Section 2007.8 General Requirements for Day Care Homes
IllinoisRegulations
Ask Donna
How this section applies to your facts.
Illinois Administrative Code › Title 23 › › Part 20070 › Section 2007.8 General Requirements for Day Care Homes
Text
Section 406
TITLE 23: EDUCATION AND CULTURAL RESOURCES
SUBTITLE A: EDUCATION
CHAPTER XI: DEPARTMENT OF EARLY CHILDHOOD
PART 2007 LICENSING STANDARDS FOR DAY CARE HOMES
SECTION 2007.8 GENERAL REQUIREMENTS FOR DAY CARE HOMES
Section 2007.8 General
Requirements for Day Care Homes
a) The physical facilities of the home, both indoors and
outdoors, shall meet the following requirements for safety to children.
1) The home shall have a first aid kit consisting of adhesive
bandages, scissors, thermometer, non-permeable gloves, Poison Control Center
telephone number (1-800-222-1222
or
1-800-942-5969), sterile gauze pads, adhesive tape, tweezers and mild soap.
2) The kitchen shall be equipped with a readily accessible and operable
fire extinguisher rated for Class A, B, and C fires and a flashlight in working
order.
3) All electrical outlets that are in areas used by the day care
children shall have protective coverings. There shall be no exposed or
uninsulated wiring.
4) The home shall be equipped with a minimum of one approved smoke
detector in operating condition on every floor level, including basements and
occupied attics.
A) A smoke detector in operating condition shall be within each
room where children nap or sleep.
The detector shall be installed on the
ceiling and at least 6 inches from any wall, or on a wall located between 4 and
6 inches from the ceiling.
In addition, there shall be at least one
detector at the beginning and end of each separate corridor or hallway 200 feet
or more in length in any occupied story.
B)
In any facility constructed after December 31, 1987, or
which undergoes substantial remodeling of its structure or wiring system after
that date, the smoke detectors shall be permanently wired into the structure's
AC power line, and, if more than one detector is required to be installed, the
detectors shall be wired so that the activation of one detector will activate
all the detectors in the facility unit
y constructed after December 31, 1987, or
which undergoes substantial remodeling of its structure or wiring system after
that date, the smoke detectors shall be permanently wired into the structure's
AC power line, and, if more than one detector is required to be installed, the
detectors shall be wired so that the activation of one detector will activate
all the detectors in the facility unit.
For purposes of this subsection
(a)(4), "substantial remodeling" represents more than 15% of the replacement
cost of the day care home. For homes that did not have wired installation of
smoke detectors in each room prior to December 15, 2011, the Department may
allow the installation of a battery-operated smoke detector in each room where
children nap or sleep and deem the home to be in compliance.
C)
Compliance with any applicable federal, State or local law,
rule or building code which requires the installation and maintenance of smoke
detectors in a manner different from this Section, but providing a level of
safety for occupants which is equal to or greater than that provided by this
Section, shall be deemed to be compliance with this Section.
(Section 2 of
the Facilities Requiring Smoke Detectors Act [425 ILCS 10/2])
D) For homes constructed after December 15, 2011, or that underwent
substantial remodeling of structure or wiring systems after December 15, 2011,
the smoke detectors shall be permanently wired into the structure's AC power
line and, if more than one detector is required to be installed, the detectors
shall be wired so that the activation of one detector will activate all the
detectors in the facility unit.
5) Carbon
Monoxide Detector
A) A home
that has an attached garage and/or relies
on combustion of fossil fuel for
heating, ventilation, or hot water shall be equipped with
a minimum of
one
approved carbon monoxide detector in operating condition
within 15 feet
of rooms
where children nap or sleep
e activation of one detector will activate all the
detectors in the facility unit.
5) Carbon
Monoxide Detector
A) A home
that has an attached garage and/or relies
on combustion of fossil fuel for
heating, ventilation, or hot water shall be equipped with
a minimum of
one
approved carbon monoxide detector in operating condition
within 15 feet
of rooms
where children nap or sleep.
B)
The
carbon monoxide detector may be combined with smoke detector devices, provided
that the combined unit complies with
subsection (a)(4) and this subsection
(a)(5). [430 ILCS 135/10]
6) The home and indoor space shall be maintained in good repair
and shall provide a safe, comfortable environment for the children.
