Protection of Stratospheric Ozone: Change of Listing Status for Certain Substitutes Under the Significant New Alternatives Policy Program
Federal RegisterAug 6, 2014
Ask Donna
What actually matters in this document.
Text
ENVIRONMENTAL PROTECTION AGENCY
40 CFR Part 82
[EPA-HQ-OAR-2014-0198; FRL-9910-19-OAR]
RIN 2060-AS18
Protection of Stratospheric Ozone: Change of Listing Status for Certain Substitutes Under the Significant New Alternatives Policy Program
AGENCY:
Environmental Protection Agency (EPA).
ACTION:
Notice of proposed rulemaking.
SUMMARY:
Pursuant to the U.S. Environmental Protection Agency's Significant New Alternatives Policy program, this action proposes to change the status of a number of substitutes that were previously listed as acceptable, based on information showing that other substitutes are available for the same uses that pose lower risk overall to human health and/or the environment. Specifically, this action proposes to modify the listings for certain hydrofluorocarbons in various end-uses in the aerosols, refrigeration and air conditioning, and foam blowing sectors. This action also proposes use conditions that would restrict the use of hydrofluorocarbons to those uses where there are not substitutes available or potentially available that reduce overall risk to human health and/or the environment. This action also proposes to change the status from acceptable to unacceptable for certain hydrochlorofluorocarbons being phased out of production under the Montreal Protocol on Substances that Deplete the Ozone Layer and Section 605(a) of the Clean Air Act.
DATES:
Comments must be received on or before October 6, 2014. EPA is planning to hold a public hearing to take place on August 27, 2014, starting at 9 a.m. in Room 1153, EPA East (entrance from 1201 Constitution Avenue), Washington, DC and further information will be provided on EPA's Stratospheric Ozone Web site at
www.epa.gov/ozone/snap.
ADDRESSES:
Submit your comments, identified by Docket ID No. EPA-HQ-OAR-2014-0198, by one of the following methods:
•
www.regulations.gov.
Follow the on-line instructions for submitting comments.
•
Email: A-And-R-Docket@epa.gov.
•
Mail:
Air and Radiation Docket, Environmental Protection Agency, Mail Code 6102T, 1200 Pennsylvania Ave. NW., Washington, DC 20460, Attention Docket ID No. EPA-HQ-OAR-2014-0198.
•
Hand Delivery:
EPA Docket Center, (EPA/DC) EPA West, Room 3334, 1301 Constitution Ave. NW., Washington, DC, Attention Docket ID No. EPA-HQ-OAR-2014-0198. Such deliveries are only accepted during the Docket's normal hours of operation, and special arrangements should be made for deliveries of boxed information.
Instructions:
Direct your comments to Docket ID No. EPA-HQ-OAR-2014-0198. EPA's policy is that all comments received will be included in the public docket without change and may be made available online at
www.regulations.gov,
including any personal information provided, unless the comment includes information claimed to be Confidential Business Information (CBI) or other information whose disclosure is restricted by statute. Do not submit information that you consider to be CBI or otherwise protected through
www.regulations.gov
or email. The
www.regulations.gov
Web site is an “anonymous access” system, which means EPA will not know your identity or contact information unless you provide it in the body of your comment. If you send an email comment directly to EPA without going through
www.regulations.gov,
your email address will be automatically captured and included as part of the comment that is placed in the public docket and made available on the Internet. If you submit an electronic comment, EPA recommends that you include your name and other contact information in the body of your comment and with any disk or CD-ROM you submit. If EPA cannot read your comment due to technical difficulties and cannot contact you for clarification, EPA may not be able to consider your comment. Electronic files should avoid the use of special characters, any form of encryption, and be free of any defects or viruses. For additional instructions on submitting comments, go to Section I.B. of the
SUPPLEMENTARY INFORMATION
section of this document.
Docket:
All documents in the docket are listed in the
www.regulations.gov
index. Although listed in the index, some information is not publicly available,
i.e.,
CBI or other information whose disclosure is restricted by statute. Certain other material, such as copyrighted material, is not placed on the Internet and will be publicly available only in hard copy form. Publicly available docket materials are available either electronically in
www.regulations.gov
or in hard copy at the Air and Radiation Docket, EPA/DC, EPA West, Room 3334, 1301 Constitution Ave. NW., Washington, DC. The Public Reading Room is open from 8:30 a.m. to 4:30 p.m., Monday through Friday, excluding legal holidays. The telephone number for the Public Reading Room is (202) 566-1744, and the telephone number for the Air and Radiation Docket is (202) 566-1742.
FOR FURTHER INFORMATION CONTACT:
Rebecca von dem Hagen, Stratospheric Protection Division, Office of Atmospheric Programs, Mail Code 6205J, Environmental Protection Agency, 1200 Pennsylvania Ave. NW., Washington, DC 20460; telephone number (202) 343-9445; fax number (202) 343-2338, email address:
vondemhagen.rebecca@epa.gov.
Notices and rulemakings under EPA's Significant New Alternatives Policy (SNAP) program are available on EPA's Stratospheric Ozone Web site at
www.epa.gov/ozone/snap/regs.
SUPPLEMENTARY INFORMATION:
Table of Contents
I. General Information
A. Executive Summary
B. Does this action apply to me?
C. What should I consider as I prepare my comments for EPA?
D. What acronyms and abbreviations are used in the preamble?
II. How does the SNAP program work?
A. What are the statutory requirements and authority for the SNAP program?
B. What are EPA's regulations implementing CAA section 612?
C. How do the regulations for the SNAP program work?
D. What are the guiding principles of the SNAP program?
E. What are EPA's criteria for evaluating substitutes under the SNAP program?
F. How are SNAP determinations updated?
G. What does EPA consider in deciding whether to modify a determination?
H. Where can I get additional information about the SNAP program?
III. What actions and information related to greenhouse gases have bearing on this proposed decision to modify prior SNAP determinations?
IV. What petitions has EPA received requesting a change in listing status for substitutes with a high global warming potential?
A. Summary of Petitions
B. How Today's Action Relates to Petitions
V. What is EPA proposing for HFCs?
A. Aerosols
1. Background
2. Aerosols Today
3. What is EPA proposing concerning aerosols?
a. What other alternatives are available?
i. Consumer Aerosols
ii. Technical Aerosols
iii. Medical Aerosols
b. What other approaches is EPA considering?
c. When would the modified listings apply?
d. On which topics is EPA requesting comment?
B. Motor Vehicle Air Conditioning for Newly Manufactured Light-Duty Motor Vehicles
1. Background
2. What is EPA proposing regarding use of HFC-134a and use of refrigerant blends in MVAC systems for newly manufactured light-duty motor vehicles?
3. Would this action affect EPA's light duty vehicle rule?
C. Retail Food Refrigeration and Vending Machines
1. Background
2. What is EPA proposing for new and retrofit retail food refrigeration (condensing units and supermarket systems)?
a. New Condensing Units and Supermarket Systems
b. Retrofit Condensing Units and Supermarket Systems
3. What is EPA proposing for new and retrofit stand-alone equipment?
a. New Stand-alone Equipment
b. Retrofit Stand-alone Equipment
4. What is EPA proposing for new and retrofit vending machines?
a. New Vending Machines
b. Retrofit Vending Machines
5. When would the listings change?
6. Applicability to Service of Existing Equipment
7. Energy Efficiency Consideration
8. What other options is EPA considering?
a. New and Retrofit Condensing Units and Supermarket Systems
b. New Stand-alone Equipment and Vending Machines
c. Retrofit Stand-alone Equipment and Vending Machines
d. Status of R-404A and R-507A in Other end-uses
D. Foam Blowing Agents
1. Background
2. What is EPA proposing for foam blowing agents?
a. What other foam blowing agents are being used?
b. What are the health and environmental impacts of the substitute foam blowing agents?
i. Proposed Unacceptable Agents
ii. Rigid Polyurethane Appliance Foam
iii. Flexible Polyurethane
iv. Rigid Polyurethane Spray Foam
v. Rigid Polyurethane Used in Commercial Refrigeration and Sandwich Panels
vi. Rigid Polyurethane Slabstock and Other Foam
vii. Rigid Polyurethane and Polyisocyanurate Laminated Boardstock
viii. Polystyrene Extruded Sheet
ix. Polystyrene Extruded Boardstock and Billet
x. Integral Skin Polyurethane
xi. Polyolefin Foam
xii. Phenolic Insulation Board and Bunstock
c. How does EPA propose to regulate foams and products containing foams?
d. When would the listings change?
e. Narrowed Use Limits for Military or Space- and Aeronautics-related Applications
f. Summary
VI. What is EPA proposing for HCFCs?
A. What are the proposed modifications to the listings for the three HCFCs and in which end-uses?
B. Why is EPA modifying the listings for HCFCs?
1. Alignment of SNAP Listings for the Three HCFCs With Regulations Implementing CAA Sections 605 and 610
2. Anticipated Effects
VII. Do SNAP requirements apply to exports and imports?
VIII. Statutory and Executive Order Reviews
A. Executive Order 12866: Regulatory Planning and Review
B. Paperwork Reduction Act
C. Regulatory Flexibility Act
D. Unfunded Mandates Reform Act
E. Executive Order 13132: Federalism
F. Executive Order 13175: Consultation and Coordination With Indian Tribal Governments
G. Executive Order 13045: Protection of Children From Environmental Health and Safety Risks
H. Executive Order 13211: Actions That Significantly Affect Energy Supply, Distribution, or Use
I. National Technology Transfer and Advancement Act
J. Executive Order 12898: Federal Actions To Address Environmental Justice in Minority Populations and Low-Income Populations
IX. References
I. General Information
A. Executive Summary
This notice of proposed rulemaking would change the status of certain substitutes
1
previously found acceptable under the Significant New Alternatives Policy (SNAP) program. EPA is proposing to modify the listings from acceptable to unacceptable for certain hydrofluorocarbons (HFCs) and HFC blends in aerosol, foam blowing, and air conditioning and refrigerant end-uses where other alternatives are available or potentially available that pose overall lower risk. Per the guiding principle stated above, EPA is considering the intersection between the specific HFC or HFC blend and the particular end-use. This action does not propose that any specific HFCs be unacceptable across all sectors and end-uses. EPA is also not proposing that, for any specific sector, the only acceptable substitutes are HFC-free. EPA recognizes that both fluorinated (e.g., HFCs, hydrofluoroolefins (HFOs)) and non-fluorinated (e.g., hydrocarbons (HCs), carbon dioxide (CO
2
)) substitutes are potentially acceptable. Instead, consistent with SNAP's history and Clean Air Act (CAA) Section 612, EPA is proposing these modifications based on the substitutes being considered, the SNAP criteria for evaluation, and the current suite of other available and potentially available substitutes.
1
The terms “substitutes” and “alternatives” are used interchangeably.
EPA is proposing to modify the following listings by end-use:
(1) For aerosol propellants, we are proposing to list, as of January 1, 2016
• HFC-125 as unacceptable;
• HFC-134a as acceptable, subject to use conditions, allowing its use only in specific types of technical and medical aerosols (e.g. metered dose inhalers) (and prohibiting its use in consumer aerosols); and
• HFC-227ea as acceptable, subject to use conditions, allowing its use only in metered dose inhalers.
(2) For motor vehicle air conditioning systems in newly manufactured light-duty vehicles, we are proposing to list
• HFC-134a as unacceptable starting with model year (MY) 2021; and
• The refrigerant blends SP34E, R-426A (also known as RS-24), R-416A (also known as HCFC Blend Beta or FRIGC FR12), R-406A, R-414A (also known as HCFC Blend Xi or GHG-X4), R-414B (also known as HCFC Blend Omicron), HCFC Blend Delta (also known as Free Zone), Freeze 12, GHG-X5, and HCFC Blend Lambda (also known as GHG-HP) as unacceptable starting with MY 2017.
(3) For new and retrofit retail food refrigeration (including stand-alone equipment, condensing units, direct supermarket systems, and indirect supermarket systems) and new and retrofit vending machines, we are proposing to list, as of January 1, 2016
• The HFC blends R-507A and R-404A as unacceptable.
(4) For new and retrofit retail food refrigeration (including direct supermarket systems and indirect supermarket systems), we are proposing to list, as of January 1, 2016
• HFC-227ea, R-407B, R-421B, R-422A, R-422C, R-422D, R-428A, and R-434A as unacceptable.
(5) For new stand-alone retail food refrigeration and new vending machines, we are proposing to list, as of January 1, 2016
• HFC-134a and certain other HFC refrigerant blends as unacceptable.
(6) For foam blowing agents, we are proposing to list, as of January 1, 2017, except where allowed under a narrowed use limit,
• HFC-134a and blends thereof as unacceptable in all foam blowing end-uses;
• HFC-143a, HFC-245fa and HFC-365mfc and blends thereof, and the HFC blends Formacel B, and Formacel Z-6 as unacceptable in all foam blowing end-uses where they are currently listed as
acceptable, except for spray foam applications; and
• The HFC blend Formacel TI as unacceptable in all foam blowing end-uses where it is currently listed as acceptable.
In general, EPA is proposing modifications to the listings based on the SNAP program's comparative risk framework. The sections that follow provide the analyses supporting the proposed listing modifications and the dates when the modified listings would apply to users of these substitutes. In addition, EPA has prepared supporting documentation on this rule including market characterizations, analyses of costs associated with sector transitions, estimated benefits associated with the transition to alternatives, and potential small business impacts.
2 3 4 5 6 7 8
The emissions reductions from this proposed rule are estimated to be 31 to 42 million metric tons of carbon dioxide equivalent (MMTCO2eq) in 2020. These documents are available in the docket for commenters to review. EPA is planning to prepare a consolidated analysis document.
2
ICF, 2014a. Market Characterization of the U.S. Aerosols Industry. Prepared for the U.S. Environmental Protection Agency. May, 2014.
3
ICF, 2014b. Market Characterization of the U.S. Foams Industry. Prepared for the U.S. Environmental Protection Agency. May, 2014.
4
ICF, 2014c. Market Characterization of the U.S Commercial Refrigeration Industry. Prepared for the U.S. Environmental Protection Agency. May, 2014.
5
ICF, 2014d. Market Characterization of the Motor Vehicle Air Conditioning Industry. Prepared for the U.S. Environmental Protection Agency. May, 2014.
6
ICF, 2014f. Economic Impact Screening Analysis for Regulatory Options to Change Listing Status of High-GWP Alternatives. April, 2014.
7
EPA, 2014. Climate Benefits of the SNAP Program Status Change Rule, June 2014.
8
ICF, 2014g. Revised Preliminary Cost Analysis for Regulatory Options to Change Listing Status of High-GWP Alternatives. June 2014.
EPA is also proposing to modify the listings for hydrochlorofluorocarbon (HCFC)-141b, HCFC-142b, and HCFC-22, as well as blends that contain these substances, from acceptable to unacceptable in aerosols, foam blowing agents, fire suppression and explosion protection agents, sterilants, and adhesives, coatings and inks. These modifications reflect the existing regulations promulgated under CAA sections 605(a) and 610(d) codified at 40 CFR part 82 subparts A and C. The modified listings would take effect 60 days following issuance of a final rule promulgating this proposal.
B. Does this action apply to me?
Potential entities that may be affected by this proposed rule include:
Table 1—Potentially Regulated Entities by North American Industrial Classification System (NAICS) Code
Category
NAICS Code
Description of regulated entities
Industry
238220
Plumbing, Heating, and Air Conditioning Contractors
Industry
324191
Petroleum Lubricating Oil and Grease Manufacturing
Industry
325199
All Other Basic Organic Chemical Manufacturing
Industry
325412
Pharmaceutical Preparation Manufacturing
Industry
325510
Paint and Coating Manufacturing
Industry
325520
Adhesive Manufacturing
Industry
325612
Polishes and Other Sanitation Goods
Industry
325620
Toilet Preparation Manufacturing
Industry
325998
All Other Miscellaneous Chemical Product and Preparation Manufacturing
Industry
326140
Polystyrene Foam Product Manufacturing
Industry
326150
Urethane and Other Foam Product (except Polystyrene) Manufacturing
Industry
333415
Air Conditioning and Warm Air Heating Equipment and Commercial and Industrial Refrigeration Equipment Manufacturing
Industry
336211
Motor Vehicle Body Manufacturing
Industry
3363
Motor Vehicle Parts Manufacturing
Industry
339113
Surgical Appliance and Supplies Manufacturing
Retail
423620
Household Appliances, Electric Housewares, and Consumer Electronics Merchant Wholesalers
Retail
423740
Refrigeration Equipment and Supplies Merchant Wholesalers
Retail
44511
Supermarkets and Other Grocery (except Convenience) Stores
Retail
445110
Supermarkets and Other Grocery (except Convenience) Stores
Retail
445120
Convenience Stores
Retail
44521
Meat Markets
Retail
44522
Fish and Seafood Markets
Retail
44523
Fruit and Vegetable Markets
Retail
445291
Baked Goods Stores
Retail
445292
Confectionary and Nut Stores
Retail
445299
All Other Specialty Food Stores
Retail
4453
Beer, Wine, and Liquor Stores
Retail
446110
Pharmacies and Drug Stores
Retail
44711
Gasoline Stations with Convenience Stores
Retail
452910
Warehouse Clubs and Supercenters
Retail
452990
All Other General Merchandise Stores
Services
72111
Hotels (except Casino Hotels) and Motels
Services
72112
Casino Hotels
Retail
72241
Drinking Places (Alcoholic Beverages)
Retail
722513
Limited-Service Restaurants
Retail
722514
Cafeterias, Grill Buffets, and Buffets
Retail
722515
Snack and Nonalcoholic Beverage Bars
This table is not intended to be exhaustive, but rather a guide regarding entities likely to use the substitute whose use is regulated by this action. If you have any questions about whether this action applies to a particular entity,
consult the person listed in the above section,
FOR FURTHER INFORMATION CONTACT
.
