HO-CHUNK NATION CODE (HCC)

Tribal code

Ask Donna

What actually matters in this document.

Text

HO-CHUNK NATION CODE (HCC)

TITLE 6 – PERSONNEL, EMPLOYMENT AND LABOR CODE

SECTION 8 – OCCUPATIONAL SAFETY AND HEALTH

PROGRAM ACT OF 2002

SUBSECTION 4 – ELECTRICAL SAFETY

ENACTED BY LEGISLATURE: MAY 20, 2002

LAST AMENDED AND RESTATED: December 6, 2022

CITE AS: 6 HCC § 8-4

1. Authority. See basic document (Occupational Safety and Health Program Act).

2. Purpose. This subsection of the Occupational Safety and Health Program Act provides practices

and procedures intended to provide for employee safety relative to electrical hazards in the

workplace.

3. Definitions. See basic document (Occupational Safety and Health Program Act). In addition, the

following definitions apply to this subsection.

a. “Accessible” as applied to wiring methods, means capable of being removed or exposed

without damaging the building structure or finish, or not permanently closed in by the structure or

finish of the building.

b. “Accessible” as applied to equipment, means admitting for close approach; not guarded by

locked doors, elevation, or other effective means.

c. “Accessible, Readily (Readily Accessible)” means capable of being reached quickly for

operation, renewal, or inspections, so that those needing ready access do not have to climb over or

remove obstacles or to resort to portable ladders, chairs, etc.

d. “Ampacity” means the current, in amperes, that a conductor can carry continuously under

the conditions of use without exceeding its temperature rating.

e. “Attachment Plug (Plug Cap) or (Cap)” means a device that, by insertion in a receptacle,

establishes a connection between the conductors of the attached flexible cord and the conductors

connected permanently to the receptacle.

f. “Barricade” means a physical obstruction such as tapes, cones, or A-frame-type wood or

metal structures intended to provide a warning about and to limit access to a hazardous area.

g. “Barrier” means a physical obstruction that is intended to prevent contact with equipment

or live parts or to prevent unauthorized access to a work area.

1

Ho-Chunk Nation Legislature

Occupational Safety and Health Program Act

Electrical Safety

Page 2 of 26

h. “Bonding (Bonded)” means the permanent joining of metallic parts to form an electrically

conductive path that will ensure electrical continuity and the capacity to conduct safely any current

likely to be imposed.

i. “Bonding Jumper” means a reliable conductor to ensure the required electrical conductivity

between metal parts required to be electrically connected.

j. “Branch Circuit” means the circuit conductors between the final overcurrent device

protecting the circuit and the outlet(s).

k. “Circuit Breaker” means a device designed to open and close a circuit by non-automatic

means and to open the circuit automatically on a predetermined overcurrent without damage to itself

when properly applied within its range.

l. “Competent Person” means one who is capable of identifying existing and predictable

hazards in the surroundings or working conditions that are unsanitary, hazardous, or dangerous to

employees and who has authorization to take prompt corrective measures to eliminate them.

m. “Concealed” means rendered inaccessible by the structure or finish of the building. Wires

in concealed raceways are considered concealed, even though they may become accessible by

withdrawing them.

n. “Conductive” means suitable for carrying electric current.

o. “Conductor” means any of the following:

(1) Bare Conductor. A conductor having no covering or electrical insulation

whatsoever.

(2) Covered Conductor. A conductor encased within material of composition or

thickness that is not recognized by this standard as electrical insulation.

(3) Insulated Conductor. A conductor encased within material of composition and

thickness that it is recognized by this standard as electrical insulation.

p. “De-energized” means free from any electrical connection to a source of potential

difference and from electrical charge; not having a potential different from that of the earth.

q. “Device” means a unit of an electrical system that is intended to carry but not utilize

electric energy.

r. “Disconnecting Means” means a device, group of devices, or other means by which the

conductors of a circuit can be disconnected from their source of supply.

2

Ho-Chunk Nation Legislature

Occupational Safety and Health Program Act

Electrical Safety

Page 3 of 26

s. “Electrical Hazard” means a dangerous condition such that contact, or equipment failure

can result in electric shock, are flash burn, thermal burn, or arc blast injury.

t. “Electrical Safety” means recognizing hazards associated with the use of electrical energy

and taking precautions to reduce the risk associated with those hazards.

u. “Electrically Safe Work Condition” means a state in which an electrical conductor or

circuit part has been disconnected from energized parts, locked/tagged in accordance with established

standards, tested to verify the absence of voltage, and if necessary, temporarily grounded for personal

protection.

v. “Exposed” as applied to live parts, means capable of being inadvertently touched or

approached nearer than a safe distance by a person. It is applied to parts that are not suitably guarded,

isolated, or insulated. (NOTE: See “Accessible” and “Concealed”)

w. “Exposed” as applied to wiring methods, means on or attached to the surface, or behind

panels designed to allow access. [NOTE: See “Accessible (As applied to wiring methods.)]

x. “Ground” means a conducting connection, whether intentional or accidental, between an

electrical circuit or equipment and the earth, or to some conducting body that serves in place of the

earth.

y. “Grounded” means connected to the earth or to some conducting body that serves in place

of the earth.

z. “Grounded Conductor” means a system or circuit conductor that is intentionally grounded.

aa. “Grounded, effectively” means intentionally connected to earth through a ground

connection or connections of sufficiently low impedance and having sufficient current-carrying

capacity to prevent the buildup of voltages that may result in undue hazards to connected equipment

or to persons.

bb. “Grounding Conductor” means a conductor used to connect equipment or the grounded

circuit of a wiring system to a grounding electrode or electrodes.

cc. “Ground-Fault Circuit-Interrupter” means a device intended for the protection of

personnel that functions to de-energize a circuit or a portion within an established period of time

when a current to ground exceeds some predetermined value that is less than that required to operate

the overcurrent protective device of the supply circuit.

3

Ho-Chunk Nation Legislature

Occupational Safety and Health Program Act

Electrical Safety

Page 4 of 26

dd. “Limited Approach Boundary” means an approach limit at a distance from an exposed

energized electrical conductor or circuit part within a shock hazard exists.

ee. “Overcurrent” means any current in excess of the rated current of equipment or the

ampacity of a conductor. It may result from overload, short circuit, or ground fault.

ff. “Overload” means the operation of equipment in excess of normal, full-load rating, or of a

conductor in excess of rated ampacity that, when it persists for a sufficient length of time, would

cause damage or dangerous overheating. A fault, such as a short circuit or ground fault, is not an

overload. (See Overcurrent.)

gg. “Panelboard” means a single panel or group of panel units designed for assembly in the

form of a single panel; including buses, automatic overcurrent devices, and with or without switches

for the control of light, heat, or power circuits; designed to be placed in a cabinet or cutout box

placed in or against a wall or partition and accessible only from the front. (See Switchboard.)

hh. “Qualified Person” means one who, by possession of a recognized degree, certificate, or

professional standing, or who by extensive knowledge, training and experience, has successfully

demonstrated his ability to solve or resolve problems relating to the subject matter, the work, or the

project.

ii. “Receptacle” means a contact device installed at the outlet for the connection of an

attachment plug. A single receptacle is a single contact device with no other contact device on the

same yoke. A multiple receptacle is two or more contact devices on the same yoke.

jj. “Restricted Approach Boundary” means an approach limit at a distance from an exposed

energized electrical conductor or circuit part within which there is an increased likelihood of electric

shock, due to electrical arc-over combined with inadvertent movement.

kk. “Switchboard” means a large single panel, frame, or assembly of panels on which are

mounted, on the face or back, or both, switches, overcurrent and other protective devices, buses, and

(usually) instruments. Switchboards are generally accessible from the rear as well as from the front

and are not intended to be installed in cabinets. (See Panelboard.)

ll. “Voltage (of a circuit)”, means the greatest root-mean-square (rms) (effective) difference

of potential between any two conductors of the circuit concerned.

mm. “Voltage, Nominal” means a nominal value assigned to a circuit or system for the

purpose of conveniently designating its voltage class (as 120/240 volts, 480Y/277 volts, 600 volts).