7) A
draft-free temperature of 65ºF to 75ºF shall be maintained during the winter
months or heating season. For infants and toddlers, a temperature of 68ºF
to 82ºF shall be maintained during the summer or air-conditioning months. When
the temperature in the home exceeds 78ºF, measures shall be taken to cool the
children. Temperatures shall be measured at least 3 feet above the floor.
8) Fixed space heaters, fireplaces, radiators, and other heating
sources in areas occupied by children shall be separated by partitions or a
sturdy barrier to prevent contact. Portable space heaters may not be used in a
day care home during the hours that child care is provided.
9) Facilities in which a wood-burning stove or fireplace has been
installed and which is used during the hours that child care is provided shall
provide a written plan of how the stove or fireplace will be used and what
actions will be taken to ensure the children's safety when in use.
10) When the basement area may be used for child care, 2 exits
shall be provided
is provided.
9) Facilities in which a wood-burning stove or fireplace has been
installed and which is used during the hours that child care is provided shall
provide a written plan of how the stove or fireplace will be used and what
actions will be taken to ensure the children's safety when in use.
10) When the basement area may be used for child care, 2 exits
shall be provided.
A) At least one exit shall be a basement exit via a door directly
to the outside (without traversing any other level of the home) or a protected
exit from a basement via a door or stairway that allows unobstructed travel directly
to the outside of the building at street or ground level. The stairway may not
be more than 8 feet high.
B) A second exit may be a window.
i) The window shall be operable from the inside without the use
of tools and provide a clear opening not less than 20 inches in width, 24
inches in height, and 5.7 square feet in area.
ii) If the window is used as a second exit, the bottom of the
window opening shall be no more than 44 inches above the floor.
iii) When the bottom of the window opening used as a second exit
is greater than 24 inches above the floor, there shall be a permanently
affixed, sturdy ramp or stairs located below the window to allow speedy access
in the event of an emergency.
C) If the basement area does not meet the requirements in
subsections (a)(10)(A) and (B), the basement may be used for child care only
with the prior written approval of OSFM.
11) All walls and surfaces shall be maintained free from lead
paint and from chipped or peeling paint.
12) Walls of rooms that children use shall be free of carpeting,
fabric or plastic products. Inflammable or combustible artwork attached to the
walls shall not exceed 20% of any wall area.
13) Furniture and equipment shall be kept in safe repair
itten approval of OSFM.
11) All walls and surfaces shall be maintained free from lead
paint and from chipped or peeling paint.
12) Walls of rooms that children use shall be free of carpeting,
fabric or plastic products. Inflammable or combustible artwork attached to the
walls shall not exceed 20% of any wall area.
13) Furniture and equipment shall be kept in safe repair.
14) First aid supplies, medication, cleaning materials, poisons,
sharp scissors, plastic bags, sharp knives, cigarettes, matches, lighters,
flammable liquids, and other hazardous materials shall be stored in places
inaccessible to children. Hazardous items for infants and toddlers also
include items that can cause choking, including but not limited to: coins,
balloons, safety pins, marbles, Styrofoam
™
and similar products, and
sponge, soft rubber or soft plastic toys that can be bitten or broken into
small pieces.
15) Tools and gardening equipment shall be stored in locked
cabinets, if possible, or in places inaccessible to all children.
16) An operable telephone shall be available on the premises of
the licensee. The number of the Poison Control Center (1-800-222-1222 or 1‑800-942-5969)
and other emergency numbers shall be posted in an area that is readily
available in an emergency.
17)
Handguns are prohibited on the premises of the day care
home except in the possession of peace officers or other adults who must
possess a handgun as a condition of employment and who reside in the day care
home.
The licensee shall post a "no firearms" sign, as described
in Section 65(d) of
the Firearm Concealed
Carry Act
[430 ILCS 66/65(d)], in a visible location where parents pick
up children.
18)
Any firearm, other than a handgun in the possession of a
peace officer or other person as provided
in subsection (a)(17)
, shall
be kept in a disassembled state, without ammunition, in locked storage in a
closet, cabinet, or other locked storage facility inaccessible to children
) of
the Firearm Concealed
Carry Act
[430 ILCS 66/65(d)], in a visible location where parents pick
up children.
18)
Any firearm, other than a handgun in the possession of a
peace officer or other person as provided
in subsection (a)(17)
, shall
be kept in a disassembled state, without ammunition, in locked storage in a
closet, cabinet, or other locked storage facility inaccessible to children.
