WAC 194-50-060. ASHRAE Standard 100, 2018 — Section 6 — Operations and maintenance requirements
WashingtonRegulations
Ask Donna
How this section applies to your facts.
Washington Administrative Code › Title 194 › Chapter 194-50 › Section 194-50-060
Text
6.3 Operation and maintenance (O&M) Implementation. The O&M program shall be implemented in accordance with Normative Annex L.
Exception to 6.3: O&M programs developed and implemented by the building's serving utility or local government and approved as equivalent or more stringent by the AHJ may be used as an alternative to the requirement in Section 6.3. Where local government programs are more stringent than applicable utility programs, local government programs shall be selected over utility programs.
6.6.1 When HVAC, domestic hot-water heating, or refrigeration equipment or appliances are replaced, the replacement equipment shall meet all applicable energy efficiency requirements in the federal equipment standards, state equipment standards , and the applicable building code .
Exception to 6.6.1 - Not adopted.
6.6.2.1 When lighting equipment is replaced, the replacement equipment shall meet all applicable energy efficiency requirements in the federal equipment standards, state equipment standards and in the applicable building code . Implementation of more efficient equipment shall be evaluated and included as specified for the capital management plan , Section 5.1.2.10.
Exception to 6.6.2.2: The existing installed lighting power may proportionally increase when the current light levels are below those recommended in the IES Lighting Handbook 4 or latest version of the Washington State Energy Code.
This is a copy of a public record, reproduced as it was published. It is not legal advice, and it may not be the version a court would rely on. Check the official source before you cite it.