The actual voltage at which a circuit operates can vary from the nominal within a range that permits

satisfactory operation of equipment.

4

Ho-Chunk Nation Legislature

Occupational Safety and Health Program Act

Electrical Safety

Page 5 of 26

nn. “Working On (energized electrical conductors or circuit parts)”, means intentionally

coming in contact with energized electrical conductors or circuit parts with the hands, feet, or other

body parts, with tools, probes, or with test equipment, regardless of the PPE a person is wearing.

There are two categories of “working on”: “Diagnostic (testing) is taking readings or measurements

of electrical equipment, conductors, or circuit parts with approved test equipment that does not

require making any physical change to the electrical equipment, conductors, or circuit parts.

“Repair” is any physical alteration of electrical equipment, conductors, or circuit parts (such as

making or tightening connections, removing or replacing components, etc.)

4. Training Requirements.

a. The training requirements contained in this section shall apply to employees exposed to an

electrical hazard when the risk associated with that hazard is not reduced to a safe level by the

electrical installation requirements. Such employees shall be trained to understand the specific

hazards associated with electrical energy. They shall be trained in safety-related work practices and

procedural requirements, as necessary, to provide protection from the electrical hazards associated

with their respective job or task assignments. Employees shall be trained to identify and understand

the relationship between electrical hazards and possible injury.

b. The training required by this section shall be classroom or on-the-job type, or a

combination of the two. The type and extent of the training provided shall be determined by the risk

to the employee.

c. Employees exposed to shock hazards and those responsible for the safe release of victims

from contact with energized electrical conductors or circuit parts shall be trained in methods of

release of victims from contact with exposed energized conductors or circuit parts. They shall be

regularly instructed in methods of first aid and emergency procedures, such as approved methods of

resuscitation, if their duties warrant such training. Refresher training shall occur annually.

d. Qualified Persons.

(1) A qualified person shall be trained and knowledgeable in the construction and

operation of equipment or a specific work method and be trained to identify and avoid the electrical

hazards that might be present with respect to that equipment or work method. Such persons shall also

be familiar with the proper use of special precautionary techniques, electrical policies and

procedures, personal protective equipment, insulating and shielding materials, and insulated tools and

test equipment. A person can be considered qualified with respect to certain equipment and tasks but

still be unqualified for others. Such persons permitted to work within the limited approach boundary

shall, at a minimum, be additionally trained in all of the following:

5

Ho-Chunk Nation Legislature

Occupational Safety and Health Program Act

Electrical Safety

Page 6 of 26

(a) The skills and techniques necessary to distinguish exposed energized

electrical conductors and circuit parts from other parts of electric equipment.

(b) The skills and techniques necessary to determine the nominal voltage of

exposed energized electrical conductors and circuit parts.

(c) The approach distances specified in Table I and the corresponding

voltages to which the qualified person will be exposed.

(d) The decision-making process necessary to determine the degree and

extent of the hazard and the PPE and job planning necessary to perform the hierarchy of risk control

methods as outlined in Section 9.

(2) An employee who is undergoing on-the-job training for the purpose of obtaining

the skills and knowledge necessary to be considered a qualified person, and who in the course of

such training, has demonstrated an ability to perform specific duties safely at his/her level of

training, and who is under the direct supervision of a qualified person shall be considered to be a

qualified person for the performance of those specific duties.

e. Unqualified Persons. Unqualified persons shall be trained in and be familiar with, any of

the electrical safety-related practices necessary for their safety.

5. Working On or Near Electrical Conductors or Circuit Parts. Safety-related work practices

shall be used to prevent electric shock or other injuries resulting from either direct or indirect

electrical contacts, when work is being performed on or near equipment or circuits that are or can

become energized. The specific safety-related work practice shall be consistent with the nature and

extent of the associated electric hazards.

a. Live parts to which an employee might be exposed shall be de-energized before an

employee works on or near them, unless the employer can demonstrate that de-energizing introduces

additional or increase hazards or is infeasible due to equipment design or operational limitations.

Live parts that operate at less than 50 volts to ground are not required to be de-energized if there will

be no increased exposure to electrical burns or to explosion due to electric arcs.

(1) Examples of increased or additional hazards include, but are not limited to,

interruption of life support equipment, deactivation of emergency alarm systems, shutdown of

hazardous location ventilation equipment, or removal of illumination for an area.

(2) Examples of work that may be performed on or near energized circuit parts

because of unfeasibility due to equipment design or operational limitations include performing

diagnostics and testing (i.e. start-up or troubleshooting) of electric circuits that can only be performed

with the circuit energized and work on circuits that form an integral part of a continuous industrial

process in a chemical plant that would otherwise need to be completely shut down in order to permit

work on one circuit or piece of equipment.

6

Ho-Chunk Nation Legislature

Occupational Safety and Health Program Act

Electrical Safety

Page 7 of 26

b. Only qualified persons shall be permitted to work on electrical equipment that has not been

de-energized. Such persons shall be capable of working safely on energized circuits and shall be

familiar with the proper use of special precautionary techniques, personal protective equipment,

insulating and shielding materials, and insulated tools.

c. Establishing and verifying an electrically safe work condition shall be achieved when

performed in accordance with paragraph 6 and verified by the following process:

(1) Determine all possible sources of electrical supply to the specific equipment.

Check applicable up-to-date drawings, diagrams, and identification tags.

(2) After properly interrupting the load current, open the disconnecting device(s) for

each source.

(3) Wherever possible, visually verify that all blades of the disconnecting devices are

fully open or that drawout-type circuit breakers are withdrawn to the test or fully disconnected

position.

(4) Release stored electrical energy.

(5) Block or relieve stored nonelectrical energy in devices to the extent the circuit

parts cannot be unintentionally energized by such devices.

(6) Apply lockout/tag-out devices in accordance with a documented and

established policy.

(7) Use an adequately rated portable test instrument to test each phase conductor or

circuit part to test for the absence of voltage. Test each phase conductor or circuit part both phase-tophase and phase-to-ground. Before and after each test, determine that the voltage detector is

operating satisfactorily through verification on any known voltage source.