C. What should I consider as I prepare my comments for EPA?
1. Submitting Confidential Business Information (CBI)
Do not submit confidential information to EPA through
www.regulations.gov
or email. Clearly mark the part or all of the information that you claim to be CBI. For CBI information in a disk or CD-ROM that you mail to EPA, mark the outside of the disk or CD-ROM as CBI and then identify electronically within the disk or CD-ROM the specific information that is claimed as CBI. In addition to one complete version of the comment that includes information claimed as CBI, a copy of the comment that does not contain the information claimed as CBI must be submitted for inclusion in the public docket. Information marked as CBI will not be disclosed except in accordance with procedures set forth in 40 CFR part 2.
2. Tips for Preparing Your Comments
When submitting comments, remember to:
• Identify the rulemaking by docket number and other identifying information (subject heading,
Federal Register
date, and page number).
• Follow directions-The agency may ask you to respond to specific questions or organize comments by referencing a CFR part or section number.
• Explain why you agree or disagree; suggest alternatives and substitute language for your requested changes.
• Describe any assumptions and provide any technical information and/or data that you used.
• If you estimate potential costs or burdens, explain how you arrived at your estimate in sufficient detail to allow for it to be reproduced.
• Provide specific examples to illustrate your concerns and suggest alternatives.
• Explain your views as clearly as possible, avoiding the use of profanity or personal threats.
• Make sure to submit your comments by the comment period deadline.
D. What acronyms and abbreviations are used in the preamble?
Below is a list of acronyms and abbreviations used in the preamble of this document:
ACGIH
—American Conference of Governmental Industrial Hygienists
AIHA—
American Industrial Hygiene Association
CAA
—Clean Air Act
CAS Reg. No.
—Chemical Abstracts Service Registry Identification Number
CBI
—Confidential Business Information
CFC
—Chlorofluorocarbon
CFR
—Code of Federal Regulations
CH
4
—Methane
CO
2
—Carbon dioxide
CO
2
eq—Carbon dioxide equivalent
DOE—United States Department of Energy
EIA—
Environmental Investigation Agency-US
EO—
Executive Order
EPA
—United States Environmental Protection Agency
EU—
European Union
FDA—
United States Food and Drug Administration
FR
—
Federal Register
GHG—
Greenhouse gas
Gt—
Gigaton
GWP
—Global warming potential
HC—
Hydrocarbon
HCFC
—Hydrochlorofluorocarbon
HFC
—Hydrofluorocarbon
HFO
—Hydrofluoroolefin
ICF
—ICF International, Inc.
ICR
—Information collection request
IGSD—
Institute for Governance and Sustainable Development
IPCC—
Intergovernmental Panel on Climate Change
MDI—
metered dose inhaler
MVAC—
Motor vehicle air conditioning
N
2
—Nitrogen
NAICS
—North American Industrial Classification System
NIOSH
—United States National Institute for Occupational Safety and Health
NRDC—
Natural Resources Defense Council
NTTAA—
National Technology Transfer and Advancement Act
OEM
—Original equipment manufacturer
ODP
—Ozone depletion potential
ODS
—Ozone-depleting substance
OMB
—United States Office of Management and Budget
OSHA
—United States Occupational Safety and Health Administration
PEL
—Permissible exposure limit
PFC
—Perfluorocarbons
ppm
—Parts per million
PRA—
Paperwork Reduction Act
REL
—Recommended exposure limit
RFA
—Regulatory Flexibility Act
SF
6
— Sulfur hexafluoride
SNAP
—Significant New Alternatives Policy
SRES—
Special Report on Emissions Scenarios
TLV—
Threshold limit value
TWA
—Time-weighted average
UMRA—
Unfunded Mandates Reform Act
VOC
—Volatile organic compounds
WEEL—
Workplace Environmental Exposure Limit
II. How does the SNAP program work?
A. What are the statutory requirements and authority for the SNAP program?
Section 612 of the Clean Air Act (CAA) requires the U.S. Environmental Protection Agency (hereafter referred to as EPA or the Agency) to develop a program for evaluating alternatives to ozone-depleting substances. This program is known as the Significant New Alternatives Policy (SNAP) program. The major provisions of section 612 are:
1. Rulemaking
Section 612(c) requires EPA to promulgate rules making it unlawful to replace any class I (e.g., chlorofluorocarbon, halon, carbon tetrachloride, methyl chloroform, methyl bromide, and hydrobromofluorocarbon) or class II (e.g., hydrochlorofluorocarbon) substance with any substitute that the Administrator determines may present adverse effects to human health or the environment where the Administrator has identified an alternative that (1) reduces the overall risk to human health and the environment and (2) is currently or potentially available.
2. Listing of Unacceptable/Acceptable Substitutes
Section 612(c) requires EPA to publish a list of the substitutes that it finds to be unacceptable for specific uses and to publish a corresponding list of acceptable alternatives for specific uses. The list of “acceptable” substitutes is found at
www.epa.gov/ozone/snap/lists
and the lists of “unacceptable,” “acceptable subject to use conditions,” and “acceptable subject to narrowed use limits” substitutes are found in the appendices to 40 CFR part 82 subpart G.
3. Petition Process
Section 612(d) grants the right to any person to petition EPA to add a substance to, or delete a substance from, the lists published in accordance with section 612(c). The Agency has 90 days to grant or deny a petition. Where the Agency grants the petition, EPA must publish the revised lists within an additional six months.
4. 90-day Notification
Section 612(e) directs EPA to require any person who produces a chemical substitute for a class I substance to notify the Agency not less than 90 days before new or existing chemicals are introduced into interstate commerce for significant new uses as substitutes for a class I substance. The producer must also provide the Agency with the producer's unpublished health and safety studies on such substitutes.
5. Outreach
Section 612(b)(1) states that the Administrator shall seek to maximize the use of federal research facilities and resources to assist users of class I and II substances in identifying and
developing alternatives to the use of such substances in key commercial applications.
6. Clearinghouse
Section 612(b)(4) requires the Agency to set up a public clearinghouse of alternative chemicals, product substitutes, and alternative manufacturing processes that are available for products and manufacturing processes which use class I and II substances.
B. What are EPA's regulations implementing CAA section 612?
On March 18, 1994, EPA published the original rulemaking (59 FR 13044) which established the process for administering the SNAP program and issued EPA's first lists identifying acceptable and unacceptable substitutes in major industrial use sectors (40 CFR part 82, subpart G). These sectors are the following: Refrigeration and air conditioning; foam blowing; solvents cleaning; fire suppression and explosion protection; sterilants; aerosols; adhesives, coatings and inks; and tobacco expansion. These sectors comprise the principal industrial sectors that historically consumed the largest volumes of ozone-depleting substances (ODS).
C. How do the regulations for the SNAP program work?
Under the SNAP regulations, anyone who produces a substitute to replace a class I or II ODS in one of the eight major industrial use sectors must provide the Agency with notice and the required health and safety information on the substitute at least 90 days before introducing it into interstate commerce for significant new use as an alternative. 40 CFR 82.176(a). While this requirement typically applies to chemical manufacturers as the person likely to be planning to introduce the substitute into interstate commerce,
9
it may also apply to importers, formulators, equipment manufacturers, or end-users
10
when they are responsible for introducing a substitute into commerce. The 90-day SNAP review process begins once EPA receives the submission and determines that the submission includes complete and adequate data. 40 CFR 82.180(a). The CAA and the SNAP regulations, 40 CFR 82.174(a), prohibit use of a substitute earlier than 90 days after a complete submission has been provided to the Agency.
9
As defined at 40 CFR 82.104 “interstate commerce” means the distribution or transportation of any product between one state, territory, possession or the District of Columbia, and another state, territory, possession or the District of Columbia, or the sale, use or manufacture of any product in more than one state, territory, possession or District of Columbia. The entry points for which a product is introduced into interstate commerce are the release of a product from the facility in which the product was manufactured, the entry into a warehouse from which the domestic manufacturer releases the product for sale or distribution, and at the site of United States Customs clearance.
10
As defined at 40 CFR 82.172 “end-use” means processes or classes of specific applications within major industrial sectors where a substitute is used to replace an ozone-depleting substance.
The Agency has identified four possible decision categories for substitute submissions: Acceptable; acceptable subject to use conditions; acceptable subject to narrowed use limits; and unacceptable.
11
40 CFR 82.180(b). Use conditions and narrowed use limits are both considered “use restrictions” and are explained below. Substitutes that are deemed acceptable without use conditions can be used for all applications within the relevant end-uses within the sector and without limits under SNAP on how they may be used. Substitutes that are acceptable subject to use restrictions may be used only in accordance with those restrictions. Substitutes that are found to be unacceptable may not be used after the date specified in the rulemaking adding such substitute to the list of unacceptable substitutes.
12
11
The SNAP regulations also include “pending,” referring to submissions for which EPA has not reached a determination, under this provision.
12
As defined at 40 CFR 82.172, “use” means any use of a substitute for a Class I or Class II ozone-depleting compound, including but not limited to use in a manufacturing process or product, in consumption by the end-user, or in intermediate uses, such as formulation or packaging for other subsequent uses. This definition of use encompasses manufacturing process of products both for domestic use and for export. Substitutes manufactured within the United States exclusively for export are subject to SNAP requirements since the definition of use in the rule includes use in the manufacturing process, which occurs within the United States.
After reviewing a substitute, the Agency may determine that a substitute is acceptable only if certain conditions in the way that the substitute is used are met to ensure risks to human health and the environment are not significantly greater than other available substitutes. EPA describes such substitutes as “acceptable subject to use conditions.” Entities that use these substitutes without meeting the associated use conditions are in violation of section 612 of the Clean Air Act and EPA's SNAP regulations. 40 CFR 82.174(c).
For some substitutes, the Agency may permit a narrow range of use within an end-use or sector. For example, the Agency may limit the use of a substitute to certain end-uses or specific applications within an industry sector. The Agency requires a user of a narrowed use substitute to demonstrate that no other acceptable substitutes are available for their specific application. EPA describes these substitutes as “acceptable subject to narrowed use limits.” A person using a substitute that is acceptable subject to narrowed use limits in applications and end-uses that are not consistent with the narrowed use limit is using these substitutes in violation of section 612 of the CAA and EPA's SNAP regulations. 40 CFR 82.174(c).
The section 612 mandate for EPA to prohibit the use of a substitute that may present risk to human health or the environment where a lower risk alternative is available or potentially available
13
provides EPA with the authority to change the listing status of a particular substitute if such a change is justified by new information or changed circumstance.
13
In addition to acceptable commercially available substitutes, the SNAP program may consider potentially available substitutes. The SNAP program's definition of “potentially available” is “any alternative for which adequate health, safety, and environmental data, as required for the SNAP notification process, exist to make a determination of acceptability, and which the Agency reasonably believes to be technically feasible, even if not all testing has yet been completed and the alternative is not yet produced or sold.” (40 CFR 82.172)
The Agency publishes its SNAP program decisions in the
Federal Register
. EPA uses notice-and-comment rulemaking to place any alternative on the list of prohibited substitutes, to list a substitute as acceptable only subject to use conditions or narrowed use limits, or to remove a substitute from either the list of prohibited or acceptable substitutes.
In contrast, EPA publishes “notices of acceptability” to notify the public of substitutes that are deemed acceptable with no restrictions. As described in the preamble to the rule initially implementing the SNAP program (59 FR 13044; March 18, 1994), EPA does not believe that rulemaking procedures are necessary to list substitutes that are acceptable without restrictions because such listings neither impose any sanction nor prevent anyone from using a substitute.
Many SNAP listings include “comments” or “further information” to provide additional information on substitutes. Since this additional information is not part of the regulatory decision, these statements are not binding for use of the substitute under the SNAP program. However, regulatory requirements so listed are binding under other regulatory programs (e.g., worker protection regulations promulgated by the U.S. Occupational Safety and Health
Administration (OSHA)). The “further information” classification does not necessarily include all other legal obligations pertaining to the use of the substitute. While the items listed are not legally binding under the SNAP program, EPA encourages users of substitutes to apply all statements in the “further information” column in their use of these substitutes. In many instances, the information simply refers to sound operating practices that have already been identified in existing industry and/or building codes or standards. Thus, many of the statements, if adopted, would not require the affected user to make significant changes in existing operating practices.
D. What are the guiding principles of the SNAP program?
The seven guiding principles of the SNAP program, elaborated in the preamble to the initial SNAP rule and based on section 612, are discussed below.
•
Evaluate substitutes within a comparative risk framework
The SNAP program evaluates the risk of alternative compounds compared to available or potentially available substitutes to the ozone depleting compounds which they are intended to replace. The risk factors that are considered include ozone depletion potential as well as flammability, toxicity, occupational health and safety, and contributions to climate change and other environmental factors.
•
Do not require that substitutes be risk free to be found acceptable
For substitutes to be found acceptable they must pose less risk than other substitutes, but they do not have to be risk free. Where risks of a substitute would otherwise be higher than other substitutes, EPA may find these alternatives acceptable subject to use conditions or narrowed use limits that would manage the risk.
•
Restrict those substitutes that are significantly worse
EPA does not intend to restrict a substitute if it has only marginally greater risk. Drawing fine distinctions would be extremely difficult. The Agency also does not want to intercede in the market's choice of substitutes by listing as unacceptable all but a few substitutes for each end-use. Thus, the Agency will not list a potential substitute as unacceptable unless EPA determines that the substitute is significantly more harmful to human health or the environment than other available or potentially available alternatives.
•
Evaluate risks by use
Central to SNAP's evaluations is the intersection between the characteristics of the substitute itself and its specific end-use application. Section 612 requires that substitutes be evaluated by use. Environmental and human health exposures can vary significantly depending on the particular application of a substitute. Thus, the risk characterizations must be designed to represent differences in the environmental and human health effects associated with diverse uses. This approach cannot, however, imply fundamental tradeoffs with respect to different types of risk to either the environment or to human health.
•
Provide the regulated community with information as soon as possible
The Agency recognizes the need to provide the regulated community with information on the acceptability of various substitutes as soon as possible. To do so, EPA issues notices or determinations of acceptability and rules identifying substitutes as unacceptable, acceptable to use conditions or acceptable subject to narrowed use limits in the
Federal Register
. In addition, we maintain lists of acceptable and unacceptable alternatives on our Web site,
www.epa.gov/ozone/snap.
•
Do not endorse products manufactured by specific companies
The Agency does not issue company-specific product endorsements. In many cases, the Agency may base its analysis on data received on individual products, but the addition of a substitute to the acceptable list based on that analysis does not represent an endorsement of that company's products.
•
Defer to other environmental regulations when warranted
In some cases, EPA and other federal agencies have developed extensive regulations under other sections of the CAA or other statutes that address any potential environmental impacts that may result from the use of alternatives to class I and class II substances. For example, use of some substitutes may in some cases entail increased use of chemicals that contribute to tropospheric air pollution. The SNAP program takes existing regulations under other programs into account when reviewing substitutes.
E. What are EPA's criteria for evaluating substitutes under the SNAP program?
EPA applies the same criteria for determining whether a substitute is acceptable or unacceptable. These criteria, which can be found at § 82.180(a)(7), include atmospheric effects and related health and environmental impacts, ecosystem risks, consumer risks, flammability, and cost and availability of the substitute. To enable EPA to assess these criteria, we require submitters to include various information including ozone depletion potential (ODP), global warming potential (GWP), toxicity, flammability, and the potential for human exposure.
