Cross connection control
WisconsinRegulations
Ask Donna
How this section applies to your facts.
Wisconsin Administrative Code › NR › Chapter NR 80 › § SPS 382.41
Text
Cross connection control.
(1) Scope. The provisions of this section set forth the requirements for the protection of water within water supply systems when and where there is the possibility of contamination due to cross connections or backflow conditions.
(2) Materials.
(a) All methods, devices, and assemblies intended to protect water supply systems from cross connections shall be of a type recognized and approved in accordance with ch. SPS 384 and as described in sub. (4) .
(b) All methods including barometric loops and air gaps intended to protect water supplies relative to cross connection or backflow shall be constructed of materials suitable for water supply systems in accordance with ch. SPS 384 .
(3) General requirements. Water supply systems and the connection of each plumbing fixture, piece of equipment, appliance or nonpotable water piping system shall be designed, installed and maintained in such a manner to prevent the contamination of water supplies by means of cross connections.
(a) Types of cross connection control.
1. Water supply systems shall be protected against contamination due to cross connections or backflow conditions by one of the methods or devices specified in Table 382.41-1 depending upon the situation or Table 382.41-2 depending upon the specific application or use, and the limitations specified in sub. (4) .
2. For the situations described in par. (b) 3. , cross connection control shall be provided as part of the fixture fitting outlet or in the water supply piping for the fixture fitting outlet.
nditions by one of the methods or devices specified in Table 382.41-1 depending upon the situation or Table 382.41-2 depending upon the specific application or use, and the limitations specified in sub. (4) .
2. For the situations described in par. (b) 3. , cross connection control shall be provided as part of the fixture fitting outlet or in the water supply piping for the fixture fitting outlet.
(b) Classifications. For the purposes of this section:
1. The designation of a high hazard or low hazard situation shall be determined on the basis of how a toxic or nontoxic solution is intended or recommended by the manufacturer of the solution to interface with the potable water supply system.
2.
a. A continuous pressure situation shall be considered to exist when a pressure greater than atmospheric within the water supply system exists for more than 12 continuous hours.
b. A noncontinuous pressure situation shall be considered to exist if the conditions in subd. 2. a. do not occur.
3. A high hazard cross connection situation shall be considered to exist for a connection of the water supply system to:
a. Any part of the drain system; and
b. Any other piping system conveying water from nonpotable sources, including but not limited to lakes, rivers, streams or creeks.
4. Except as provided in subd. 5. , a high hazard cross connection situation shall be considered to exist at:
a. A water supply hose bibb, faucet, wall hydrant, sill cock or other outlet which terminates with hose threads allowing a hose to be attached;
b. A water supply faucet, wall hydrant or other outlet which terminates with a serrated nipple allowing a hose to be attached;
c. A water supply faucet, hydrant or outlet serving a sink used for building maintenance in a public building;
d. A chemical pot-feeder or automatic chemical feeder is installed to serve a boiler, cooling tower or chilled water system; and
e. In the water supply piping connecting to the outlet of a fire hydrant for any purpose other than fire fighting.
5
ated nipple allowing a hose to be attached;
c. A water supply faucet, hydrant or outlet serving a sink used for building maintenance in a public building;
d. A chemical pot-feeder or automatic chemical feeder is installed to serve a boiler, cooling tower or chilled water system; and
e. In the water supply piping connecting to the outlet of a fire hydrant for any purpose other than fire fighting.
5. A cross connection may not be considered to exist at the hose threaded outlet installed for the sole purpose of any of the following:
a. Draining a water supply system or any portion thereof.
bm. Connecting individual portable dialysis machines when enclosed in a lockable box.
c. Connecting individual residential-type automatic clothes washers or dryers.
6.
a. A high hazard situation shall be considered to exist for the connection of 2 water supply systems one supplied by a public water supply and the other system supplied by a private well.
b. Cross connection control devices used in conjunction with automatic fire sprinkler systems shall be listed by an acceptable testing agency for such an application under the standards governing the design and installation of automatic fire sprinkler systems.
7. A cross connection situation shall not be considered to exist when a multipurpose piping system serves a one- or 2- family dwelling provided the sprinkler system is constructed of materials and joints suitable for water distribution systems as specified in ss. SPS 384.30 (4) (e) and 384.40 , respectively.
r the standards governing the design and installation of automatic fire sprinkler systems.
7. A cross connection situation shall not be considered to exist when a multipurpose piping system serves a one- or 2- family dwelling provided the sprinkler system is constructed of materials and joints suitable for water distribution systems as specified in ss. SPS 384.30 (4) (e) and 384.40 , respectively.
(c) Containment.
1. For sewerage treatment facilities which are required to conform with ch. NR 110 , in addition to the cross connection control required for each potable water usage or water outlet, a reduced pressure principle backflow preventer shall be installed:
a. In the water service to each building or structure within the complex;
b. In the private water main upstream of all water services serving the facility; or
c. In the water distribution system upstream of all water outlets and in the process piping network upstream of all points of use, if both a water distribution system and a process network is contained within the same building or structure.
2. For marinas, wharves and docks where potable water outlets are provided to serve boats or ships, in addition to the cross connection control required for each potable water outlet or usage, a reduced pressure principle backflow preventer shall be installed in the water supply system to limit backflow into the water supply source.
3. The installation of a cross connection control device in the water supply system for a building or structure shall not alleviate the requirement to provide cross connection control for the connection of each plumbing fixture, piece of equipment, appliance or other piping system.
(d) Prohibitions.
1. The use of a toxic solution as a heat transfer fluid in single-wall heat exchanger for potable water is prohibited.
2. A cross connection control method, device, or assembly may not be bypassed without a cross connection control method, device, or assembly of at least equal protection.
e connection of each plumbing fixture, piece of equipment, appliance or other piping system.
(d) Prohibitions.
1. The use of a toxic solution as a heat transfer fluid in single-wall heat exchanger for potable water is prohibited.
2. A cross connection control method, device, or assembly may not be bypassed without a cross connection control method, device, or assembly of at least equal protection.
(e) Existing automatic fire sprinkler systems. An alteration, modification or addition to an existing automatic fire sprinkler shall necessitate conformance with this section, if the:
1. Existing water supply line to the existing sprinkler system is increased in diameter; or
2. Existing device or method which had been previously recognized to address cross connection concerns is to be removed or replaced.
(4) Limitations.
(a) Cross connection control devices shall be limited in use in accordance with the respective standard, unless otherwise specifically permitted under this subsection.
(b)
1. Except as provided in pars. (b) 2. and (o) , an atmospheric-type vacuum breaker shall be installed such that the bottom of the device or the critical level mark on the device is at least 6 inches above all of the following:
a. The flood level rim of the receptor serving the water supply port.
b. The highest point downstream from the device where backpressure would be created.
c. The highest point of an injection or aspiration port.
2. A deck-mounted atmospheric type vacuum breaker shall be installed such that the bottom of the device or the critical level mark on the device is at least 1 inch above all of the following:
a. The flood level rim of the receptor serving the water supply port.
b. The highest point downstream from the device where backpressure would be created.
c. The highest point of an injection or aspiration port.
This is a copy of a public record, reproduced as it was published. It is not legal advice, and it may not be the version a court would rely on. Check the official source before you cite it.