(8) Where the possibility of induced voltages or stored electrical energy exists,

ground all circuit conductors and circuit parts before touching them. Where it could be reasonably

anticipated that the conductors or circuit parts being de-energized could contact other exposed

energized conductors or circuit parts, apply temporary protective grounding equipment rated for the

available fault duty.

6. Establishing an Electrically Safe Work Condition. Each enterprise or department shall

establish, document, and implement a lock-out/tag-out program. The lockout/tagout program shall

specify lockout/tagout procedures to safeguard employees from exposure to electrical hazards. The

lock-out/tag-out program and procedures shall also be applicable to the experience and training of the

employees and conditions as they exist in the workplace, meet the requirements of 6 HCC § 8-5, and

apply to fixed, permanently installed equipment, temporarily installed equipment, and portable

equipment.

7

Ho-Chunk Nation Legislature

Occupational Safety and Health Program Act

Electrical Safety

Page 8 of 26

7. Work Involving Electrical Hazards. This section covers requirements for work involving

electrical hazards such as the electrically safety-related work practices, assessments, precautions, and

procedures when an electrically safe work condition cannot be established.

a. Safety-related work practices shall be used to protect employees from injury while they are

exposed to electrical hazards from electrical conductors or circuit parts that are or can become

energized.

b. When energized electrical conductors and circuit parts operating at voltages equal to or

greater than 50 volts are not put into an electrically safe work condition, and work is performed as

permitted, all the following requirements shall apply:

1) Only qualified persons shall be permitted to work on electrical conductors or

circuit parts that have not been put into an electrically safe condition.

2) A shock risk assessment shall be performed as required by this section.

3) An arc flash risk assessment shall be performed as required by this section.

c. Shock Risk Assessment. A shock risk assessment shall be performed to identify shock

hazards, to estimate the likelihood of occurrence of injury or damage to health and the potential

severity of injury or damage to health, and to determine if additional protective measures are

required, including the use of PPE.

(1) Estimate of Likelihood and Severity. The estimate of likelihood of occurrence of

injury or damage to health and the potential severity of injury or damage to health shall take into

consideration the design of the electrical equipment, and the electrical equipment operating condition

and the condition of maintenance. The results of the shock risk assessment shall be documented

(2) Shock Protection Boundaries. The shock protection boundaries identified as

limited approach boundary and restricted approach boundary shall be applicable where employees

are approaching exposed energized electrical conductors or circuit parts. Table I (page 10) shall be

used for the distances associated with various ac system voltages. Table II shall be used for the

distances associated with various dc system voltages.

a. Restricted Approach Boundary. No qualified person shall approach or

take any conductive object closer to exposed energized electrical conductors or circuit parts than the

restricted approach boundary set forth in Table III and Table IV, unless one of the following

conditions applies:

1) The qualified person is insulated or guarded from energized

electrical conductors or circuit parts operating at 50 volts or more. Insulating gloves and sleeves are

considered insulation only with regard to the energized parts upon which work is performed.

8

Ho-Chunk Nation Legislature

Occupational Safety and Health Program Act

Electrical Safety

Page 9 of 26

2) The energized electrical conductors or circuit parts are insulated

from the qualified person and from any other conductive object at a different potential.

(3) Limited Approach Boundary.

a. Unqualified person shall not be permitted to approach nearer than the limited

approach boundary of energized conductors and circuit parts.

b. Where one or more unqualified persons are working at or close to the limited

approach boundary, alerting methods (safety signs and tags, barricades, or attendants) shall be

applied to advise the unqualified person(s) of the electrical hazard and warn him or her to stay

outside of the limited approach boundary.

c. Where there is a need for an unqualified person(s) to cross the limited

approach boundary, a qualified person shall advise the unqualified person(s) of the possible hazards

and continuously escort the unqualified person(s) while inside the limited approach boundary. Under

no circumstances shall unqualified person(s) be permitted to cross the restricted approach boundary.

(4) Restricted Approach Boundary. No qualified person shall approach or take any

conductive object closer to live parts nearer than the restricted approach boundary set forth in Table

I (page 12), unless one of the following conditions applies:

(a) The qualified person is insulated or guarded from the live parts (insulating

gloves or insulating gloves and sleeves are considered insulation only with regard to the energized

parts upon which work is being performed), and no insulated part of the qualified person’s body

enters the prohibited space set forth in Table I; or

(b) The live part is insulated from the qualified person and from any other

conductive object at a different potential; or

(c) The qualified person is insulated from any other conductive object as

during live-line bare-hand work.

(5) Arc Flash Risk Assessment.

(a) An arc flash assessment shall be performed to identify arc flash hazards,

to estimate the likelihood of occurrence of injury or damage to health and the potential severity of

injury or damage to health, and to determine if additional protective measures are required,

including the use of PPE.

9

Ho-Chunk Nation Legislature

Occupational Safety and Health Program Act

Electrical Safety

Page 10 of 26

(b) The estimate of the likelihood of occurrence of injury or damage to health

and the potential severity of injury or damage to health shall take into consideration the design of the

electrical equipment, including its overcurrent protective device and its operating time; and the

electrical equipment operating condition and condition of maintenance.

(c) If additional protective measures are required, they shall be selected and

implemented according to the hierarchy of risk control. When the additional protective measures

include the use of PPE, the appropriate safety-related work practices, the arc flash boundary, and the

PPE to be used within the arc flash boundary shall be determined.

(d) The results of the arc flash risk assessment shall be documented.

(6) Arc Flash Boundary.

(a) The arc flash boundary shall be the distance at which the incident energy

equals 1.2 cal/cm² (5 J/cm²).

(b) The arc flash boundary shall be permitted to be determined by Table II

[Section 10, paragraph (8)(a)] when the requirements of this table apply.

Table I: Shock Protection Approach Boundaries to Exposed Energized Electrical Conductors

or Circuit Parts for Direct-Current Systems.

(All dimensions are distance from live part to employee.)

(1)

(2)

Limited Approach

Boundary

(3)

Limited Approach

Boundary

Nominal System

Voltage Range,

Phase to Phase

Less than 50 V

50 V to 300 V

301 V to 1 kV

1.1 kV to 5 kV

5 kV to 15 kV

15.1 kV to 45 kV

45.1 kV to 75 kV

75.1 kV to 150 kV

150.1 kV to 250 kV

250.1 kV to 500 kV

500.1 kV to 800 kV

Exposed

Movable

Conductor

Not specified

10 ft 0 in

10 ft 0 in

10 ft 0 in

10 ft 0 in

10 ft 0 in

10 ft 0 in

10 ft 8 in

11 ft 8 in

20 ft 0 in

26 ft 0 in

Exposed

Fixed

Circuit Part

Not specified

3 ft 6 in

3 ft 6 in

5 ft 0 in

5 ft 0 in

8 ft 0 in

8 ft 0 in

10 ft 0 in

11 ft 8 in

20 ft 0 in

26 ft 0 in

10

(4)

Restricted

Approach

Boundary;

Includes

Inadvertent

Movement

Adder

Not specified

Avoid contact

1 ft 0 in

1 ft 5 in

2 ft 2 in

2 ft 9 in

3 ft 6 in

3 ft 10 in

5 ft 3 in

11 ft 6 in

16 ft 5 in

Ho-Chunk Nation Legislature

Occupational Safety and Health Program Act

Electrical Safety

Page 11 of 26

(7) Protective Clothing and PPE for Application with an Arc Flash Risk Assessment. Where it has

been determined that work will be performed within the arc flash boundary by paragraph (6) above,

the arc flash risk assessment shall determine, and the enterprise/ department shall document, the

incident energy exposure level of the worker (in calories per square centimeter). This incident energy

exposure level shall be based on the working distance of the employee’s face and chest areas from a

prospective arc source for the specific task to be performed. Arc-rated (AR) Clothing and PPE shall

be used by the employee based upon the incident energy exposure associated with the specific task.

