501 KAR 3:070. Safety; emergency procedures

KentuckyRegulations

Ask Donna

How this section applies to your facts.

Kentucky Administrative Regulations › Title 501 (Justice and Public Safety Cabinet - Department of Corrections) › Chapter 003 › 501 KAR 3:070

This text was captured on Aug 14, 2026. It is a snapshot, not a live feed, so check the official code before relying on it.

Text

Section 1. Policy and Procedure. (1) Each jail shall have a written policy and procedure that specifies fire prevention practices to provide for the safety of prisoners, visitors, and jail employees. The policy shall include: (a) A fire emergency planning session for jail employees at least quarterly; (b) Maintaining written documentation of the fire planning session including evacuation, fire drills, and other procedures covered during the session; (c) A fire safety inspection by the department at least once a year; (d) Inspection and testing of fire protection equipment by a qualified person at least annually with visual inspections by jail employees monthly; (e) Being a tobacco-free facility; and (f) An evacuation plan coordinated with local fire officials and approved by the department. (2) Each jail shall have written policy and procedures for emergency situations including: (a) Escape; (b) Hostage taking; (c) Riot; (d) Food poisoning; (e) Civil disturbance in the community; (f) Natural disaster; (g) Suicide; (h) Other death and disorder; and (i) Mass evacuation disaster plan. Section 2. Physical Plant. (1) Each jail shall comply with the Kentucky Building Code, incorporated by reference in 815 KAR 7:120. An existing jail for which approval has been granted may continue without change, except if a significant alteration, addition or change of occupancy occurs. (2) Each exit shall be: (a) Distinctly and permanently marked; (b) Visible at all times; (c) Kept clear; and (d) Maintained in usable condition. (3) Each jail shall have equipment necessary to maintain essential lights, power, HVAC, and communications in an emergency situation. (4) In each area where a prisoner may be confined, there shall be an emergency smoke control system activated by smoke detectors and operated by emergency power. Inspection and testing of the smoke control system shall be conducted by a qualified person at least annually. (5) Each jail shall have a fire alarm and smoke detection system

ts, power, HVAC, and communications in an emergency situation. (4) In each area where a prisoner may be confined, there shall be an emergency smoke control system activated by smoke detectors and operated by emergency power. Inspection and testing of the smoke control system shall be conducted by a qualified person at least annually. (5) Each jail shall have a fire alarm and smoke detection system. (6) Each direct supervision area shall have an automatic fire extinguishing system.

This is a copy of a public record, reproduced as it was published. It is not legal advice, and it may not be the version a court would rely on. Check the official source before you cite it.

A word about cookies

We need a few to keep you signed in and the library working. The rest help us see which pages people use and where they get stuck. They stay off unless you say yes.

501 KAR 3:070. Safety; emergency procedures · 501 KAR 3:070 | Frix