TVCE
”
12-31-2026
“
”
”
”
“
”
TVCE
12-31-2026
TRINIDAD RANCHERIA
INTERPRETIVE VISITORS CENTER
TVCE
12-31-2026
TVCE
12-31-2026
TVCE
12-31-2026
TVCE
12-31-2026
TVCE
12-31-2026
TVCE
12-31-2026
TVCE
12-31-2026
TVCE
12-31-2026
TRINITY VALLEY CONSULTING ENGINEERS, INC.
KEYED NOTES:
-AMMETER, AMPERE
CONDUIT EXPOSED
AC
-ALTERNATING CURRENT
CONDUIT CONCEALED OR BURIED
ACH
-ABOVE COUNTER HEIGHT
CROSS HATCHES W/ BARS INDICATES NUMBER OF #10 CONDUCTORS
AFCI
-ARC FAULT CIRCUIT INTERRUPT
AFF
-ABOVE FINISHED FLOOR
AIC
-AMPS INTERRUPTING CAPACITY
ATS
-AUTOMATIC TRANSFER SWITCH
BRKR
-BREAKER
BOE
-BOTTOM OF EQUIPMENT
CEC
-CALIFORNIA ELECTRICAL CODE
C/COND
-CONDUIT
CKT
-CIRCUIT
COD
-CENTER OF DEVICE
INDICATES THREE-POLE WALL SWITCH
3
D
OC
a
b
c
d
LV
K
M
-DIRECT CURRENT
INDICATES WALL SWITCH WITH INTEGRAL OCCUPANCY SENSOR
(E)
-EXISTING
INDICATES WALL SWITCHES FOR MULTIPLE LIGHTING GROUPS
1
E1.0
DC
G
-GROUND
INDICATES LOW VOLTAGE WALL SWITCH
GFCI
-GROUND FAULT CIRCUIT INTERRUPT
INDICATES KEY-OPERATED WALL SWITCH
J
-JUNCTION BOX
INDICATES MOTOR RATED SWITCH
LCP
-LIGHTING CONTROL PANEL
MOTOR RATED SWITCH
MFR
-MANUFACTURER
OC
OCCUPANCY SENSOR
MSB
-MAIN SWITCH BOARD
J
JUNCTION BOX
MTS
-MANUAL TRANSFER SWITCH
CR
CONTACT RELAY
NEC
-NATIONAL ELECTRIC CODE
NEMA
-NATIONAL ELECTRIC MANUFACTURER'S ASSOCIATION
20A SPECIFICATION GRADE
QUADRUPLEX RECEPTACLE
20A SPECIFICATION GRADE
GROUND FAULT CIRCUIT
INTERRUPTER RECEPTACLE
20A SPECIFICATION GRADE GROUND
FAULT CIRCUIT INTERRUPTER
QUADRUPLEX RECEPTACLE
208/240V RECEPTACLE 18" COD UNLESS
OTHERWISE NOTED ON PLANS
SPLITWIRED RECEPTACLES
XXA/XXF
60/40 F XX
XX
30
XX
XXAS
XXAF
FUSED DISCONNECT
NON-FUSED DISCONNECT
-NEUTRAL
PB
-PULLBOX
PNL
-PANELBOARD
RECEPT
-RECEPTACLE
(R)
-RELOCATED
SWBD
-SWITCHBOARD
2" MIN
D
2" MIN
3" MIN
D=3" MIN FOR 2" AND LARGER CONDUIT
D=2" MIN FOR 1-1/2" AND SMALLER CONDUIT
-THERMOSTAT OR TELE CONDUIT
T
NEMA 1
CIRCUITS:
18
MAIN:
Circuit Description
LAY-IN 2 FT x 2 FT.
TYP
-TYPICAL
V
-VOLTMETER, VOLT
2
TYPICAL UNDERGROUND CONDUIT
E1.0
NOT TO SCALE
-WEATHERPROOF (NEMA 3R)
XFMR
-TRANSFORMER
(E) ICE HOUSE 70 A
(E) BOAT LAUNCH 100 A
3
(E) SPACE
(E) SPACE
(E) SPACE
1
1
1
400A,
3P
200A,
3P
200A,
2P
2400
2400
200A,
3P
---
--PHASE B
27012 VA
225 A
PHASE A
27557 VA
230 A
LOCATION:
VOLTS:
120/240 Delta
A.I.C. RATING: 10 KAIC
MOUNTING:
SURFACE
WIRES:
4
BUS RATING: 225 A
ENCLOSURE:
NEMA 3R
CIRCUITS:
42
MAIN:
CKT
1
3
5
7
9
11
13 2
15 2
17
19
21
23
25
27
29
31
33
35
37
39
41
Circuit Description
Rating Poles
LIGHTING - EXTERIOR 20 A
1
LIGHTING - INTERIOR 20 A
1
HVAC - HP-1 30 A
2
HVAC - AHU-1 15 A
2
REFRIGERATOR - BACK ENTRY 20 A
FREEZER - BACK ENTRY 20 A
1
1
WATER HEATER - WH-1 50 A
2
HVAC - AHU-1 SUPPLEMENTAL HEAT 50 A
2
SPARE
SPARE
SPACE
SPARE
SPARE
SPACE
SPARE
SPARE
SPACE
20 A
20 A
-20 A
20 A
-20 A
20 A
--
B
C
97
865
4"C-4#500,1#3G
2"C-4#3/0,1#6G
MTS-3
MTS-2
400A MTS-1
(E) 200A MTS
4"C-4#500,1#3G
(E)
200A
PNL P1
RESTAURANT
PHASE Q=305A
PHASE B=305A
PHASE C=65A
TREATMENT
PLANT
PHASE A=120A
PHASE B=120A
NEMA 3R
DISCONNECT
225A
PNL
(E) P-3
200A
3P
2"C-4#3/0,1#6G
(E) WP
J-BOX
ONE-LINE DIAGRAM
E1.0
NOT TO SCALE
(E) 2"C-4#3/0,1#6G
1"
2"
-----
2600
C
Poles Rating
Circuit Description
1
20 A RECEPTS - OFFICE
3000
720
864
1080
864
350
2250
2250
350
360
4500
4500
-360
3840
720
3840
0
-180
0
360
--
0
-0
0
0
--
0
-0
0
0
-PHASE B
11413 VA
95 A
(E) SPACE
(E) SPACE
(E) SPACE
(E) SPACE
-PHASE C
17054 VA
142 A
2
30 A COFFEE BREWER
1
1
20 A RECEPTS - SEATING
20 A RECEPTS - RECEPTION
2
30 A COFFEE ESPRESSO
1
1
1
1
1
1
1
1
1
1
1
1
1
1
20 A
-20 A
20 A
-20 A
20 A
-20 A
20 A
-20 A
20 A
--
RECEPT - COFFEE BAR
SPACE
RECEPT - COFFEE BAR
RECEPT - COFFEE BAR
SPACE
RECEPT - COFFEE BAR
RECEPT - RCP, EXTERIOR GFI, INTERIOR
SPACE
SPARE
SPARE
SPACE
SPARE
SPARE
SPACE
CKT
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
PHASE C IS HIGH LEG
LUMINAIRE SCHEDULE
ID
1
Manufacturer
LITHONIA
Model
EPANL 1X4
Lamp
LED
Luminous Flux
4000 lm
Color
Temperature
3500 K
2
LITHONIA
EPANL 2X2
LED
3400 lm
3500 K
3
LITHONIA
VG03C
LED
600 lm
3500 K
4
LITHONIA
LDN6
LED
1000 lm
3500 K
5
LITHONIA
ARC1
LED
2000 lm
3500 K
LITHONIA
LQM
LED
0 lm
0K
Apparent Load
Description
37 VA
INTERIOR SURFACE MOUNTED EDGE-LIT FLAT PANEL, 80 CRI, 0-10V
DIMMING DOWN TO 1%, 120V AC. PROVIDE EMERGENCY BATTERY
PACK WHERE INDICATED.
30 VA
INTERIOR SURFACE MOUNTED EDGE-LIT FLAT PANEL, 80 CRI, 0-10V
DIMMING DOWN TO 1%, 120V AC. PROVIDE EMERGENCY BATTERY
PACK WHERE INDICATED.
25 VA
EXTERIOR VANDAL-RESISTANT WALLPACK, POLYCARBONATE LENS,
DARK BRONZE FINISH, 120V AC. PROVIDE WITH PHOTOCELL AT ALL
LOCATIONS.
10 VA
INTERIOR RECESSED 6"Ø DOWNLIGHT, CLEAR TRIM, SEMI-SPECULAR
FINISH, WHITE PAINTED FLANGE, 0-10V DIMMING DOWN TO 1%, 120V
AC. PROVIDE WITH EMERGENCY BATTERY PACK WHERE INDICATED.
17 VA
EXTERIOR SURFACE MOUNTED ARCHITECTURAL WALL LUMINAIRE,
PERFORMANCE PACKAGE P2, DAR BRONZE FINISH, 120-277V AC.
PROVIDE WITH EMERGENCY BATTERY PACK AND BUTTON TYPE
PHOTOCELL.
5 VA
INTERIOR EXIT SIGN, STENCIL FACE, WHITE HOUSING, GREEN
LETTERS, 120V AC. PROVIDE WITH EMERGENCY BATTERY PACK AT ALL
LOCATIONS.
PHASE A = 190A
PHASE B = 190A
PHASE C = 70A
(N)
PNL
P4
(N) 2"C-4#1,1#6G
DATE OF ISSUE:
7/12/2023
SCALE:
1/8" = 1'-0"
(E)
P-1
PROJECT NO:
427.11
PIER
PHASE A=160A
PHASE B=150A
PHASE C=135A
1/2"
1
1
1
1
(E) 4"C-4 #500,1#3G
BAIT SHOP/OFFICE/
ICE HOUSE/BOAT LAUNCH
3
30 A (E) OFFICE
(E) 400A MTS-3
2"C-4#3/0,1#6G
400A
PNL
(E) P-2
2
2"C-4#3/0,1#6G
MTS-1
(E) 400A MTS-2
B
3000
4"C-4#500,1#3G
(E) C
A
900
PHASE A
11957 VA
100 A
125 A (N) PANEL P4
200 A
2600
1
1
1
1
1
1
1
1
1
3
CKT
2
1 4
6
8
10
12
14
16
18
PHASE C IS HIGH LEG
P4
2"C-3#3/0,1#6G
C
-PHASE C
21854 VA
182 A
(N) BRANCH PANEL
LED STANDARD EMERGENCY LIGHT
4"C-4#500,1#3C
--
--
GND BUS
DOUBLE FACED ILLUMINATED DIRECTIONAL EXIT SIGN.
SINGLE FACED ILLUMINATED DIRECTIONAL EXIT SIGN.
----
Circuit Description
17054
7200
TOTAL LOAD (AMPS)
#3/0 BARE COPPER
CONDUCTOR
M
M
M
11413
6000
2400
800A,
3P
M
C
Poles Rating
3
TOTAL LOAD (AMPS)
65000 AIC, 800A, 120/240V, 3Ø, 4W
B
11957
7200
(E) MSB
PENDANT MOUNTED LIGHT FIXTURE
A
2400
TO PG&E
SERVICE XFMR
T-1091
RECESSED LIGHT FIXTURE.
SINGLE FACE ILLUMINATED EXIT SIGN
200 A
Rating Poles
TOTAL LOAD (VOLT-AMPS):
WP
C
6000
-WATT
W
B
A
-PHOTOCELL
PC
-TOP OF DEVICE
HATCHING INDICATES EMERGENCY LIGHTING.
CLEAN SAND 6" ABOVE
AND BELOW CONDUIT
6" CLEAR ALL AROUND
TOD
SURFACE MOUNTED 1 FT x 4 FT FLUORESCENT LIGHT FIXTURE.
12"
3" MIN
N
ENCLOSURE:
REPAIR ASPHALT PAVING
OR CONCRETE TO MATCH
EXISTING
UNDISTURBED EARTH
FUSED SWITCH
SURFACE MOUNTED 2 FT x 4 FT FLUORESCENT LIGHT FIXTURE.
NOT TO SCALE
WARNING TAPE
-LIGHTING
20A SPECIFICATION GRADE
RECEPTACLE, COORDINATE
CONFIGURATION W/ SUPPLIED
EQUIPMENT
PULLBOX - SWEEP UP
BACKFILL IN 6" LAYERS. EACH
LAYER TAMPED TO 95% MAX. DRY
DENSITY PER ASTM D-1557-64T
LTR
M
BUS RATING: 225 A
TOTAL LOAD (VOLT-AMPS):
INDICATES WALL SWITCH WITH INTEGRAL TIMER
T
4
CKT
1
3
5
7
9
11
13
15
17
CONDUIT, TYP.
INDICATES WALL SWITCH WITH INTEGRAL DIMMER
WIRES:
A
-DEMOLISHED
(D)
RECESSED
6"
-CURRENT TRANSFORMER
CT
MOUNTING:
67 WALNUT WAY
PO BOX 1567
WILLOW CREEK, CA 95573
P:(530)629-3000
F:(530)629-3011
DWN BY DES BY CHK BY APP BY
WALL SWITCH, 46" TO COD AFF UNLESS OTHERWISE NOTED
A.I.C. RATING: EXISTING
DESCRIPTION
TELE/DATA CONNECTION POINT; 18" TO COD AFF UNLESS
OTHERWISE NOTED. 3/4" C - STUB UP TO CEILING PLENUM
120/240 Delta
DATE
DATA CONNECTION POINT; 18" TO COD AFF UNLESS OTHERWISE
NOTED. 3/4" C - STUB UP TO CEILING PLENUM
VOLTS:
REV
TELEPHONE
TELE/DATA CONNECTION
CONNECTIONPOINT;
POINT;18"
18"TO
TOCOD
CODAFF
AFFUNLESS
UNLESS
OTHERWISE NOTED. 3/4" C - STUB UP TO CEILING PLENUM
LOCATION:
DRAWING NO:
E1.0
HUMBOLDT COUNTY, CALIFORNIA
CONNECTION POINT
P3
ELECTRICAL LEGEND AND SCHEDULES
CONDUIT UP
(E) BRANCH PANEL
TRINIDAD RANCHERIA
INTERPRETIVE CENTER
TRINIDAD, CA. 95570
CONDUIT DOWN
PEA GRAVEL OR 3/4"
CRUSHED ROCK
24" MIN.
HOME RUN-DESTINATION SHOWN
ELECTRICAL PULLBOX AND
EXTENSIONS AS REQUIRED
12"
LA-2
TVCE
2 PROVIDE BREAKER WITH GFCI PROTECTION FOR
PERSONNEL IN ACCORDANCE WITH CEC 210.8.
FINISH GRADE, TYP.
6"
CAT 5e LIGHTING CABLE
1/2" C - 2# 12.1 #12G
COVER
6"
5e
A
1 REPLACE EXISTING 100A, 3-POLE CIRCUIT BREAKER WITH
NEW 125A, 3-POLE CIRCUIT BREAKER. DISCONNECT
EXISTING FEEDER CONDUCTORS AND CONNECT NEW AS
SHOWN. MODIFY PANEL AS REQUIRED.
24" MIN.
SYMBOLS
ELECTRICAL ABBREVIATIONS
1"
ELECTRICAL LEGEND
TRINITY VALLEY CONSULTING ENGINEERS, INC.
ELECTRICAL SPECIFICATIONS
2.2 EQUIPMENT FINISH
A. UNLESS OTHERWISE INDICATED, FINISH FOR ELECTRICAL EQUIPMENT AND
ENCLOSURES SHALL BE MANUFACTURER'S STANDARD GRAY OR ANSI 61 GRAY OVER
A PRIMER AND RUST INHIBITOR.
2.3 OUTLET AND DEVICE BOXES
A. SHEET STEEL: ONE-PIECE DRAWN TYPE, ZINC- OR CADMIUM-PLATED.
2.4 JUNCTION AND PULLBOXES
A. OUTLET BOXES USED AS JUNCTION OR PULL BOX: AS SPECIFIED UNDER OUTLET AND
DEVICE BOXES.
B. LARGE SHEET STEEL BOX: NEMA 1.
1. BOX: CODE-GAUGE, GALVANIZED STEEL.
2. COVER: FULL ACCESS, SCREW TYPE.
3. MACHINE SCREWS: CORROSION-RESISTANT.
C. LARGE WEATHERPROOF: NEMA 3R
1. BOX: GALVANIZED STEEL.
2. COVER: FULL ACCESS, SCREW TYPE.
3. EMBOSSED OUNTING HOLES ON BACK OF ENLCOSURE.
4. NO GASKETING.
2.5 CONDUIT AND TUBING
A. GALVANIZED RIGID STEEL CONDUIT (GRS):
1. MEET REQUIREMENTS OF ANSI C80.1 AND UL 6.
2. MATERIAL: HOT-DIP GALVANIZED, WITH CHROMATED PROTECTIVE LAYER.
B. ELECTRIC METALLIC TUBING (EMT):
1. MEET REQUIREMENTS OF ANSI C80.3 AND UL 797.
2. MATERIAL: HOT-DIP GALVANIZED, WITH CHROMATED AND LACQUERED
PROTECTIVE LAYER.