Recognizing that incident energy increases as the distance from the arc flash decreases, additional

PPE shall be used for any parts of the body that are closer than the working distance at which the

incident energy was determined. As an alternative, the PPE requirements of paragraph 10c(8) shall

be permitted to be used in lieu of the detailed arc flash risk assessment approach described in

paragraph (6) above.

8. Work On or Near Uninsulated Overhead Lines.

a. Uninsulated and Energized. Where work is performed in locations containing uninsulated

energized overhead lines that are not guarded or isolated, precautions shall be taken to prevent

employees from contacting such lines directly with any unguarded parts of their body or indirectly

through conductive materials, tools, or equipment. Where the work to be performed is such that

contact with uninsulated energized overhead lines is possible, the lines shall be de-energized and

visibly grounded at the point of work, or suitably guarded.

b. De-energizing or Guarding. If the lines are to be de-energized, arrangements shall be made

with the person or organization that operates or controls the lines to de-energize them and visibly

ground them at the point of work. If arrangements are made to use protective measures, such as

guarding, isolating, or insulation, these precautions shall prevent each employee from contacting

such lines directly with any part of his or her body or indirectly through conductive materials, tools,

or equipment.

c. The enterprise/department and employee shall be responsible to ensure that guards or

protective measures are satisfactory for the conditions. Employees shall comply with established

work methods and the use of protective equipment.

d. Approach Distances for Unqualified Persons. When unqualified employees are working on

the ground or in an elevated position near overhead lines, the location shall be such that the employee

and the longest conductive object the employee might contact cannot come closer to any unguarded,

energized overhead power line than the limited approach boundary in Table I. If the voltage on the

line exceeds 50 kV, the distance shall be 10 ft plus 4 in. for every 10 kV over 50 kV.

11

Ho-Chunk Nation Legislature

Occupational Safety and Health Program Act

Electrical Safety

Page 12 of 26

e. Vehicular and Mechanical Equipment.

(1) Where any vehicle or mechanical equipment structure will be elevated near

energized overhead lines, it shall be operated so that the limited approach boundary distance of Table

I, Column 2 is maintained. However, under any of the following conditions, the clearances shall be

permitted to be reduced:

(a) If the vehicle is in transit with its structure lowered, the limited approach

boundary to overhead lines shall be permitted to be reduced by 6 ft.

(b) If insulated barriers, rated for the voltages involved, are installed, and they

are not part of an attachment to the vehicle, the clearance shall be permitted to be reduced to the

design working dimensions of the insulating barrier.

(c) If the equipment is an aerial lift insulated for the voltage involved, and if

the work is performed by a qualified person, the clearance (between the uninsulated portion of the

aerial lift and the power line) shall be permitted to be reduced to the restricted approach boundary

given in Table I, Column 4.

(2) Employees standing on the ground shall not contact the vehicle or mechanical

equipment or any of its attachments, unless:

(a) The employee is using protective equipment rated for the voltage; or

(b) The equipment is located so that no uninsulated part of its structure (that

portion of the structure that provides a conductive path to employees on the ground) can come closer

to the line than permitted in (a) above.

(3) If any vehicle or mechanical equipment is capable of having parts of its structure

elevated within the limited approach boundary of exposed movable conductors of energized

overhead lines and is intentionally grounded, employees working on the ground near the point of

grounding shall not stand at the grounding location whenever there is a possibility of overhead line

contact. Additional precautions, such as the use of barricades or insulation, shall be taken to protect

employees from hazardous ground potentials (step and touch potential), which can develop within a

few feet or more outward from the grounded point.

9. Electrical Safety Program.

a. Job Briefing.

12

Ho-Chunk Nation Legislature

Occupational Safety and Health Program Act

Electrical Safety

Page 13 of 26

(1) Before starting each job each job that involves exposure to electrical hazards, the

employee in charge shall complete a job safety plan and conduct a job briefing with the employees

involved. The briefing shall cover a description of the job and the individual tasks; identification of

the electrical hazards associated with each task; a shock risk assessment in accordance with 7(c)(1)

above for tasks involving a shock hazard; an arc flash risk assessment in accordance with 7(c)(5)

above for tasks involving an arc flash hazard; and work procedures involved, special precautions, and

energy source controls.

(2) If the work or operations to be performed during the workday or shift are

repetitive and similar, at least one job briefing shall be conducted before the start of the first job of

the day or shift. Additional job safety planning and job briefings shall be held if changes that might

affect the safety of the employees occur during the course of the work.

(3) A brief discussion shall be satisfactory if the work involved is routine and if the

employee, by virtue of training and experience, can reasonably be expected to recognize and avoid

the hazards involved in the job. A more extensive discussion shall be conducted if:

(a) The work is complicated or particularly hazardous, or

(b) The employee cannot be expected to recognize and avoid the hazards

involved in the job.

b. Alertness.

(1) Employees shall be instructed to be alert at all times where electrical hazards

might exist.

(2) Employees shall not be permitted to work where electrical hazards exist while

their alertness is recognizably impaired due to illness, fatigue, or other reasons.

c. Blind Reaching. Employees shall be instructed not to reach blindly into areas that might

contain exposed electrical conductors or circuit parts where an electrical hazard exists.

d. Illumination.

(1) Employees shall not enter spaces where electrical hazards exist unless

illumination is provided that enables the employees to perform the work safely.

(2) Where lack of illumination or an obstruction precludes observation of the work to

be performed, employees shall not perform any task where an electrical hazard exists.

13

Ho-Chunk Nation Legislature

Occupational Safety and Health Program Act

Electrical Safety

Page 14 of 26

e. Conductive Articles Being Worn. Conductive articles of jewelry and clothing (such as

watchbands, bracelets, rings, key chains, necklaces, metalized aprons, cloth with conductive thread,

metal headgear, or metal frame glasses) shall not be worn within the restricted approach boundary or

where they present an electrical contact hazard with exposed energized electrical conductors or

circuit parts.

f. Conductive Materials, Tools, and Equipment Being Handled.

(1) Conductive materials, tools, and equipment that are in contact with any part of an

employee’s body shall be handled in a manner that prevents unintentional contact with energized

electrical conductors or circuit parts. Such materials and equipment shall include, but are not limited

to, long conductive objects, such as ducts, pipes and tubes, conductive hose and rope, metal-lined

rules and scales, steel tapes, pulling lines, metal scaffold parts, structural members, bull floats, and

chains.