When evaluating potential substitutes, EPA evaluates these criteria in the following groupings:
•
Atmospheric effects—
The SNAP program evaluates the potential contributions to both ozone depletion and climate change. The SNAP program considers the ozone depletion potential and the 100-year integrated GWP of compounds to assess atmospheric effects.
•
Exposure assessments—
The SNAP program uses exposure assessments to estimate concentration levels of substitutes to which workers, consumers, the general population, and environmental receptors may be exposed over a determined period of time. These assessments are based on personal monitoring data or area sampling data if available. Exposure assessments may be conducted for many types of releases including:
(1) Releases in the workplace and in homes;
(2) Releases to ambient air and surface water;
(3) Releases from the management of solid wastes.
•
Toxicity data—
The SNAP program uses toxicity data to assess the possible health and environmental effects of exposure to substitutes. We use broad health-based criteria such as:
(1) Permissible Exposure Limits (PELs) for occupational exposure;
(2) Inhalation reference concentrations (RfCs) for non-carcinogenic effects on the general population;
(3) Cancer slope factors for carcinogenic risk to members of the general population.
When considering risks in the workplace, if OSHA has not issued a PEL for a compound, EPA then considers Recommended Exposure Limits from the National Institute for Occupational Safety and Health, Workplace Environmental Exposure Limits (WEELs) set by the American Industrial Hygiene Association, or Threshold Limit Values set by the American Conference of Governmental Industrial Hygienists. If limits for occupational exposure or exposure to the general population are not already established, then EPA derives these values following the Agency's peer reviewed guidelines. Exposure
information is combined with toxicity information to explore any basis for concern. Toxicity data are used with existing EPA guidelines to develop health-based limits for interim use in these risk characterizations.
•
Flammability—
The SNAP program examines flammability as a safety concern for workers and consumers. EPA assesses flammability risk using data on:
(1) Flash point and flammability limits (e.g. OSHA flammability/combustibility classifications);
(2) Data on testing of blends with flammable components;
(3) Test data on flammability in consumer applications conducted by independent laboratories; and
(4) Information on flammability risk mitigation techniques.
•
Other environmental impacts—
The SNAP program also examines other potential environmental impacts such as ecotoxicity and local air quality impacts. A compound that is likely to be discharged to water may be evaluated for impacts on aquatic life. Some substitutes are volatile organic compounds (VOCs). EPA also notes whenever a potential substitute is considered a hazardous or toxic air pollutant (under CAA sections 112 (b) and 202 (l)) or hazardous waste under the Resource Conservation and Recovery Act subtitle C regulations.
Over the past twenty years, the menu of substitutes has become much broader and a great deal of new information has been developed on many substitutes. Because the overall goal of the SNAP program is to ensure that substitutes listed as acceptable do not pose significantly greater risk to human health and the environment than other available substitutes, the SNAP criteria should be informed by our current overall understanding of environmental and human health impacts and our experience with and current knowledge about available and potentially available substitutes. Over time, the range of substitutes reviewed by SNAP has changed, and, at the same time, scientific approaches have evolved to more accurately assess the potential environmental and human health impacts of these chemicals and alternative technologies.
F. How are SNAP determinations updated?
Three mechanisms exist for modifying the list of SNAP determinations. First, under section 612(d), the Agency must review and either grant or deny petitions to add or delete substances from the SNAP list of acceptable or unacceptable substitutes. That provision allows any person to petition the Administrator to add a substance to the list of acceptable or unacceptable substitutes or to remove a substance from either list. The second means is through the notifications which must be submitted to EPA 90 days before introduction of a substitute into interstate commerce for significant new use as an alternative to a class I or class II substance. These 90-day notifications are required by section 612(e) of the CAA for producers of substitutes to class I substances for new uses and, in all other cases, by EPA regulations issued under sections 114 and 301 of the Act to implement section 612(c).
Finally, we interpret the section 612 mandate to find substitutes acceptable or unacceptable to include the authority to act on our own to add or remove a substance from the SNAP lists. In determining whether to add or remove a substance from the SNAP lists, we consider whether there are other available substitutes that pose a lower risk to human health and the environment. In determining whether to modify a listing of a substitute we consider new data not considered at the time of our original listing decision, including information on new substitutes and new information on substitutes previously reviewed.
G. What does EPA consider in deciding whether to modify a determination?
As described in this document and elsewhere, including in the original SNAP rulemaking published in the
Federal Register
on March 18, 1994 (59 FR 13044), section 612 of the CAA requires EPA to list as unacceptable any substitute substance where it finds that there are other substitutes currently or potentially available that reduce overall risk to human health and the environment. In addition to comparing the human health and environmental effects of other available or potentially available substitutes for the same end-uses, we also compare substitutes to the ozone-depleting substances being phased out under the
Montreal Protocol on Substances that Deplete the Ozone Layer
(Montreal Protocol) and under the CAA.
The original SNAP rule included submission requirements and presented the environmental and health risk factors that the SNAP program considers in its comparative risk framework. Environmental and human health exposures can vary significantly depending on the particular application of a substitute; therefore, EPA makes decisions based on the particular end-use where a substitute is to be used. EPA has, in many cases, found certain substitutes acceptable only for limited end-uses or subject to use restrictions.
In May 2013 EPA stated:
EPA recognizes that during the nearly two- decade long history of the SNAP program, new alternatives and new information about alternatives have emerged. To the extent possible, EPA considers new information and improved understanding of the risk factors for the environment and human health in the context of the available or potentially available alternatives for a given use.
(78 FR 29035)
It has now been about twenty years since the initial SNAP rule was promulgated. In that period, the menu of available alternatives has expanded greatly and now includes many substitutes with diverse characteristics and effects on human health and the environment. When the SNAP program began, the number of substitutes available for consideration was, for many end-uses, somewhat limited. While the SNAP program's initial comparative assessments of overall risk to human health and the environment were rigorous, often there were few substitutes to apply the comparative assessment. The immediacy of the class I phaseout often meant that SNAP listed class II ODS (i.e., HCFCs) as acceptable, recognizing that they too would be phased out and were only an interim solution. Other Title VI provisions such as the section 610 Nonessential Products Ban and the section 605 Use Restriction meant a listing under the SNAP program did not convey permanence.
Since EPA issued the initial SNAP rule in 1994, the Agency has issued 18 rules and 28 notices expanding the menu of options for all SNAP sectors and end-uses. Comparisons today are to a broader range of options—both chemical and non-chemical—than at the inception of the SNAP program. Industry experience with these substitutes has also grown during the history of the program. This varies by sector and by end-use.
In addition to an expanding menu of substitutes, developments over the past 20 years have improved our understanding of global environmental issues. With regards to that information, many of the substitute-specific actions proposed in this rule have undergone comparative assessments that consider our evolving understanding of climate change. GWPs and climate effects are not new elements in our evaluation framework, but along with all of our review criteria the amount and quality of information has expanded.
To the extent possible, EPA's ongoing management of the SNAP program considers new information and
improved understanding of the risk to the environment and human health. EPA previously has taken several actions revising listing determinations from acceptable or acceptable with use conditions to unacceptable based on information made available to EPA after a listing was issued. For example, on January 26, 1999, EPA listed the refrigerant known by the trade name MT-31 as unacceptable for all refrigeration and air conditioning end-uses. EPA previously listed this blend as an acceptable substitute in various end-uses within the refrigeration and air conditioning sector (June 3, 1997; 62 FR 30275). Based on new information about the toxicity of one of the chemicals in the blend, EPA subsequently removed MT-31 from the list of acceptable substitutes and listed it as unacceptable in all refrigeration and air conditioning end-uses (January 26, 1999; 64 FR 3861).
Another example of EPA revising a listing determination occurred in 2007 when EPA listed HCFC-22 and HCFC-142b as unacceptable for use in the foam sector (March 28, 2007; 72 FR 14432). These HCFCs, which are ozone depleting and subject to a global production phaseout, were initially listed as acceptable substitutes since they had a lower ODP than the substances they were replacing and there were no other available substitutes that posed lower risk at the time of EPA's listing decision. HCFCs offered a path forward for some sectors and end-uses at a time when substitutes were far more limited. In light of the expanded availability of alternative substitutes with lower overall risk to human health and the environment in specific foam end-uses, and taking into account the 2010 class II ODS phasedown step, EPA changed the listing for these HCFCs in these end-uses from acceptable to unacceptable. In that rule, EPA noted that continued use of these HCFCs would contribute to unnecessary depletion of the ozone layer and delay the transition to substitutes that pose lower overall risk to human health and the environment. EPA allowed existing users to continue use for a limited time to ensure that they could adjust their manufacturing processes to safely accommodate the use of other substitutes.
H. Where can I get additional information about the SNAP program?
For copies of the comprehensive SNAP lists of substitutes or additional information on SNAP, refer to EPA's Web site at
www.epa.gov/ozone/snap.
For more information on the Agency's process for administering the SNAP program or criteria for evaluation of substitutes, refer to the SNAP final rulemaking published March 18, 1994 (59 FR 13044), codified at 40 CFR part 82, subpart G. A complete chronology of SNAP decisions and the appropriate citations are found at
www.epa.gov/ozone/snap/chron.html.
III. What actions and information related to greenhouse gases have bearing on this proposed decision to modify prior SNAP determinations?
GWP, along with other criteria, is a factor in the overall evaluation of alternatives under the SNAP program. During the past two decades, the general science on climate change and the potential contributions of greenhouse gases (GHGs) such as HFCs to climate change have become better understood.
On December 7, 2009, at 74 FR 66496, the Administrator issued two distinct findings regarding GHGs under section 202(a) of the Clean Air Act
14
:
14
The relevant scientific and technical information summarized to support the Endangerment Finding and the Cause or Contribute Finding can be found at:
www.epa.gov/climatechange/Downloads/endangerment/Endangerment_TSD.pdf
•
Endangerment Finding:
the current and projected concentrations of the six key well-mixed greenhouse gases in the atmosphere — CO
2
, methane (CH
4
), nitrous oxide (N
2
O), HFCs, perfluorocarbons (PFCs), and sulfur hexafluoride (SF
6
) — threaten the public health and welfare of current and future generations.
•
Cause or Contribute Finding:
the combined emissions of these well-mixed greenhouse gases from new motor vehicles and new motor vehicle engines contribute to the greenhouse gas pollution which threatens public health and welfare.
Like the ODSs they replace, HFCs are potent GHGs.
15
Though they represent a small fraction of the current total volume of GHG emissions, their warming impact is very strong because they can remain trapped in the atmosphere for up to 250+ years impacting climate change 20,000 times more powerfully than CO
2
, and their emissions are projected to accelerate over the next several decades if left unregulated. In the United States, emissions of HFCs are increasing more quickly than those of any other GHGs, and globally they are increasing 10-15% annually.
16
At that rate, emissions are projected to double by 2020 and triple by 2030.
17
HFCs are rapidly accumulating in the atmosphere. The atmospheric concentration of HFC-134a, the most abundant HFC, has increased by about 10% per year from 2006 to 2012, and the concentrations of HFC-143a and HFC-125 have risen over 13% and 16% per year from 2007-2011, respectively.
18 19
15
IPCC/TEAP (2005) Special Report: Safeguarding the Ozone Layer and the Global Climate System: Issues Related to Hydrofluorocarbons and Perfluorocarbons (Cambridge Univ Press, New York).
16
UNEP 2011. HFCs: A Critical Link in Protecting Climate and the Ozone Layer. United Nations Environment Programme.
17
Akerman, Nancy H. Hydrofluorocarbons and Climate Change: Summaries of Recent Scientific and Papers, 2013.
18
Montzka, S.A.: HFCs in the Atmosphere: Concentrations, Emissions and Impacts, ASHRAE/NIST Conference 2012.
19
NOAA data at
ftp://ftp.cmdl.noaa.gov/hats/hfcs/.
Annual global emissions of HFCs are projected to rise to about 6.4 to 9.9 Gt CO
2
eq in 2050
20
, which is comparable to the drop in annual GHG emissions from ODS of 8.0 GtCO
2
eq between 1988 and 2010 (UNEP, 2011). By 2050, the buildup of HFCs in the atmosphere is projected to increase radiative forcing by up to 0.4 W m
2
. This increase may be as much as one-fifth to one-quarter of the expected increase in radiative forcing due to the buildup of CO
2
since 2000, according to the IPCC's Special Report on Emissions Scenarios (SRES) (UNEP, 2011). To appreciate the significance of the effect of projected HFC emissions within the context of all GHGs, HFCs would be equivalent to 5 to 12% of the CO
2
emissions in 2050 based on the IPCC's highest CO
2
emissions scenario and equivalent to 27 to 69% of CO
2
emissions based on the IPCC's lowest CO
2
emissions pathway.
21 22
Additional information concerning the peer-reviewed scientific literature and emission scenarios is available in the docket for this rulemaking.
20
Velders, G. J. M., D. W. Fahey, J. S. Daniel, M. McFarland, S. O. Andersen (2009) The large contribution of projected HFC emissions to future climate forcing.
Proceedings of the National Academy of Sciences USA
106: 10949-10954.
21
HFCs: A Critical Link in Protecting Climate and the Ozone Layer. United Nations Environment Programme (UNEP), 2011, 36pp
22
IPCC, 2013: Annex II: Climate System Scenario Tables [Prather, M., G. Flato, P. Friedlingstein, C. Jones, J.-F. Lamarque, H. Liao and P. Rasch (eds.)]. In: Climate Change 2013: The Physical Science Basis. Contribution of Working Group I to the Fifth Assessment Report of the Intergovernmental Panel on Climate Change [Stocker, T.F., D. Qin, G.-K. Plattner, M. Tignor, S.K. Allen, J. Boschung, A. Nauels, Y. Xia, V. Bex and P.M. Midgley (eds.)]. Cambridge University Press, Cambridge, United Kingdom and New York, NY, USA.
IV. What petitions has EPA received requesting a change in listing status for substitutes with a high global warming potential?
A. Summary of Petitions
EPA received three petitions requesting EPA to modify certain acceptability listings of HFC-134a and HFC-134a blends. The first petition was submitted on May 7, 2010, by Natural Resources Defense Council (NRDC) on behalf of NRDC, the Institute for Governance and Sustainable Development (IGSD), and the Environmental Investigation Agency-US (EIA). The petition requested that EPA remove HFC-134a from the list of acceptable substitutes for ODS and move it to the list of unacceptable substitutes in multiple uses. The petitioners subsequently clarified that they were requesting this change for the use of HFC-134a in new passenger cars and light-duty trucks, non-medical aerosols, and for certain refrigeration and foam blowing end-uses. In support of their petition, the petitioners identified other substitutes for use in motor vehicle air conditioning (MVAC) and other sectors, and claimed that these other substitutes present much lower risks to human health and environment than HFC-134a.
On February 14, 2011, EPA found the petition complete for MVAC in new passenger cars and light-duty vehicles and determined it was incomplete for other uses of HFC-134a. EPA noted in its response that, at a future date, the Agency would initiate a notice-and-comment rulemaking in response to the one complete aspect of the petition, noting in particular that EPA would evaluate and take comment on many factors, including, but not limited to, the timeframe for introduction of newer substitutes for MVAC systems into the automotive market and potential lead time for manufacturers of motor vehicles to accommodate substitutes. This proposed rule responds to the aspect of that petition that we found complete.
On April 26, 2012, EPA received a petition from EIA. EIA stated that, in light of the comparative nature of the SNAP program's evaluation of substitutes and given that other acceptable substitutes are on the market or soon to be available, EPA should remove HFC-134a and HFC-134a blends from the list of acceptable substitutes for uses where EPA found CFCs and HCFCs to be nonessential under section 610 of the Act. EIA also requested that the schedule for moving HFC-134a and HFC-134a blends from the list of acceptable to unacceptable substitutes be based on the “most rapidly feasible transitions to one or more of the” acceptable substitutes for each use. The petitioner noted that initial approvals of HFC-134a for a number of end-uses occurred in the 1990s and were based on the assessment made then that (1) HFC-134a does not contribute to ozone depletion; (2) HFC-134a's GWP and atmospheric lifetime were close to those of other substitutes that had been determined to be acceptable for the end-uses; and (3) HFC-134a is not flammable, and its toxicity is low.
23
The petitioner stated that the analysis used in the listing decisions may have been appropriate in the 1990s but was no longer reflected accurately given the range of other available or potentially available substitutes at present.
23
See, e.g., 60 FR at 31097.