C. FLEXIBLE METAL, LIQUID-TIGHT CONDUIT:
1. UL 360 LISTED FOR 105°C INSULATED CONDUCTORS.
2. MATERIAL: GALVANIZED STEEL, WITH AN EXTRUDED PVC JACKET.
D. GALVANIZED STEEL FLEXIBLE CONDUIT:
1. HOT-DIP GALVANIZED.
2. UL 1 AND UL 1479.
E. PVC SCHEDULE 40 CONDUIT:
1. MEET REQUIREMENTS OF NEMA TC2 AND UL 651
2. UL LISTED FOR CONCRETE ENCASEMENT, UNDERGROUND DIRECT BURIAL,
CONCEALED OR DIRECT SUNLIGHT EXPOSURE, AND 90°C INSULATED
CONDUCTORS.
2.6 FITTINGS
A. GALVANIZED RIGID STEEL:
1. MEET REQUIREMENTS OF UL 514B.
2. TYPE: THREADED, GALVANIZED. SETSCREW FITTINGS NOT PERMITTED.
3. MATERIAL: MALLEABLE IRON WITH INSULATED THROAT.
B. ELECTRIC METALLIC TUBING:
1. MEET REQUIREMENTS OF UL 514B.
2. TYPE: STEEL BODY AND LOCK NUTS WITH STEEL OR MALLEABLE IRON
COMPRESSION NUTS.
3. TYPE: STEEL BODY WITH SET SCREWS AND INSULATED THROAT.
C. FLEXIBLE METAL, LIQUID-TIGHT CONDUIT: INSULATED THROAT AND SEALING O-RINGS.
D. GALVANIZED STEEL FLEXIBLE CONDUIT: CAST, SCREW-IN TYPE OR TWO-SCREW
CLAMP TYPE.
E. PVC CONDUIT:
1. MEET REQUIREMENT OF NEMA TC-3 AND UL514B.
2. TYPE: PVC, SLIP-ON.
2.7 CONDUCTORS
A. ALL CONDUCTORS SHOWN SHALL BE NEW UNLESS OTHERWISE INDICATED.
B. CONDUCTOR TYPE:
1. 120VAC AND 277VAC LIGHTING: SOLID COPPER.
2. 120 AC RECEPTACLE CIRCUITS: SOLID COPPER.
3. ALL OTHER CIRCUITS: STRANDED COPPER.
C. INSULATION: TYPE THHN/THWN, 90°C DRY OR 75°C WET.
D. METAL-CLAD CABLE - TYPE MC
1. STANDARDS:
a. LISTED AND LABELED AS DEFINED IN NFPA 70, BY A QUALIFIED TESTING
AGENCY, AND MARKED FOR INTENDED LOCATION AND USE.
b. COMPLY WITH UL 1569.
c. ROHS COMPLAINT.
d. CONDUCTOR AND CABLE MARKING: COMPLY WITH WIRE AND CABLE MARKING
ACCORDING TO UL'S "WIRE AND CABLE MARKING AND APPLICATION GUIDE."
2. CIRCUITS:
a. SINGLE CIRCUIT WITH COLOR-CODED CONDUCTORS.
b. POWER-LIMITED FIRE-ALARMCIRCUITS: COMPLY WITH UL 1424.
3. CONDUCTORS: COPPER, COMPLYING WITH ASTM B3 FOR BARE ANNEALED
COPPER AND WITH ASTM B8 FOR STRANDED CONDUCTORS.
4. GROUND CONDUCTOR: INSULATED
5. CONDUCTOR INSULATION:
a. TYPE TFN/THHN/THWN-2: COMPLY WITH UL 83.
b. TYPE XHHW-2: COMPLY WITH UL 44.
6. ARMOR: ALUMINUM, INTERLOCKED.
7. JACKET: PVC APPLIED OVER ARMOR.
2.8 CONDUCTOR ACCESSORIES
A. TAPE:
1. GENERAL PURPOSE, FLAME RETARDANT: 7 MIL, VINYL PLASTIC, RATED FOR 90°C
MINIMUM MEETING REQUIREMENTS OF UL 510.
2. FLAME RETARDANT, COLD AND WEATHER RESISTANT: 8.5 MIL, VINYL PLASTIC.
B. CABLE TIES:
1. NYLON, ADJUSTABLE, AND SELF-LOCKING.
2.10
DEVICE PLATES
A. PLASTIC
1. MATERIAL: NYLON HIGH IMPACT MATERIAL NONCOMBUSTIBLE.
2. COLOR: TO MATCH ASSOCIATED WIRING DEVICE.
3. MOUNTING SCREW: OVAL-HEAD METAL, COLOR MATCHED TO PLATE.
2.11
DISCONNECT SWITCH, INDIVIDUAL, 0 TO 600 VOLTS:
A. NEMA KS 1.
B. QUICK-MAKE, QUICK-BREAK, MOTOR RATED, LOAD-BREAK, HEAVY-DUTY (HD) TYPE
WITH EXTERNAL MARKINGS CLEARLY INDICATING ON/OFF POSITIONS.
C. ENCLOSURE: NEMA 12, INDUSTRIAL USE, NEMA 3R, DENOTED BY WP, UNLESS
OTHERWISE SHOWN.
D. INTERLOCK: ENCLOSURE AND SWITCH TO PREVENT OPENING COVER WITH SWITCH IN
THE ON POSITION.
E. LOCKABLE TO THE OPEN POSITION. PROVIDE TAG READING “DO NOT OPEN UNDER
LOAD.”
2.12
PANELBOARDS
A. RATINGS: AS SHOWN ON THE PLANS.
B. CONSTRUCTION:
1. INTERIORS SHALL BE COMPLETELY FACTORY ASSEMBLED. THEY SHALL BE
DESIGNED SUCH THAT SWITCHING AND PROTECTIVE DEVICES CAN BE REPLACED
WITHOUT DISTURBING ADJACENT UNITS AND WITHOUT REMOVING THE MAIN BUS
CONNECTORS.
2. TRIMS FOR BRANCH CIRCUIT PANELBOARDS SHALL BE SUPPLIED WITH A HINGED
DOOR OVER ALL CIRCUIT BREAKER HANDLES. DOORS IN PANELBOARD TRIMS
SHALL NOT UNCOVER ANY LIVE PARTS. DOORS SHALL HAVE A SEMI FLUSH
CYLINDER LOCK AND CATCH ASSEMBLY. DOOR-IN-DOOR TRIM SHALL BE
PROVIDED. BOTH HINGED TRIM AND TRIM DOOR SHALL UTILIZE THREE POINT
LATCHING. NO TOOLS SHALL BE REQUIRED TO INSTALL OR REMOVE TRIM. TRIM
SHALL BE EQUIPPED WITH A DOOR-ACTUATED TRIM LOCKING TAB. EQUIP LOCKING
TAB WITH PROVISION FOR A SCREW SUCH THAT REMOVAL OF TRIM REQUIRES A
TOOL, AT THE OWNER'S OPTION. INSTALLATION SHALL BE TAMPER RESISTANT
WITH NO EXPOSED HARDWARE ON THE PANELBOARD TRIM.
3. DISTRIBUTION PANELBOARD TRIMS SHALL COVER ALL LIVE PARTS. SWITCHING
DEVICE HANDLES SHALL BE ACCESSIBLE.
4. SURFACE TRIMS SHALL BE SAME HEIGHT AND WIDTH AS BOX. FLUSH TRIMS SHALL
OVERLAP THE BOX BY 3/4 OF AN INCH ON ALL SIDES.
5. A DIRECTORY CARD WITH A CLEAR PLASTIC COVER SHALL BE SUPPLIED AND
MOUNTED ON THE INSIDE OF EACH DOOR.
C. BUS
1. MAIN BUS BARS SHALL BE TIN-PLATED COPPER SIZED IN ACCORDANCE WITH UL
STANDARDS TO LIMIT TEMPERATURE RISE ON ANY CURRENT CARRYING PART TO
A MAXIMUM OF 65 DEGREES C ABOVE AN AMBIENT OF 40 DEGREES C MAXIMUM.
2. A SYSTEM GROUND BUS SHALL BE INCLUDED IN ALL PANELS.
3. FULL-SIZE (100%-RATED) INSULATED STAND-OFF NEUTRAL BARS SHALL BE
INCLUDED FOR PANELBOARDS SHOWN WITH NEUTRAL. BUS BAR TAPS FOR
PANELS WITH SINGLE-POLE BRANCHES SHALL BE ARRANGED FOR SEQUENCE
PHASING OF THE BRANCH CIRCUIT DEVICES. NEUTRAL BUSING SHALL HAVE A
SUITABLE LUG FOR EACH OUTGOING FEEDER REQUIRING A NEUTRAL
CONNECTION. 200%-RATED NEUTRALS SHALL BE SUPPLIED FOR PANELS
DESIGNATED ON DRAWINGS WITH OVERSIZED NEUTRAL CONDUCTORS.
D. CIRCUIT BREAKER
1. THE MINIMUM SHORT-CIRCUIT RATING FOR BRANCH CIRCUIT PANELBOARDS
SHALL BE AS INDICATED ON THE DRAWINGS. PANELBOARDS SHALL BE FULLY
RATED.
2. BOLT-ON TYPE, HEAVY-DUTY, QUICK-MAKE, QUICK-BREAK, SINGLE- AND MULTIPOLE CIRCUIT BREAKERS SHALL BE PROVIDED FOR EACH CIRCUIT WITH TOGGLE
HANDLES THAT INDICATE WHEN UNIT HAS TRIPPED.
3. ALL CIRCUIT BREAKERS SHALL BE THERMAL-MAGNETIC TYPE WITH COMMON
HANDLE FOR ALL MULTIPLE POLE CIRCUIT BREAKERS.
4. CIRCUIT BREAKERS SHALL BE PROVIDED WITH LOCKABLE HANDLES WHEN
INDICATED.
E. ENCLOSURE
1. ENCLOSURES SHALL BE AT LEAST 20 INCHES WIDE MADE FROM GALVANIZED
STEEL. PROVIDE MINIMUM GUTTER SPACE IN ACCORDANCE WITH THE NATIONAL
ELECTRICAL CODE. WHERE FEEDER CABLES SUPPLYING THE MAINS OF A PANEL
ARE CARRIED THROUGH ITS BOX TO SUPPLY OTHER ELECTRICAL EQUIPMENT, THE
BOX SHALL BE SIZED TO INCLUDE THE ADDITIONAL REQUIRED WIRING SPACE. AT
LEAST FOUR INTERIOR MOUNTING STUDS WITH ADJUSTABLE NUTS SHALL BE
PROVIDED.
2. ENCLOSURES SHALL BE PROVIDED WITH BLANK ENDS.
3. WHERE INDICATED ON THE DRAWINGS, BRANCH CIRCUIT PANELBOARDS SHALL BE
COLUMN WIDTH TYPE.
4. ENCLOSURE SHALL BE NEMA 1 UNLESS OTHERWISE INDICATED ON THE
DRAWINGS.
F. NAMEPLATES
1. PROVIDE AN ENGRAVED NAMEPLATE FOR EACH PANEL.
G. FINISH
1. SURFACES OF THE TRIM ASSEMBLY SHALL BE PROPERLY CLEANED, PRIMED, AND
A FINISH COAT OF GRAY ANSI 61 PAINT APPLIED.
2.13
LUMINAIRES
A. LUMINAIRES AS SHOWN, WITH PROPER HANGERS, PENDANTS, CANOPIES LAMES,
ETC., NECESSARY FOR COMPLETE INSTALLATION.
B. LUMINAIRES INSTALLED OUTDOORS WITH SUITABLE FOR WET LOCATIONS LABEL.
C. SWINGING LUMINAIRES WITH A SAFETY CABLE ATTACHED TO THE STRUCTURE AND
THE LUMINAIRE AT EACH SUPPORT CAPABLE OF SUPPORTING FOUR TIMES THE
VERTICAL LOAD.
3.5 CLEANING AND TOUCH-UP PAINTING
A. KEEP THE PREMISES FREE FROM ACCUMULATION OF WASTE MATERIAL OR RUBBISH.
UPON COMPLETION OF WORK, REMOVE MATERIALS, SCRAPS, AND DEBRIS FROM THE
PREMISES AND FROM THE INTERIOR AND EXTERIOR OF ALL DEVICES AND EQUIPMENT.
REFINISH DAMAGED SURFACES TO NEW CONDITION USING SKILLED CRAFTSMEN OF
THE TRADES INVOLVED.
3.6 RACEWAY SYSTEM
A. UNLESS OTHERWISE INDICATED, RECEPTACLES AND JUNCTION BOXES SHALL BE
CONNECTED TO THE CIRCUIT INDICATED USING ½” C-2#12, 1#12G. RECEPTACLE
CIRCUITS SHALL BE CONCEALED IN WALLS OR ABOVE CEILINGS.
B. PROVIDE AND INSTALL ¾” CONDUIT STUB CONCEALED IN WALL FROM ALL LOWVOLTAGE DEVICE BOXES (DATA, TELEPHONE, LIGHTING CONTROLS, ETC.) TO THE
SPACE ABOVE THE CEILING. PROVIDE A CONDUIT BUSING AT CONDUIT END TO
PROTECT CONDUCTOR INSTALLATION.
C. UNLESS OTHERWISE SPECIFIED OR INDICATED, WIRING SHALL CONSIST OF
INSULATED CONDUCTORS INSTALLED IN RACEWAYS OF THE TYPES INDICATED.
D. INTERIOR, EXPOSED:
1. ELECTRIC METALLIC TUBING.
E. INTERIOR, CONCEALED (NOT EMBEDDED IN CONCRETE):
1. GALVANIZED RIGID STEEL: WHEN ENTERING THE BUILDING FROM AN OUTSIDE
SOURCE WHERE THE CONDUIT RUN MUST BE WATERTIGHT.
2. GALVANIZED STEEL FLEX; USE ONLY IN INDOOR, DRY LOCATIONS FOR FINAL
CONNECTION TO FIXTURES IN LAY IN APPLICATIONS OR OTHER EQUIPMENT
SUBJECT TO VIBRATION OR MOVEMENT.
3. ALL OTHER LOCATIONS: EMT, MC CABLE.
F. FOR EQUIPMENT WHERE FLEXIBLE CONNECTION IS REQUIRED TO MINIMIZE
VIBRATION:
1. FLEXIBLE METAL, LIQUID-TIGHT CONDUIT.
2. LENGTH: 18-INCH MINIMUM, 60-INCH MAXIMUM OF SUFFICIENT LENGTH TO ALLOW
MOVEMENT OR ADJUSTMENT OF EQUIPMENT.
G. BOX TYPE (ALL RACEWAY SYSTEMS)
1. EXTERIOR LOCATIONS: WEATHERPROOF TYPE 3R.
H. INSTALL PULL BOXES WHERE SHOWN AND WHERE NECESSARY TO TERMINATE, TAPOFF, OR REDIRECT MULTIPLE CONDUIT RUNS. INSTALL PULL BOXES WHERE
NECESSARY IN RACEWAY SYSTEM TO FACILITATE CONDUCTOR INSTALLATION.
INSTALL PULL BOXES IN CONDUIT RUNS AT LEAST EVERY 150 FEET OR AFTER THE
EQUIVALENT OF THREE RIGHT-ANGLE BENDS. USE OUTLET BOXES AS JUNCTION AND
PULL BOXES WHEREVER POSSIBLE AND ALLOWED BY APPLICABLE CODES.
I. SUPPORT BOXES INDEPENDENTLY OF CONDUIT BY ATTACHMENT TO BUILDING
STRUCTURE OR STRUCTURAL MEMBER. INSTALL BAR HANGERS IN FRAME
CONSTRUCTION, OR FASTEN BOXES DIRECTLY WITH WOOD SCREWS ON WOOD,
BOLTS AND EXPANSION SHIELDS ON CONCRETE OR BRICK, TOGGLE BOLTS ON
HOLLOW MASONRY UNITS, AND MACHINE SCREWS OR WELDED THREADED STUDS ON
STEELWORK.