A)
Ammunition for such
firearms
shall be kept in
locked storage separate from that of the disassembled
firearms
,
inaccessible
to children.
B)
The operator of the home shall notify the
parents
or guardian of any child accepted for care that firearms and ammunition are
stored on the premises. The operator shall also notify the
parents
or
guardian that such firearms and ammunition are locked in storage inaccessible
to children.
(Section 7 of the Child Care Act of 1969 [225 ILCS 10/7]) The
notification need not disclose the location where the firearms and ammunition
are stored.
19) Written emergency preparedness plans shall be developed and
shall specify the actions to be taken in the event of a fire, tornado or other
emergency. Caregivers and assistants in the home shall be familiar with these
plans. The emergency preparedness plans shall include, but are not limited to:
A) A fire evacuation plan identifying exits from each area used
for child care and specifying the evacuation route;
B) A fire
evacuation plan identifying a safe assembly area outside of the home
of a fire, tornado or other
emergency. Caregivers and assistants in the home shall be familiar with these
plans. The emergency preparedness plans shall include, but are not limited to:
A) A fire evacuation plan identifying exits from each area used
for child care and specifying the evacuation route;
B) A fire
evacuation plan identifying a safe assembly area outside of the home. It shall
also identify a nearby indoor location for post-evacuation holding if needed;
C) A fire evacuation plan requiring that the home be evacuated immediately
and the children's safety insured before calling the local emergency number 911
or attempting to combat the fire;
D) A
tornado plan specifying actions that will be taken in the event of tornado or
other severe weather warning, including designation of those areas of the home
to be used as safe spots;
E) Specific
procedures for notifying parents if evacuation is necessary and how they will
be reunited with their children;
F) Specific
procedures for evacuating children who are less than 30 months of age and/or
for evacuating special needs children when applicable;
G) Monthly
fire drills to be conducted for the purpose of removing children from the home
as quickly as possible; and
H) Monthly
tornado drills to be conducted for the purpose of getting children accustomed
to moving to a position of safety in the event of a tornado.
20) The licensee shall hold monthly fire safety inspections of
the day care home and maintain documentation on file for a period of 1 year.
21) Fire
and tornado drills shall be documented and that documentation shall be maintained
on file for a period of 3 years.
22) Escape
routes from the home shall be designed and maintained for swift and safe
exiting in the event of an emergency.
A) All
corridors and escape routes from the home shall be kept clear of obstructions
mentation on file for a period of 1 year.
21) Fire
and tornado drills shall be documented and that documentation shall be maintained
on file for a period of 3 years.
22) Escape
routes from the home shall be designed and maintained for swift and safe
exiting in the event of an emergency.
A) All
corridors and escape routes from the home shall be kept clear of obstructions.
B) Dead-end
paths or corridors within the home shall be a maximum of 20 feet in length.
C) All
escape routes from the home shall have operable lighting. The lighting shall be
activated during any hours of operation when natural lighting is reduced to a
level that prohibits visibility within the escape route.
D) Bathroom
doors in areas accessible to day care children shall allow a caregiver to open
the door from outside of the bathroom if necessary.
E) All
closet doors accessible to children shall be able to be opened from inside of
the closet without the use of a key.
F) There
shall be no more than 2 releasing devices (door knobs, hand-operated deadbolts,
thumb-turn locks, etc.) on any exit door or exit window.
G) Exit
doors and exit windows shall be operable without the use of a key, a tool or
special knowledge to open for exit to the outsid
H) Exit doors and exit windows shall be kept clear of equipment
and debris at all times.
23) The
licensee shall inspect the home daily, prior to arrival of children, ensuring
that escape routes are clear and that exit doors and exit windows are operable.
A log of these daily inspections shall be maintained for at least one year, and
shall be available for review. The log shall reflect, at minimum, the date and
time of each inspection and the full name of the person who conducted it.
24) All in-ground swimming pools located in areas accessible to
children shall be fenced. The fence shall be at least 5 feet in height and
secured by a locked gate
these daily inspections shall be maintained for at least one year, and
shall be available for review. The log shall reflect, at minimum, the date and
time of each inspection and the full name of the person who conducted it.