In addition to petitioning EPA for action under SNAP, the petitioner requested that the section 610 Nonessential Products Ban be extended to HFC-134a and HFC-134a blends for aerosols and pressurized dispensers (including tire inflators); foam blowing agents; novelty products (including propelled plastic party streamers, web string, artificial snow, specialty paints and excrement “poop” freeze); noise horns (including marine safety noise horns, sporting event noise horns, personal safety noise horns, wall-mounted industrial noise horns used as alarms in factories and other work areas, and intruder noise horns used as alarms in homes and cars); foam and refrigerants in new domestic refrigerators and freezers and other retail stand-alone coolers and freezers; and cleaning fluids for noncommercial electronic, photographic, and other equipment.
On August 7, 2012, EPA notified the petitioner that this petition was incomplete. EPA and the petitioner have exchanged further correspondence that can be found in the docket. Although EPA has found the petition incomplete, EPA's action in this proposal may be considered responsive to certain aspects of the petitions given EPA is proposing to change the listing of certain HFCs used in aerosols and foams from acceptable to unacceptable for most uses, and proposing to place use conditions on the remaining aerosol uses.
A third petition was filed on April 27, 2012, by NRDC, EIA and IGSD. They requested that EPA:
• Remove HFC-134a from the list of acceptable substitutes for CFC-12 in household refrigerators and freezers and stand-alone retail food refrigerators and freezers;
• Restrict the sales of SNAP-listed refrigerants to all except certified technicians with access to service tools required under existing EPA regulations;
• Adopt a standardized procedure to determine the speed of transition from obsolete high-GWP HFCs to next-generation alternatives and substitutes;
• Remove, in addition to HFC-134a, all other refrigerants with 100-year GWPs greater than 150 from the acceptable substitutes list for household refrigerators and freezers and stand-alone retail food refrigerators and freezers.
On August 7, 2013, EPA found this petition to be incomplete. EPA and the petitioner have exchanged further correspondence that can be found in the docket. Although EPA has found the petition incomplete, EPA's action in this proposal may be considered responsive to certain aspects of the petition, given EPA is proposing to change the listing of HFC-134a from acceptable to unacceptable for new stand-alone retail food refrigerators and freezers, as well as changing the listing of a number of refrigerant blends with higher GWPs for new and retrofit stand-alone retail food refrigerators and freezers.
B. How Today's Action Relates to Petitions
This action primarily recognizes a call in the President's Climate Action Plan announced June 2013:
To reduce emissions of HFCs, the United States can and will lead both through international diplomacy as well as domestic actions . . . Moving forward, the Environmental Protection Agency will use its authority through the Significant New Alternatives Policy Program to encourage private sector investment in low-emissions technology by identifying and approving climate-friendly chemicals while prohibiting certain uses of the most harmful chemical alternatives.
The Climate Action Plan also states “to reduce emissions of HFCs, the United States can and will lead both through international diplomacy as well as domestic actions.” This proposed rule is part of our domestic commitment to take action now and, by doing so, also supporting efforts to secure a global HFC phasedown. For the past five years, the United States, Canada, and Mexico have proposed an amendment to the Montreal Protocol to phase down the production and consumption of HFCs. Global benefits of the proposal would yield significant reductions of over 90 gigatons of carbon dioxide equivalent CO2eq through 2050. The United States,
the European Union, Japan and other countries are all taking actions that will promote the uptake of low-GWP alternatives and reduce use and emissions of high-GWP HFCs.
This proposal responds to the President's Climate Action Plan and also addresses certain aspects of the three petitions referred to above. First, this action responds to the one aspect of the three petitions that EPA found complete, namely petitioners' request that EPA change the listing of HFC-134a from acceptable to unacceptable in new MVACs. (See section V.B. in today's notice.) While EPA found all remaining issues in the three petitions incomplete with respect to the other end-uses, EPA has independently acquired sufficient information to address certain other requests made by the petitioners regarding listing high GWP HFCs as unacceptable. Specifically, based on our review of the aerosols, foams, and air conditioning and refrigeration sectors, we are proposing to revise the listings for a number of substitutes from acceptable to acceptable subject to use conditions, or unacceptable. (See sections V.A., V.C., and V.D. of today's notice.) These substitutes have high GWPs as compared with other available or potentially available substitutes in those end-uses and pose significantly greater risk overall to human health and the environment. EPA considers the intersection between the specific HFC or HFC blend and the particular end-use. This action does not propose that any specific HFC be unacceptable across all sectors and end-uses. EPA is also not proposing that, for any specific sector, the only acceptable substitutes are HFC-free. EPA recognizes that both fluorinated (e.g., HFCs, HFOs and non-fluorinated (e.g., HCs, CO
2
) substitutes are potentially acceptable. Instead, consistent with SNAP's history and Clean Air Act (CAA) Section 612, EPA is proposing these modifications, and will consider future modifications, based on the substitutes being considered, the SNAP criteria for evaluation, and the current suite of other available and potentially available substitutes in specific sectors and end-uses.
EPA recently issued a proposed rule (July 9, 2014; 79 FR 38811) that would list as acceptable subject to use conditions a group of refrigeration and air-conditioning alternatives that have been submitted and reviewed under the SNAP program. That rule would enhance the SNAP menu of acceptable alternatives for a number of related end-uses by proposing to add several alternatives as acceptable subject to use conditions.
As noted previously, to date, EPA has considered approximately 400 alternatives. This level of development work serves as a clear demonstration of the efforts of industry to commercialize alternatives that continue to reduce overall risk and meet the needs of a wide range of consumers.
Throughout the process of our discussions with the regulated community on the SNAP related aspects of the President's Climate Action Plan, we have sought to convey our continued understanding of the role that certainty plays in enabling this robust development and uptake of alternatives. Unfortunately, some of the key strengths of the SNAP program, such as its chemical and end-use specific consideration, its multi criteria basis for action, and its petition process tend to militate against some measures that could provide more certainty, such as bright line cut offs. That being said we do believe that the proposals we are making today, and future proposals we may make, may provide some guidelines on how EPA intends to apply specific criteria in individual end-uses. In addition, we remain committed to continuing our outreach efforts and to sharing our thinking at the earliest moment practicable on any future actions we might consider. Finally, and as it relates to potential future actions that that EPA might consider under the SNAP program, the Agency continues to welcome comments and ideas on measures we might consider within the SNAP context to provide greater certainty to both producers and consumers in SNAP regulated industrial sectors.
V. What is EPA proposing for HFCs?
EPA is proposing to modify the listings from acceptable to unacceptable for certain HFCs and HFC blends in aerosol, foam blowing, and air conditioning and refrigerant end-uses where other alternatives are available or potentially available that pose overall lower risk. Per the guiding principle stated above, EPA is considering the intersection between the specific HFC or HFC blend and the particular end-use. This action does not propose that any specific HFCs be unacceptable across all sectors and end-uses. EPA is also not proposing that, for any specific sector, the only acceptable substitutes are HFC-free. EPA recognizes that both fluorinated (e.g., HFCs, HFOs) and non-fluorinated (e.g., HCs, CO
2
) substitutes are potentially acceptable. Instead, consistent with SNAP's history and CAA Section 612, EPA is proposing these modifications based on the substitutes being considered, the SNAP criteria for evaluation, and the current suite of other available and potentially available substitutes.
EPA is proposing to modify the following listings by end-use:
(1) For aerosol propellants, we are proposing to list, as of January 1, 2016
• HFC-125 as unacceptable;
• HFC-134a as acceptable, subject to use conditions, allowing its use only in specific types of technical and medical aerosols (e.g. metered dose inhalers) (and prohibiting its use in consumer aerosols); and
• HFC-227ea as acceptable, subject to use conditions, allowing its use only in metered dose inhalers.
(2) For motor vehicle air conditioning systems in newly manufactured light-duty vehicles, we are proposing to list
• HFC-134a as unacceptable starting with model year MY 2021; and
• The refrigerant blends SP34E, R-426A (also known as RS-24), R-416A (also known as HCFC Blend Beta or FRIGC FR12), R-406A, R-414A (also known as HCFC Blend Xi or GHG-X4), R-414B (also known as HCFC Blend Omicron), HCFC Blend Delta (also known as Free Zone), Freeze 12, GHG-X5, and HCFC Blend Lambda (also known as GHG-HP) as unacceptable starting with MY 2017.
(3) For new and retrofit retail food refrigeration (including stand-alone equipment, condensing units, direct supermarket systems, and indirect supermarket systems) and new and retrofit vending machines, we are proposing to list, as of January 1, 2016
• The HFC blends R-507A and R-404A as unacceptable.
(4) For new and retrofit retail food refrigeration (including direct supermarket systems and indirect supermarket systems), we are proposing to list, as of January 1, 2016
• HFC-227ea, R-407B, R-421B, R-422A, R-422C, R-422D, R-428A, and R-434A as unacceptable.
(5) For new stand-alone retail food refrigeration and new vending machines, we are proposing to list, as of January 1, 2016
• HFC-134a and certain other HFC refrigerant blends as unacceptable.
(6) For foam blowing agents, we are proposing to list, as of January 1, 2017, except where allowed under a narrowed use limit,
• HFC-134a and blends thereof as unacceptable in all foam-blowing end-uses;
• HFC-143a, HFC-245fa and HFC-365mfc and blends thereof, and the HFC blends Formacel B, and Formacel Z-6 as unacceptable in all foam blowing end-uses where they are currently listed as acceptable, except for spray foam applications; and
• The HFC blend Formacel TI as unacceptable in all foam blowing end-uses where it is currently listed as acceptable.
In general, the dates in this proposal for modifying the SNAP listings are based on information concerning the availability of alternatives with lower overall risk to human health and the environment for the end-uses considered. EPA is requesting comment on the proposed dates. As noted in the Regulatory Flexibility Act discussion in section IX of this preamble, EPA would like information on technical challenges that may exist. EPA is particularly interested in information concerning the supply of substitutes in sufficient quantities to meet the dates proposed in this action. EPA notes that several of the end-uses could be broken down further. EPA could consider adopting temporary narrowed use limits for a specific application of an end-use if the Agency determined that substitutes would be available for all but that specific application as of a particular date. For other applications in that end-use, the rule would list the substitute as unacceptable as of that date. For the specific application at issue, the rule could contain both a temporary narrowed use limit with an expiration date and a listing as unacceptable upon the expiration of the narrowed use limit. While the temporary narrowed use limit was in place, only persons using a substitute in the end-use for that specific application would be considered to not be in violation of section 612 of the CAA and EPA's SNAP regulations (40 CFR 82.174(c)). In addition, any such end user would need to comply with the requirement to analyze and document that there are no other alternatives that are technically feasible for their specific end-use. To support the adoption of a temporary narrowed use limit for a specific application of an end-use in the final rule, commenters should explain why other alternatives would not be available for the specific application of that end-use and for what period of time.
In determining whether to modify the listing decisions for substitutes based on whether other alternatives are available that pose lower risk to human health and the environment, we considered, among other things: scientific findings, information provided by the Technology and Economic Assessment Panel that supports the Montreal Protocol, journal articles, submissions to the SNAP program, the regulations and supporting dockets for other EPA rulemakings, presentations and reports presented at domestic and international conferences, and materials from trade associations and professional organizations. The materials on which we have relied may be found in the docket for this action. Key references are highlighted in section IX of today's notice.
A. Aerosols
1. Background
The SNAP program provides listings for two aerosol end-uses: propellants and solvents. Aerosols typically use a liquefied or compressed gas to propel active ingredients in liquid, paste, or powder form. In the case of duster sprays used to blow dust and contaminants off of surfaces, the propellant is also itself the active ingredient. Some aerosols also contain a solvent, which may be used in manufacturing, maintenance and repair to clean off oil, grease, and other soils.
Historically, a variety of propellants and solvents have been available to formulators. HCs (e.g., propane, isobutane) and compressed gases (e.g., CO
2
, N
2
, N
2
O, compressed air) have long been used as propellants. Prior to 1978, the aerosol industry predominantly used CFCs. CFCs were excellent propellants because of their ability to produce a fine spray, their non-flammability, their ability to be stored under low pressure, and their low reactivity with other ingredients. In 1978, in response to evidence regarding depletion of the earth's ozone layer, the United States banned CFC propellants. These regulations did not address HCFCs or solvent uses. For example, CFC-113 and methyl chloroform continued to be used as solvents in aerosols and HCFCs continued to be used.
Many consumer products that previously used CFC propellants were reformulated or replaced with a variety of alternatives, including not-in-kind substitutes, such as pump sprays or solid and roll-on deodorants. Aerosol propellant substitutes included HCFCs, HCs, HFCs, compressed gases, and oxygenated organic compounds. HCFCs are controlled substances under the Montreal Protocol and subject to regulation under the CAA including a phaseout of production and import under section 605(b)-(c) and use restrictions under section 605(a).
In 1993, EPA issued regulations that implemented CAA section 610's Congressionally mandated ban on the sale and distribution or offer for sale and distribution of certain non-essential products containing ozone-depleting substances (40 CFR Part 82 Subpart C). All aerosol products and pressurized dispensers containing, or manufactured with, CFCs and HCFCs—except those specifically exempted by the regulations—are banned from sale and distribution in interstate commerce in the United States. As a result of the Nonessential Products Ban, most aerosol products have been using low-GWP alternatives with no ozone depletion potential since the early 1990s.
2. Aerosols today
Following the 1994 ban on the sale and distribution of aerosols using HCFCs, HCFC propellants were replaced with a range of alternatives including HFCs (e.g., HFC-134a, HFC-152a), HCs, compressed gases, and not-in-kind alternatives. HCFC solvents were replaced by HFC-43-10mee, HFC-365mfc, HFC-245fa, HCs, oxygenated organic compounds, hydrofluoroethers (HFEs), and
trans
-dichloroethylene (typically blended with an HFC or HFE to reduce flammability of the formulation). Other acceptable low-GWP fluorinated compounds include HFOs. HFO-1234ze(E) is in use and under development for use in the aerosol industry as a propellant for manufacturing aerosol products. EPA regulations issued pursuant to CAA section 605 prohibit the use of HCFC-22 and HCFC-142b for manufacturing aerosol products. 40 CFR 82.15(g). EPA has proposed regulations addressing the use after January 1, 2015 of other HCFCs in aerosol products (e.g., HCFC-225ca/cb), as well as other provisions related to the phaseout of HCFCs under section 605 of the CAA (December 24, 2013; 78 FR 78072).
The United States aerosol industry manufactures aerosol products in the following three categories: (1) Consumer aerosols, (2) technical aerosols, and (3) medical aerosols. Consumer aerosols includes products for personal and household use. Examples include personal care products, such as: Cosmetics, hairspray, body sprays, and deodorants; automotive products such as tire inflators, auto lubricants, and brake cleaners; noise horns and safety horns; animal repellants; spray adhesives with various applications; household cleaning products; hand-held spray paint cans; eyeglass and keyboard dusters; consumer freeze sprays (e.g. chewing gum or excrement removal); air fresheners; food dispensing products; and novelty aerosols (e.g., artificial snow, plastic string, noise makers, and cork poppers).
Technical aerosols are aerosol products for sale and use solely in commercial and industrial applications, not for normal day-to-day consumer use or medical use. Technical aerosols includes industrial cleaners (e.g.,
electronic contact cleaners, brake cleaners, flux removers, degreasers); pesticides (e.g., certain wasp and hornet sprays, aircraft insecticides); a subset of dusters (e.g., for photographic negatives, semiconductor chip manufacture, specimens for observation under electron microscope); and spinnerette lubricant/cleaning sprays. Technical aerosols also includes other miscellaneous products such as industrial spray paints and document preservation sprays.
Medical aerosols are for sale and use for medical purposes and include, but are not limited to, products regulated by the U.S. Food and Drug Administration (FDA). Medical aerosols include metered dose inhalers for the treatment of asthma and chronic obstructive pulmonary disease, calamine spray, anti-fungals, wart treatments, wound care sprays, freeze or coolant spray for pain relief, spray-on “liquid” bandages, and products for removing bandage adhesives.
Some aerosols could be considered under more than one of the categories described above. For example, insect sprays include products with both commercial and consumer applications. The commercial application would include insect sprays used by utility power line workers around high tension power lines (i.e., a technical aerosol) and the consumer use would include residential household insect repellant commonly sold to homeowners (i.e., a consumer aerosol). Another example is freeze sprays which may be either consumer aerosols (e.g., food freeze sprays, animal waste sprays) or medical aerosols (e.g., wart removers, pain relievers).
Most of the demand for consumer aerosols in the United States is concentrated within household consumer products. This category has the highest production volume, reporting a 2.4% increase from 2010 to 2011 (CSPA 2012). The NAICS code that includes many personal care products (325620) is the highest grossing NAICS category of those that EPA has identified as manufacturing consumer aerosols (ICF 2014a). Some of the dominant consumer aerosols includes air fresheners, deodorants, household cleaners, and hairspray.
