

VRF Air Conditioners

<65,000 Btu/h

13.0 SEER

June 16, 2008.

1

VRF Heat Pumps

<65,000 Btu/h

13.0 SEER

7.7 HSPF

June 16, 2008.

1

1

And manufactured before January 1, 2025. For equipment manufactured on or after January 1, 2025, see table 19 to this paragraph (i) for updated efficiency standards.

Table 19 to Paragraph (

i

)—Updated Minimum Efficiency Standards for Air-Cooled, Three-Phase, Commercial Package Air Conditioning and Heating Equipment With a Cooling Capacity of Less Than 65,000 Btu/

h

and Air-Cooled, Three-Phase, Small Variable Refrigerant Flow Multi-Split Air Conditioning and Heating Equipment With a Cooling Capacity of Less Than 65,000 Btu/

h

Equipment type

Cooling

capacity

Subcategory

Minimum efficiency

Compliance date: equipment

manufactured

starting on . . .

Commercial Package Air Conditioning Equipment

<65,000 Btu/h

Split-System

13.4 SEER2

January 1, 2025.

Commercial Package Air Conditioning Equipment

<65,000 Btu/h

Single-Package

13.4 SEER2

January 1, 2025.

Commercial Package Air Conditioning and Heating Equipment

<65,000 Btu/h

Split-System

14.3 SEER2

7.5 HSPF2

January 1, 2025.

Commercial Package Air Conditioning and Heating Equipment

<65,000 Btu/h

Single-Package

13.4 SEER2

6.7 HSPF2

January 1, 2025

000 Btu/h

Split-System

13.4 SEER2

January 1, 2025.

Commercial Package Air Conditioning Equipment

<65,000 Btu/h

Single-Package

13.4 SEER2

January 1, 2025.

Commercial Package Air Conditioning and Heating Equipment

<65,000 Btu/h

Split-System

14.3 SEER2

7.5 HSPF2

January 1, 2025.

Commercial Package Air Conditioning and Heating Equipment

<65,000 Btu/h

Single-Package

13.4 SEER2

6.7 HSPF2

January 1, 2025.

Space-Constrained Commercial Package Air Conditioning Equipment

≤30,000 Btu/h

Split-System

12.7 SEER2

January 1, 2025.

Space-Constrained Commercial Package Air Conditioning Equipment

≤30,000 Btu/h

Single-Package

13.9 SEER2

January 1, 2025.

Space-Constrained Commercial Package Air Conditioning and Heating Equipment

≤30,000 Btu/h

Split-System

13.9 SEER2

7.0 HSPF2

January 1, 2025.

Space-Constrained Commercial Package Air Conditioning and Heating Equipment

≤30,000 Btu/h

Single-Package

13.9 SEER2

6.7 HSPF2

January 1, 2025.

Small-Duct, High-Velocity Commercial Package Air Conditioning

<65,000 Btu/h

Split-System

13.0 SEER2

January 1, 2025.

Small-Duct, High-Velocity Commercial Package Air Conditioning and Heating Equipment

<65,000 Btu/h

Split-System

14.0 SEER2

6.9 HSPF2

January 1, 2025.

VRF Air Conditioners

<65,000 Btu/h

13.4 SEER2

January 1, 2025.

VRF Heat Pumps

<65,000 Btu/h

13.4 SEER2

7.5 HSPF2

January 1, 2025.

[89 FR 44134, May 20, 2024]