(2) Means shall be employed to ensure that conductive materials approach exposed

energized electrical conductors or circuit parts no closer than that permitted by Table I.

g. Confined or Enclosed Workspaces. When an employee works in a confined or enclosed

space (such as a manhole or vault) where an electrical hazard exists, the employee shall use

protective shields, protective barriers, or insulating materials as necessary to against electrical

hazards. Doors, hinged panels, and the like shall be secured to prevent their swinging into an

employee and causing the employee to contact exposed energized electrical conductors or circuit

parts where an electrical hazard exists if movement of the door, hinged panel, and the like is likely to

create a hazard.

h. Safety Interlocks. Only a qualified person following the requirements for working inside

the restricted approach boundary shall be permitted to defeat or bypass an electrical safety interlock

over which the person has sole control, and then only temporarily while the qualified person is

working on the equipment. The safety interlock system shall be returned to its operable condition

when the work is complete.

i. Housekeeping Duties. Employees shall not perform housekeeping duties inside the limited

approach boundary where there is a possibility of contact with energized electrical conductors or

circuit parts, unless adequate safeguards (such as insulating equipment or barriers) are provided to

prevent contact. Electrically conductive cleaning materials (including conductive solids such as steel

wool, metabolized cloth, and silicon carbide, as well as conductive liquid solution) shall not be used

inside the limited approach boundary unless procedures to prevent electrical contact are followed.

14

Ho-Chunk Nation Legislature

Occupational Safety and Health Program Act

Electrical Safety

Page 15 of 26

j. Occasional Use of Flammable Materials. Where flammable materials are present only

occasionally, electric equipment capable of igniting them may not be used, unless measures are taken

to prevent hazardous conditions from developing. Such materials include, but are not limited to

flammable gases, vapors, or liquids; combustible dust; and ignitable fibers or flyings.

k. Overcurrent Protection Modification. Overcurrent protection of circuits and conductors

shall not be modified, even on a temporary basis.

10. Personal and Other Protective Equipment.

a. Employees exposed to electrical hazards when the risk associated with that hazard is not

adequately reduced by the applicable electrical installation requirements shall be provided with, and

shall use, protective equipment that is designed and constructed for the specific part of the body to be

protected and for the work to be performed.

b. Care of Equipment. Protective equipment shall be maintained in a safe, clean, and reliable

condition and in accordance with manufacturers’ instructions. The protective equipment shall be

visually inspected before each use. Protective equipment shall be stored in a manner to prevent

damage from physically damaging conditions and from moisture, dust, and other deteriorating

agents.

c. Personal Protective Equipment.

(1) When an employee is working within the restricted approach boundary, he/she

shall wear PPE in accordance with the shock risk assessment. When an employee is working within

the arc flash boundary, he or she shall wear protective clothing and other PPE in accordance with the

arc flash assessment. All parts of the body inside the arc flash boundary shall be protected.

(2) Employees will wear nonconductive head protection wherever there is a danger of

head injury from electric shock or burns due to contact with energized electrical conductors or circuit

parts or from flying objects resulting from an electrical explosion.

(3) Head, Face, Neck, and Chin Protection. Employees shall wear nonconductive

head protection wherever there is a danger of head injury from electric shock or burns due to contact

with energized electrical conductors or circuit parts or from flying objects resulting from an electrical

explosion. Employees shall wear nonconductive protective equipment for the face, neck, and chin

whenever there is a danger of injury from exposure to electric arcs or flashes or from flying objects

resulting from electrical explosion. If employees wear hairnets or beard nets, or both, these items

shall be arc rated.

(4) Eye Protection. Employees shall wear protective equipment for the eyes whenever

there is danger of injury from electric arcs, flashes, or from flying objects resulting from electrical

explosion.

15

Ho-Chunk Nation Legislature

Occupational Safety and Health Program Act

Electrical Safety

Page 16 of 26

(5) Hearing Protection. Employees shall wear hearing protection whenever working

within the arc flash boundary.

(6) Body Protection. Employees shall wear arc-rated clothing wherever there is

possible exposure to an electric arc flash above the threshold incident energy level for a seconddegree burn [1.2 cal/cm² (5 J/cm²)].

(7) Hand and Arm Protection. Employees shall wear rubber insulating gloves with

leather protectors where there is danger of hand injury from electric shock and burns due to

contact with exposed energized electrical conductors or circuit parts. Hand and arm protection

shall be worn where there is possible exposure to arc flash burn.

(8) Foot and Leg Protection. Where insulated footwear is used as protection against

step and touch potential, dielectric overshoes shall be required. Insulated soles shall not be used

as primary electrical protection.

(9) Protective Clothing and PPE.

Table II (page 17) shall be used to determine the required PPE.

(a) Energized parts that operate at less than 50 volts are not required to be deenergized to satisfy an “electrically safe work condition.” Consideration should be given to the

capacity of the source; any overcurrent protection between the energy source and the worker, and

whether the work task related to the source operating at less than 50 volts increases exposure to

electrical burns or to explosion from an electric arc.

(b) Once the Arc Flash PPE Category has been identified, refer to Table III

(page 19). This Table lists the requirements for protective equipment based on Arc Flash Category

numbers 1 – through 4. This clothing and equipment shall be used when working within the Arc

Flash Boundary.

(c) The PPE requirements of this section are intended to protect a person from

arc flash hazards. While some situations may result in burns to the skin even with the protection

described in Table III, burn injury should be reduced and survivable. Due to the explosive effect of

some arc events, physical trauma injuries may occur. The PPE requirements of this section do not

provide protection against physical trauma other than exposure to the thermal effects of an arc flash.

16

Ho-Chunk Nation Legislature

Occupational Safety and Health Program Act

Electrical Safety

Page 17 of 26

Table II: Arc Flash PPE Categories for Direct Current (dc) Systems

Equipment

Arc Flash

PPE

Category

Arc Flash

Boundary

Storage batteries, dc switchboards, and other dc supply

sources

Parameters: Greater than or equal to 100 volts and less than

or equal to 250 volts

Maximum arc duration and minimum working distance: 2

sec @ 18 in

Available fault current less than 4 kV

2

3 ft

Available fault current greater than or equal to 4 kV and less

2

4 ft

than 7 kV

Available fault current greater than or equal to 7 kV and less

3

6 ft

than 15 kV

Storage batteries, dc switchboards, and other dc supply

sources

Parameters: Greater than 250 volts and less than or equal to

600 volts

Maximum arc duration and minimum working distance: 2

sec @ 18 in

Available fault current less than 1.5 kV

2

3 ft

Available fault current greater than or equal to 1.5 kV and

2

4 ft

less than 3 kV

Available fault current greater than or equal to 3 kV and less

3

6 ft

than 7 kV

Available fault current greater than or equal to 7 kV and less

4

8 ft

than 10 kV

Notes:

(1) Apparel that can be expected to be exposed to electrolyte must meet both of the following conditions:

a. Be evaluated for electrolyte protection

b. Be arc rated

(2) A two-second arc duration is assumed if there is no overcurrent protective device (OCPD) or if the

fault clearing time is not known. If the fault clearing time is known and is less than 2 seconds, an incident

energy analysis could provide a more representative result.

Note 1: When determining available fault current, the effects of cables and any other impedances in the

circuit should be included. Power system modeling is the best method to determine the available shortcircuit current at the point of the arc. Battery cell short-circuit current can be obtained from the battery

manufacturer.