3. What is EPA proposing concerning aerosols?
Today's action addresses HFCs in propellants in aerosols. EPA is proposing to modify the listings for HFC-125, HFC-134a and HFC-227ea as of January 1, 2016 as follows:
• EPA is proposing to change the listing for the aerosol propellant HFC-125 from acceptable to unacceptable.
• We are proposing to list the aerosol propellant HFC-134a as acceptable, subject to use conditions allowing its use only in the following: Cleaning products for removal of grease, flux and other soils from electrical equipment or electronics; lubricants for electrical equipment or electronics; sprays for aircraft maintenance; pesticides for use near electrical wires, in aircraft, in total release insecticide foggers, or in certified organic use pesticides for which EPA has specifically disallowed all other lower-GWP propellants; mold release agents; lubricants and cleaners for spinnerettes for synthetic fabrics; duster sprays specifically for removal of dust from photographic negatives, semiconductor chips, and specimens under electron microscopes; document preservation sprays; metered dose inhalers for the treatment of asthma, chronic obstructive pulmonary disease, allergic rhinitis, and other diseases where aerosols can be used for systemic delivery through lung, nose, or other organs; wound care sprays; topical coolant sprays for pain alleviation; and products for removing bandage adhesives from skin.
• EPA is also proposing to list HFC-227ea as acceptable, subject to use conditions, allowing its use only in metered dose inhalers.
a. What other alternatives are available?
EPA is proposing to change the listing decisions for HFC-125, HFC-134a, and HFC-227ea as of January 1, 2016 because safer alternatives (i.e., chemical compounds and technological options) are available or potentially available that reduces the overall risk to human health and the environment. Other substitutes listed as acceptable propellants include HFC-152a, HFO-1234ze(E), butane, propane, isobutane, CO
2
and other compressed gases, and dimethyl ether (DME). In addition, technological options include not-in-kind alternatives such as finger/trigger pumps, powder formulations, sticks, rollers, brushes, and wipes. These alternatives have GWPs ranging from zero to 124 compared with HFC-134a's GWP of 1,430, HFC-227ea's GWP of 3,220 and HFC-125's GWP of 3,500.
24
All of these alternatives have an ODP of zero, are relatively low in toxicity, and are capable of remaining below their respective exposure limits when used as aerosol propellants. In addition to GWP and climate impacts, some of the other environmental and health attributes that the SNAP program considers that differ for these alternatives include impacts on local air quality and flammability. For example, butane, propane, isobutane, and DME are VOCs as well as being flammable. Butane, propane, isobutane, and DME are defined as VOCs under CAA regulations (see 40 CFR 51.100(s)) addressing the development of state implementation plans (SIPs) to attain and maintain the national ambient air quality standards; thus, these propellants are subject to federal, state, and local regulation that may prevent their use as a propellant in aerosols in some states and counties that have nonattainment areas for ground-level ozone. HFC-125, HFC-134a, HFC-227ea, HFC-152a, HFO-1234ze(E), and the compressed gases CO
2
and N
2
are not defined as VOCs under these regulations and their use is expected to have negligible impact on ground-level ozone levels.
24
GWP values cited in this proposal are from the IPCC Fourth Assessment Report (AR4) unless stated otherwise. Where no GWP is listed in AR4, GWP values shall be determined consistent with the calculations and analysis presented in AR4 and referenced materials.
i. Consumer Aerosols
For consumer aerosols, there are three alternatives with lower GWPs that meet other environmental regulatory requirements: HFC-152a, which has a GWP of 124; HFO-1234ze(E) with a GWP of 6; and CO
2
with a GWP of 1. All three have GWPs significantly lower than those of the HFCs proposed to be unacceptable or subject to use conditions (range of GWPs from 1430 to 3500 for HFC-134a, HFC-227ea and HFC-125). These three substitutes also provide a range of performance based on vapor pressure, which is important because it affects the ability to propel the necessary ingredients out of the aerosol container. The vapor pressures of HFO-1234ze(E), HFC-152a, and CO
2
at 20 °C are 422 kPa, 510 kPa, and 5776 kPa, respectively.
ii. Technical Aerosols
Technical aerosols sometimes need to meet more rigorous requirements for selection because of performance demands that do not exist for most consumer aerosols. For example, nonflammable aerosols are needed for use on energized electrical circuits, where sparking can create a fire or explosion hazard. Of the different acceptable alternatives, the nonflammable options at room temperature include HFC-125, HFC-134a, HFC-227ea, HFO-1234ze(E) and compressed gases including CO
2
and N
2
. At slightly higher temperatures (30 °C or 85 °F), HFO-1234ze(E) exhibits lower and higher flammability limits and
could catch fire under specific conditions of concentration and in the presence of a high energy spark or flame. Some aerosol product formulators have expressed concern that the lower vapor pressure of HFO-1234ze(E) and the significantly higher vapor pressure of CO
2
and other compressed gases may not provide adequate performance in propelling contents of a can or in remaining within the can for technical aerosols. For comparison, the vapor pressures of HFO-1234ze(E), HFC-134a, and CO
2
at 20 °C are 422 kPa, 655 kPa, and 5776 kPa, respectively.
The conditions under which technical aerosols are often used requires non-flammability and/or specific vapor pressure be met. Based on the information available today, EPA believes it is necessary to continue to allow for HFC-134a to be used for certain technical spray applications because of these technical limitations. We are therefore proposing to list HFC-134a as acceptable subject to use conditions which would limit use to those specific applications.
HFC-134a is the propellant with the lowest GWP that can consistently meet the technical aerosol performance requirements, other environmental regulatory requirements, and is nonflammable. EPA considered whether HFC-227ea or HFC-125 should be continue to be listed as acceptable for any specific uses. However, both these HFCs have significantly higher GWPs than HFC-134a (HFC-227ea's GWP is 3220 and HFC-125's GWP is 3500). Moreover, EPA is not aware of the use of HFC-227ea in technical aerosols. Similarly, EPA is not aware of any significant use of HFC-125 in technical aerosols. Neither HFC-227ea nor HFC-125 provides greater reduction in health or environmental risk than HFC-134a.
iii. Medical Aerosols
EPA is proposing to list HFC-134a and HFC-227ea as acceptable subject to use conditions which specify that these two HFCs are acceptable for metered dose inhalers (MDIs) to ensure that there is no confusion about the ability to continue to use these HFCs in these medical aerosols. In addition, we are proposing to list HFC-134a as acceptable subject to use conditions for wound care sprays, for topical coolant sprays for pain alleviation and for products for removing bandage adhesives from skin. For medical aerosols, there are special needs for safety and low toxicity. Furthermore, in order for a substitute to be available for use in medical devices, it must first be reviewed and approved by the FDA. FDA has approved medications for use in metered dose inhalers using HFC-134a and HFC-227ea as propellants, as well as some not-in-kind dry powder medications.
FDA has not approved medications for MDIs or other medical aerosols using HFC-125. EPA is aware of some medical aerosols that are currently using hydrocarbons or DME as the propellant, as well as not-in-kind alternatives; these medical aerosols include antifungals, calamine sprays, freeze sprays for wart removal, and liquid bandages (ICF, 2014a). EPA has insufficient information that alternatives other than HFC-134a are available as propellants in wound care sprays; topical coolant sprays for pain alleviation; and products for removing bandage adhesives from skin. Therefore, we cannot conclude that these are available alternatives with less overall risk to human health and the environment than HFC-134a. For these reasons, we are proposing to list HFC-227ea as acceptable subject to a use condition limiting its use to MDIs and to list HFC-134a as acceptable subject to use conditions limiting its use to MDIs and the other medical uses listed above.
HFC-125 has a GWP of 3,500, which is higher than the GWP of all other alternatives that are available for use as aerosol propellants (HFC-227ea has a GWP of 3220; HFC-134 has a GWP of 1430; HFO-1234ze(E) has a GWP of 6). Like HFC-134a, HFC-227ea, CO
2
and HFO-1234ze(E), it is VOC-exempt, nonflammable and low in toxicity. When EPA listed HFC-227ea as acceptable (May 22, 1998; 63 FR 28251), EPA noted that it was doing so despite the relatively high GWP of this compound, because it fit a specialized application, metered dose inhalers, where other substitutes were not available that would provide acceptable performance.
EPA's proposed approach to restricting the use of HFC-134a and HFC-227ea only to manufacturing certain specific types of aerosol products is modeled upon the Nonessential Product Ban exemptions for ODS in subpart C of 40 CFR part 82. A difference between that ban and the proposed use conditions is that the Nonessential Products Ban addressed the
sale and distribution
or offer for sale and distribution of aerosol products in interstate commerce, whereas this proposal addresses the propellants that may be
used in manufacturing
aerosol products.
Today, EPA is proposing to list HFC-125 as unacceptable, HFC-227ea as acceptable subject to use conditions allowing its use only for MDIs and HFC-134a as acceptable subject to use conditions allowing its use only for specific technical and medical aerosols, including MDIs. We request comment on this approach to modifying the listings of these three HFCs. We also request comment on whether any of the proposed technical aerosol uses of HFC-134a should not be allowed or whether there are additional uses that should be added to the list of allowed uses under the use conditions. Through this action, EPA is not intending to alter the listing as acceptable for HFC-227ea and HFC-134a for metered dose inhalers. EPA is seeking comment on the additional medical and technical aerosol uses of HFC-134a.
b. What other approaches is EPA considering?
EPA is considering two approaches to changing the listings for aerosols and seeks comments on both. The first, as discussed above, is to find HFC-125 unacceptable and find HFC-227ea and HFC-134a acceptable subject to use conditions, where the use conditions specify a list of allowed uses or product types that may continue to use these HFCs (e.g., metered dose inhalers for both HFCs, insect sprays used near high tension power lines for HFC-134a). A second approach we are considering is to find HFC-125 unacceptable and to find HFC-134a acceptable subject to narrowed use limits in technical and medical aerosols and HFC-227ea subject to narrowed use limits in metered dose inhalers. Narrowed use limits are considered “use restrictions” and are explained above. In this case, only persons using HFC-227ea in metered dose inhalers or using HFC-134a in technical or medical aerosols would be considered to not be in violation of section 612 of the CAA and EPA's SNAP regulations (40 CFR 82.174(c)). The terms “technical aerosol” and “medical aerosol” would apply to the types of aerosols described above in section 2. “Aerosols today.” Under the narrowed use limits, a manufacturer or other user intending to use the substitute could only use HFC-134a in manufacturing a technical or medical aerosol, or HFC-227ea in manufacturing a metered-dose inhaler, after ascertaining that other alternatives are not technically feasible. The user also would be required to document their evaluation. 40 CFR 82.180(b)(3).
Advantages to the proposed approach of specifying the allowed uses are that the list is clear about which products are allowed to use HFC-134a or HFC-227ea, both for users and for EPA. In addition, because EPA is specifying the uses in advance, end-users would not be
required to perform an evaluation and would not be required keep paperwork to document their evaluation, thereby reducing regulatory burden. A potential advantage of setting narrowed use limits is that it may encourage a larger number of manufacturers and users to evaluate alternatives and potentially identify more uses where HFC-134a is not required. Further, establishing narrowed use limits may allow greater flexibility if there are additional types of technical or medical aerosol products with performance or safety constraints requiring HFC-134a that EPA has not identified in this proposal. EPA requests comment on these two approaches to modifying the listings of HFC-134a and HFC-227ea as aerosol propellants.
c. When would the modified listings apply?
EPA is proposing January 1, 2016 as the date on which the listings for HFC-125, HFC-134a and HFC-227ea would be modified. Thus products manufactured on or after January 1, 2016 in contravention of the unacceptable or acceptable subject to use conditions listing for these substitutes could not be used.
We are proposing this date because we believe it is expeditious but will allow sufficient time after this proposed rule for end users to make the transition to alternatives. Based on the information available to EPA today and on various discussions with industry representatives. EPA believes that formulators and packagers of aerosols can make the necessary changes within this timing (ICF, 2014a; Honeywell, 2014). In most cases, EPA believes it will take approximately six months for the necessary changes to be made. This timing would provide the affected aerosol manufacturers and packagers sufficient time to change and test formulations and, to the extent necessary, to change the equipment in their factories.
To prevent stranded inventory, we are proposing that products manufactured prior to January 1, 2016 using these propellants, could be still be sold, imported, exported, and used by the end user after January 1, 2016. This would avoid the possibility that end users would need to dispose of a usable product, including the potential for improper releases of the content into the environment.
d. On which topics is EPA requesting comment?
EPA requests comment on the proposal to change the listing for the following aerosol propellants: HFC-125 from acceptable to unacceptable; HFC-134a from acceptable to acceptable, subject to use conditions allowing its use only in: cleaning products for removal of grease, flux and other soils from electrical equipment or electronics; lubricants for electrical equipment or electronics; sprays for aircraft maintenance; pesticides for use near electrical wires, in aircraft, in total release insecticide foggers, or in certified organic use pesticides for which EPA has specifically disallowed all other lower-GWP propellants; mold release agents; lubricants and cleaners for spinnerettes for synthetic fabrics; duster sprays specifically for removal of dust from photographic negatives, semiconductor chips, and specimens under electron microscopes; document preservation sprays; metered dose inhalers for the treatment of asthma, chronic obstructive pulmonary disease, allergic rhinitis, and other diseases where aerosols can be used for systemic delivery through lung, nose, or other organs; wound care sprays; topical coolant sprays for pain alleviation; and products for removing bandage adhesives from skin; and HFC-227ea from acceptable to acceptable, subject to use conditions, allowing its use only in metered dose inhalers.
EPA also received suggestions from the aerosol industry to consider an exception to allow the use of HFC-134a in additional categories of aerosol products. EPA is not proposing to include these categories, either because we are aware of existing products in these categories using low GWP propellants, or because we have insufficient information indicating that the use of HFC-134a is necessary for these categories of products because other substitutes that pose lower risk are not currently or potentially available. These categories include: component freeze sprays, tissue freezes, refrigeration system flushes, portable safety horns for use in marine and industrial applications, tire inflators, and personal defense sprays. We are aware of low-GWP formulations already on the market today for defensive sprays and tissue freezes. These formulations may use flammable and/or non-flammable propellants. We request information on why available substitutes other than HFC-134a are not and cannot be used in these categories of products, including information on why flammability may be a concern or not in the product category; whether other alternative propellants with lower GWP in place of HFC-134a have been tested in these products; and what results of those tests have shown about the technical feasibility and/or safety of the other alternative propellants.
Finally, we request comments on modifying the listings as of January 1, 2016. We request commenters include specific information on whether it would be technically feasible for end-users to transition by January 1, 2016, and, if not, what steps are necessary for manufacturers to switch to other alternatives and how long those steps are expected to take.
B. Motor Vehicle Air Conditioning for Newly Manufactured Light-Duty Motor Vehicles
1. Background
MVAC systems cool passenger cars, light duty trucks, buses, and rail vehicles. CFC-12 refrigerant was historically used in MVAC systems. HFC-134a replaced CFC-12 in new equipment in the early 1990s. Today, HFC-134a is the dominant refrigerant used in light-duty vehicles worldwide. When EPA found HFC-134a acceptable in MVAC for light duty vehicles in 1994 (March 18, 1994; 59 FR 13044), the Agency stated:
HFC-134a does not contribute to ozone depletion. HFC-134a's GWP and atmospheric lifetime are close to those of other alternatives which have been determined to be acceptable for this end-use. However, HFC-134a's contribution to global warming could be significant in leaky end-uses such as MVACs. EPA has determined that the use of HFC-134a in these applications is acceptable because industry continues to develop technology to limit emissions. In addition, the number of substitutes available for use in MVACs is currently limited. HFC-134a is not flammable and its toxicity is low.
This analysis was consistent with the information available in 1994. Since that time, four additional substitutes have been added to the list of substitutes that are acceptable subject to use conditions for light duty vehicles. As described more fully below, if these other substitutes are used in systems designed consistent with the prescribed use conditions, they pose significantly lower risk to human health and the environment than HFC-134a. EPA is therefore proposing to remove HFC-134a from the list of acceptable substitutes for new light-duty vehicles' MVAC systems and add it to the list of unacceptable substitutes.
Since 1994, additional alternatives for MVACs have been listed as acceptable subject to use conditions.