J. DIRECT EARTH BURIAL: PVC SCHEDULE 40.
K. UNDER SLAB-ON-GRADE: PVC SCHEDULE 40.
L. ALL UNDERGROUND CONDUIT ORGINATING OUTSIDE THE BUILDING AND ENTERING
THE BUILDING SHALL BE EQUIPPED WITH CONDUIT SEALING. THE CONDUIT AND
ASSOCIATED FITTINGS FROM THE SLAB TO THE ENCLOSURE SHALL BE GALVANIZED
STEEL AND WATERTIGHT.
3.7 RACEWAY INSTALLATION
A. CONDUIT AND TUBING SIZES SHOWN ARE BASED ON THE USE OF COPPER
CONDUCTORS.
B. MAINTAIN RACEWAY ENTIRELY FREE OF OBSTRUCTIONS AND MOISTURE.
C. GROUP RACEWAYS INSTALLED IN SAME AREA.
D. FOLLOW STRUCTURAL SURFACE CONTOURS WHEN INSTALLING EXPOSED
RACEWAYS. AVOID OBSTRUCTION OF PASSAGEWAYS. RUN EXPOSED RACEWAYS
PARALLEL OR PERPENDICULAR TO WALLS, STRUCTURAL MEMBERS, OR
INTERSECTIONS OF VERTICAL PLANES.
E. INSTALL WATERTIGHT CONDUIT SEALING IN OUTDOOR, UNDERGROUND, OR WET
LOCATIONS.
F. ALL METAL CONDUIT TO BE REAMED, BURRS REMOVED, AND CLEANED BEFORE
INSTALLATION OF CONDUCTORS, WIRES, OR CABLES.
G. HORIZONTAL RACEWAYS INSTALLED UNDER FLOOR SLABS SHALL LIE COMPLETELY
UNDER THE SLAB, WITH NO PART EMBEDDED WITHIN SLAB.
H. INSTALL, CONCEALED, EMBEDDED, AND BURIED RACEWAYS SO THAT THEY EMERGE
AT RIGHT ANGLES TO SURFACE AND HAVE NO CURVED PORTION EXPOSED.
I. FOR EMPTY CONDUIT INSTALL A NYLON PULL CORD TO BE USED FOR FUTURE
INSTALLATION.
3.8 RACEWAY PENETRATIONS
A. MAKE AT RIGHT ANGLES, UNLESS OTHERWISE SHOWN.
B. NOTCHING OR PENETRATION OF STRUCTURAL MEMBERS, INCLUDING FOOTING AND
BEAMS, NOT PERMITTED.
C. FIRE-RATED WALLS, FLOORS, OR CEILINGS: FIRE-STOP OPENINGS AROUND
PENETRATIONS TO MAINTAIN FIRE-RESISTANCE RATING.
D. APPLY SINGLE LAYER OF WRAP AROUND DUCT BANK TO ALL METALLIC CONDUIT
PROTRUDING THROUGH CONCRETE FLOOR SLABS TO A POINT 2 INCHES ABOVE
CONCRETE SURFACE.
E. CONCRETE WALLS, FLOORS, OR CEILINGS (ABOVEGROUND): PROVIDE NONSHRINK
GROUT DRY-PACK, OR USE WATERTIGHT SEAL DEVICE.
F. ENTERING STRUCTURES:
1. SEAL RACEWAY AT THE FIRST BOX WITH A CONDUIT SEALING BUSING TO PREVENT
THE ENTRANCE OF GASES OR LIQUIDS FROM ONE AREA TO ANOTHER.
2. HEATING, VENTILATING, AND AIR CONDITIONING EQUIPMENT: PENETRATE
EQUIPMENT IN AREA ESTABLISHED BY MANUFACTURER.
3. EXISTING OR PRECAST WALL (UNDERGROUND): CORE DRILL WALL AND INSTALL A
WATERTIGHT ENTRANCE SEAL DEVICE.
3.9 RACEWAY SUPPORT
A. SUPPORT FROM STRUCTURAL MEMBERS ONLY, AT INTERVALS NOT EXCEEDING NEC
REQUIREMENTS, AND IN ANY CASE NOT EXCEEDING 10 FEET. DO NOT SUPPORT FROM
PIPING, PIPE SUPPORTS, OR OTHER RACEWAYS.
B. WALL BRACKETS AND ASSOCIATED HARDWARE IN CONTACT WITH CONCRETE OR
MASONRY SHALL BE STAINLESS STEEL. PROVIDE GALVANIZED STEEL AT ALL OTHER
LOCATIONS. STRAP HANGERS, AND CEILING TRAPEZE INCLUDING HARDWARE, SHALL
BE GALVANIZED STEEL.
C. PROVIDE AND ATTACH WALL BRACKETS, STRAP HANGERS, OR CEILING TRAPEZE AS
FOLLOWS:
1. WOOD: WOOD SCREWS.
2. HOLLOW MASONRY UNITS: TOGGLE BOLTS.
3. CONCRETE OR BRICK: EXPANSION SHIELDS, OR THREADED STUDS DRIVEN IN BY
POWDER CHARGE, WITH LOCK WASHERS AND NUTS.
4. STEELWORK: MACHINE SCREWS.
D. NAILS OR WOODEN PLUGS INSERTED IN CONCRETE OR MASONRY FOR ATTACHING
RACEWAY NOT PERMITTED. DO NOT WELD RACEWAYS OR PIPE STRAPS TO STEEL
STRUCTURES. DO NOT USE WIRE IN LIEU OF STRAPS OR HANGERS.
3.12
TERMINATION AT ENCLOSURES
A. SHEET METAL BOXES, CABINETS, AND ENCLOSURES:
1. ELECTRIC METALLIC TUBING: PROVIDE GLAND COMPRESSION, INSULATED
CONNECTORS.
2. FLEXIBLE METAL CONDUIT: PROVIDE TWO SCREW TYPE, INSULATED, MALLEABLE
IRON CONNECTORS.
3.13
CONDUCTORS
A. DO NOT SPLICE INCOMING SERVICE CONDUCTORS AND BRANCH POWER
DISTRIBUTION CONDUCTORS NO. 6 AWG AND LARGER UNLESS SPECIFICALLY
INDICATED OR APPROVED BY THE ENGINEER.
B. CONNECTIONS AND TERMINATIONS:
1. INSTALL WIRE NUTS ONLY ON SOLID CONDUCTORS.
2. INSTALL NYLON SELF-INSULATED CRIMP CONNECTORS AND TERMINATORS FOR
CIRCUIT CONDUCTORS NO. 6 AWG AND SMALLER.
3. INSTALL UNINSULATED CRIMP CONNECTORS AND TERMINATORS FOR CIRCUIT
CONDUCTORS NO. 4 AWG THROUGH NO. 2/0 AWG.
4. INSTALL UNINSULATED, BOLTED, TWO-WAY CONNECTORS AND TERMINATORS FOR
CIRCUIT CONDUCTORS NO. 4/0 AWG AND LARGER.
5. TAPE INSULATE ALL UNINSULATED CONNECTIONS.
6. PLACE NO MORE THAN ONE CONDUCTOR IN ANY SINGLE-BARREL PRESSURE
CONNECTION.
7. INSTALL CRIMP CONNECTORS WITH TOOLS APPROVED BY CONNECTOR
MANUFACTURER.
8. COMPRESSION LUGS:
a. ATTACHED WITH A TOOL SPECIFICALLY DESIGNED FOR PURPOSE.
b. DO NOT USE PLIER TYPE CRIMPERS.
C. DO NOT USE SOLDERED MECHANICAL JOINTS.
D. SPLICES AND TERMINATIONS:
1. INDOORS: USE GENERAL PURPOSE, FLAME RETARDANT TAPE.
2. OUTDOORS: USE FLAME RETARDANT, COLD- AND WEATHER-RESISTANT TAPE.
E. CAP SPARE CONDUIT WITH UL LISTED END CAPS.
F. CABINETS AND PANELS:
1. REMOVE SURPLUS WIRE, BRIDLE AND SECURE.
2. WHERE CONDUCTORS PASS THROUGH OPENINGS OR OVER EDGES IN SHEET
METAL, REMOVE BURRS CHAMFER EDGES, AND INSTALL BUSHINGS AND
PROTECTIVE STRIPS OF INSULATING MATERIAL TO PROTECT THE CONDUCTORS.
DWN BY DES BY CHK BY APP BY
2.1 GENERAL
A. UNLESS OTHERWISE INDICATED, PROVIDE ALL FIRST-QUALITY NEW MATERIALS, FREE
FROM ANY DEFECTS, AND SUITABLE FOR THE INTENDED USE AND THE SPACE
PROVIDED. PROVIDE MATERIALS APPROVED BY UL WHEREVER STANDARDS HAVE
ITEMS NOT SPECIFICALLY SHOWN OR SPECIFIED WHICH ARE REQUIRED TO PROVIDE
THE COMPLETE SYSTEMS SPECIFIED HEREIN. WHERE TWO OR MORE UNITS OF THE
SAME CLASS OF MATERIAL OR EQUIPMENT ARE REQUIRED, PROVIDE PRODUCTS OF A
SINGLE MANUFACTURER. COMPONENT PARTS OF MATERIALS OR EQUIPMENT NEED
NOT BE PRODUCTS OF THE SAME MANUFACTURER.
3.4 CUTTING AND PATCHING
A. DO NOT CUT OR NOTCH ANY STRUCTURAL MEMBER OR BUILDING SURFACE WITHOUT
SPECIFIC APPROVAL OF THE ENGINEER. FOLLOWING SUCH WORK, RESTORE
SURFACES NEATLY TO NEW CONDITION USING SKILLED CRAFTSMEN OF THE TRADES
INVOLVED.
3.11
EXPANSION/DEFLECTION FITTINGS
A. PROVIDE ON ALL RACEWAYS AT STRUCTURAL EXPANSION JOINTS.
DESCRIPTION
PART 2 - PRODUCTS
3.3 MATERIAL AND EQUIPMENT INSTALLATION
A. FOLLOW THE MANUFACTURER'S INSTALLATION RECOMMENDATIONS UNLESS
OTHERWISE INDICATED. FOLLOW THE ENGINEER'S DECISION, WHEREVER ANY
CONFLICT ARISES. KEEP COPY OF THE MANUFACTURER'S INSTALLATION
INSTRUCTIONS AVAILABLE ON THE JOBSITE FOR REVIEW AT ALL TIMES.
67 WALNUT WAY
PO BOX 1567
WILLOW CREEK, CA 95573
P:(530)629-3000
F:(530)629-3011
3.14
GROUNDING
A. UNLESS OTHERWISE INDICATED, GROUND ALL EXPOSED NONCURRENT-CARRYING
METALLIC PARTS OF ELECTRICAL EQUIPMENT, RACEWAY SYSTEMS, AND THE
NEUTRAL OF ALL WIRING SYSTEMS IN ACCORDANCE WITH THE CEC, STATE, AND
OTHER APPLICABLE LAWS AND REGULATIONS.
3.15
LUMINARIES
A. AFTER CONSTRUCTION HAS COMPLETED FOR THE PROJECT, CLEAN LUMINAIRES,
TOUCH UP ANY.
END OF SECTION
DATE
1.4 COORDINATION
A. CLOSE COORDINATION BETWEEN THE ELECTRICAL AND MECHANICAL TRADES IS A
PART OF THE WORK THAT IS REQUIRED BY THIS CONTRACT. NO ALLOWANCE WILL BE
MADE FOR OMISSIONS BASED ON INCORRECTLY ASSUMING ANOTHER TRADE WILL BE
PERFORMING YOUR WORK. CONFIRM YOUR SCOPE OF WORK WITH THE GENERAL
CONTRACTOR.
3.2 PROTECTION DURING CONSTRUCTION
A. FOLLOWING INSTALLATION, PROTECT MATERIALS, EQUIPMENT, AND INSULATION
FROM CORROSION, PHYSICAL DAMAGE, AND MOISTURE. CAP CONDUIT RUNS DURING
CONSTRUCTION WITH MANUFACTURED SEALS. KEEP OPENINGS IN BOXES OR
EQUIPMENT CLOSED DURING CONSTRUCTION.
REV
1.3 SUBMITTALS
A. BEFORE ANY MATERIAL IS FABRICATED OR SHIPPED, FURNISH TO THE ENGINEER FULL
DETAILS, SHOP DRAWINGS, DIMENSIONS, CATALOG CUTS, SCHEMATIC (ELEMENTARY)
DIAGRAMS, AND OTHER DESCRIPTIVE MATTER AS REQUIRED TO FULLY DESCRIBE THE
EQUIPMENT SPECIFIED.
3.1 GENERAL PROCEDURES
A. COORDINATE ELECTRICAL WORK WITH THE OWNER AND WORK OF OTHER TRADES TO
AVOID CONFLICTS, ERRORS, DELAYS, AND UNNECESSARY INTERFERENCE DURING
CONSTRUCTION.
3.10
RACEWAY BENDS
A. INSTALL CONCEALED RACEWAYS WITH A MINIMUM OF BENDS IN THE SHORTEST
PRACTICAL DISTANCE.
B. AVOID FIELD-MADE BENDS AND OFFSETS, BUT WHERE NECESSARY, MAKE WITH
ACCEPTABLE HICKEY OR BENDING MACHINE. DO NOT HEAT METAL RACEWAYS TO
FACILITATE BENDING.
C. PVC CONDUIT:
1. BENDS 30° AND LARGER: PROVIDE FACTORY-MADE ELBOWS.
2. 90° BENDS: PROVIDE GALVANIZED RIGID STEEL ELBOWS; EXCEPT ON UTILITY
SERVICE RUNS IF NOT ALLOWED BY THE UTILITY.
D. FLEXIBLE CONDUIT: DO NOT MAKE BENDS THAT EXCEED ALLOWABLE CONDUCTOR
BENDING RADIUS OF CABLE TO BE INSTALLED OR THAT SIGNIFICANTLY RESTRICTS
CONDUIT FLEXIBILITY.
DATE OF ISSUE:
7/12/2023
SCALE:
PROJECT NO:
427.11
DRAWING NO:
E1.1
1/2"
1"
2"
HUMBOLDT COUNTY, CALIFORNIA
1.2 CODES, PERMITS, AND REGULATIONS
A. DO ALL WORK AND INSTALL ALL MATERIALS AND EQUIPMENT IN ACCORDANCE WITH
THE REQUIREMENTS OF THE NATIONAL ELECTRICAL CODE (NEC), APPLICABLE STATE
AND LOCAL LAWS AND ORDINANCES, AND THE POWER COMPANY. CONFLICTS, IF ANY,
WILL BE RESOLVED AT THE DISCRETION OF THE ENGINEER.
PART 3 - EXECUTION
ELECTRICAL SPECIFICATIONS
1.1 GENERAL
A. ELECTRICAL PLAN DRAWINGS SHOW ONLY GENERAL LOCATIONS OF EQUIPMENT,
DEVICES, AND RACEWAY UNLESS SPECIFICALLY DIMENSIONED. THE CONTRACTOR IS
RESPONSIBLE FOR THE PROPER ROUTING OF RACEWAY, SUBJECT TO THE APPROVAL
OF THE ENGINEER. MAKE ADJUSTMENTS AS NECESSARY TO WIRING, CONDUIT,
DISCONNECTS, BRANCH CIRCUIT PROTECTION, AND OTHER AFFECTED MATERIAL OR
EQUIPMENT TO ACCOMMODATE ACTUAL EQUIPMENT SUPPLIED FOR THIS PROJECT.
2.9 WIRING DEVICES
A. DUPLEX RECEPTACLE:
1. NEMA WD 1 AND FS WC596.
2. SPECIFICATION GRADE, TWO-POLE, THREE-WIRE GROUNDING TYPE WITH SCREW
TYPE TERMINALS SUITABLE FOR NO. 10.
3. HIGH STRENGTH THERMOPLASTIC.
4. COLOR: WHITE
5. CONTACT ARRANGEMENT: CONTRACT TO BE MADE ON TWO SIDES OF EACH
INSERTED BLADE WITHOUT DETENT.
6. RATING: 120VAC, 20A.
7. CONFIGURATION: 5-20 R.
B. GROUND FAULT INTERRUPTER (GFCI) RECEPTACLE:
1. NEMA WD 1.
2. RATING: 120VAC, 20A.
3. CONFIGURATION: 5-20 R.
4. PROTECTIONS: TRIPS AT 5 MA AND CAPABLE OF INTERRUPTING 1,000A WITHOUT
DAMAGE.
5. COLOR: WHITE
6. PROVISION FOR TESTING.
7. ALL RECEPTACLE TYPES SHALL BE FROM A SINGLE MANUFACTURER.
C. MANUAL SWITCH
1. NEMA WD 1 AND FS WS896E.
2. SPECIFICATION GRADE, TOTALLY ENCLOSED, AS TYPE, WITH QUIET TUMBLE
SWITCHES AND SCREW TERMINALS.