24) All in-ground swimming pools located in areas accessible to
children shall be fenced. The fence shall be at least 5 feet in height and
secured by a locked gate. Day care homes that have a license or a permit on
April 1, 2001 and are in compliance with the requirement for a 3½ foot fence
shall be considered in compliance with the fence requirement.
25) All above-ground pools shall have non-climbable sidewalls
that are at least 4 feet high or shall be enclosed with a 5 foot fence that is
at least 36 inches away from the pool's side wall and secured with a locked
gate. When the pool is not in use, steps shall be removed from the pool or
otherwise protected to insure the pool cannot be accessed. Day care homes that
have a license or a permit on April 1, 2001 and are in compliance with the
requirement for a 3½ foot fence shall be considered in compliance with the
fence requirement.
26) Portable wading pools shall be emptied daily and disinfected
before being air-dried.
27) All hot tubs shall have securely locked covers or otherwise
be inaccessible to children.
28) Free hanging cords on blinds, shades and drapes shall be tied
or otherwise kept out of reach of children.
29) Effective January 1, 2013, the home shall be tested for radon
at least once every 3 years. The most current radon measurements shall be
posted next to the license in the home, on a form provided by the Department,
containing the required informative statement from Section 5.8(d) of the Child
Care Act of 1969 [225 ILCS 10].
b) The kitchen shall be clean, equipped for the preservation,
storage, preparation and serving of food, and reasonably safe from hazards
e every 3 years. The most current radon measurements shall be
posted next to the license in the home, on a form provided by the Department,
containing the required informative statement from Section 5.8(d) of the Child
Care Act of 1969 [225 ILCS 10].
b) The kitchen shall be clean, equipped for the preservation,
storage, preparation and serving of food, and reasonably safe from hazards.
c) Garbage and refuse containers used to discard diapering
supplies, food products or disposable meal service supplies in areas for child
care shall be disinfected daily unless plastic liners are used and disposed of
daily.
d) A safe and sanitary water supply shall be maintained. If a
private water supply is used instead of an approved public water supply, the
applicant shall supply written records of current test results indicating the
water supply is safe for drinking. New test results must be provided prior to renewal
of license. If nitrate content exceeds 10 ppm, bottled water must be used for
children under 15 months of age.
e) Any
day care home currently licensed as of January 1, 2019 shall submit a survey
provided by its day care licensing office that includes the construction date
of the home.
The construction date for new day care
home applicants is captured on the CFS 597
-DCI form.
f) Any
day care home serving children under 6 years of age and housed in a building
constructed on or before January 1, 2000 shall be subject to lead in water
testing by an IEPA laboratory or an IEPA-certified laboratory.
A current list of certified laboratories can be obtained
by contacting the Day Care Information Line at 1-877-746-0829, or can be
accessed online through https://sunshine.dcfs.illinois.gov/ Content/Licensing/LeadTesting.aspx.
Water sampling guidelines followed by certified laboratories may also be
accessed through this link
water
testing by an IEPA laboratory or an IEPA-certified laboratory.
A current list of certified laboratories can be obtained
by contacting the Day Care Information Line at 1-877-746-0829, or can be
accessed online through https://sunshine.dcfs.illinois.gov/ Content/Licensing/LeadTesting.aspx.
Water sampling guidelines followed by certified laboratories may also be
accessed through this link. Test results and mitigation plans, when required,
shall be submitted to the local licensing office within 120 days after
notification of test results of 2.01 ppb or above.
1) All lead in water
test results (at, above or below 2.01 ppb) shall be posted in the home in a
visible location and submitted by the applicant or licensee directly to his or
her local licensing office.
2) A
mitigation plan shall be made available to parents and submitted to the local
licensing office if test results indicate the presence of lead for each
drinking water source with a result of 2.01 ppb or above and shall specify:
A) Interim
measures the applicant/licensee will take to ensure a safe drinking water supply
during mitigation;
B) Mitigation
plan start and planned completion dates;
C) Retesting
dates, to include one test to occur no later than six months following the
completion of a mitigation plan and a second test no later than one year after the
completion of a mitigation plan;
D) Each
drinking water source that tested at 2.01 ppb or higher and the planned
mitigation activity for each source
) Mitigation
plan start and planned completion dates;
C) Retesting
dates, to include one test to occur no later than six months following the
completion of a mitigation plan and a second test no later than one year after the
completion of a mitigation plan;
D) Each
drinking water source that tested at 2.01 ppb or higher and the planned
mitigation activity for each source. Examples of acceptable mitigation
strategies include, but are not limited to, installation of mechanical flushing
devices, replacement of lead-based lines or fixtures, or reverse osmosis
filters installed at affected drinking water fixtures; and
E) In
extenuating circumstances in which mitigation cannot be readily undertaken
(e.g., lead in the municipal water source), alternative external sources of
water that tests below 2.01 ppb, such as bottled water with that test result,
may be used subject to Department approval.