25
Three of these alternatives—HFO-1234yf, HFC-152a, and carbon dioxide (R-744)—are non-ozone depleting like HFC-134a and have low GWPs compared to HFC-134a. HFC-152a has a GWP of 124, HFO-1234yf has a GWP of 4, and R-744 (by
definition) has a GWP of 1 while HFC-134a has a GWP of 1,430. R-744 is nonflammable, HFO-1234yf and HFC-152a are flammable, but are subject to use conditions that address flammability concerns. All three substitutes are subject to use restrictions that ensure exposure limits that protect against adverse health effects will not be exceeded and all three are VOC exempt.
25
Listed at 40 CFR part 82, subpart G.
At the time EPA listed HFC-134a as acceptable, the agency was not aware of any vehicle manufacturer, MVAC supplier, or chemical producer considering HFO-1234yf as a refrigerant. Today, HFO-1234yf is in use in MVAC systems in approximately nine
26
models in the United States by several manufacturers of light-duty vehicles. EPA expects additional models will be introduced using HFO-1234yf systems over the next several years.
26
http://www.autonews.com/article/20131230/OEM01/312309996/warming-to-the-idea.
To date, at least one global manufacturer of light-duty vehicles has announced their intention to commercialize vehicles using R-744 in MVAC systems later this decade.
27
In the mid-1990s, EPA became aware that R-744 systems might be a feasible alternative in this application, but the state of research and development indicated that it was not yet available because a design had not yet been developed that would allow safe use in MVAC systems in light duty vehicles. Nearly 20 years later, EPA is still not aware of current commercial use of R-744 in MVAC systems. However, significant research and development is occurring in order to ensure R-744 can be used safely in MVAC systems.
27
Daimler, 2014
In addition to HFO-1234yf, HFC-152a, and R-744, EPA is aware of ongoing research and development which could ultimately result in future listings of additional alternatives for MVAC systems. One chemical producer indicated their intent to seek SNAP approval for another low-GWP alternative that is a blend with a GWP below 150.
28
28
Mexichem statement during motor vehicle stakeholder meeting December 6, 2013
There are also other blends which EPA has listed as acceptable or acceptable subject to use conditions. None of these are currently used by the original equipment manufacturers (OEMs). Several of these previously listed substitutes have GWPs that are significantly higher than the GWPS for HFO-1234yf, HFC-152a, and R-744 and higher overall risk than these other three substitutes. EPA is proposing to list as unacceptable the following substitutes in addition to HFC-134a: SP34E (GWP of 1300), R-426A (also known as RS-24) (GWP of 1508), R-416A (also known as HCFC Blend Beta or FRIGC FR12) (GWP of 1015) and the HCFC blends, R-406A, R-414A (also known as HCFC Blend Xi or GHG-X4), R-414B (also known as HCFC Blend Omicron), HCFC Blend Delta (also known as Free Zone), Freeze 12, GHG-X5, and HCFC Blend Lambda (also known as GHG-HP), with GWPs ranging from 1480 to 2340 and ODPs ranging from 0.012 to 0.056. For simplicity, we refer to these substitutes as “the refrigerant blends” in the following discussion.
2. What is EPA proposing regarding use of HFC-134a and use of refrigerant blends in MVAC systems for newly manufactured light-duty motor vehicles?
EPA is proposing to list HFC-134a as unacceptable for use in MVAC systems in newly manufactured light-duty vehicles beginning with MY 2021. We are proposing MY 2021 because that is the time by which all light-duty vehicle models can be redesigned to safely use MVAC systems using other available refrigerants. As explained above, three alternatives on the SNAP list of acceptable substitutes subject to use conditions —HFC-152a, R-744, and HFO-1234yf—have significantly lower GWPs than HFC-134a. All three of these lower-GWP alternatives are non-ozone depleting and are subject to use restrictions that ensure exposure limits that protect against adverse health effects will not be exceeded. All three are VOC exempt. HFO-1234yf and HFC-152a are flammable, but are subject to use conditions that address flammability concerns. R-744 is not flammable. Because HFC-134a has a significantly higher GWP than HFC-152a, R-744, and HFO-1234yf and because the risks posed by these three refrigerants are addressed through use conditions, we are proposing to list HFC-134a as unacceptable. However, because the three refrigerant alternatives pose lower risk than HFC-134a only if used consistent with the established use conditions, in deciding when the unacceptability determination should apply, we considered the date by which automobile manufacturers will be able to redesign all vehicle models (including design of the MVAC systems) consistent with the use conditions.
EPA is proposing to list the refrigerant blends SP34E, R-426A, R-416A, R-406A, R-414A (also known as HCFC Blend Xi or GHG-X4), R-414B (also known as HCFC Blend Omicron), HCFC Blend Delta (also known as Free Zone), Freeze 12, GHG-X5, and HCFC Blend Lambda (also known as GHG-HP) as unacceptable beginning in MY 2017 for use in MVAC systems in newly manufactured light-duty motor vehicles. Since these refrigerant blends are not currently in use in any MVAC systems in light-duty vehicles, we believe it is appropriate for the unacceptability determination to apply to model year vehicles currently being designed. Further, all but the first two of these blends have ODPs, and all have significantly higher GWPs than other alternatives such as HFC-152a, HFO-1234yf, and CO
2
.
EPA has previously examined when automobile manufacturers may be able to transition their fleets to lower GWP refrigerants in its rules to extend the greenhouse gas and fuel economy standards for model year (MY) 2017-2025 light-duty vehicles. 77 FR 62624, 62807-810 (October 15, 2012); see also 75 FR 25325, 25431-32 (May 7, 2010) (discussing the same issue for MY 2012-2016 light duty vehicles). EPA and the National Highway Traffic Safety Administration jointly issued these rules on August 28, 2012. Over the lifetime of the MY 2017-2025 light-duty vehicles (passenger cars, light-duty trucks, and medium-duty passenger vehicles), these rules are projected to save approximately 4 billion barrels of oil and 2 billion metric tons of GHG emissions, with societal net benefits up to $451 billion. 77 FR 62629. The standards build off those set in April 2010 for MY 2012-2016 light-duty vehicles, which are projected to save approximately 1.85 billion barrels of oil and 962 million metric tons of GHG emissions over the lifetime of the affected vehicles, with societal net benefits of up to $192 billion. 75 FR 25347. EPA projects that the entire light-duty vehicle fleet will meet a target of 163 grams of carbon dioxide equivalent (CO
2
eq) per mile in MY 2025 (or 54.5 mpg if the automotive industry meets the target exclusively through fuel efficiency improvements).
When refrigerants leak from current motor vehicle air conditioning systems, they contribute to overall GHG emissions. Using lower GWP refrigerants can significantly reduce the climate impact of these emissions. Given the increasing availability of lower-GWP chemicals suitable for this purpose and systems that can use them, as well as increasing requirement for lower-GWP refrigerants in Europe,
29
EPA based the light-duty GHG standards
for MYs 2017-2025 in part on an expected gradual transition to lower-GWP refrigerants. Thus, in setting the level of the standards, EPA projected that the industry will make the full transition to lower-GWP refrigerants over the period of time spanning between MY 2017 and MY 2021, and the level of the standard in each of these model years reflects a projected 20 percent increase in substitution in each model year and complete transition by MY 2021. 77 FR 62720/2-3. In support of the assumption of this multi-year transition, the Light-Duty GHG rule for MYs 2017-2025 includes an extensive discussion of the refrigerant substitute availability and technical feasibility of transitioning the fleet. 77 FR 62720; 62807-810.
29
Directive 2006/40/EC of the European Parliament and of the Council of 17 May 2006 (EU MAC Directive). Available at:
http://eur-lex.europa.eu/LexUriServ/LexUriServ.do?uri=CELEX:32006L0040:EN:HTML.
At the time the Light Duty GHG rule was promulgated, EPA (and other entities) voiced concerns with the potential supply of HFO-1234yf, but today production plans for the refrigerant appear to be in place to make it available in volumes that meet current and projected domestic auto industry demand, consistent with the projections in the Light Duty GHG rulemaking. Multiple production facilities are now producing HFO-1234yf, and recently another global chemical producer announced plans to produce HFO-1234yf by 2017. Moreover, some automotive manufacturers are developing systems that can safely use other substitutes, including R-744, and continued progress is likely given the EU's implementation of the MAC Directive. If some global light-duty motor vehicle manufacturers use R-744, additional volumes of HFO-1234yf that would have been used by those manufacturers will then become available. Therefore, there also appears to be sufficient supply to meet demand domestically and abroad, including in the European Union, during this time frame.
In addition to considering when the supply of alternative refrigerants would be sufficient to transition the entire light duty vehicle fleet, EPA necessarily also considered when vehicle manufacturers could design systems for safe use of these alternatives consistent with the regulatory use conditions.
30
EPA considered the practices used by the auto manufacturing industry in introducing new technologies into their vehicles. For each vehicle model, manufacturers establish a “redesign” (or product development) cycle over which they plan any significant technological changes to that vehicle. Between the major redesign model years, they may make only minor “refresh” changes. Redesign cycles vary by model and by manufacturer and average about 5 model years in duration. (See 77 FR 62712 and 75 FR 25407, 25451 for a more detailed discussion of this practice.) At any point in time, a manufacturer may have some vehicles at or approaching a major redesign point and others that are earlier in their product cycle.
30
As previously noted, HFO-1234yf, R-744 and HFC-152a are all listed as acceptable subject to use conditions and many of the use conditions address the design of systems to account for the flammability or exposure.
In the final rule establishing light-duty vehicle GHG standards for MYs 2017-2025, EPA assumed that the transition to alternative refrigerants would generally occur during manufacturer model redesigns and used the overall typical industry redesign cycle of 5 model years to estimate how the expected industry-wide transition to new refrigerants might occur. For analytical purposes, and based on information available at the time, we projected that the transition would occur from MY 2017 until MY 2021. EPA recognizes there have been some early adopters. The transition began in a small number of MY 2013 vehicles and is increasing in MY 2014 but has been relatively limited to date.
31
While some may maintain that early adoption equates to a faster overall transition, EPA notes that early adoption remains limited and therefore we continue to view our projection of full transition not occurring until MY 2021 as reasonable.
31
Nelson, Gabe “Automakers' switch to new refrigerant will accelerate with EPA credits, European mandate” Automobile News, December 30, 2013.
http://www.autonews.com/article/20131230/OEM01/312309996/warming-to-the-idea.
Although there may be some limited ability to switch a vehicle model to an MVAC system using a low GWP refrigerant in between redesign periods, most model types will require significant hardware changes that may only be possible during a redesign. HFO-1234yf, for example, has measurably lower efficiency than that of HFC-134a, usually requiring hardware changes and/or changes to overall air conditioning system design and layout.
32 33
This contrasts with the case of the transition in the 1990s from CFC-12 to HFC-134a, where the systems had similar coefficients of performance and manufacturers were able to switch many vehicles mid-cycle. Vehicles that require relatively more cooling capacity will be more dependent on a redesign cycle for a transition to HFO-1234yf since the specifications for hardware would need to be revisited. Most manufacturers have “locked-in” their planned product designs out to MY 2016, MY 2017, or even MY 2018. If any of these manufacturers have not planned to implement alternative refrigerant systems in these late model year vehicles, the next design cycle opportunity to make a change would be unlikely to occur until MY 2021 (or even MY 2022). In addition, at least one manufacturer has stated that it plans on using R-744 (CO
2
) systems. R-744 systems require significantly more complex redesign and hardware and would need to occur during product redesign, not product refresh given its pressure is significantly different than HFC-134a. These systems are currently in prototype phase, and there are significant technical hurdles yet to overcome. Given EPA's understanding, above, of the supply of the alternative refrigerants and the redesign cycle for MVAC systems, EPA is proposing to list HFC-134a as unacceptable for new MVAC systems beginning with MY 2021 because this is the time by which all light-duty vehicle models can be redesigned to safely use MVAC systems with alternative refrigerants.
32
Weissler, Paul, “A/C Industry Faces Challenges From Daimler R-1234yf Issue, Explores Other Options,” Automotive Engineering International, April 2, 2013.
33
One manufacturer informed EPA in a meeting that hardware changes were necessary or likely when shifting from a HFC-134a to a HFO-1234yf system, including the following: compressor oil and/or compressor changes, possible A/C piping modification due to the change in valve shape, and, in the vehicle manufacturing plant, additional refrigerant charging process changes. (EPA Memorandum: “Notes from Meeting with Nissan Concerning Alternative Refrigerant Transition”, Tad Wysor, April 2014.) Other manufacturers made similar statements to EPA.
As a cross-check, EPA explored whether vehicles and MVAC systems designed consistent with the use conditions for the three alternative refrigerants might be available earlier than MY 2021, evaluating (but not proposing) MYs 2017 and 2019. MY 2017 is the date included in the petition described above and in the EU MAC Directive. Since most motor vehicle manufacturers will seek a global vehicle design platform, selecting the same date as the date in the EU MAC Directive has some weight. MY 2019 is an intermediate date between MYs 2017 and 2021.
The agency believes it is necessary for MVAC system redesigns for many vehicles to occur during a design cycle to safely use the substitute refrigerants, as just explained. Manufacturers are currently designing or have “locked in” designs for vehicles several model years into the future. The information currently before the Agency thus indicates that it would not be
technically feasible for manufacturers to safely transition all vehicles from HFC-134a MVACs by MY 2017. EPA is not proposing the MY 2019 date for the same reasons. However, we solicit comment on whether all manufacturers would be able to safely transition all vehicles away from HFC-134a MVAC systems by MY 2017 or MY 2019.
We also considered whether a MY later than MY 2021 should be the appropriate time for use of HFC-134a in MVAC systems in new vehicles to be listed as unacceptable. In recent meetings with the major trade associations for the auto industry (the Alliance and Global Automakers) as well as with meetings with several individual manufacturers, industry representatives indicated that some of them may have a relatively small number of vehicle models that will not have had the opportunity for an engineering redesign by MY 2021. They also indicated that there may be technical barriers for certain models that would require longer product design cycles if the systems were to use substitute refrigerants. However, we do not have sufficient non-confidential information to conclude that systems capable of using alternative refrigerant safely will not be “currently or potentially available”—within the meaning of section 612 (c)(2) of the Act—until after MY 2021. EPA requests comments on changing the status of HFC-134a in a model year later than MY 2021 (such as MY 2025), including specific information supporting claims that a transition by MY 2021 would not be technically feasible because specific model vehicles cannot be redesigned to safely use alternative refrigerants by MY2021. For the reasons explained earlier, EPA believes safer alternatives will be available by MY 2021.
Based on the information before the Agency, EPA is thus proposing to modify the listing of HFC-134a to unacceptable as of MY 2021 for light duty vehicles, while seeking comment on MYs 2017, 2019, and MYs later than 2021.
34
34
Typically, regulations promulgated under CAA Title VI have applied to specified calendar years, However, because the MVAC system used is so closely related to vehicle design, we have used MY for purposes of this proposed rule. Model years cover almost two calendar years, beginning after January 1 of the previous calendar year and ending on January 1 of the following calendar year.
EPA is not proposing changes that would alter the ability to service existing motor vehicles designed to use HFC-134a. Such a change could strand the installed base of equipment or force retrofits to other refrigerants. In order to safely use most MVAC refrigerants, the vehicle design as well as the MVAC design may need to be modified in order to ensure the refrigerant can be used safely. For that reason, the three low-GWP refrigerants that currently are listed as acceptable in new MVACs—HFO-1234yf, HFC-152a, and R-744-are not listed as acceptable to retrofit a system designed to use a different refrigerant.
Once MVAC systems are designed and installed with lower GWP substitutes, they will likely need to be serviced. Some stakeholders have expressed a concern that the price differential between HFO-1234yf and HFC-134a provides an economic incentive to replace HFO-1234yf with HFC-134a during servicing. See 77 FR 62807. Two sets of regulations under title VI of the CAA make it clear that doing so is unlawful. First, the SNAP regulations prohibit using a substitute refrigerant to `top-off' a system that uses another refrigerant. Second, the original refrigerant must be recovered in accordance with regulations issued under section 609 of the CAA prior to charging with a substitute (40 CFR 82.34). Thus, the recycling and recovery regulations prohibit adding a new refrigerant to the system without first recovering the refrigerant already in the system. Therefore, it is not permissible to add HFC-134a to an MVAC system that contains HFO-1234yf, as may well occur if a consumer were to service his or her own car's A/C system without refrigerant recovery equipment. In addition, the SNAP listings for HFO-1234yf and HFC-134a require the use of unique fittings for each alternative refrigerant. Using an adapter or deliberately modifying a fitting to use a different refrigerant is a violation of these use conditions.
