§ 111.79-1 Receptacle outlets; general.

FederalRegulations

Ask Donna

How this section applies to your facts.

Title 46 CFR: Shipping › Chapter I: COAST GUARD, DEPARTMENT OF HOMELAND SECURITY › Part 111: ELECTRIC SYSTEMS—GENERAL REQUIREMENTS › Subpart 111.79: Subpart 111.79—Receptacles › § 111.79-1: § 111.79-1 Receptacle outlets; general.

This text was captured on Aug 14, 2026. It is a snapshot, not a live feed, so check the official code before relying on it.

Text

(a) There must be a sufficient number of receptacle outlets in the crew accommodations for an adequate level of habitability.

(b) There must be a sufficient number of receptacle outlets throughout the machinery space so that any location can be reached by a portable power cord having a length not greater than 24 meters (75 feet).

(c) Each receptacle outlet must be compatible with the voltage and current of the circuit in which it is installed.

(d) Each receptacle outlet must be suitable for the environment in which it is installed and constructed to the appropriate NEMA or IEC protection standard as referenced in § 111.01-9. Special attention must be given to outlets in hazardous locations.

(e) A receptacle outlet must not have any exposed live parts with the plug opening uncovered.

[CGD 94-108, 61 FR 28283, June 4, 1996]