Note 2: The methods for estimating dc arc flash incident energy that were used to determine the categories

for this table are based on open-air incident energy calculations. Open-air calculations were used because

many battery systems and other dc process systems are in open areas or rooms. If the specific task is within

an enclosure, it would be prudent to consider additional PPE protection beyond the value shown in this

table.

17

Ho-Chunk Nation Legislature

Occupational Safety and Health Program Act

Electrical Safety

Page 18 of 26

d. Protective Clothing.

(1) Factors in Selection of Protective Clothing.

(a) Protective clothing includes shirts, pants, coveralls, jackets, and parkas worn

routinely by workers who, under normal working conditions, are exposed to momentary electric arc

and related thermal hazards. Arc-rated rainwear worn in inclement weather are included in this

category.

(b) Clothing and equipment that provide worker protection from shock and arc flash

hazards shall be used. Clothing and equipment required by the degree of exposure shall be permitted

to be worn alone or be integrated with flammable, non-melting apparel. It shall cover associated

parts of the body and all normal apparel that is not flash-flame resistant, while allowing movement

and visibility. All PPE shall be maintained in a sanitary and reliable condition. Individual protection

items will normally be used in conjunction with one another as a system to provide appropriate

protection.

(c) Layering. Non-melting, flammable fiber garments shall be permitted to be used

as under layers in conjunction with arc-rated garments in a layered system. A typical layering system

may include cotton underwear, a cotton shirt and trouser, and an arc-rated coverall. Specific tasks

may call for additional arc-rated layers to achieve the required protection level.

(d) Outer Layers. Garments worn as outer layers over arc-rated clothing, such as

jackets, high-visibility apparel, or rainwear, shall also be made from arc-rated material.

(e) Under layers. Meltable fibers such as acetate, nylon, polyester, polypropylene,

and spandex shall not be permitted in fabric under layers. Arc-rated garments worn as under layers

that neither ignite nor melt and drip in the course of an exposure to electric arc and related thermal

hazard generally provide a higher system arc rating than non-melting flammable fiber under layers.

(f) Coverage. Clothing shall cover potentially exposed areas as completely as

possible. Shirt and coverall sleeves shall be fastened at the wrists, shirts shall be tucked into pants,

and shirts, coveralls, and jackets shall be closed at the neck.

(g) Fit. Tight-fitting clothing shall be avoided. Loose-fitting clothing provides

additional thermal insulation due to air spaces. Arc-rated apparel shall fit properly such that it does

not interfere with the work task.

(h) Interference. The garment selected shall result in the least interference with the task but

still provide the necessary protection. The work method, location, and task may influence the

protective equipment selected.

18

Ho-Chunk Nation Legislature

Occupational Safety and Health Program Act

Electrical Safety

Page 19 of 26

Table III: Personal Protective Equipment (PPE)

Arc-Flash PPE

Category

1

2

3

4

PPE

Arc-Rated Clothing, Minimum Arc Rating of 4 cal/cm² (16.75 J/cm²)ª

Arc-rated long-sleeve shirt and pants or arc-rated coverall

Arc-rated face shieldᵇ or arc flash suit hood

Arc-rated jacket, parka, high-visibility apparel, rainwear, or hard hat liner (AN)ᶠ

Protective Equipment

Hard hat

Safety glasses or safety goggles (SR)

Hearing protection (ear canal inserts)ᶜ

Heavy-duty leather gloves, arc-rated gloves, or rubber insulating gloves with leather protectors (SR)ͩ

Leather footwearͤ (AN)

Arc-Rated Clothing, Minimum Arc Rating of 8 cal/cm² (33.5 J/cm²)

Arc-rated long-sleeve shirt and pants or arc-rated coverall

Arc-rated flash suit hood or arc-rated face shieldᵇ and arc-rated balaclava

Arc-rated jacket, parka, high-visibility apparel, rainwear, or hard hat liner (AN)ᶠ

Protective Equipment

Hard hat

Safety glasses or safety goggles (SR)

Hearing protection (ear canal inserts)ᶜ

Heavy-duty leather gloves, arc-rated gloves, or rubber insulating gloves with leather protectors (SR)ͩ

Leather footwearᶜ

Arc-Rated Clothing Selected so That the System Arc Rating Meets the Required Minimum Arc Rating of 40 cal/cm² (167.5 J/cm²)ª

Arc-rated long-sleeve shirt (AR)

Arc-rated pants (AR)

Arc-rated coverall (AR)

Arc-rated arc flash suit jacket (AR)

Arc-rated arc flash suit pants (AR)

Arc-rated arc flash suit hood

Arc-rated gloves or rubber insulating gloves with leather protectors (SR)ͩ

Arc-rated jacket, parka, high-visibility apparel, rainwear, or hard hat liner (AN)ᶠ

Protective Equipment

Hard hat

Safety glasses or goggles (SR)

Hearing protection (ear canal inserts)ᶜ

Leather footwearͤ

Arc-Rated Clothing Selected so That the System Arc Rating Meets the Required Minimum Arc Rating of 40 cal.cm² (167.5 J/cm²)ª

Arc-rated long-sleeve shirt (AR)

Arc-rated pants (AR)

Arc-rated coverall (AR)

Arc-rated arc flash suit jacket (AR)

Arc-rated arc flash suit pants (AR)

Arc-rated arc flash suit hood

Arc-rated gloves or rubber insulating gloves with leather protectors (SR)ͩ

Arc-rated jacket, parka, high-visibility apparel, rainwear, or hard hat liner (AN)ᶠ

Protective Equipment

Hard hat

Safety glasses or safety goggles (SR)

Hearing protection (ear canal inserts) ᶜ

Leather footwearͤ

AN: As needed (optional) AR: As required, SR: Selection Required.

ª Arc rating is defined is defined as the value attributed to materials that describes their performance to exposure to an electrical arc discharge.

ᵇFace shields are to have wrap-around guarding to protect not only the face but also the forehead, ears, and neck, or, alternately, an arc-rated arc

flash suit hood is required to be worn.

ᶜOther types of hearing protection are permitted to be used in lieu of or in addition to ear canal inserts provided they are worn under an arc-rated

arc flash suit hood.

ͩRubber insulating gloves with leather protectors provide arc flash protection in addition to shock protection. Higher class rubber insulating gloves

with leather protectors, due to their increased material thickness, provide increased arc flash protection.

ᶜFootwear other than leather or dielectric shall be permitted to be used provided it has been tested to demonstrate no ignition, melting, or dripping

at the minimum arc rating for the respective arc flash PPE category.

ͤThe arc rating of outer layers worn over arc-rated clothing as protection from the elements or for other safety purposes, and that are not used as

part of a layered system, shall not be required to be equal to or greater than the estimated incident energy exposure.

19

Ho-Chunk Nation Legislature

Occupational Safety and Health Program Act

Electrical Safety

Page 20 of 26

(3) Arc Flash Protective Equipment.

(a) Arc Flash suits. Arc flash suit design shall permit easy and rapid removal by the wearer.