3. RATING: 20A, 120/277VAC.
4. COLOR: TO BE DETERMINED.
D. OCCUPANCY SENSING SWITCH
1. TYPE: DUAL TECHNOLOGY WITH PASSIVE INFRARED AND MICROPHONIC
TECHNOLOGIES.
2. EACH POLE INDEPENDENTLY/SELECTABLE AUTO-ON OR MANUAL-ON.
3. RATING: AS REQUIRED TO SWITCH LOAD. PROVIDE AUXILIARY RELAY(S)/POWER
PACK(S) AS REQUIRED.
4. TIME DELAYS: 30 SECONDS TO 20 MINUTES.
5. COLOR: TO BE DETERMINED.
E. CEILING MOUNTED OCCUPANCY SENSOR:
1. CEILING MOUNTED LOW PROFILE APPEARANCE.
2. TYPE: DUAL TECHNOLOGY WITH PASSIVE INFRARED AND MICROPHONIC
TECHNOLOGIES.
3. TIME DELAYS: 30 SECONDS TO 20 MINUTES.
4. BUILT-IN LIGHT LEVEL SENSOR.
5. POWER PACK: PROVIDE AS REQUIRED TO ACCOMMODATE INSTALLATION.
6. COVERAGE PATTERN. 40-FOOT X 40-FOOT MINIMUM.
TRINIDAD RANCHERIA
INTERPRETIVE CENTER
TRINIDAD, CA. 95570
PART 1 - GENERAL
TVCE
TRINITY VALLEY CONSULTING ENGINEERS, INC.
TVCE
GENERAL NOTES:
1.
MAINTAIN A MINIMUM 30" WIDE AND 36" DEEP CLEAR
SPACE IN FRONT OF ALL ELECTRICAL DISCONNECTS
AND PANELS.
KEYED NOTES:
CONNECT TO EXISTING 2" DATA CONDUIT.
67 WALNUT WAY
PO BOX 1567
WILLOW CREEK, CA 95573
P:(530)629-3000
F:(530)629-3011
DWN BY DES BY CHK BY APP BY
1
DATA
PULLBOX
(2) 2"C-EMPTY
DESCRIPTION
1
E1.0
J WP
REV
DATE
(N) PNL P4
2"C-4#1,1#6G
2"C-EMPTY
2
E1.0
(E) PNL P3
DATE OF ISSUE:
7/12/2023
SCALE:
1/8" = 1'-0"
PROJECT NO:
1
E1.2
ELECTRICAL SITE PLAN
1/8" = 1'-0"
427.11
DRAWING NO:
E1.2
1/2"
1"
2"
HUMBOLDT COUNTY, CALIFORNIA
ELECTRICAL SITE PLAN
1
TRINIDAD RANCHERIA
INTERPRETIVE CENTER
TRINIDAD, CA. 95570
2"C-EMPTY
TRINITY VALLEY CONSULTING ENGINEERS, INC.
KEYED NOTES:
1 INDICATED EQUIPMENT IS LOCATED ABOVE CEILING.
DAYLIGHTING ZONE LEGEND
TVCE
PRIMARY DAYLIGHTING ZONE
67 WALNUT WAY
PO BOX 1567
WILLOW CREEK, CA 95573
P:(530)629-3000
F:(530)629-3011
J WP
P4-2
OFFICE
P4-2
107
OFFICE
107
2
2
P4-3
P4-3
P4-17,19
(2) 2"C-EMPTY
D D D
P4-3
P4-3
60A
2P
1
D,OC
1
3/4"C-2#6,1#10G
P4-28
WH-1 1
CAFE
P4-8
105
1
OC
BREWER
2
2
GFCI
WP
P4-28
CAFE
P4-9,11
3/4"C-2#10,1#10G
1 AHU-1
GFCI
P4-26
P4-4,6
+42"
105
GFCI
P4-16
4
30A
2P
+42"
GFCI
P4-20
4
SEATING AREA
+42"
3/4"C-2#10,1#10G
OC
1
E1.0
RECEPTION
30
WP
(2) 2"C-EMPTY
P4-5,7
RECEPTION
P4-10
4
2
1
4
P4-1
DATA
PULLBOX
3/4"C-2#6,1#10G
P4-21,23
104
103
P4-10
J
WP
UFER GROUND #4 BARE COPPER
CONDUCTOR 20FT LONG, ENCASED BY
MIN. 2-INCHES OF CONCRETE
LOCATED HORIZONTALLY IN FOOTING
SEATING AREA
P4-8
P4-10
(2) 2"C-EMPTY
DATE
4
2
104
P4-8
GFCI
P4-22
HP-1
103
60A
2P
+42"
1
2
P4-12,14
ESPRESSO
DESCRIPTION
5
+8' AFF
P4-2
DWN BY DES BY CHK BY APP BY
P4-1
(N) PANEL P4
1-1/2"C-4#3,1#8G
4
P4-1
2
ST
ST
2
VISTOR'S
CENTER
OC
(1) 2"C-EMPTY
ST
P4-10
VISTOR'S
CENTER
1
101
REV
ST
2
P4-8
101
1
4
OC
2
2
2
TR
P4-3
TR
2"C-4#1,1#6G
OC
TR
TR
ST
UNISEX ADA R/RM
P4-10
102
106
2
2
+42"
D
3
+8' AFF
UNISEX ADA R/RM
P4-15
102
GFCI
+8' AFF
3
106
CONNECT TO EXISTING, SEE
E1.2 FOR CONTINUATION
2
E2.0
ELECTRICAL FLOOR PLAN - LIGHTING
1/4" = 1'-0"
P4-13
P4-10
P4-1
EF-1
BACK ENTRY
1
E2.0
ELECTRICAL FLOOR PLANS
2 ENTRY
BACK
ELECTRICAL FLOOR PLAN - POWER
1/4" = 1'-0"
DATE OF ISSUE:
7/12/2023
SCALE:
As indicated
PROJECT NO:
427.11
DRAWING NO:
E2.0
1/2"
1"
2"
HUMBOLDT COUNTY, CALIFORNIA
ST
TRINIDAD RANCHERIA
INTERPRETIVE CENTER
TRINIDAD, CA. 95570
4
TRINITY VALLEY CONSULTING ENGINEERS, INC.
HEAT PUMP SCHEDULE
MECHANICAL LEGEND
AFF
ABOVE FINISHED FLOOR
AD
AD
ACCESS DOOR
12/8
AL
ACOUSTIC LINED DUCT (DIM IS INTERNAL)
AC
AIR CONDITIONING
BHP
BRAKE HORSE POWER
CFM
CUBIC FEET PER MINUTE
A
123
DIFFUSER TAG
D
DEMO
DB
DRY BULB
12/8
DUCT (RECTANGULAR DUCT, DIMENSIONS IN INCHES)
12Ø
DUCT (ROUND DUCT, DIAMETER IN INCHES)
D
DUCT DROP IN DIRECTION OF ARROW
R
DUCT RISE IN DIRECTION OF ARROW
EA
EER
ENERGY EFFICIENCY RATIO
EAT
ENTERING AIR TEMPERATURE
EA
EXHAUST AIR DUCT
EF
EXHAUST FAN
EXHAUST GRILLE
(E), EX
EXISTING
ESP
EXTERNAL STATIC PRESSURE
FPM
FEET PER MINUTE
Model
5TWR5036A1
Rated Capacity Btu/h
34,500
Cooling
Rating Conditions
80°F DB / 67°F WB / 95°F OAT
Heating
Rated Capacity Btu/h
31,400
FULL LOAD AMPS
LAT
LEAVING AIR TEMPERATURE
MOCP
MAXIMUM OVER CURRENT PROTECTION
MCA
MINIMUM CIRCUIT AMPACITY
MOTORIZED DAMPER
M
(N)
NEW
MOCP
40
Refrigerant
R-454B
Dimensions
34-1/4"W x 37-1/4"D x 45-1/8"H
Operating
Weight (lbs)
315
Notes
1-2
67 WALNUT WAY
PO BOX 1567
WILLOW CREEK, CA 95573
P:(530)629-3000
F:(530)629-3011
AIR HANDLING UNIT SCHEDULE
ID
AHU-1
Manufacturer
TRANE
Model
Location Served
5TEM6D06AV41 INTERPRETIVE CENTER
Supply Fan
Airflow
CFM
OA CFM
1,200
400
Nominal
Tonnage
3
Cooling Coil
MBh (Total /
Sens)
34.5 / 26.7
Refrigerant
R-454B
Heating Coil
Electric Heat
(kw)
Total MBh
26.2
7.68
Electrical Data
Service
208-230/1/60
MCA
9
MOCP
15
Dimensions
57-3/8"W x 21-1/16"D x 23-1/2"H
Weight
200
Notes
1-5
NOTES:
1. PROVIDE WITH ALL NECESSARY REFRIGERATION PIPING AND APPURTENANCES.
2. RL/RS LINE SIZES PER MANUFACTURER.
3. MERV 13 FILTER IN HONEYWELL FILTER RACK. SEE AIR HANDLING UNIT DETAILS.
4. DIVERITECH CONDENSATE CS-2 SWITCH WIRED TO UNIT FOR OVERFLOW PROTECTION.
5. PROVIDE 7-DAY PROGRAMMABLE THERMOSTAT
EXHAUST FAN SCHEDULE
ID
EF-1
Location
RESTROOM
Manufacturer
GREENHECK
Model
SP-80-VG
CFM
70
S.P.
0.25
Fan Drive
DIRECT
Service
115/1/60
Motor Watts
6
Weight (lbs)
20
Notes
1-2
NOTES:
1. INTERLOCK WITH LIGHTS
2. INTEGRAL BACKDRAFT DAMPER.
LOUVER SCHEDULE
ID
L-1
L-2
Manufacturer
RUSKIN
RUSKIN
Model
ELF375DXH
ELF375DXH
CFM
400
400
Size
18"x18"
18"x18"
Velocity (fpm)
416
416
Free Area (sf)
0.96
0.96
Pressure Drop
0.05
0.05
Notes
1-3
1-3
Finish
BAKED ENAMEL
BAKED ENAMEL
Notes
1
1
Finish
BAKED ENAMEL
BAKED ENAMEL
Notes
1
2
NOTES:
1. ALUMINUM CONSTRUCTION WITH 0.125" NOMINAL WALL THICKNESS FOR FRAME AND BLADES.
2. 1/4" MESH SCREEN.
3. COORDINATE FINISH WITH ARCHITECT.
AIR INLET SCHEDULE
ID
1
2
Manufacturer
TITUS
TITUS
Model
50F
50F
Mounting
SURFACE
SURFACE
Face Size
12"x12"
14"x14"
Material
ALUMINUM
ALUMINUM
NOTES:
1. EGGCRATE RETURN GRILLE.
AIR OUTLET SCHEDULE
LOUVERED DOOR
L
Electrical Data
Service
MCA
208-230/1/60
25
NOTES:
1. TWO SPEED COMPRESSOR.
2. SEA COAST COATING.
FLEXIBLE DUCT
FLA
Rating Conditions
70°F DB / 60°F WB / 47° OAT
DWN BY DES BY CHK BY APP BY
ABOVE CEILING
Location Manufacturer
OUTSIDE
TRANE
DESCRIPTION
ABC
Service
INTERPRETIVE CENTER
ID
A
B
Manufacturer
TITUS
TITUS
Model
TDC
TDC
Mounting
SURFACE
SURFACE
Face Size
12"x12"
12"x12"
Neck Size
SEE PLANS
SEE PLANS
Material
STEEL
STEEL
DATE
ID
HP-1
ABBREVIATIONS
NOTES:
1. LOUVER FACE DIFFUSER, 4-WAY THROW.
2. LOUVER FACE DIFFUSER, 2-WAY THROW.
REV
SYMBOLS
TVCE
NEW CONNECTION TO EXISTING
OA
1
123
OUTSIDE AIR
REGISTER/GRILLE TAG
(R), R
RELOCATE
REMOVE TO THIS POINT
RA
RA
RETURN AIR DUCT
SEER
SEASONAL ENERGY EFFICIENCY RATIO
SD
SMOKE DETECTOR
SA
SUPPLY AIR DUCT
SUPPLY DIFFUSER
T
T'STAT
THERMOSTAT (48" AFF TOP OF BOX)
TSP
TOTAL STATIC PRESSURE
TURNING VANES
TYP
TYPICAL
UNDERCUT DOOR
UC
UG
UNDERGROUND
VIF
VERIFY IN FIELD
VOLUME DAMPER - MANUAL OPERATION
WB
WET BULB
DATE OF ISSUE:
7/12/2023
SCALE:
1/8" = 1'-0"
PROJECT NO:
427.11
DRAWING NO:
M1.0
1/2"
1"
2"
HUMBOLDT COUNTY, CALIFORNIA
SA
REFRIGERANT LINE SET
MECHANICAL LEGEND AND SCHEDULES
SD
RL/RS
TRINIDAD RANCHERIA
INTERPRETIVE CENTER
TRINIDAD, CA. 95570
RETURN GRILLE
TRINITY VALLEY CONSULTING ENGINEERS, INC.
TVCE
MECHANICAL SPECIFICATIONS
B. WHEN THE CONTRACT DOCUMENTS CALL FOR MATERIALS OR CONSTRUCTION OF A HIGHER STANDARD
THAN IS REQUIRED BY THE ABOVE, THE CONTRACT DOCUMENT REQUIREMENTS SHALL TAKE
PRECEDENCE OVER THE REQUIREMENTS OF THE APPLICABLE LAWS, ORDINANCES, RULES, OR
REGULATIONS. NOTHING IN THE CONTRACT DOCUMENTS SHALL BE INTERPRETED AS PERMITTING
WORK IN VIOLATION OF SAID LAWS, RULES, AND/OR REGULATIONS.
C. THE CONTRACTOR FOR THIS WORK SHALL FURNISH, WITHOUT EXTRA CHARGE, ANY ADDITIONAL
MATERIALS AND/OR LABOR AS MAY BE REQUIRED FOR COMPLIANCE WITH THESE LAWS, RULES,
AND/OR REGULATIONS THOUGH SUCH MATERIALS AND/OR LABOR ARE NOT SPECIALLY SET FORTH IN
THE CONTRACT DOCUMENTS.
1.3 LICENSING REQUIREMENTS
A. ALL WORK OF DIVISION 22 AND 23 SHALL BE PERFORMED BY AN APPROPRIATELY LICENSED
CONTRACTOR. THE LICENSES SHALL BE CURRENT, VALID THROUGH THE TERM OF THE CONTRACT AND
IN THE NAME OF THE CONTRACTOR.
1.
ALL HVAC WORK, WHICH INCLUDES WARM AIR HEATING SYSTEMS AND WATER HEATING PUMPS,
VENTILATING SYSTEMS, AIR CONDITIONING SYSTEMS, AND DUCTWORK, REGISTERS, FLUES,
HUMIDITY, AND THERMOSTATIC CONTROLS IN CONNECTION WITH THESE SYSTEMS, SHALL BE
PERFORMED BY A C-20 – WARM-AIR HEATING, VENTILATING AND AIR-CONDITIONING
CONTRACTOR.
A. EQUIPMENT WARRANTIES SHALL BE PROVIDED FOR ALL EQUIPMENT, WITH ALL NECESSARY
INFORMATION FILLED IN, EXCEPT PURCHASE DATE, IN FAVOR OF THE OWNER.
B. THE CONTRACTOR SHALL GUARANTEE THAT ALL WORK UNDER THIS SECTION IS FREE FROM DEFECTS
IN MATERIAL AND WORKMANSHIP FOR A PERIOD OF ONE YEAR FROM THE DATE OF FILING THE NOTICE
OF COMPLETION. REPLACEMENT OF DEFECTIVE WORK AND DAMAGE CAUSED TO WORK OF OTHER
TRADES AS A RESULT OF SUCH DEFECTIVE WORK SHALL BE THE RESPONSIBILITY OF THE
CONTRACTOR, AND SHALL BE MADE AT NO COST TO THE OWNER.
1.12
ALTERNATIVE MATERIALS AND METHODS
B. SCREENS – INSTALL REMOVABLE BIRD SCREENS AT ALL OUTSIDE INTAKES AND EXHAUST AIR
DISCHARGES. SCREENS SHALL BE FABRICATED FROM ½” X 14 GAUGE MESH SECURED IN FULL FRAMES.
SCREENS AND FRAMES SHALL BE CONSTRUCTED OF THE SAME MATERIAL AS THE DUCT, HOOD, OR
EQUIPMENT TO WHICH ATTACHED.
C. JOINTS – TAPE ALL JOINTS AIRTIGHT USING HARDCAST TYPE “DT” PRESSURELESS TAPE AND “HD-20”
ADHESIVE, PER MANUFACTURER’S DIRECTIONS.