EPA seeks comments on changing the listing of SP34E, R-426A, R-416A, R-406A, R-414A (also known as HCFC Blend Xi or GHG-X4), R-414B (also known as HCFC Blend Omicron), HCFC Blend Delta (also known as Free Zone), Freeze 12, GHG-X5, and HCFC Blend Lambda (also known as GHG-HP) to unacceptable for use as refrigerants in air conditioning systems for newly manufactured light-duty motor vehicles beginning with MY 2017 and changing the listing of HFC-134a to unacceptable beginning with MY 2021.
3. Would this action affect EPA's light duty vehicle rule?
Today's proposal, should EPA adopt it, will have no direct effect on the MY 2017-2025 light duty vehicle GHG standards. Those standards are established by rule and EPA is not reopening that rule in this proceeding. We do note, however, that today's proposal is relevant to one of the compliance flexibilities in the light duty vehicle standards. The light duty vehicle standards do not require any specific means of compliance. Manufacturers thus have the flexibility to either switch refrigerants or to comply with the standards by other means. The light duty standards do provide that manufacturers can generate credits from use of alternative refrigerants with lower GWPs than that of HFC-134a through MY 2025, and the ability to generate and use those credits towards compliance with the light duty standards will not change if this action is finalized as proposed. See 77 FR 62804-809. (As noted above, the level of the standard reflects the assumption of 100% substitution by MY 2021). Even though a manufacturer may choose to comply with the light duty standard by a strategy not involving refrigerant substitution, in MY 2021, this proposed rule, if finalized, would still require the manufacturer to use an MVAC designed for a refrigerant other than HFC-134a.
C. Retail Food Refrigeration and Vending Machines
1. Background
Retail food refrigeration, an end-use within the SNAP program that is also considered a subset of the broader term “commercial refrigeration,” is characterized by storing and displaying, generally for sale, food and beverages at different temperatures for different products (e.g., chilled and frozen food). The designs and refrigerating capacities of equipment vary widely. Vending machines are another subset of commercial refrigeration considered as a separate end-use within the SNAP program due to differences in where such equipment is placed and the additional mechanical and electronic components required to accept payment, provide the selected product, and prevent theft or damage from vandalism.
Retail food refrigeration is composed of three main categories of equipment: Stand-alone equipment; condensing units; and supermarket systems, the latter often in designs referred to as multiplex or centralized refrigeration systems. Stand-alone equipment consists of refrigerators, freezers, and reach-in coolers (either open or with doors) where all refrigeration components are integrated and, for the smallest types, the refrigeration circuit is entirely brazed or welded. These systems are charged with refrigerant at the factory and typically require only an electricity supply to begin operation.
Condensing units exhibit refrigerating capacities ranging typically from 1 kW to 20 kW (0.3 to 5.7 refrigeration tons). They are composed of one (and sometimes two) compressor(s), one condenser, and one receiver assembled into a single unit, which is normally located external to the sales area. This equipment is connected to one or more nearby evaporator(s) used to cool food and beverages stored in display cases and/or walk-in storage rooms. Condensing units are commonly installed in convenience stores and specialty shops such as bakeries and butcher shops.
Typical supermarket systems are known as multiplex or centralized systems. They operate with racks of compressors installed in a machinery room; different compressors turn on to match the refrigeration load necessary to maintain temperatures. Two main design classifications are used: Direct and indirect systems. In the United States, direct systems are the most widespread. At least 70 percent of supermarkets in the United States use centralized direct expansion (DX) systems to cool their display cases.
35
The refrigerant circulates from the machinery room to the sales area, where it evaporates in display-case heat exchangers, and then returns in vapor phase to the suction headers of the compressor racks. The supermarket walk-in cold rooms are often integrated into the system and cooled similarly, but an alternative option is to provide a dedicated condensing unit for a given storage room. Another type of supermarket design, often referred to as a distributed refrigeration system, uses an array of separate compressor racks located near the display cases rather than having a central compressor rack system. Each of these smaller racks handles a portion of the supermarket load, with 5-10 such systems in a store.
35
http://www2.epa.gov/greenchill/advanced-refrigeration
.
Indirect supermarket designs include secondary loop systems and cascade refrigeration. Indirect systems use a chiller or other refrigeration system to cool a secondary fluid that is then circulated throughout the store to the cases. Compact chiller versions of an indirect system rely on a lineup of 10-20 units, each using small charge sizes. As the refrigeration load changes, more or fewer of the chillers are active. Compact chillers are used in a secondary loop system whereby the chillers cool a secondary fluid that is then circulated throughout the store to the display cases. Each compact chiller is an independent unit with its own refrigerant charge, reducing the potential for refrigerant to be released from leaks or catastrophic failures. Cascade systems use a compressor to raise the low-temperature coolant from low-temperature conditions up to an intermediate temperature while a separate refrigerant system uses a different refrigerant to condense the coolant. Each system within the cascade design contains its own refrigerant charge allowing the use of different refrigerants in each system. This application has generally used a low-GWP refrigerant, specifically carbon dioxide (R-744), in the low-temperature system, with a variety of refrigerants in the medium-temperature system.
Refrigerant choices depend on the refrigerant charge, the temperature required, and energy efficiency, among other things. In addition to regulations pursuant to the SNAP program, other federal or local regulations may also affect refrigerant choice. For instance, regulations from the OSHA may restrict or place requirements on the use of some refrigerants, such as ammonia (R-717). Building codes from local and State agencies may also incorporate limits on the amount of particular refrigerants used. There are and will continue to be a number of factors that retailers must consider when selecting the refrigerant and operating system design. While a number of approaches exist, there is no uniformly accepted holistic analysis of the multiple factors, which include the following: Energy efficiency; system performance; potential impact on community safety; ambient temperatures; potential risk to personal safety; cost; and minimization of direct and indirect environmental impacts. EPA recognizes that these and other factors mean there will be a range of options, and the ultimate selection remains with the owner and operator of the system.
Acceptable non-HFC substitutes in use today for new multiplex systems include R-717 and R-744. These can be used alone or in combination with other refrigerants in other parts of the equipment, depending on the equipment and its design (e.g., a secondary-loop contains one refrigerant while the primary loop contains a different refrigerant). For stand-alone refrigeration equipment, propane (R-290) is listed as acceptable subject to use conditions, and EPA has also proposed that the hydrocarbon blend R-441A and isobutane (R-600a) be listed as acceptable subject to use conditions (July, 9, 2014; 79 FR 38811). The Agency also has proposed elsewhere that these three hydrocarbon refrigerants be listed as acceptable subject to use conditions for vending machines (July, 9, 2014; 79 FR 38811). Other substitutes, such as blends of saturated HFCs already listed as acceptable under SNAP, are currently in use in the United States, while HFOs and blends containing HFOs are being developed and tested but have not yet been submitted to the SNAP program for review.
The most commonly-used HFCs and HFC blends in retail food refrigeration include HFC-134a, R-404A, R-407A, R-422D, and R-507A. HFC-134a is a non-ozone depleting chemical with the chemical formula C
2
H
2
F
4
. It is used in a variety of air-conditioning and refrigeration end-uses, including motor vehicle air conditioners, home appliances (such as refrigerator-freezers), vending machines and building air-conditioning chillers. It is also used in other sectors such as foam blowing and aerosol propellants. HFC-134a has a GWP of 1,430.
R-404A is a non-ozone depleting blend of refrigerants HFC-125, HFC-143a, and HFC-134a with GWPs of 3,500, 4,470, and 1,430 respectively. R-404A's GWP is about 3,920 based on the 44/52/4 mass percentages of the three HFCs contained in the blend. R-404A is currently acceptable for a variety of medium- and low-temperature refrigeration applications including retail food refrigeration equipment such as food display and storage cases; vending machines; cold storage warehouses; commercial ice machines; refrigerated transport; and industrial process refrigeration.
R-407A is a non-ozone depleting blend of refrigerants HFC-32, HFC-125 and HFC-134a with GWPs of 675, 3,500, and 1,430 respectively. R-407A's GWP is about 2,100 based on the 20/40/40 mass percentages of the three HFCs contained in the blend. R-407A is acceptable for a variety of medium- and low-temperature refrigeration applications including retail food refrigeration equipment such as food display and storage cases; cold storage warehouses; commercial ice machines; refrigerated transport; and industrial process refrigeration. R-407A is not currently on the SNAP lists of acceptable or unacceptable refrigerants for vending machines.
R-422D is a non-ozone depleting blend of refrigerants HFC-125, HFC-134a, and R-600a with GWPs of 3,500, 1,430, and 8 (GE, 2008) respectively. R-422D's GWP is about 2,700 based on the approximate 65.1/31.5/3.4 mass percentages of the two HFCs and one hydrocarbon contained in the blend. R-422D is acceptable for a variety of medium- and low-temperature
refrigeration applications including retail food refrigeration equipment such as food display and storage cases; cold storage warehouses; commercial ice machines; refrigerated transport; and industrial process refrigeration. R-422D is most commonly used to retrofit existing systems such as those operating on HCFC-22 and is less likely to be used in manufacturing new equipment.
R-507A (also designated as R-507) is a non-ozone depleting blend of refrigerants HFC-125 and HFC-143a which have GWPs of 3,500 and 4,470, respectively. R-507A's GWP is about 3,990 based on the 50/50 mass percentages of the two HFCs contained in the blend. R-507A is acceptable for a variety of medium- and low-temperature refrigeration applications including in retail food refrigeration equipment such as food display and storage cases; cold storage warehouses; refrigerated transport; and industrial process refrigeration.
2. What is EPA proposing for new and retrofit retail food refrigeration (condensing units and supermarket systems)?
EPA is proposing to change the listing for nine HFC blends for new and retrofit retail food refrigeration equipment from acceptable to unacceptable as of January 1, 2016. These nine blends are R-404A, R-407B, R-421B, R-422A, R-422C, R-422D, R-428A, R-434A and R-507A. EPA is not aware of any significant use in the United States of the blends R-407B, R-421B, R-428A or R-434A in retail food refrigeration equipment. In addition, EPA is proposing to change the listing of HFC-227ea in new retail food refrigeration equipment from acceptable to unacceptable.
36
These ten refrigerants have GWPs ranging from 2,730 to 3,985. They are nonflammable. They contain compounds that are exempt from the definition of “VOC,” with the exception of small amounts of R-290 and R-600a in five of the blends, and thus are not expected to contribute significantly to smog. These refrigerants are relatively low in toxicity, and practices common in the refrigeration industry ensure that their workplace exposure limits are not exceeded. These practices include adhering to those specified in the material safety data sheets and others common in the commercial refrigeration industry. Applicable workplace exposure limits for the compounds comprising these refrigerants—HFC-32, HFC-125, HFC-134a, HFC-143a, HFC-227ea, R-290 and R-600a—include Workplace Environmental Exposure Limits (WEELs) of 1000 ppm on an 8-hour time-weighted average (TWA) from the American Industrial Hygiene Association (AIHA); a manufacturer's recommended occupational exposure limit of 1000 ppm (8-hr TWA); a permissible exposure limit (PEL) of 1000 ppm (8-hr TWA) from the Occupational Safety and Health Administration (OSHA) and a recommended exposure limit (REL) of 800 ppm (10-hr TWA) from the National Institutes for Occupational Safety and Health (NIOSH).
36
EPA has not previously found HFC-227ea acceptable as a retrofit refrigerant in this end-use.
EPA believes there are several HFC and non-HFC substitutes that provide lower overall risk than the refrigerants EPA is proposing to list as unacceptable and that are currently used in commercial refrigeration. For both new and retrofit equipment, acceptable refrigerants that pose less risk to human health and the environment include HFC-134a, R-407A, R-407C, R-407F, R-417A, R-421A, R-422B, R-424A, R-426A, and R-438A. Additionally, in new retail food refrigeration, three other substitute refrigerants are listed as acceptable: R-717 vapor compression with secondary loop, R-410A, and R-744.
a. New Condensing Units and Supermarket Systems
EPA is proposing to change the listing of the following refrigerants from acceptable to unacceptable in new retail food refrigeration equipment (condensing units and supermarket systems) as of January 1, 2016: HFC-227ea, R-404A, R-407B, R-421B, R-422A, R-422C, R-422D, R-428A, R-434A, and R-507A. These refrigerants have GWPs ranging from approximately 2,730 to 3,985. Two of these refrigerants, R-404A and R-507A, are currently in extensive use in the retail food refrigeration market. EPA is also aware of some use of R-422A and R-422D in retrofit situations only, not in new equipment. We are not aware of the use of any of the other six refrigerants in retail food refrigeration, although we seek comment on such use.
Other acceptable alternatives that pose lower risk are also in use in the various types of retail food refrigeration equipment. For condensing unit systems, R-407C and R-407F are in use in the United States, and R-744 and HCs are being used in limited demonstration trials in Europe and elsewhere. The GWP for R-407C (a blend of HFC-32, HFC-125, and HFC-134a) is about 1,770, and R-407F (another blend of HFC-32, HFC-125, and HFC-134a) has a GWP of about 1,820. As a comparison, R-404A has a GWP of 3,920, R-507A has a GWP of 3,990, and the other refrigerants proposed unacceptable have GWPs ranging from 2,730 to 3,985.
For multiplex rack systems, substitutes R-407A, R-407F, and R-744 are all currently in use in the United States and can be used more safely than the substances that EPA is proposing to list as unacceptable. These substitutes have GWPs ranging from 1 to 2,110. In addition, testing is underway with HCs and HFC/HFO blends, though these refrigerants have not been submitted to SNAP for review in this application. Each of these four substitutes as well as other substitutes in development with lower GWPs have zero ODP and are safe for the ozone layer. R-407A, R-407F, and R-744 all have toxicity lower than or comparable to the refrigerants proposed unacceptable. None of the three examples that would remain on the acceptable list is flammable, and none is considered a VOC.
b. Retrofit Condensing Units and Supermarket Systems
EPA is proposing to change the listing of the following refrigerants from acceptable to unacceptable in retrofit retail food refrigeration equipment (condensing units and supermarket systems) as of January 1, 2016: R-404A, R-407B, R-421B, R-422A, R-422C, R-422D, R-428A, R-434A, and R-507A. We are aware of four of these nine refrigerants being used to retrofit retail food equipment: R-404A, R-507A, R-422A, and R-422D. We are not aware of any use of the other five refrigerants to retrofit retail food refrigeration equipment but seek comment on any such use. This action would not apply to servicing existing equipment designed for these nine refrigerants or to equipment that had been retrofitted to use those refrigerants before January 1, 2016. For instance, systems retrofitted to R-404A or R-507A prior to January 1, 2016, would be allowed to continue to operate and to be serviced using those refrigerants.
For condensing units and supermarket systems, where retrofits are common, blends such as R-407A and R-407F have become the norm for retrofits, rather than the four identified in the previous paragraph. The blends R-407A and R-407F have zero ODP and GWPs of 2,107 and 1,825, respectively. Other zero-ODP refrigerants that are currently listed as acceptable for use as retrofits in retail food refrigeration include HFC-134a, R-407C, R-417A, R-421A, R-422B, R-426A and R-427A and they have GWPs ranging from 1,430 to 2,630, lower than the GWPs of the other nine blends we are proposing as
unacceptable, which have GWPs ranging from 2,729 to 3,985.
An unacceptability listing for these nine blends in retrofitted equipment could primarily affect the many stores that operate using HCFC-22, but also those using CFC-12, R-502, and several HCFC-containing blends such as R-401A, R-402A and R-408A. This is because as EPA reduces or eliminates the production and import of ODSs, stores will have less material to meet service demands. While the ODS phaseout does not require owners to retrofit their equipment, a decrease in the availability of virgin material may in turn lead operators of those stores to consider retrofits, although under our proposal certain refrigerants would not be acceptable. For instance, some stores currently using HCFC-22 may choose to retrofit as the production and import of HCFC-22 is phased down and eventually phased out by 2020 per 40 CFR 82.16. EPA recently proposed HCFC-22 allowance allocations for the 2014-2019 time period (December 24, 2013; 78 FR 78071). Some have questioned whether finding certain refrigerants unacceptable for retrofit might provide an incentive to stores to continue to operate with the ODS they are currently using for longer than they might otherwise plan, and we seek comment on this question. In response to this question, we note that many retail chains have been able to minimize the impact of the HCFC-22 phasedown by maintaining their own stockpile of HCFC-22, for instance by recovering from stores that are decommissioned or retrofitted and using such supplies in stores that continue to operate with HCFC-22. We also note that some service is being performed with reclaimed material, with over four million pounds of HCFC-22 being reclaimed every year since at least 2000, and over seven million pounds every year since 2006.
37
While we don't know how this reclaim market will change in the future, recent history shows that the market is using reclaimed material in addition to limited newly-produced supplies that are being reduced by the phaseout.