3) Following successful mitigation that results in two
consecutive tests of lower than 2.01 ppb, further testing is only required if
there has been any change to the water profile of the building, including, but
not limited to, replacement of the hot water heater, change in the water source,
or change to, or replacement of, the water service lines.
4) The Department reserves the right to require testing upon
suspicion of the day care home misrepresenting the construction date of the
building, submitting false or altered testing results, failing to follow
mitigation remedies, or committing other actions that may compromise the health
and welfare of children. Any day care home that fails to insure testing and reasonable
mitigation actions when necessary may be subject to enforcement action, up to
and including revocation of, or refusal to renew, the license.
g) Hot and cold running water shall be provided
ting results, failing to follow
mitigation remedies, or committing other actions that may compromise the health
and welfare of children. Any day care home that fails to insure testing and reasonable
mitigation actions when necessary may be subject to enforcement action, up to
and including revocation of, or refusal to renew, the license.
g) Hot and cold running water shall be provided. When children
under age 10 or who are developmentally disabled are cared for, the maximum hot
water temperature from all faucets of sinks designated for children washing
hands shall be no more than 115º Fahrenheit. Caregivers shall always test the
hot water before allowing children less than 5 years of age to use the water.
h) Insect and rodent control shall be maintained.
1) All outside doors except those with operable self-closing
devices, operable windows, and other openings used for ventilation shall be
screened.
2) Chemicals for insect and rodent control shall be applied in
minimum amounts and shall not be used when children are present.
Over-the-counter products may be used only according to package instructions.
Commercial chemicals, if used, shall be applied by a licensed pest control
operator and shall meet all standards of the Department of Public Health
(Structural Pest Control Code, 77 Ill. Adm. Code 830). A record of any
pesticides used shall be maintained.
i) Healthy household pets that present no danger to children are
permitted.
1) A licensed veterinarian shall certify that the animals are
free of diseases that could endanger the children's health and that dogs and
cats have been inoculated for rabies.
2) If certification is not available, animals shall be confined
at all times in an area inaccessible to children.
3) There shall be careful supervision of children who are
permitted to handle and care for the animals.
4) Immediate treatment shall be available to any child who is
bitten or scratched by an animal
lth and that dogs and
cats have been inoculated for rabies.
2) If certification is not available, animals shall be confined
at all times in an area inaccessible to children.
3) There shall be careful supervision of children who are
permitted to handle and care for the animals.
4) Immediate treatment shall be available to any child who is
bitten or scratched by an animal.
5) The presence of monkeys, ferrets, turtles, iguanas, psittacine
birds (birds of the parrot family) or any wild or dangerous animal is
prohibited in areas accessible to children during the hours the day care home
is in operation. Wild and dangerous animals include, but are not limited to,
venomous and constricting snakes, undomesticated cats and dogs, raccoons, and
other animals determined to be dangerous by local public health authorities.
j) Indoor space shall consist of a clean, comfortable
environment for children.
1) The day care home shall be well-ventilated, free from
observable hazards, properly lighted and heated, and free of fire hazards.
2) The dwelling shall be kept clean, sanitary, and in good
repair.
3) There shall be provision for isolating a child who becomes ill
or who is suspected of having a contagious disease.
4) When used for child care, floors shall have protective
covering such as, but not limited to, tile, carpet or linoleum. Paint or
sealer alone is not acceptable as a protective covering.