D. DAMPERS – PROVIDE BUTTERFLY OR MULTI-BLADE DAMPERS WHERE INDICATED ON THE DRAWINGS
OR AS REQUIRED FOR BALANCING AIR QUANTITIES TO VALUES SHOWN WITHOUT GENERATING
EXCESSIVE NOISE. PROVIDE DURO-DYNE “KS-385,” OR APPROVED EQUAL, LOCKING QUADRANTS ON
EACH MANUAL DAMPER. LOCATE DAMPERS IN FURRED CEILINGS NEAR ACCESS PANELS WHERE
POSSIBLE.
A. THESE PLANS AND SPECIFICATIONS DESCRIBE THE GENERAL SCOPE OF THE MECHANICAL SYSTEMS.
THESE PLANS AND SPECIFICATIONS DO NOT PRECLUDE THE SUBMITTAL OF ALTERNATIVE METHODS OR
MATERIALS. MANUFACTURER’S NAMES AND CATALOG NUMBERS ARE STATED TO IDENTIFY THE TYPE
AND QUALITY OF THE EQUIPMENT OR MATERIALS REQUIRED FOR THE PROJECT.
B. THE CONTRACTOR MAY SUBMIT SHOP DRAWINGS AND/OR TECHNICAL INFORMATION ON ALTERNATIVE
EQUIPMENT, MATERIALS OR INSTALLATION DETAILS TO ACCOMPLISH THE INTENT OF THE PLANS AND
SPECIFICATIONS. APPROVAL OF THE ALTERNATIVE EQUIPMENT, MATERIALS OR INSTALLATION DETAILS
SHALL NOT RELIEVE THE CONTRACTOR OF ANY RESPONSIBILITY FOR COMPLYING WITH THE INTENT OF
THE PLANS AND SPECIFICATIONS. SUBMIT THE MANUFACTURERS' TECHNICAL INFORMATION, SHOP
DRAWINGS, AND/OR WRITTEN DESCRIPTION OF ALTERNATIVE METHODS FOR EACH ITEM DESCRIBED BY
MANUFACTURER'S NAME AND CATALOG NUMBER AND FOR EACH COMPONENT, EQUIPMENT, MATERIAL,
OR INSTALLATION DETAIL REQUIRED.
INSTALL AT EACH POINT WHERE A BLOWER UNIT IS CONNECTED TO A DUCT. A MINIMUM
CLEARANCE OF THREE INCHES BETWEEN THE DUCT AND THE SOURCE OF VIBRATION SHALL BE
MAINTAINED. INSTALL PER FIGURE 2-17.
1.
BUTTERFLY DAMPERS SHALL BE CONSTRUCTED AS PER FIGURE 7-4, FIGURE A, B, AND C IN THE
DUCT MANUAL.
2.
MULTI-BLADE DAMPERS SHALL CONFORM TO FIGURE 7-5.
3.
BACK-DRAFT DAMPERS SHALL BE AIR BALANCE “AIR DYNAMIC” MODEL DY-1002-V, OR EQUAL.
2.5 INSULATION
A. EXTERIOR OF DUCTWORK:
1.
UNLESS SPECIFIED TO BE LINED, ALL SHEET METAL SUPPLY AND RETURN DUCTS IN INDIRECTLY
CONDITIONED SPACES SHALL BE INSULATED ON THE OUTSIDE WITH JOHNS MANVILLE “MICROLITE
XG” FLEXIBLE FIBERGLASS BLANKET-TYPE DUCT WRAP, WITH FACTORY APPLIED FSK ALUMINUM
FOIL FACING, WITH A COMPOSITE UL RATING OF 25/50, MINIMUM R-6 INSTALLED.
2.
UNLESS SPECIFIED TO BE LINED, ALL SHEET METAL SUPPLY AND RETURN DUCTS IN
UNCONDITIONED SPACES SHALL BE INSULATED ON THE OUTSIDE WITH JOHNS MANVILLE
“MICROLITE XG” FLEXIBLE FIBERGLASS BLANKET-TYPE DUCT WRAP, WITH FACTORY APPLIED FSK
ALUMINUM FOIL FACING, WITH
A COMPOSITE UL RATING OF 25/50, MINIMUM R-8 INSTALLED.
PART 2 – PRODUCTS
2.1 GENERAL
A. ALL MATERIALS, APPLIANCES, AND EQUIPMENT SHALL BE NEW AND BEST OF THEIR RESPECTIVE KINDS,
FREE FROM DEFECTS, AND OF THE MAKE, BRAND, OR QUALITY SPECIFIED OR AS ACCEPTED BY THE
ARCHITECT.
B. INTERIOR OF DUCTWORK:
1.4 COOPERATION WITH OTHER TRADES
A. COOPERATE FULLY WITH OTHER TRADES DOING WORK ON THE PROJECT AS MAY BE NECESSARY FOR
THE PROPER COMPLETION OF THE PROJECT. REFER TO THE STRUCTURAL, PLUMBING, AND
ELECTRICAL DRAWINGS FOR DETAILS OF THE BUILDING STRUCTURE AND EQUIPMENT INSTALLATION
THAT WILL TEND TO OVERLAP, CONFLICT WITH OR REQUIRE COORDINATION WITH THE WORK OF THIS
SECTION, AND SCHEDULE THIS WORK ACCORDINGLY.
B. WHEN TWO OR MORE UNITS OF MATERIALS OR EQUIPMENT OF THE SAME TYPE OR CLASS ARE
REQUIRED, THESE UNITS SHALL BE PRODUCTS OF ONE MANUFACTURER.
1.
C. APPLY AND INSTALL ALL ITEMS IN ACCORDANCE WITH MANUFACTURER’S WRITTEN INSTRUCTIONS.
REFER CONFLICTS BETWEEN MANUFACTURER’S INSTRUCTIONS AND THE CONTRACT DRAWINGS AND
SPECIFICATIONS TO THE ARCHITECT FOR RESOLUTION.
2.2 THERMOSTATS
B. ANY WORK DONE WITHOUT REGARD FOR OTHER TRADES SHALL BE MOVED, REPLACED, OR REDONE
AS REQUIRED, WITHOUT EXTRA CHARGES TO OWNER.
A. ELECTRIC, SOLID-STATE, MICROCOMPUTER-BASED ROOM THERMOSTAT WITH THE FOLLOWING
FEATURES.
2.
ALL EXPOSED EXTERIOR SUPPLY AND RETURN DUCTWORK SHALL HAVE MINIMUM 2” INTERIOR
INSULATION, AS SPECIFIED IN THIS SECTION.
3.
MAXIMUM VELOCITY: 5,000 FT/MIN.
4.
FASTENERS: DUCT LINER GALVANIZED STEEL PINS, WELDED OR MECHANICALLY FASTENED.
5.
DEVELOPED SMOKE DENSITY SHALL NOT EXCEED 50. FLAME SPREAD RATING SHALL NOT EXCEED
25.
1.5 DIVISION OF WORK BETWEEN DIVISIONS 23 AND 26
A. CLOSE COORDINATION BETWEEN THE ELECTRICAL AND MECHANICAL TRADES IS A PART OF THE WORK
THAT IS REQUIRED BY THIS CONTRACT. NO ALLOWANCE WILL BE MADE FOR OMISSIONS BASED ON
INCORRECTLY ASSUMING ANOTHER TRADE WILL BE PERFORMING YOUR WORK. CONFIRM YOUR SCOPE
OF WORK WITH THE GENERAL CONTRACTOR.
B. THE DIVISION OF RESPONSIBILITIES BETWEEN TRADES SUPPLYING EQUIPMENT IN OTHER DIVISIONS
MAY BE DIFFERENT. FOR INSTANCE, DIVISION 26 CONTRACTOR MAY BE REQUIRED TO SUPPLY
DISCONNECT SWITCHES AND STARTERS FOR NON-HVAC MECHANICAL EQUIPMENT SUPPLIED UNDER
OTHER DIVISIONS.
1.
2.
3.
4.
5.
6.
7.
8.
9.
AUTOMATIC SWITCHING FROM HEATING TO COOLING.
PREFERENTIAL RATE CONTROL TO MINIMIZE OVERSHOOT AND DEVIATION FROM SET POINT.
SET UP FOR FOUR SEPARATE TEMPERATURES PER DAY.
INSTANT OVERRIDE OF SET POINT FOR CONTINUOUS OR TIMED PERIOD FROM 1 HOUR TO 31 DAYS.
SHORT-CYCLE PROTECTION.
PROGRAMMING BASED ON EVERY DAY OF WEEK.
SELECTION FEATURES INCLUDE DEGREE F OR DEGREE C DISPLAY, 12- OR 24-HOUR CLOCK,
KEYBOARD DISABLE, REMOTE SENSOR, AND FAN ON-AUTO.
BATTERY REPLACEMENT WITHOUT PROGRAM LOSS.
THERMOSTAT DISPLAY FEATURES INCLUDE THE FOLLOWING:
DUCT LINING SHALL BE INSTALLED IN SUPPLY AND RETURN DUCTS AND PLENUMS WHERE NOTED
ON THE DRAWINGS. LINING SHALL BE JOHNS MANVILLE “PERMACOTELINACOUSTIC R” RIGID
FIBERGLASS BOARD FOR PLENUMS AND “PERMACOTELINACOUSTIC HP” FIBERGLASS DUCT LINER
FOR DUCTS, 1” THICK, UNLESS OTHERWISE NOTED, WITH FIRE RESISTANT COATING. DUCT LINER
SHALL MEET ASTM C 1071, WITH AIR SURFACE COATED WITH ACRYLIC COATING TREATED WITH EPA
REGISTERED ANTI-MICROBIAL AGENT PROVE TO RESIST MICROBIAL GROWTH AS DETERMINED BY
ASTM G 21 AND G 22. INSULATION WITH TORN OR BROKEN COATING SHALL BE REMOVED AND
REPLACED. LOOSE CORNERS, EDGES, AND BUTT JOINTS WILL NOT BE ACCEPTED.
B. INSTALL EQUIPMENT TO PROVIDE GOOD APPEARANCE, EASY ACCESS, AND ADEQUATE SPACE TO
ALLOW REPLACEMENT AND MAINTENANCE. PROVIDE BASES, SUPPORTS, ANCHOR BOLTS, AND OTHER
ITEMS REQUIRED TO ACHIEVE THIS. INSTALLATION SHALL BE LEVEL, ABOVE MOISTURE LEVEL, AND
ADEQUATELY BRACED.
C. THOROUGHLY LUBRICATE EQUIPMENT BEFORE OPERATING. REPAIR OF DAMAGE RESULTING FROM
FAILURE TO COMPLY WITH THIS REQUIREMENT SHALL BE THE CONTRACTOR’S RESPONSIBILITY.
D. CONNECTIONS TO PIPING SHALL BE SECURED AND PROPERLY ALIGNED AND ALL UTILITY AND CONTROL
CONNECTIONS SHALL BE PROPERLY ISOLATED FROM THE BUILDING STRUCTURE BY MEANS OF
ISOLATORS AND FLEXIBLE CONNECTIONS. ANY EQUIPMENT NOT MEETING THIS REQUIREMENT WILL BE
MODIFIED AND REINSTALLED AT NO EXPENSE TO THE OWNER.
E. MOVE EQUIPMENT INTO BUILDING THROUGH AVAILABLE OPENINGS. DISMANTLE EQUIPMENT WHERE
NECESSARY TO ACCOMPLISH THIS. AFTER REASSEMBLY, TEST EQUIPMENT TO VERIFY ITS
SATISFACTORY OPERATING CONDITION.
3.3 DUCTWORK
A. ALL DUCTWORK SHALL BE INSTALLED WITHIN SPACES PROVIDED WHERE POSSIBLE. DUCTS SHALL BE
INSTALLED TRUE TO LINE AND GRADE, FULLY SECURED TO STRUCTURAL FAMING WITH SPECIFIED
HANGERS AND SUPPORTS, INSULATED, AND VIBRATION ISOLATED, WHERE REQUIRED.
B. EACH SECTION OF SUPPLY AIR DUCTWORK SHALL BE CLEANED AT THE SHOP, DUST AND OIL FREE,
USING A DEGREASING AGENT AND DETERGENT AND SEALED AIRTIGHT AT BOTH ENDS WITH VISQUEEN
AND TAPE. SUPPLY DUCTS SHALL BE ADDITIONALLY CLEANED WITH A DISINFECTING SOLUTION. ENDS
OF ALL SUPPLY AND INTERNALLY INSULATED EXHAUST DUSTS SHALL BE KEPT SEALED UNTIL THE TIME
THEY ARE JOINTED. WHEN DUCT SECTIONS ARE JOINED, WIPE DOWN ALL INTERIOR SURFACES WITH A
CLEAN TACK CLOTH. IF TACK CLOTH SHOWS ANY DUST, THEN RE-CLEAN DUCT AS DESCRIBED ABOVE.
THE INTENT IS THAT NO FOREIGN MATTER BE ALLOWED TO ENTER THE DUCTWORK AT ANY TIME AFTER
FACTORY CLEANING AND DURING CONSTRUCTION.
3.4 CONTROLS
A. THIS CONTRACTOR SHALL PROVIDE ALL REQUIRED CONTROL COMPONENTS, INCLUDING BUT NOT
LIMITED TO THERMOSTATS, TEMPERATURE SENSORS, STATIC PRESSURE SENSORS, HUMIDITY
SENSORS, DAMPER ACTUATORS, VALVE ACTUATORS, UNITARY CONTROLLERS, RELAYS, AND LOWVOLTAGE WIRING, SUCH THAT THE OWNER IS PROVIDED WITH A FULLY FUNCTIONAL CONTROL SYSTEM.
B. WHERE WORK IS PERFORMED IN AN EXISTING BUILDING, THIS CONTRACTOR SHALL INTEGRATE ALL
CONTROL MODIFICATIONS INTO THE EXISTING BUILDING CONTROL SYSTEM, IF APPLICABLE. SPECIFIC
REQUIREMENTS SHALL BE COORDINATED WITH OWNER AND APPROVED BY ARCHITECT PRIOR TO
INSTALLATION.
C. INSTALLATION OF THE SYSTEM SHALL BE MADE UNDER THE SUPERVISION OF THE MANUFACTURER OF
THE EQUIPMENT, OR HIS FACTORY AUTHORIZED REPRESENTATIVE.
D. ROOM THERMOSTATS SHALL BE INSTALLED IN THE LOCATIONS INDICATED ON THE CONTRACT
DRAWINGS. FINAL LOCATIONS SHALL BE COORDINATED WITH OWNER’S MAINTENANCE PERSONNEL
AND SHALL BE INSTALLED IN LOCATIONS WHICH SHALL PROVIDE REPRESENTATIVE TEMPERATURES
FOR THE ADJACENT AREAS.
E. LOW VOLTAGE CONTROL WIRING AND CONDUIT SHALL BE INSTALLED IN ACCORDANCE WITH
REQUIREMENTS OF DIVISION 26.
3.5 INSULATION
A. EXTERIOR DUCTWORK:
2.6 REFRIGERATION PIPING AND APPURTENANCES
1.
THE INSULATION SHALL BE CUT LONGER THAN THE PERIMETER OF THE DUCT TO PROVIDE 2”
STAPLE LAP AND MINIMUM COMPRESSION AT THE CORNERS. ALL JOINTS SHALL BE LAPPED 2’ AND
STAPLED WITH OUTWARD CLINCHING STAPLES 2” ON CENTER. THE INSULATION SHALL BE
MECHANICALLY FASTENED TO THE UNDERSIDE OF ALL DUCTS 24” WIDE OR MORE USING CUP-HEAD
PINS, WELD PINS, OR STICK PINS WITH SPEED CLIPS 18” ON CENTER. ALL JOINTS AND
PENETRATIONS OF THE VAPOR BARRIER JACKET SHALL BE SEALED WITH A MINIMUM 3” WIDE
MATCHING PRESSURE SENSITIVE TAPE. PRESSURE-SENSITIVE TAPE SHALL BE FIRMLY RUBBED IN
PLACE IMMEDIATELY AFTER APPLICATION USING A “SQUEEGEE” TYPE TOOL.
2.
WHEN A VAPOR SEAL IS REQUIRED, TWO COATS OF VAPOR RETARDER MASTIC REINFORCED WITH
ONE LAYER OF 4” WIDE, OPEN WEAVE GLASS FABRIC MAY BE USED IN LIEU OF PRESSURESENSITIVE TAPE. MASTIC SHALL BE BRUSHED ONTO JOINT AND GLASS FABRIC UNTIL THE FABRIC IS
FILLED. MASTICS SHALL BE APPLIED IN ACCORDANCE WITH APPLICATION INSTRUCTIONS ON THE
CONTAINER.