The entire flash suit, including the hood’s face shield, shall have an arc rating suitable for the arcflash exposure. When exterior air is supplied into the hood, the air hoses and pump housing shall

either be covered by arc-rated materials or constructed of non-melting and nonflammable materials.

(b) Face Protection. Face shields shall have an arc rating suitable for the arc flash exposure.

Face shields with a wrap-around guarding to protect the face, chin, forehead, ears and

neck area shall be used. Eye protection (safety glasses or goggles) shall always be worn under face

shields or hoods.

(c) Hand Protection. Heavy-duty gloves or arc-rated gloves shall be worn where required for

arc flash protection. Heavy-duty leather gloves are made entirely of leather with minimum thickness

of 0.03 in. (0.7 mm) are unlined or lined with nonflammable, non-melting fabrics. Heavy-duty

leather gloves have been shown to have an ATPV values in excess of 10 cal/cm² (41.9 J/cm²).

Where insulating rubber gloves are used for shock protection, leather protectors shall be worn over

the rubber gloves. The leather protectors worn over rubber insulating gloves provide additional arc

flash protection for the hands for arc flash protection exposure.

(d) Foot Protection. Leather footwear or dielectric footwear provide some arc flash protection

to the feet and shall be used in all exposures greater than 4 cal/cm² (16.75 J/cm²). Footwear other

than leather or dielectric shall be permitted to be used provided it has been tested to demonstrate no

ignition, melting, or dripping at the estimated incident energy exposure or the minimum arc rating for

the respective arc flash PPE category.

(4) Care and Maintenance of Arc-Rated Clothing and Arc-Rated Arc Flash Suits.

(a) Inspection. Arc-rated apparel shall be inspected before each use. Work clothing or arc

flash suits that are contaminated or damaged to the extent their protective qualities are impaired shall

not be used. Protective items that become contaminated with grease, oil, or flammable liquids or

combustible materials shall not be used.

(b) Manufacturer’s Instructions. The garment manufacturer’s instructions for care and

maintenance of arc-rated apparel shall be followed.

(c) Clothing Material Characteristics.

1 Melting. Clothing consisting of fabrics, zipper tapes, and findings from flammable

synthetic materials that melt at temperatures below 600°F, such as acetate, acrylic, polyester, nylon,

polyethylene, polypropylene, and spandex shall not be used. These materials melt as a result of arc

flash exposure conditions, form intimate contact with the skin, and aggravate the burn injury.

20

Ho-Chunk Nation Legislature

Occupational Safety and Health Program Act

Electrical Safety

Page 21 of 26

2 Flammability. Non-arc-rated cotton, polyester-cotton blends, silk, rayon, wool,

nylon and nylon-cotton blends are flammable. Fabrics, zipper tapes, and findings made of these

materials can ignite and continue to burn on the body, resulting in serious burn injuries.

3 Clothing and Other Apparel Not Permitted. Clothing and other apparel (such as

hard hat liners and hair nets) made from materials that do not meet the requirements of paragraph

4(c) above regarding melting or made from materials that do not meet the flammability requirements,

shall not be permitted to be worn.

11. Other Protective Equipment.

a. Insulated Tools. Tools and handling equipment used within the restricted approach

boundary shall be insulated. Insulated tools shall be protected from damage to the insulating

material.

(1) Requirements for Insulated Tools.

(a) Insulated tools shall be rated for the voltages on which they are used.

(b) Insulated tools shall be designed and constructed for the environment to

which they are exposed and the manner in which they are used.

(c) Insulated tools and equipment shall be inspected before each use. The

inspection shall look for damage to the insulation or damage that can limit the tool from performing

its intended function or could increase the potential for an incident (e. g., damaged tip on a

screwdriver).

(2) Fuse or Fuseholder Handling Equipment. Fuse or fuse holder handling

equipment, insulated for the circuit voltage, shall be used to remove or install a fuse if the fuse

terminals are energized.

(3) Ropes and Handlines. Ropes and handlines used within the limited approach

boundary shall be nonconductive.

(4) Fiberglass-Reinforced Plastic Rods. Fiberglass-reinforced plastic rod and tube

used for live-line tools shall meet the requirements of ASTM F 711 and standards dealing with

electrical installation requirements.

(5) Portable Ladders. Portable ladders shall have nonconductive side rails if they are

when used within the limited approach boundary or where the employee or the ladder could contact

live exposed energized electrical conductors or circuit parts.

21

Ho-Chunk Nation Legislature

Occupational Safety and Health Program Act

Electrical Safety

Page 22 of 26

b. Barriers. Exposed energized electrical conductors or circuit parts operating at 50 volts or

more shall be guarded by a barrier in accordance with paragraphs 11(a)(1) through 11(a)(5) to

prevent unintentional contact while an employee is working within the restricted approach boundary

of those conductors or circuit parts. Barriers shall be supported to remain in place and shall prevent

unintentional contact by a person, tool, or equipment.

(1) Rubber Insulating Equipment. Rubber insulating equipment used for protection

from unintentional contact with energized conductors or circuit parts shall be rated for the voltage

and shall meet the requirements of this Ordinance.

(2) Voltage Rated Plastic Guard Equipment. Plastic guard equipment for protection

of employees from accidental contact with live parts, or to protect the employee or energized

equipment or material from contact with ground, shall meet the requirements of the ASTM standards

given in Table V.

(3) Physical or Mechanical Barriers. Physical or mechanical (field fabricated) barriers

shall be installed no closer than the restricted approach distance given in Table I. While the barrier is

being installed, the restricted approach boundary distance specified in Table I shall be maintained, or

the energized conductors or circuit parts shall be placed in an electrically safe work condition.

a. Alerting Techniques.

(1) Safety Signs and Tags. Safety signs, safety symbols, or tags shall be used where

necessary to warn employees about electrical hazards that might endanger them. Such signs and tags

shall meet the requirements of Table IV.

(2) Barricades. Barricades shall be used in conjunction with safety signs where it is

necessary to prevent or limit employee access to work areas containing live parts. Conductive

barricades shall not be used where it might cause an electrical hazard. Barricades shall be placed no

closer than the limited approach boundary given in Table I.

(3)Attendants. If signs and barricades do not provide sufficient warning and

protection from electrical hazards, an attendant shall be stationed to warn and protect employees. The

primary duty and responsibility of an attendant providing manual signaling and alerting shall be to

keep unqualified employees outside a work area where the unqualified employee might be exposed

to electrical hazards. An attendant shall remain in the area as long as there is a potential for

employees to be exposed to the electrical hazards.

b. Standards for Other Protective Equipment. Other protective equipment required in this

section shall conform to the standards given in Table IV.

22

Ho-Chunk Nation Legislature

Occupational Safety and Health Program Act

Electrical Safety

Page 23 of 26

12. Use of Specific Safety-Related Equipment and Work Practices.

a. Test Instruments and Equipment Use. Only qualified persons shall perform testing work on

electric circuits or equipment.

b. Visual Inspection. Test instruments and equipment and all associated test leads, cables,

power cords, probes, and connectors shall be visually inspected for external defects and damage

before the equipment is used. If there is a defect or evidence of damage that might expose an

employee to injury, the defective or damaged item shall be removed from service, and no employee

shall use it until repairs and tests necessary to render the equipment safe have been made.

c. Rating of Equipment. Test instruments and equipment and their accessories shall be rated

for the circuits and equipment to which they will be connected and shall be designed for the

environment in which they will be used.

d. Energizing and De-energizing Electrical Power Circuits.