37
The latest data on refrigerant reclamation can be found on EPA's Web site at:
www.epa.gov/spdpublc/title6/608/reclamation/recsum.pdf
.
Regardless of the continued supply of HCFC-22, we believe that the majority of retrofits are planned for reasons other than the supply of the refrigerant currently in-use, for instance during planned maintenance overhauls or when upgrading to more energy efficient equipment. We also see that many retrofits are already directed towards lower-GWP blends such as R-407A and R-407F instead of R-404A and R-507A, as mentioned above. Further, we believe that other options, given the multi-year history of their successful use, are sufficient to meet the various features—such as capacity, efficiency, materials compatibility, cost and supply—that affect the choice of a retrofit refrigerant.
38
38
For example, see CCAC 2012.
3. What is EPA proposing for new and retrofit stand-alone equipment?
a. New Stand-Alone Equipment
EPA is proposing to change the listing for HFC-134a and other refrigerants for new stand-alone retail food refrigeration equipment from acceptable to unacceptable as of January 1, 2016. These other refrigerants are FOR12A, FOR12B, HFC-227ea, IKON B, KDD6, R-125/290/134a/600a (55.0/1.0/42.5/1.5), R-404A, R-407A, R-407B, R-407C, R-407F, R-410A, R-410B, R-417A, R-421A, R-421B, R-422A, R-422B, R-422C, R-422D, R-424A, R-426A, R-428A, R-434A, R-437A, R-438A, R-507A, RS-24 (2002 formulation), RS-44 (2003 formulation), SP34E, and THR-03. These refrigerants have GWPs ranging from approximately 600 up to approximately 3,990.
Acceptable substitutes in new stand-alone equipment include R-744 and R-290. EPA recently proposed to find R-600a and R-441A acceptable subject to use conditions in new stand-alone equipment (July 9, 2014; 79 FR 38811). These existing and potential substitutes have GWPs ranging from 1 to 8 compared to HFC-134a with a GWP of 1,430, R-404A with a GWP of approximately 3,920, and R-507A with a GWP of approximately 3,990. None of the substitutes currently listed or proposed for listing as acceptable has an ODP. While R-290, R-600a, and R-441A are VOCs, EPA's analysis indicates that their use as refrigerants in this end-use would not significantly affect meeting national ambient air quality standards. At the time we listed R-290 as acceptable subject to use conditions, we analyzed the potential air quality impacts of emissions of these VOCs and did not find this potential risk to the environment to be significant (ICF, 2014e).
39
We have likewise proposed to exempt R-600a and R-441A used in stand-alone equipment from the venting prohibition (July 9, 2014; 79 FR 38811). These three substitutes are also flammable; however, the use conditions specified (or proposed for R-600a and R-441A) would ensure that they do not pose greater risk than any of the substitutes currently listed as acceptable in new stand-alone equipment.
40
None of the refrigerants currently listed as acceptable or that we have proposed to add to the list of acceptable substitutes presents significant human health toxicity concerns or other ecosystem impacts. Apart from R-290 and R-744, those refrigerants listed acceptable for new stand-alone equipment either contain an HCFC (and are addressed in Section VI below) and/or do not appear to be in production.
39
EPA has proposed to exempt R-290 in stand-alone retail food refrigeration equipment from the venting prohibition found at 40 CFR 82.154 (78 FR 21871).
40
The risks due to the flammability of these refrigerants in this end-use were analyzed in the SNAP rule finding them acceptable subject to use conditions (December 20, 2011; 76 FR 78832) and docket (Docket ID No. EPA-HQ-OAR-2009-0286) and information is found in a SNAP proposed rule signed June XX, 2014 and docket (EPA-HQ-OAR-2013-0748).
We understand that R-290 is already in use globally, including in the United States, and that R-600a is in use outside of the United States as well as in test market trials in the United States. We believe that these two refrigerants can satisfy the vast majority of the current market for use in stand-alone equipment. We note that there may be a need to modify the equipment design in order to meet the use conditions for R-290 and the proposed use conditions for R-600a and R-441A (July 9, 2014; 79 FR 38811). Because there are other substitutes that pose lower risk, we are proposing to change the listing to unacceptable for new stand-alone equipment of the following refrigerants: FOR12A, FOR12B, HFC-134a, HFC-227ea, IKON B, KDD6, R-125/290/134a/600a (55.0/1.0/42.5/1.5), R-404A, R-407A, R-407B, R-407C, R-407F, R-410A, R-410B, R-417A, R-421A, R-421B, R-422A, R-422B, R-422C, R-422D, R-424A, R-426A, R-428A, R-434A, R-437A, R-438A, R-507A, RS-24 (2002 formulation), RS-44 (2003 formulation), SP34E, and THR-03.
b. Retrofit Stand-Alone Equipment
EPA is proposing to change the listing for R-404A and R-507A from acceptable to unacceptable as retrofit refrigerants for stand-alone equipment as of January 1, 2016. This action would not apply to servicing existing equipment designed for those refrigerants or to equipment retrofitted to use those refrigerants before January 1, 2016. For instance, equipment retrofitted to R-404A or R-507A prior to January 1, 2016, would be allowed to continue to operate using those refrigerants.
While we do not believe retrofits are common in stand-alone retail food refrigeration equipment, a number of refrigerants are listed as acceptable for this purpose. For equipment still operating using ozone-depleting refrigerants, we believe there are options available other than R-404A and R-507A that present lower overall risk to human health and the environment that are available. Our analysis indicates that other options such as HFC-134a can be used to retrofit stand-alone units.
4. What is EPA proposing for new and retrofit vending machines?
a. New Vending Machines
EPA is proposing to change the listing for HFC-134a and other refrigerants for new vending machines from acceptable to unacceptable as of January 1, 2016. These other refrigerants are FOR12A, FOR12B, IKON B, KDD6, R-125/290/134a/600a (55.0/1.0/42.5/1.5), R-404A, R-407C, R-410A, R-410B, R-417A, R-421A, R-422B, R-422C, R-422D, R-426A, R-437A, R-438A, R-507A, RS-24 (2002 formulation), and SP34E. These refrigerants have GWPs ranging from approximately 600 up to approximately 3,990.
Acceptable existing substitutes with lower GWPs that pose less risk to human health and the environment in this end-use include R-744, which is currently being used in this end-use. In addition, EPA recently proposed to find R-600a, R-290 and R-441A acceptable subject to use conditions in new vending machines (July 9, 2014; 79 FR 38811). We note that some redesign would be required to meet the use conditions set for all three of these substitutes—R-600a, R-290 and R-441A— in the recent proposal (July 9, 2014; 79 FR 38811).
These four substitutes (R-744 and the three proposed hydrocarbons) have GWPs ranging from 1 to 8 compared to HFC-134a with a GWP of 1,430, R-404A with a GWP of approximately 3,920, and R-507A with a GWP of approximately 3,990. None of these substitutes currently listed or proposed for listing as acceptable has an ODP. While the HCs (R-441A, R-600a and R-290) are VOCs, EPA's analysis indicates that their use as refrigerants in this end-use would not significantly affect meeting national ambient air quality standards. (ICF 2014e).
41
These three substitutes are also flammable; however, the proposed use conditions for these three substitutes would ensure they do not pose greater risk than substitutes that are already listed as acceptable (July 9, 2014; 79 FR 38811). None of the substitutes currently listed or proposed to be listed as acceptable present significant human health toxicity concerns or other ecosystem impacts. Hence, we find that R-290, R-600a and R-441A are potentially available and present a lower overall risk to human health and the environment than HFC-134a and the other refrigerants proposed to be listed as unacceptable in new vending machines.
41
EPA has proposed to exempt R-290 (propane) R-600a (isobutane) and R-441A in vending machines from the venting prohibition found at 40 CFR 82.154 (78 FR 21871).
For new vending machines, EPA has found R-744 acceptable without use conditions. While the vast majority of vending machines using non-ODS refrigerant currently use HFC-134a, units are now being manufactured to use R-744. At least one major global buyer of vending machines is committed to transitioning all of their new U.S.-placed equipment to R-744.
42
Given the large market share that this company holds, it is likely that R-744 components and units are already or will shortly become a viable option for all vending machine OEMs and purchasers.
42
The Coca-Cola Company has identified carbon dioxide as its HFC-free refrigerant of choice for new equipment (Coca Cola, 2012).
Given the zero ODP and low GWP of R-744 and the other hydrocarbons that EPA has proposed to find acceptable subject to use conditions in vending machines, the use conditions that we have proposed to establish for the hydrocarbon refrigerants, and the fact that the risks based on other factors such as toxicity are not greater than for HFC-134a, we propose to change the listing of HFC-134a and the alternatives listed in the first paragraph of this section to unacceptable in new vending machines.
b. Retrofit Vending Machines
EPA is proposing to change the listing for R-404A and R-507A from acceptable to unacceptable as retrofit refrigerants for vending machines operating on CFC-12, HCFC-22, and blends containing HCFCs, as of January 1, 2016. This action would not apply to servicing existing equipment designed for those refrigerants or to equipment that had been retrofitted to use those refrigerants before January 1, 2016, including those systems previously using ozone-depleting refrigerants such as HCFC-22. For instance, systems retrofitted to R-404A or R-507A prior to January 1, 2016, would be allowed to continue to operate using those refrigerants.
Under our proposal, the following refrigerants would remain acceptable for retrofitting vending machines: FOR12A, FOR12B, HFC-134a, IKON A, IKON B, KDD6, R-125/290/134a/600a (55.0/1.0/42.5/1.5), R-407C, R-417A, R-417C, R-421A, R-422B, R-422C, R-422D, R-426A, R-437A, R-438A, RS-24 (2002 formulation), SP34E, and THR-02. These refrigerants have GWPs from approximately 50 to approximately 3,100, while the two refrigerants proposed unacceptable, R-404A and R-507A, have GWPs of 3,922 and 3,985, respectively. In this respect, these two refrigerants present a higher risk to human health and the environment. Looking at the other SNAP criteria, we find that those refrigerants remaining acceptable present similar risk to human health and the environment: they are nonflammable, they are not VOCs, and they do not exhibit significant human health toxicity concerns or other ecosystem impacts. Hence, we believe these options present lower overall risk to human health and the environment than R-404A and R-507A.
5. When would the listings change?
Through this action, we are proposing that all listing changes that apply within commercial refrigeration would occur on the same date—January 1, 2016. Looking at the intersection between the end-use and the alternatives EPA believes that changing the listings as of January 1, 2016, allows sufficient opportunity for any planned new installations or manufacturing equipment lines in these end-uses to be redesigned to use a substitute to the refrigerants we are proposing to find unacceptable. We also believe that this date would allow any plans for future retrofits to these blends to be reconsidered, given the multiple other substitutes that would remain acceptable. For many years other refrigerants such as R-407A and R-407F that would remain on the acceptable lists pursuant to our proposal have been gaining market share in supermarket applications, in both new equipment and as retrofit fluids.
43
As part of this market expansion, manufacturers have developed equipment to use them, and that equipment is available to buyers now. In addition, many companies have implemented these other refrigerants, in both new construction and as retrofits, and have built up the skills, knowledge and experience to more fully utilize these refrigerants in a timeframe that would accommodate January 1, 2016 as
the date of unacceptability. For stand-alone equipment and vending machines, new equipment is being installed using refrigerants that are acceptable or are proposed acceptable with use conditions, including R-744, R-290 and R-600a.
44
EPA requests comment on this proposed date. EPA is also interested in information concerning the supply of substitutes in sufficient quantities to meet a domestic transition within the proposed timeframe.
43
ICF, 2014c. Market Characterization of the U.S Commercial Refrigeration Industry. Prepared for the U.S. Environmental Protection Agency. May, 2014.
44
Ibid.
6. Applicability To Service of Existing Equipment
As noted above, EPA is not proposing to alter the ability to service existing retail food refrigeration equipment or vending machines with the refrigerant they contain as of January 1, 2016. We recognize the value of the currently installed appliances and are not seeking to shorten their useful lifetime. EPA also recognizes that servicing for existing equipment is often accomplished with recovered and recycled refrigerants.
EPA seeks comments on allowing for the continued servicing of the existing retail food refrigeration equipment and vending machines with the refrigerant they contain as of January 1, 2016.
7. Energy Efficiency Consideration
Energy efficiency has not historically been a criterion by which a refrigerant is analyzed under the SNAP program, and it is not used as one of the criteria in this proposal. However, EPA recognizes that the energy efficiency of particular models of equipment is a significant factor when choosing commercial refrigeration equipment. We also recognize that the energy efficiency of any given piece of equipment is in part affected by the choice of refrigerant and the particular thermodynamic and thermophysical properties that refrigerant possesses.
Throughout the phaseout of ozone-depleting substances, EPA has seen the energy efficiency of refrigeration and air-conditioning equipment increase, despite changing refrigerant options. In some cases, this was because new chemicals were developed that possessed unique properties that allowed high energy efficiency levels to be obtained. In addition, technological improvement in equipment designs and controls has increased energy efficiency. Although today's proposal would eliminate some refrigerant choices, we do not believe it would have a detrimental effect on this trend in increased energy efficiency. In fact, there are multiple case studies available that highlight the energy efficiency gains achieved by some of the low-GWP refrigerants, such as R-744, R-290 and R-600a, that are available or potentially available for the end-uses addressed in this proposal. We welcome additional information and comment on improved energy efficiency associated with switching refrigerants.
For instance, in supermarket refrigeration, a theoretical analysis (Emerson 2014) examined the energy use of R-407A and R-410A, both of which would remain acceptable under this proposal, against that of R-404A, which would be listed as unacceptable. Although this analysis found that both blends would see a 3.6% to 6.7% drop in efficiency in the low-temperature part of the store (e.g., frozen food, ice cream), they would achieve a 4.3% to 13.3% increase in the medium-temperature part of the store (e.g., meat, dairy products, chilled prepared food). Given that supermarkets have significantly larger use of medium-temperature equipment, the net effect would be for the alternatives to use less energy than R-404A. This manufacturer's analyses showed similar increases in energy efficiency compared to R-404A in supermarkets and stand-alone equipment for a variety of low-GWP refrigerants that are not yet listed under SNAP but are in development.
While that manufacturer's analysis showed slightly higher energy consumption than R-134a in theoretical calculations for stand-alone equipment, other results with actual equipment have shown otherwise. For instance, in stand-alone equipment, one user reported that “HC freezers are significantly more energy-efficient and use a natural hydrocarbon refrigerant with lower global warming potential than the HFC refrigerants commonly used in US freezers” (Ben and Jerry's, 2014). Likewise, for vending machines, one purchaser has indicated that while introducing over one million units using R-744, they have increased the energy efficiency of their cooling equipment over 40% since 2000, many years after they adopted HFC-134a (Coca-Cola, 2014).
Finally, we note that energy efficiency is influenced, but not determined, by the refrigerant. As new products are designed for the use of particular refrigerants, manufacturers have the opportunity to change designs to take advantage of a given refrigerant's characteristics. The redesign and development phase is also an opportunity to improve other components that will affect the overall efficiency of the equipment, such as the use of more efficient motors and compressors, improved heat exchangers, better controls, improved insulation (e.g., on display cases) and sealing (for products with doors), more efficient lighting, etc.
The United States Department of Energy (DOE) has promulgated, under separate rulemaking and separate authority, energy efficiency requirements for several types of commercial refrigeration equipment, including products that would be affected by this proposal. While EPA's proposal would limit the choice of refrigerant a manufacturer could use in new equipment, EPA notes that such equipment would still be subject to the DOE requirements and would normally need to meet the standards set.
45
As discussed above, EPA does not believe this proposal would prevent compliance with the DOE rules, and we note that many compliant models are already commercially available that do not use the refrigerants EPA has proposed as unacceptable. EPA requests comment on the effects this proposal would have on the energy efficiency of the commercial refrigeration end-uses addressed and in particular the effect, if any, this proposal would have on meeting applicable DOE standards.
45
Refrigeration equipment in the applicable covered equipment class would still be subject to DOE's standards, regardless of the refrigerant that the equipment uses. If a manufacturer believes that its design is subjected to undue hardship by a regulatory standard prescribed by DOE (in contrast to one that is statutorily prescribed by Congress), the manufacturer may petition DOE's Office of Hearing and Appeals (OHA) for exception relief or exemption from the standard pursuant to OHA's authority under section 504 of the DOE Organization Act (42 U.S.C. 7194), as implemented at subpart B of 10 CFR part 1003. OHA has the authority to grant regulatory relief from a standard promulgated by DOE on a case-by-case basis if it determines that a manufacturer has demonstrated that meeting the standard would cause hardship, inequity, or unfair distribution of burdens.
8. What other options is EPA considering?
E