A. REFRIGERANT PIPING SHALL BE TYPE “ACR” DE-OXIDIZED HARD TEMPER COPPER TUBE, ASTM B280.
C. DIVISION 23 RESPONSIBILITIES
1.
2.
3.
4.
5.
6.
7.
8.
9.
ASSUME RESPONSIBILITY FOR THE PROPER FUNCTIONING OF THE HVAC SYSTEMS IN THEIR
ENTIRETY.
FURNISH AND INSTALL ALL CONDUCTORS AND CONDUIT REQUIRED FOR CONTROL OF HVAC
EQUIPMENT.
MAKE ALL TERMINATIONS WITH THE EXCEPTION OF POWER CONDUCTORS.
FURNISH AND INSTALL ALL CONTROL PANELS AND DEVICES TO PROVIDE A COMPLETE AND
FUNCTIONAL CONTROLS SYSTEM, INCLUDING ALL CONTROLS TRANSFORMERS.
FURNISH AND INSTALL MOTOR STARTERS FOR ALL EQUIPMENT SPECIFIED IN DIVISION 23.
INSTALL DUCT SMOKE DETECTORS FURNISHED BY FIRE ALARM CONTRACTOR IN BUILDINGS WITH
FIRE ALARM SYSTEMS.
FURNISH AND INSTALL DUCT SMOKE DETECTORS IN BUILDINGS WITHOUT FIRE ALARM SYSTEMS.
FURNISH AND INSTALL ALL CONTROL CONDUCTORS AND CONDUIT CONNECTING DUCT SMOKE
DETECTORS TO SMOKE DAMPERS AND FAN START CONTROLS.
ALL ELECTRICAL WORK PERFORMED UNDER DIVISION 23 SHALL CONFORM TO THE REQUIREMENTS
OF DIVISION 26.
a.
b.
c.
d.
e.
f.
g.
TIME OF DAY.
ACTUAL ROOM TEMPERATURE.
PROGRAMMED TEMPERATURE.
PROGRAMMED TIME.
DURATION OF TIMED OVERRIDE.
DAY OF WEEK.
SYSTEM MODE INDICATIONS INCLUDE "HEATING," "OFF," "FAN AUTO," AND "FAN ON."
B. THERMOSTAT COVER CONSTRUCTION: HEAVY-DUTY, LOCKING THERMOSTAT GUARD, OF SOLID METAL
TAMPERPROOF CONSTRUCTION.
B. MECHANICAL JOINTS ON REFRIGERANT PIPING SYSTEMS ARE PROHIBITED. ALL REFRIGERANT PIPING
JOINTS SHALL BE BRAZED. USE LEAD-FREE, SILVER SOLDER, MINIMUM 15% SILVER CONTENT.
C. PIPE FITTINGS SHALL BE WROUGHT-COPPER WITH SOLDERED JOINTS, ASME B16.22.
D. FLEXIBLE CONNECTIONS SHALL BE BRONZE, DOUBLE BRAIDED, SWEAT SOLDER ENDS.
E. MOISTURE/LIQUID INDICATORS (SIGHT GLASSES) SHALL BE COLOR CHANGE MOISTURE INDICATION
TYPE, REPLACEABLE ELEMENT, FILTER SCREEN AND PAD, SWEAT SOLDER ENDS; SPORLAN “SEE-ALL”,
HENRY, OR EQUAL.
C. ACCURACY: PLUS OR MINUS 0.5 DEG. F AT CALIBRATION POINT.
F.
D. WIRE: TWISTED, SHIELDED-PAIR CABLE.
CHARGING AND PURGE VALVES SHALL BE FORGED BRASS, DIAPHRAGM PACKLESS, GLOBE TYPE,
ANGLE OR STRAIGHT THROUGH, ONE END SOLDER, ONE END FLARE; HENRY 623 AND 643 SERIES,
SPORLAN OR EQUAL.
E. CONTRACTOR SHALL FIELD VERIFY DIMENSIONS PRIOR TO ORDERING FAN AND CURB ADAPTOR.
2.3 DUCTWORK
B. INTERIOR DUCT LINER
1.
APPLY TO THE INSIDE FACE OF DUCTS, COATED SIDE FACING AIR STREAM, FASTEN USING FIRE
RETARDANT ADHESIVE MEETING ASTM C 9169, AND SECURE WITH MECHANICAL LINER FASTENERS
AT 24” MAXIMUM O.C., BOTH DIRECTIONS. PIN LENGTH SHOULD BE SUCH AS TO LIMIT COMPRESSION
OF LINER.
2.
EXPOSED EDGES MUST BE FACTORY OR FIELD COATED. FOR SYSTEMS OPERATING AT 4000 FPM OR
HIGHER, A METAL NOSING MUST BE INSTALLED ON ALL LINER LEADING EDGES. INSULATION WITH
TORN OR BROKEN COATINGS SHALL BE REMOVED OR REPLACED. LOOSE CORNERS, EDGES, AND
BUTT JOINTS WILL NOT BE ACCEPTED.
G. SOLENOID VALVES SHALL BE FORGED BRASS, EXTENDED END CONNECTIONS, SOLDER ENDS, MOLDED
COIL; SPORLAN “E” SERIES OR EQUAL. COMPLY WITH ARI 760 & UL 429.
D. DIVISION 26 RESPONSIBILITIES
A. SHEET METAL DUCTWORK - RECTANGULAR
1.
2.
3.
4.
5.
FURNISH AND INSTALL ALL RACEWAYS, CONDUIT, DISCONNECT SWITCHES, AND CONDUCTORS
NECESSARY FOR ELECTRICAL POWER SUPPLY.
MAKE ALL POWER SUPPLY TERMINATIONS TO MOTORS, STARTERS, DISCONNECT SWITCHES,
CONTROL TRANSFORMERS, AND OTHER MECHANICAL DEVICES.
FIRE ALARM CONTRACTOR TO FURNISH DUCT SMOKE DETECTORS IN BUILDINGS WITH FIRE ALARM
SYSTEMS.
PROVIDE POWER TO ALL DUCT SMOKE DETECTORS AND SMOKE DAMPERS.
COORDINATE ALL WORK WITH MECHANICAL CONTRACTORS.
1.6 AS-BUILT DRAWINGS
1.
2.
A. A COMPLETE SET OF CONTRACT DRAWINGS SHALL BE MAINTAINED AT THE WORK SITE, AND ALL
CHANGES IN THE WORK SHALL BE RECORDED ON THIS SET, ON A DAILY BASIS. THE FINAL AS-BUILT
DRAWINGS SHALL BE SUBMITTED TO THE ARCHITECT FOR APPROVAL.
1.7 DESIGN DRAWINGS
A. THE DRAWINGS INDICATE DIAGRAMMATICALLY THE GENERAL LAYOUT OF THE MECHANICAL SYSTEMS
AND OTHER RELATED WORK. FIELD VERIFICATION OF SCALED DIMENSIONS TAKEN FROM THE
DRAWINGS IS REQUIRED.
B. THE CONTRACTOR SHALL REVIEW AND COMPARE THE ARCHITECTURAL, STRUCTURAL, PLUMBING,
MECHANICAL, AND ELECTRICAL DRAWINGS AND ALL OWNER SUPPLIED EQUIPMENT DRAWINGS, AND
ADJUST THEIR WORK TO BE IN CONFORMITY WITH THE CONDITIONS INDICATED THEREON.
DISCREPANCIES BETWEEN DRAWINGS, BETWEEN DRAWINGS AND ACTUAL FIELD CONDITIONS, OR
BETWEEN DRAWINGS AND SPECIFICATIONS, SHALL PROMPTLY BE BROUGHT TO THE ATTENTION OF
THE ARCHITECT FOR A DETERMINATION OF THE MODIFICATIONS TO BE EFFECTED. IN THE EVENT THAT
A MAJOR MODIFICATION IS REQUIRED, A CHANGE ORDER WILL BE PREPARED.
1.8 OPERATING AND MAINTENANCE INSTRUCTIONS
A. FURNISH THREE SETS OF TYPEWRITTEN INSTRUCTIONS COVERING MAINTENANCE, ADJUSTMENT, AND
OPERATION OF EACH PIECE OF APPARATUS, BOUND IN A HARD COVER LOOSE-LEAF BINDER. NEATLY
OBSCURE OR CROSS OUT INAPPLICABLE DATA FROM MANUFACTURER’S LITERATURE. SUBMIT DATA TO
THE ARCHITECT.
B. OPERATING INSTRUCTIONS SHALL SHOW SEQUENCE OF OPERATIONS, LUBRICATION, CARE, AND
MAINTENANCE REQUIREMENTS OF ALL EQUIPMENT. FINAL ACCEPTANCE OF THE WORK WILL NOT BE
MADE UNTIL A SATISFACTORY SUBMISSION OF THIS MATERIAL IS RECEIVED AND APPROVED BY THE
ARCHITECT.
C. THE OWNER’S AUTHORIZED REPRESENTATIVE SHALL BE INSTRUCTED IN THE OPERATION AND
SERVICING OF ALL HVAC & PLUMBING SYSTEMS.
1.9 ACCURACY OF DATA
A. THE DATA GIVEN HEREIN AND ON THE DRAWINGS ARE AS EXACT AS COULD BE REASONABLY SECURED,
BUT ABSOLUTE ACCURACY IS NOT GUARANTEED. EXACT LOCATIONS, DISTANCES, ELEVATIONS, ETC.
WILL BE GOVERNED BY SHOP DRAWINGS, THE BUILDING ITSELF, AND ACTUAL FIELD CONDITIONS.
3.
DUCTS AND PLENUMS SHALL BE FABRICATED AND INSTALLED IN CONFORMANCE WITH THE LATEST
EDITIONS OF: NFPA PAMPHLET NO. 90A; CALIFORNIA BUILDING CODE; CALIFORNIA MECHANICAL
CODE AND THE SMACNA HVAC DUCT CONSTRUCTION STANDARDS (METAL AND FLEXIBLE). DUCTS
AND PLENUMS SHALL BE CONSTRUCTED OF HOT DIPPED GALVANIZED MILD STEEL AND SHALL HAVE
AIRTIGHT CLASS “B” SEALS AT ALL TRANSVERSE JOINTS AND LONGITUDINAL SEAMS. TABLES AND
FIGURES HEREINAFTER REFERENCED ARE FROM THE 2005 EDITION OF THE SMACNA HVAC DUCT
CONSTRUCTION STANDARDS (METAL AND FLEXIBLE).
RECTANGULAR DUCT CONSTRUCTION SHALL CONFORM TO TABLE 2-3. ALL TRANSVERSE JOINTS
SHALL BE FLANGED PER TABLE 2-32, WITH CORNER CLOSURES OR “DUCT MATE” FLANGED
CONNECTIONS WITH CORNER CLOSURES PER FIGURE 2-17. ELBOWS SHALL BE STANDARD RADIUS
(TYPE RE 1) OR SQUARE THROAT WITH VANES (TYPE RE 2) PER FIGURE 4-2, WITH DOUBLE
THICKNESS TURNING VANES PER FIGURES 4-3 AND 4-4. OFFSETS AND TRANSITIONS SHALL BE PER
FIGURE 4-7. SUPPLY, RETURN, AND EXHAUST BRANCH CONNECTIONS SHALL BE PER FIGURE 4-5 OR
4-6. SPLITTERS SHALL NOT BE USED.
LINED DUCTS SHALL BE FABRICATED SUCH THAT THE NET INSIDE DIMENSIONS EQUALS THE DUCT
SIZES SHOWN ON THE DRAWINGS.
B. SHEET METAL DUCTWORK – ROUND DUCTS SHALL BE SPIRAL, UNITED MCGILL OR EQUAL. ALL
TRANSVERSE JOINTS AND LONGITUDINAL SEAMS SHALL HAVE CLASS “B” SEALS. ALL BRANCHES IN
ROUND DUCT SYSTEMS SHALL BE MADE WITH FACTORY FABRICATED REDUCING WYE BRANCHES.
DUCT TURNS SHALL BE MADE WITH STANDARD, FACTORY FABRICATED, THREE-PIECE ELBOWS.
C. FLEXIBLE DUCTWORK – FLEXIBLE DUCTS SHALL BE FLEXMASTER “8M” OR APPROVED EQUAL. FLEXIBLE
DUCTS SHALL BE USED ONLY WHERE SHOWN ON THE DRAWINGS, AND MAXIMUM LENGTH OF ANY
GIVEN FLEXIBLE DUCT SHALL NOT EXCEED 5 FT. GALVANIZED SHEET METAL ELBOWS SHALL BE USED
FOR TURNS GREATER THE 45° ON FLEXIBLE DUCTS 10” AND LARGER. CONNECTIONS TO RECTANGULAR
DUCTS SHALL BE MADE WITH “SPIN-IN” FITTINGS WITH AIR SCOOPS. THE INSTALLATION OF FLEXIBLE
DUCTS SHALL CONFORM TO FIGURE 3-10, WITH THE EXCEPTIONS NOTED HEREIN.
D. SUPPORTS – SUPPORTS FOR HORIZONTAL DUCTS AND PLENUMS SHALL BE FABRICATED PER FIGURES
5-5 AND 5-6 AND TABLES 5-1, 5-2, AND 5-3. THE MAXIMUM DISTANCE BETWEEN HANGERS SHALL BE
EIGHT FEET FOR RECTANGULAR DUCTS AND TWELVE FEET FOR ROUND DUCTS. ATTACHMENTS TO
THE STRUCTURE SHALL BE MADE WITH ADEQUATELY SIZED LAG BOLTS FOR STRAPHANGERS AND
ADEQUATELY SIZED MACHINE BOLTS AND SIDE BEAM BRACKETS FOR ROD HANGERS. SUPPORTS FOR
VERTICAL DUCTS SHALL BE BAND IRON STRAP OR ANGLE BRACKET TYPE PER FIGURE 5-8 AND 5-9.
E. DUCT ACCESS DOORS: INCLUDING THOSE FOR REMOVING FILTERS, DUCT ACCESS DOORS SHALL BE
AS DETAILED IN FIGURE 7-2 WITH SASH LOCKS, PIANO HINGES, AND GASKETS. ACCESS DOORS SHALL
HAVE AN UNOBSTRUCTED FULL SWING.
67 WALNUT WAY
PO BOX 1567
WILLOW CREEK, CA 95573
P:(530)629-3000
F:(530)629-3011
DWN BY DES BY CHK BY APP BY
NATIONAL FIRE PROTECTION ASSOCIATION.
CALIFORNIA MECHANICAL CODE.
CALIFORNIA PLUMBING CODE.
UNDERWRITERS LABORATORIES.
TITLES 8, 17, 19, 21, 24 OF THE CALIFORNIA CODE OF REGULATIONS.
CALIFORNIA ELECTRIC CODE.
SMACNA STANDARDS.
ASHRAE STANDARDS 55 AND 62.1.
WARRANTIES
2.
A. EQUIPMENT SHALL OPERATE QUIETLY AND WITHOUT OBJECTIONABLE VIBRATION. SUCH PROBLEMS,
OTHER THAN FROM EQUIPMENT OPERATING AT OPTIMUM CONDITIONS, SHALL BE THE CONTRACTOR’S
RESPONSIBILITY AND SHALL BE ELIMINATED AT THE DIRECTION OF THE ARCHITECT.
DESCRIPTION
1.
2.
3.
4.
5.
6.
7.
8.
1.11
DURO-DYNE “METAL-FAB” WITH DUROION, VENTFABRICS “VENTGLASS,” OR APPROVED EQUAL.
DATE
A. ALL WORK SHALL BE DONE IN CODE WITH ALL APPLICABLE LOCAL, STATE, AND FEDERAL BUILDING
SAFETY CODES, ORDINANCES, AND REGULATIONS. ADDITIONALLY, ALL WORK SHALL CONFORM TO THE
LATEST EDITIONS OF THE FOLLOWING STANDARDS:
1.
3.2 EQUIPMENT, GENERAL REQUIREMENTS
REV
1.2 CODES AND STANDARDS
A. FLEXIBLE DUCT CONNECTIONS
H. FILTER DRIERS SHALL BE REPLACEABLE MEDIA, ANGLE TYPE; HENRY “DRI-COR” OR EQUAL; ARI 730.
I.
THERMSOTATIC EXPANSION VALVES SHALL HAVE FORGED BRASS BODY, STAINLESS STEEL SEATS AND
PINS, ODF SOLDER CONNECTIONS, EXTERNAL EQUALIZER,; ARI 750.
J.
OUTDOOR CONDENSING UNITS SHALL HAVE A FLEXIBLE PIPING SECTION AT THE OUTDOOR UNIT.
A. REFRIGERANT PIPING
2.7 ACCESS PANELS
1.
