§ 143.560 Electrical distribution panels and switchboards.
FederalRegulations
Ask Donna
How this section applies to your facts.
Title 46 CFR: Shipping › Chapter I: COAST GUARD, DEPARTMENT OF HOMELAND SECURITY › Part 143: MACHINERY AND ELECTRICAL SYSTEMS AND EQUIPMENT › Subpart C: Requirements for New Towing Vessels › § 143.560: § 143.560 Electrical distribution panels and switchboards.
Text
(a) Each distribution panel or switchboard on a towing vessel must be:
(1) In a location that is accessible, as dry as practicable, adequately ventilated, and protected from falling debris and dripping or splashing water; and
(2) Totally enclosed and of the dead-front type.
(b) Each switchboard accessible from the rear must be constructed to prevent a person's accidental contact with energized parts.
(c) Nonconductive mats or grating must be provided on the deck in front of each switchboard and, if it is accessible from the rear, on the deck behind the switchboard.
(d) Each un-insulated current-carrying part must be mounted on noncombustible, nonabsorbent, and high-dielectric insulating material.
(e) Equipment mounted on a door of an enclosure must be constructed or shielded so that a person will not come into accidental contact with energized parts.
This is a copy of a public record, reproduced as it was published. It is not legal advice, and it may not be the version a court would rely on. Check the official source before you cite it.