(1) Routine Opening and Closing of Circuits. Load-rated switches, circuit breakers,

or other devices specifically designed as disconnecting means shall be used for the opening,

reversing, or closing of circuits under load conditions. Cable connectors not of the load-break type,

fuses, terminal lugs, and cable splice connections shall not be permitted to be used for such purposes,

except in an emergency.

23

Ho-Chunk Nation Legislature

Occupational Safety and Health Program Act

Electrical Safety

Page 24 of 26

Table IV: Standards on Other Protective Equipment

Subject

Arc Protective Blankets

Arc Protective Blankets –

Selection Care, and Use

Blankets

Blankets – In-Service Care

Covers

Fiberglass Rods – Live Line

Tools

Insulated Hand Tools

Ladders

Line Hose

Line Hose and Covers – InService Care

Plastic Guard

Sheeting

Safety signs and tags

Shield Performance on Live

Line Tool

Temporary Protective

Grounds – In-Service Testing

Temporary Protective

Grounds – Test Specification

Number and Title

ASTM F2676, Standard Test Method for Determining the Protective Performance of an Arc

Protective Blanket for Electric Arc Hazards

ASTM F3272, Standard Guide for Selection, Care, and Use of Arc Protective Blankets

ASTM D1048, Standard Specification for Rubber Insulating Blankets

ASTM F479, Standard Specification for In-Service Care of Insulating Blankets

ASTM D1049, Standard Specification for Rubber Insulating Covers

ASTM F711, Standard Specification for Fiberglass-Reinforced Plastic (FRP) Rod and Tube Used

in Live Line Tools

ASTM F1505, Standard Specification for Insulated and Insulating Hand Tools

ANSI ASC A14.1, American National Standard for Ladders – Wood -Safety Requirements

ANSI ASC A14.3, American National Standard for Ladders – Fixed - Safety Requirements

ANSI ASC A14.4, American National Standard Safety Requirements for Job-Made Ladders

ANSI ASC A14.5, American National Standard for Ladders – Portable Reinforced Plastic - Safety

Requirements

ASTM D1050, Standard Specification for Rubber Insulating Line Hoses

ASTM F478, Standard Specification for In-Service Care of Insulating Line Hose and Covers

ASTM F712, Standard Test Methods and Specifications for Electrically Insulating Plastic Guard

Equipment for Protection of Workers

ASTM F1742, Standard Specification for PVC Insulating Sheeting

ASTM F2320, Standard Specification for Rubber Insulating Sheeting

ANSI Z535, Series of Standards for Safety Signs and Tags

ASTM F2522, Standard Test Method for Determining the Protective Performance of a Shield

Attached on Live Line Tools or on Racking Rods for Electric Arc Hazards

ASTM F2249, Standard Specification for In-Service Test Methods for Temporary Grounding

Jumper Assemblies Used on De-energized Electric Power Lines and Equipment

ASTM F855, Standard Specification for Temporary Protective Grounds to Be Used on Deenergized Electric Power Lines and Equipment

ASTM – American Society for Testing and Materials

ANSI ASC – American National Standards Institute

(2) Reclosing Circuits after Protective Device Operation. After a circuit is deenergized by the operation of a circuit protective device, the circuit shall not be manually reenergized until it has been determined that the equipment and circuit can be safely energized. The

repetitive manual reclosing of circuit breakers or re-energizing circuits through replaced fuses is shall

be prohibited. When it is determined from the design of the circuit and the overcurrent devices

involved that the automatic operation of a device was caused by an overload rather than a fault

condition, examination of the circuit or connected equipment shall not be required before the circuit

is re-energized.

e. Portable Electric Equipment. This section applies to the use of cord and plug connected

equipment, including flexible cord sets (extension cords).

24

Ho-Chunk Nation Legislature

Occupational Safety and Health Program Act

Electrical Safety

Page 25 of 26

(1) Handling. Portable equipment shall be handled in a manner that will not cause

damage. Flexible electric cords connected to equipment shall not be used for raising or lowering the

equipment. Flexible cords shall not be fastened with staples or hung in such a fashion as could

damage the outer jacket or insulation.

(2) Grounding Type Equipment.

(a) A flexible cord used with grounding type equipment shall contain an

equipment grounding conductor

(b) Attachment plugs and receptacles shall not be connected or altered in a

manner that would prevent proper continuity of the equipment grounding conductor at the point

where plugs are attached to receptacles. Additionally, these devices shall not be altered to allow the

grounding pole of a plug to be inserted into slots intended for connection to the current-carrying

conductors.

(c) Adapters that interrupt the continuity of the equipment grounding

conductor shall not be used.

(3) Visual Inspection of Portable Cord and Plug Connected Equipment and Flexible

Cord Sets.

(a) Frequency of Inspection. Before use on any shift, portable cord and plug

connected equipment shall be visually inspected for external defects (such as loose parts, deformed

and missing pins, or damage to outer jacket or insulation) and for evidence of possible internal

damage (such as pinched or crushed outer jacket). An exception is that cord- and plug-connected

equipment and flexible cord sets (extension cords) that remain connected once they are put in place

and are not exposed to damage shall not be required to be visually inspected until they are relocated.

(b) Defective Equipment. If there is a defect or evidence of damage that

might expose an employee to injury, the defective or damaged item shall be removed from service,

and no employee shall use it until repairs and tests necessary to render the equipment safe have been

made.

(c) Proper Mating. When an attachment plug is to be connected to a

receptacle (including on a cord set), the relationship of the plug and receptacle contacts shall first be

checked to ensure that they are of mating configurations.

(4) Conductive Work Locations. Portable electric equipment used in highly

conductive work locations (such as those inundated with water or other liquids) or in job locations

where employees are likely to contact water or conductive liquids, shall be approved for those

25

Ho-Chunk Nation Legislature

Occupational Safety and Health Program Act

Electrical Safety

Page 26 of 26

locations. In job locations where employees are likely to contact or be drenched with water or

conductive liquids, ground-fault circuit-interrupter protection for personnel shall also be followed.

(5) Connecting Attachment Plugs.

(a) Employees’ hands shall not be wet when plugging and unplugging

flexible cords and cord and plug equipment, if energized equipment is involved.

(b) Energized plug and receptacle connection shall be handled only with

insulating protective equipment if the condition of the connection provides a conductive path to the

employee’s hand (if, for example, a cord connector is wet from being immersed in water).

(c) Locking-type connectors shall be installed after connection.

13. Administration and Enforcement. See Section 12 of the Occupational Safety and Health

Program Act.

______________________________________________________________________________

Legislative History:

01/09/02

05/20/02

09/29/22

12/06/22

Legislature posts for 45-day Public Review.

Enacted as Electrical Safety (6 HCC § 8-4) by Legislative Resolution 5/20/02E.

Legislature posts for 45-Day Review.

Enacted as Electrical Safety (6 HCC § 8-4) by Legislative Resolution 12-06-22E.

26