A. WHERE CONSTRUCTION IS NOT INHERENTLY ACCESSIBLE, PROVIDE ADEQUATELY SIZED AND
CONVENIENTLY LOCATED ACCESS DOORS IN CEILINGS, WALLS, AND FURRING FOR SERVICING VALVES,
EQUIPMENT, ETC. DOORS SHALL BE DELIVERED TO THE GENERAL CONTRACTOR FOR INSTALLATION.
B. FIRE RATED: INRYCO/MILCOR, U.L. LISTED, “B” LABEL, 1 ½ HOUR RATING. MINIMUM SIZE SHALL BE 12” X
12”. PROVIDE LARGER SIZES WHERE REQUIRED. LOCKS SHALL BE FLUSH SCREWDRIVER OPERATED.
C. DRYWALLED SURFACES: INRYCO/MILCOR, STYLE DW, PRIME COATED STEEL. MINIMUM SIZE SHALL BE
12” X 12”. PROVIDE LARGER SIZES WHERE REQUIRED. LOCKS SHALL BE FLUSH SCREWDRIVER
OPERATED.
D. CONCRETE AND TILED SURFACES: INRYCO/MILCOR, STYLE M, PRIME COATED STEEL, EXCEPT ACCESS
PANELS INSTALLED IN TILED SURFACES SHALL BE STAIN FINISH STAINLESS STEEL. MINIMUM SIZE
SHALL BE 12” X 12”. PROVIDE LARGER SIZES WHERE REQUIRED. LOCKS SHALL BE FLUSH
SCREWDRIVER OPERATED.
E. PLASTERED SURFACES: INRYCO/MILCOR, STYLE K, PRIME COATED STEEL. MINIMUM SIZE SHALL BE 12”
X 12”. PROVIDE LARGER SIZES WHERE REQUIRED. LOCKS SHALL BE FLUSH SCREWDRIVER OPERATED.
PART 3 – EXECUTION
THE INSULATION SHALL BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER’S
INSTRUCTIONS. ALL JOINTS AND SEAMS SHALL BE SEALED WITH WATERPROOF VAPOR RETARDANT
ADHESIVE. ALL PIPES EXPOSED TO THE WEATHER SHALL BE COATED WITH ALUMINUM JACKETING
TO PROTECT THE INSULATION FROM ULTRA-VIOLET RADIATION IN ACCORDANCE WITH THE
MANUFACTURER’S PUBLISHED INSTRUCTIONS.
3.6 TEST, INSPECTIONS
A. MAKE ALL NECESSARY CONTROL ADJUSTMENTS AND BALANCING OF AIR AND WATER FLOWS.
OPERATE THE ENTIRE SYSTEM FOR A PERIOD OF TIME NOT LESS THAN THREE (3) WORKING DAYS FOR
THE PURPOSE OF PROVING SATISFACTORY PERFORMANCE. DURING THIS PERIOD, INSTRUCT SUCH
PERSONS AS THE OWNER AND/OR ARCHITECT MAY DESIGNATE IN THE PROPER OPERATION OF THE
SYSTEMS. SHOULD FURTHER ADJUSTMENT PROVE NECESSARY, OPERATING TESTS SHALL BE
REPEATED UNTIL A SATISFACTORY TEST IS OBTAINED.
B. THIS CONTRACTOR SHALL NOT ALLOW OR CAUSE ANY WORK OF THIS SECTION TO BE COVERED OR
ENCLOSED UNTIL IT HAS BEEN INSPECTED, TESTED, AND APPROVED BY THE ARCHITECT AND THE
AUTHORITIES HAVING JURISDICTION OVER THE WORK. SHOULD ANY OF THIS WORK BE ENCLOSED OR
COVERED UP BEFORE SUCH INSPECTION, TESTING, AND APPROVAL, THIS CONTRACTOR SHALL
UNCOVER THE WORK, HAVE THE NECESSARY INSPECTIONS, TESTS, AND APPROVALS MADE AND, AT NO
EXPENSE TO THE OWNER, MAKE ALL REPAIRS NECESSARY TO RESTORE BOTH HIS WORK AND THAT OF
OTHER CONTRACTORS WHICH MAY HAVE BEEN DAMAGED TO BE IN CONFORMITY WITH THE CONTRACT
DOCUMENTS.
3.1 EQUIPMENT STARTUP
A. NOTIFY THE OWNER’S REPRESENTATIVE A MINIMUM OF TWO WEEKS PRIOR TO EQUIPMENT STARTUP
DATE TO ALLOW FOR OWNER’S PERSONNEL TO BE PRESENT DURING STARTUP.
B. MANUFACTURER MUST PROVIDE A SERVICE TECHNICIAN TO SUPERVISE RIGGING OF THE UNITS TO
ENSURE PROPER FIT.
DATE OF ISSUE:
C. UNIT MUST BE CHECKED OUT, TESTED AND PLACED INTO OPERATION BY THE INSTALLING
CONTRACTOR UNDER THE SUPERVISION OF AN AUTHORIZED REPRESENTATIVE OF THE FACTORY.
D. DURING STARTUP, THE FULL FUNCTIONALITY OF THE EQUIPMENT SHALL BE DEMONSTRATED TO THE
SATISFACTION OF THE OWNER’S REPRESENTATIVE, INCLUDING HEATING, MECHANICAL COOLING,
ECONOMIZER COOLING, ZONE MODULATION, AND ALL EMERGENCY SHUTDOWN FEATURES.
7/12/2023
SCALE:
PROJECT NO:
427.11
DRAWING NO:
M1.1
1/2"
1"
2"
HUMBOLDT COUNTY, CALIFORNIA
A. THIS SECTION COVERS MECHANICAL WORK, COMPLETE. WORK INCLUDES FURNISHING, INSTALLING,
CALIBRATING, ADJUSTING, TESTING, DOCUMENTING, AND STARTING UP EQUIPMENT IN ACCORDANCE
WITH THESE SPECIFICATIONS, THE ACCOMPANYING PLANS, AND THE DIRECTIONS OF THE ENGINEER.
A. CONTRACTOR SHALL BE RESPONSIBLE FOR DELIVERY, STORAGE, PROTECTION, AND PLACING OF ALL
EQUIPMENT AND MATERIALS. CONTRACTOR SHALL PROTECT THE WORK AND MATERIALS FROM
DAMAGE DURING CONSTRUCTION. EQUIPMENT STORED AT THE JOB SITE SHALL BE PROTECTED FROM
DUST, WATER, OR OTHER DAMAGE, AND BE COVERED IF EQUIPMENT IS EXPOSED TO WEATHER.
PROTECT INTERIORS OF NEW EQUIPMENT AND PIPING SYSTEMS AGAINST ENTRY OF FOREIGN MATTER.
CLEAN BOTH INSIDE AND OUTSIDE BEFORE PAINTING OR PLACING EQUIPMENT IN OPERATION. ANY
ITEMS DAMAGED SHALL BE REPAIRED OR REPLACED, AT NO ADDITIONAL COST TO THE OWNER.
2.4 DUCTWORK ACCESSORIES
MECHANICAL SPECIFICATIONS
1.1 INCLUDED
DELIVERY, STORAGE, AND HANDLING
TRINIDAD RANCHERIA
INTERPRETIVE CENTER
TRINIDAD, CA. 95570
1.10
PART 1 – GENERAL
TRINITY VALLEY CONSULTING ENGINEERS, INC.
KEYED NOTES:
TVCE
1 MOUNT THERMOSTAT 48" ABOVER FINISHED
FLOOR. COORDINATE FINAL LOCATION WITH
OWNER.
67 WALNUT WAY
PO BOX 1567
WILLOW CREEK, CA 95573
P:(530)629-3000
F:(530)629-3011
L-1
DWN BY DES BY CHK BY APP BY
A
12"ø OA
115 CFM
1
115 CFM
8"ø RA
12"ø OA ABV.
14"ø RA BLW.
2
675 CFM
14"ø RA
ACCESS DOOR,
SEE ARCH DWG
8"ø SA
A
RL/RS ABC
1-1
A
AHU-1
160 CFM
1
M3.0
DESCRIPTION
210 CFM
2
M3.0
HP-1
16"ø SA
10"ø SA
10"ø SA
RL/RS UIW
10"ø SA
A
T
AHU-1 1
220 CFM
ST
REV
DATE
10"ø SA
1
ST
330 CFM
10"ø SA
A
210 CFM
6"ø SA
A
205 CFM
8"ø SA
6"ø SA
CBD
55 CFM
L-2
1
M2.0
MECHANICAL FLOOR PLAN
B
6"ø EA
TRINIDAD RANCHERIA
INTERPRETIVE CENTER
TRINIDAD, CA. 95570
EF-1
MECHANICAL FLOOR PLAN
1/4" = 1'-0"
DATE OF ISSUE:
7/12/2023
SCALE:
1/4" = 1'-0"
PROJECT NO:
427.11
DRAWING NO:
M2.0
1/2"
1"
2"
HUMBOLDT COUNTY, CALIFORNIA
TR
A
3
M3.0 45 CFM
ST
TR
10"x8" RELIEF AIR
TRINITY VALLEY CONSULTING ENGINEERS, INC.
TVCE
TABLE 1
AIRFLOW
(MAX)
FILTER
EFFICIENCY
FILTER
SIZE
FILTER
DEPTH
INITIAL P.D.
(INCHES W.G.)
1,200
MERV 13
20/20
4"
0.14
TRUSS TOP CHORD, SEE STRUCTURAL
1-1/2" x 1-1/2" x 4" STL ANGLE
W/ (2) 3/8 THRU BOLTS
2 x 6 BLOCKING & SIMPSON LB26
HANGERS BETWEEN TRUSS, TYP.
2-3/4" MIN.
O.A. DUCT, SEE
PLANS FOR SIZES
2-POSITION OR MODULATING
MOTORIZED DAMPER
67 WALNUT WAY
PO BOX 1567
WILLOW CREEK, CA 95573
P:(530)629-3000
F:(530)629-3011
1/8"Ø AIRCRAFT CABLE LEAVE
1/2" SLACK AT CENTER OF CABLE
SPRING ISOLATOR HANGER, TYP. 4,
MASON 30N SIZED FOR 30% UNIT
WEIGHT. COLA# RR24589
TRUSS TOP CHORD, SEE
STRUCTURAL
HONEYWELL F200 MEDIA AIR
CLEANER WITH 20/20 MERV
13 FILTER MODEL F200F2020
3/8"Ø EYE BOLT W/ FLAT WASHER
EA. SIDE (CENTERED ON BLOCK)
NAIL PLYWOOD TO BLOCKING PER
STRUCTURAL PLAN REQUIREMENTS
2-CABLE CLAMPS
EA. END, TYP.
3/8" ALL-THREAD
AIRCRAFT CABLE
RL/RS PIPING
AHU
1" x 3/16" BENT PLATE
W/ 3/16"Ø HOLE
#10 SMS, 2 PER ANGLE
HEAT PUMP
2" X 2" X 3/16" ANGLE
DWN BY DES BY CHK BY APP BY
1/4 - 14 SELF DRILLING SCREWS AT EACH CORNER
6" MIN
190 LBS.
MAX
(N) CONRETE PAD, 6" HEIGHT
R.A. DUCT
SA DUCT
CD
GALVANIZED L1-1/2" x 1-1/2" x 1/8"
THICK. 2" MINIMUM LENGTH AT 4
CORNERS
OVERFLOW PAN
#4 REBAR @ 12" O.C., EACH WAY
PLAN VIEW
3/4" C.D. TO MOP SINK
M3.0
LATERAL BRACING,
TYP
SUPPLY PLENIUM
CDO
3/4" OVERFLOW TO EAVE
2
EQUIPMENT
AIR HANDLING UNIT HANGING DETAIL
NOT TO SCALE
TYPICAL FOR HP-1
1
M3.0
HEAT PUMP DETAIL
NOT TO SCALE
DESCRIPTION
RETURN PLENUM
B-LINE B24 1-5/8" STEEL CHANNEL
3/8"Ø HILTI KB-TZ2 AT EACH CORNER 2"
MINIMUM EMBEDMENT AT 4 CORNERS
200 LBS
#7 x 1/2" SM SCREWS MIN. 4" O.C.,
TAPE WITH 2" HARD CAST TAPE
INTEGRAL BACK DRAFT DAMPER
WOOD FRAMING
22 GA x 2" WIDE
GALVANIZED SHEET
METAL STRAP
#10 SHEET
METAL SCREW
#10 x 1/2" WOOD
SCREWS TYP. 2
SQUARE TO ROUND GALVIZED
SHEET METAL TRANSITION
ROUND GALVIZED SHEET METAL DUCT TO
L-2, SEE MECHANICAL PLAN FOR SIZE
CEILING MOUNTED EXHAUSTFAN
ADJUSTABLE MOUNTING FLANGE ON EACH
SIDE, FURNISHED WITH EXHAUST FAN
1/4"Ø x 1-1/2" LAG SCREW INTO EACH
WOOD FRAMING OR BLOCKING
DATE
#10 x 1/2" WOOD
SCREWS TYP. 2
2X WOOD FRAMING OR BLOCKING
GALVANIZED SHEET
METAL DUCT
GYPSUM BOARD CEILING
4
NOT TO SCALE
LESS THAN 18"Ø
GRILLE BUTTON FUSNISHED WITH FAN
3
M3.0
CEILING EXHAUST FAN DETAIL
NOT TO SCALE
TRINIDAD RANCHERIA
INTERPRETIVE CENTER
TRINIDAD, CA. 95570
M3.0
DUCT HANGING DETAILS
MOLDED WHITE PLASTIC GRILLE
FURNISHED WITH EXHAUST FAN
DATE OF ISSUE:
7/12/2023
SCALE:
1/8" = 1'-0"
PROJECT NO:
427.11
DRAWING NO:
M3.0
1/2"
1"
2"
HUMBOLDT COUNTY, CALIFORNIA
LESS THAN 32"
SPIRAL SHEET
METAL DUCT
MECHANICAL DETAILS
1" MIN.
REV
22 GA x 2" WIDE
GALVANIZED SHEET
METAL STRAP
TRINITY VALLEY CONSULTING ENGINEERS, INC.
PLUMBING FIXTURE SCHEDULE
ABBREVIATIONS
ABC
BFP
WASTE
& VENT
ABOVE CEILING
BACKFLOW PREVENTER
GREASE
WASTE & VENT
Location
Size
INTERIOR, AFF
Material
Notes
Model No.
K-3999
Description
ACCESSIBLE GRAVITY TANK WATER CLOSET, 1.28 GPF,
CONFORT HEIGHT, ELONGATED BOWL, WITH KOHLER
K-4731-SC-0 OPEN TOILET SEAT, RIGHT HAND OR LEFT HAND
TRIP LEVER
DIMENSIONS: 29-3/4" x 18" x 31-1/4"
Mounting
FLOOR
Material
VIT CHINA
L-1
KOHLER
K-2005
WALL HUNG LAVATORY WITH OVERFLOW, HOT/COLD WATER
HOLES 4" O.C. CHICAGO FAUCETS 420-T45E2805ABCP ASSE
1070 LISTED THERMOSTATIC MIXING FAUCET, 0.50 GPM
AERATOR, CHROME PLATE FINISH, J.R. SMITH CONCEALED
ARM SUPPORT, CHICAGO 1013-ABCP ANGLE STOPS,
PRE-FABRICATED CLOESED CELL VINYL INSULATE SAFETY
COVER OVER TRAP AND WATER PIPING.
DIMENSIONS: 20" x 18"
WALL
VIT CHINA
STANDARD WEIGHT HUBLESS CAST IRON
ALL
SLOPED AT 1/4" PER FOOT
INTERIOR, BELOW SLAB
STANDARD WEIGHT HUBLESS CAST IRON
INTERIOR, AFF
SCHEDULE 40 PCV-DWV
ALL
INTERIOR, BELOW SLAB
SLOPED AT 1/4" PER FOOT
SCHEDULE 40 PCV-DWV
BALL VALVE
BG
BELOW GRADE
BS
BELOW SLAB
CHECK VALVE
INTERIOR, ABOVE GROUND
ALL
TYPE "L" COPPER
INTERIOR, BELOW SLAB
ALL
TYPE "K" COPPER
AIR CONDITIONING
CONDENSATE
ALL
TYPE M - HARD TEMPER COPPER
CW / HW
COND. DRAIN
67 WALNUT WAY
PO BOX 1567
WILLOW CREEK, CA 95573
P:(530)629-3000
F:(530)629-3011
TP-1
PPP
LTP-500
1-1/2" TAIL PIECE FLOOR DRAIN TRAP PRIMING ASSEMBLY,
1/2" BRAIDED STAINLESS STEEL PRIMING WATER LINE WITH
1/2" COMPRESSION FITTINGS, CHROME-PLATED
ESCUTCHEONS FOR BOTH WALL TUBE AND MAKE UP WATER
LINE.