5) When children under 30 months of age are in care, stairs
leading to second levels, attics or basements shall be fitted with a sturdy
gate, door or other barrier to prevent the children's access to stairs without
adult supervision. Such a barrier shall be moveable enough so as not to impede
evacuation, if necessary.
k) The licensee shall identify those areas in the home used for
child care. The identified areas minus any special use areas shall be measured
to calculate the square footage available for child care
dy
gate, door or other barrier to prevent the children's access to stairs without
adult supervision. Such a barrier shall be moveable enough so as not to impede
evacuation, if necessary.
k) The licensee shall identify those areas in the home used for
child care. The identified areas minus any special use areas shall be measured
to calculate the square footage available for child care. When the licensed capacity
of the home exceeds 8 children, there shall be:
1) A minimum of 35 square feet of floor space per each child in
care; and
2) An additional 20 square feet of floor space for each child
under 30 months of age when the play area is the same as the sleep area.
However, if portable bedding is used for napping, then removed, the licensing
representative shall approve the use of only 35 square feet of space for each
child if the applicant/licensee has adequate storage for the bedding materials
and the bedding materials are removed before and after naptime.
l)
No person may smoke tobacco in any area of the day care
home in which day care services are being provided to children, while those
children are present
on the premises. In addition, no person may smoke
tobacco while providing transportation, in either an open or enclosed motor
vehicle, to children who are receiving child care services.
Nothing in this
subsection prohibits smoking in the home in the presence of a person's own
children or in the presence of children to whom day care services are not then
being provided.
[225 ILCS 10/5.5]
m) There shall be safe outdoor space for active play.
1) Space shall be provided for play in yards, nearby parks or
playgrounds under adult supervision
ving child care services.
Nothing in this
subsection prohibits smoking in the home in the presence of a person's own
children or in the presence of children to whom day care services are not then
being provided.
[225 ILCS 10/5.5]
m) There shall be safe outdoor space for active play.
1) Space shall be provided for play in yards, nearby parks or
playgrounds under adult supervision.
2) Space shall be protected by physical means (e.g., fence, tree
line, chairs, ropes, etc.) against all water hazards, including, but not
limited to, pools, ponds, standing water, ornamental bodies of water, and
retention ponds, regardless of the depth of the water, and by adult caregiver
supervision at times when children in care are present. Other hazards, such
as, but not limited to, heavy traffic and construction, shall be inaccessible
to children in care through a physical barrier and adult supervision.
3) Play areas shall be well drained and safely maintained.
4) All pieces of outdoor equipment used by children 5 years of
age and younger on the day care home premises that is purchased or installed on
or after April 1, 2001 shall meet the following standards to guard against
entrapment or situations that may cause strangulation.
A) Openings in exercise rings shall be smaller than 4½ inches or
larger than 9 inches in diameter.
B) There shall be no openings in a play structure with a dimension
between 3½ inches and 9 inches (except for exercise rings). Side railings,
stairs and other locations that a child might slip or climb through shall be
checked for appropriate dimensions.
C) Distances between vertical slats or poles, where used, must be
3½ inches or less (to prevent head entrapment).
D) No opening shall form an angle of less than 55 degrees unless
one leg of the angle is horizontal or slopes downward.
E) No openings shall be between ⅜ inch and one inch in size
(to prevent finger entrapment)
rough shall be
checked for appropriate dimensions.
C) Distances between vertical slats or poles, where used, must be
3½ inches or less (to prevent head entrapment).
D) No opening shall form an angle of less than 55 degrees unless
one leg of the angle is horizontal or slopes downward.
E) No openings shall be between ⅜ inch and one inch in size
(to prevent finger entrapment).
5) The use of a trampoline by children in care is prohibited.
6) Children shall be closely supervised by the caregiver when public
parks or playgrounds are used for play, during play and while traveling to and
from the area.
7) Supervision shall be provided during outdoor play by
caregivers who meet the requirements of Section 2007.9.
n) Operation of other business on the premises must not interfere
with the care of children.
o) A day care home may not house bedridden or chronically ill
persons except by permission of the supervising agency. The supervising agency
shall grant such permission unless the person has a contagious or a reportable
communicable disease or requires care that adversely affects the ability of the
caregiver to supervise children.
p) A day
care home shall have certification that all cribs used by the home meet or
exceed the federal safety standards in 16 CFR 1219 or 1220 (2011). This
certification from the manufacturer shall be available for inspection by the
licensing representative. In the absence of a manufacturer's certificate,
proof that the crib was manufactured on or after June 28, 2011 will meet the
required standard.
(Recodified from the
Department of Children and Family Services (89 Ill. Adm. Code 406) pursuant to
P.A. 103-0594, at 50 Ill. Reg. 9917)