UNDER SINK
BRASS
TMV-1
ZURN
1070XL
ASSE 1070 LISTED THERMOSTATIC MIXING VALVE. 0.35GPM
ACTIVATION FLOW. 110°F OUTLET TEMPERATURE. WAX
BASED THERMOSTATIC MOTOR DESIGN. MOUNT AT ALL
KITCHEN HANDWASHING FIXTURES. FIXTURES TO BE
SPECIFIED BY OWNER.
UNDER SINK
BRASS
2" NPT CONNECTION, 5" NICKEL BRONZE ADJUSTABLE
STRAINER HEAD, TRAP PRIMER CONNECTION.
CAST IRON FLOOR SINK WITH 12" SQUARE TOP, 6" DEEP. ACID
RESISTANT COATED INTERIOR, LOOSE SET ACID RESISTENCE
COATED CAST IRON 1/2 GRATE, AND ALUMINUM DOME
BOTTOM STRAINER. 3" WASTE CONNECTION.
ELECTRIC WATER HEATER, 40 GALLON STORAGE CAPACITY,
41 GPH AT 90°F RISE, 140°F TEMPERATURE SETTING.
ELECTRICAL 240V/1-PHASE, DUAL SIMULTANEOUS 4.5kW
ELEMENTS.
DIMENSIONS: 32-1/4"H x 24"ø W.
125 LBS EMPTY, 450 LBS FULL.
FLOOR
BRONZE
FLOOR
CAST IRON
ABOVE
CEILING
GLASS LINED STEEL
SLOPED AT 1/8" PER FOOT
CW
COLD WATER SUPPLY
CD
CONDENSATE DRAIN
CDO
CONDENSATE DRAIN OVERFLOW
FD-1
JR SMITH
2005Y
CONNECTION TO BOTTOM OF PIPE
FS-1
JR SMITH
3420Y-12
WH-1
AO SMITH
DEL 40
ET-1
AMTROL
ST-5-C
4.0 GALLON STAINLESS STEEL EXPANSION TANK, 200°F
MAXIMUM OPERATING TEMP, 150 PSIG MAX WORKING
PRESSURE, POLYPROPYLENE LINER, SHEEL CONSTRUCTED
OF POWDER COATED STEEL.
DIMENSIONS: 15-1/2" H, 14-1/4" DIAMETER
WEIGHT: 35 LBS EMPTY, 85 LBS FULL
WALL
STEEL
RCP-1
B&G
E3-6V/BURPZ
OPEN SYSTEM RECIRCULATION PUMP. 230°F MAX TEMP. 36°F
MIN TEMP. 150 PSI MAX SYSTEM PRESSURE. ADJUSTABLE
THERMOSTAT. 1/2" LEAD-FREE BRASS UNION CONNECTIONS.
E3 TIMER AND HIGH EFFICIENCY ECM MOTOR.
ELECTRICAL: 115/1/60
PIPE
BRASS
BFP-1
WATTS
SD3
--
STAINLESS STEEL
HB-1
JR SMITH
5619
DUAL CHECK VALVES BACKFLOW PREVENTER, W/
ATMOSPHERIC VENT, LEAD FREE.
1/4 TURN NON-FREEZE WALL HYDRANT, AUTOMATIC
DRAINING, STAINLESS STEEL FACE, INTEGRAL VACUUM
BREAKER AND DUAL CHECK VALVE, "T" HANDLE KEY, 3/4" NPT
CONNECTION.MOUNTING HEIGHT: 54" A.F.F.
WALL
BRASS
CONNECTION TO TOP OF PIPE
D
DEMO
DOMESTIC COLD WATER
DOMESTIC HOT WATER
DN
DOWN
DIW
DOWN IN WALL
E, EX
EXISTING
FLANGE
FCO
FLOOR CLEAN OUT
FD
FLOOR DRAIN
FS
FLOOR SINK
GSM
GALVANIZED SHEET METAL
GCO
GRADE CLEAN OUT
GW
GREASE WASTE
HB
HOSE BIB
HW
HOT WATER SUPPLY
HWR
HOT WATER RECIRC
N
NEW
NEW CONNECTION TO EXISTING
OH
TVCE
DWN BY DES BY CHK BY APP BY
SYMBOLS
Service
Make
KOHLER
DESCRIPTION
PLUMBING LEGEND
ID
WC-1
PLUMBING FIXTURE CONNECTION SCHEDULE
ID
WC-1
L-1
FD-1
FS-1
Description
WATER CLOSET
LAVATORY
FLOOR DRAIN
FLOOR SINK
Accessible
YES
YES
---
Waste
3"
2"
2"
2"
Connection Size (Inches)
Vent
CW
2"
3/4
1-1/2"
1/2"
1-1/2"
1/2"
1-1/2"
--
HW
-1/2"
---
DATE
PIPING MATERIALS SCHEDULE
OVERHEAD
PIPE CAP
REV
PIPE TURNED DOWN
PIPE TURNED UP
PRESSURE GAUGE
PRESSURE REDUCING VALVE
P-TRAP
RELIEF VALVE
SOV
SHUT-OFF VALVE
SK
SINK
STRAINER
THERMOMETER
TMV
THERMOSTATIC VALVE
TP
TRAP PRIMER
TRIPLE DUTY VALVE
UG
UNDERGROUND
UNION
UIW
UP IN WALL
UR
URINAL
V
VENT
VTR
VENT TO ROOF
WC
WATER CLOSET
WHA
WATER HAMMER ARRESTER
WCO
WALL CLEANOUT
DATE OF ISSUE:
7/12/2023
SCALE:
1/8" = 1'-0"
PROJECT NO:
427.11
DRAWING NO:
P1.0
1/2"
1"
2"
HUMBOLDT COUNTY, CALIFORNIA
SANITARY SEWAGE (BELOW GRADE)
PLUMBING LEGEND AND SCHEDULES
SS
TRINIDAD RANCHERIA
INTERPRETIVE CENTER
TRINIDAD, CA. 95570
REMOVE TO THIS POINT
TRINITY VALLEY CONSULTING ENGINEERS, INC.
TVCE
PLUMBING SPECIFICATION
PART 2 – PRODUCTS
1.1 INCLUDED
2.1 PIPE AND FITTINGS
A. THIS SPECIFICATION ESTABLISHES THE REQUIRED STANDARDS FOR ALL LABOR, MATERIALS,
EQUIPMENT, AND WORKMANSHIP IN CONNECTION WITH THE FURNISHING, FABRICATION, AND
INSTALLATION OF “PLUMBING.”
1.2 CODES AND STANDARDS
A. ALL WORK SHALL BE DONE IN CODE WITH ALL APPLICABLE LOCAL, STATE, AND FEDERAL BUILDING
SAFETY CODES, ORDINANCES, AND REGULATIONS. ADDITIONALLY, ALL WORK SHALL CONFORM TO THE
LATEST EDITIONS OF THE FOLLOWING STANDARDS:
1.
2.
3.
4.
5.
6.
NATIONAL FIRE PROTECTION ASSOCIATION.
CALIFORNIA MECHANICAL CODE.
CALIFORNIA PLUMBING CODE.
UNDERWRITERS LABORATORIES.
TITLES 8, 17, 19, 21, 24 OF THE CALIFORNIA CODE OF REGULATIONS.
CALIFORNIA ELECTRIC CODE.
B. WHEN THE CONTRACT DOCUMENTS CALL FOR MATERIALS OR CONSTRUCTION OF A HIGHER STANDARD
THAN IS REQUIRED BY THE ABOVE, THE CONTRACT DOCUMENT REQUIREMENTS SHALL TAKE
PRECEDENCE OVER THE REQUIREMENTS OF THE APPLICABLE LAWS, ORDINANCES, RULES, OR
REGULATIONS. NOTHING IN THE CONTRACT DOCUMENTS SHALL BE INTERPRETED AS PERMITTING
WORK IN VIOLATION OF SAID LAWS, RULES, AND/OR REGULATIONS.
C. THE CONTRACTOR FOR THIS WORK SHALL FURNISH, WITHOUT EXTRA CHARGE, ANY ADDITIONAL
MATERIALS AND/OR LABOR AS MAY BE REQUIRED FOR COMPLIANCE WITH THESE LAWS, RULES,
AND/OR REGULATIONS THOUGH SUCH MATERIALS AND/OR LABOR ARE NOT SPECIALLY SET FORTH IN
THE CONTRACT DOCUMENTS.
A. SANITARY SOIL, WASTE, AND VENT PIPING, BELOW GROUND: LINES 2” AND LARGER SHALL BE SERVICE
WEIGHT, HUB-LESS CAST IRON SOIL PIPE AND FITTINGS, AND SHALL CONFORM TO THE REQUIREMENTS
OF ASTM A 888 AND CISPI STANDARD 301. APPROVED MANUFACTURERS: CHARLOTTE, TYLER, OR AB&I.
JOINTS: COUPLINGS SHALL CONFORM TO THE REQUIREMENTS OF ASTM C1540 AND SHALL BE HEAVY
DUTY TYPE 304 STAINLESS STEEL SHIELDED, HAVING 4 SEALING CLAMPS FOR PIPE SIZES 1 ½” THRU 4”,
AND 6 SEALING CLAMPS FOR PIPE SIZES 5” THRU 10”. GASKETS SHALL COMPLY WITH ASTM C-564.
ANACO, TYLER, OR EQUAL.
B. SANITARY SOIL, WASTE, AND VENT PIPING, ABOVE GROUND: LINES 2” AND LARGER SHALL BE
STANDARD WEIGHT, HUB-LESS CAST IRON SOIL PIPE AND FITTINGS, AND SHALL CONFORM TO THE
REQUIREMENTS OF ASTM A 888 AND CISPI STANDARD 301. APPROVED MANUFACTURERS: CHARLOTTE,
TYLER, OR AB&I. JOINTS: COUPLINGS SHALL CONFORM TO THE REQUIREMENTS OF ASTM C1540 AND
SHALL BE HEAVY DUTY TYPE 304 STAINLESS STEEL SHIELDED, HAVING 4 SEALING CLAMPS FOR PIPE
SIZES 1 ½” THRU 4:, AND 6 SEALING CLAMPS FOR PIPE SIZES 5” THRU 10”. GASKETS SHALL COMPLY
WITH ASTM C-564. ANACO, TYLER, OR EQUAL.
C. CONDENSATE PIPING: TYPE M, HARD TEMPER, COPPER WITH WROUGHT COPPER OR CAST BRASS
FITTINGS. JOINTS SHALL BE MADE UP WITH “STAY-SAFE 50” LEAD FREE SOLDER.
D. COLD AND HOT WATER PIPING: ALL DOMESTIC COLD WATER PIPING 3” AND SMALLER SHALL BE TYPE L,
HARD TEMPER, COPPER PIPE WITH WROUGHT COPPER OR CAST BRASS SOLDER JOINT FITTINGS. ALL
JOINTS SHALL BE MADE UP WITH “STAY-SAFE 50” LEAD FREE SOLDER. A SUITABLE NON-CORROSIVE
FLUX SHALL BE USED AT ALL JOINTS. PIPES BELOW GRADE INSIDE BUILDINGS SHALL BE SOFT DRAWN,
TYPE L OR K COPPER WITH NO JOINTS BELOW SLABS. PIPES SHALL BE INSTALLED IN A PVC CONDUIT
NOT LESS THAN SCHEDULE 40. THE INTERIOR DIAMETER OF THE CONDUIT SHALL NOT BE LESS THAN 1/2
INCH LARGER THAN THE OUTSIDE DIAMETER OF THE WATER PIPING.
2.2 UNIONS
2.7 PIPE INSULATION
3.5 INSTALLATION, PIPING
A. INSULATE ALL HOT WATER SUPPLY PIPING, ALL HOT WATER RETURN PIPING, ALL COLD WATER SUPPLY
PIPING IN EXTERIOR WALLS OR UNCONDITIONED SPACES WITH MANVILLE “MICRO-LOK” 650,
FIBERGLASS, CERTAINTEED, OR EQUAL, RIGID FIBERGLASS ONE-PIECE PIPE INSULATION WITH AND ALL
PURPOSE JACKET. JACKETS SHALL BE CONSTRUCTED OF HIGH DENSITY, WHITE KRAFT BONDED TO
ALUMINUM FOIL WITH FIBERGLASS YARN, WITH A PRESSURE SENSITIVE CLOSURE SYSTEM.
B. ALL INSULATION SHALL HAVE COMPOSITE (INSULATION, JACKET, AND ADHESIVE USED TO ADHERE THE
JACKET TO THE INSULATION) FIRE AND SMOKE HAZARD RATINGS AS TESTED UNDER PROCEDURE ASTM
E-84, NFPA 255 OR UL 723, NOT EXCEEDING: FLAME SPREAD – 25, SMOKE DEVELOPED – 50.
C. INSERTS SHALL BE INSTALLED AT OUTSIDE HANGERS. INSERTS BETWEEN THE PIPE AND PIPE
HANGERS SHALL CONSIST OF RIGID PIPE INSULATION OF THICKNESS EQUAL TO THE ADJOINING
INSULATION. INSERTS SHALL NOT BE LESS THAN 10” LONG FOR PIPE SIZES THROUGH 2 ½” AND NOT
LESS THAN 12” LONG FOR PIPES LARGER THAN 2 ½”.
D. METAL SHIELDS SHALL BE APPLIED BETWEEN HANGERS OR SUPPORTS AND THE PIPE INSULATION.
SHIELDS SHALL BE FORMED TO FIT THE INSULATION AND SHALL EXTEND UP TO THE CENTERLINE OF
THE PIPE AND THE LENGTH SPECIFIED FOR HANGER INSERTS.
A. CONDENSATE PIPING INDIRECT WASTE PIPING SHALL BE INSTALLED TO A UNIFORM MINIMUM GRADE OF
¼” PER FOOT UNLESS OTHERWISE NOTED. CHANGES IN DIRECTION OF INDIRECT WASTE PIPING SHALL
BE ACCOMPLISHED BY THE USE OF APPROPRIATE DRAINAGE FITTINGS.
B. FLASHING: ALL ROOF AND WALL PENETRATIONS SHALL BE FLASHED AND COUNTERFLASHED WATER
TIGHT WITH 26 GAUGE SHEET METAL, EXCEPT AS NOTED. VENTS THROUGH ROOF SHALL BE FLASHED
WITH SEMCO #1100-4 LEAD FLASHING ASSEMBLIES. FLASHING SHALL EXTEND OVER TOP OF PIPE AND
SHALL BE TURNED DOWN INSIDE TOP OF PIPE.
C. SOIL, WASTE, VENT, DRAIN PIPING: SOIL, WASTE, AND VENT PIPING OCCURRING WITHIN THE BUILDING
SHALL BE INSTALLED TO A UNIFORM MINIMUM GRADE OF ¼” PER FOOT UNLESS OTHERWISE NOTED.
VENT PIPING SHALL BE GRADED SO THAT ALL CONDENSATION SHALL FLOW DIRECTLY TO A SOIL OR
WASTE LINE. CHANGES IN DIRECTION OF DRAINAGE PIPING SHALL BE ACCOMPLISHED BY THE USE OF
APPROPRIATE DRAINAGE AND SANITARY FITTINGS. PROTECTION AGAINST BREAKAGE OF PIPING
PASSING UNDER OR THROUGH WALLS SHALL BE PROVIDED USING SPECIFIED SLEEVES AND CAULKING.
CLEANOUTS SHALL BE LOCATED WHERE INDICATED ON THE DRAWINGS; AT ALL HORIZONTAL OFFSETS;
AT ENDS OF WASTE OR SEWER BRANCHES MORE THE 5’ IN LENGTH; AT INTERVALS OF 100’ IN STRAIGHT
RUNS OF PIPING, OR AT CLOSER INTERVALS IF DIRECTED OR REQUIRED BY LOCAL CODE. LOCATION OF
CLEANOUTS IN FINISHED SPACES SHALL BE APPROVED BY THE ARCHITECT PRIOR TO INSTALLATION.
67 WALNUT WAY
PO BOX 1567
WILLOW CREEK, CA 95573
P:(530)629-3000
F:(530)629-3011
E. INSULATION THICKNESS SHALL BE AS FOLLOWS:
1.
2.
ALL PIPING 1” AND SMALLER:
ALL PIPING 1 ¼” AND LARGER:
1”
1 ½”
2.8 FIXTURES
A. THE QUANTITY AND LOCATION OF FIXTURES SHALL BE TAKEN FROM THE ARCHITECTURAL AND
PLUMBING DRAWINGS. PROVIDE ADEQUATE SUPPORTS AND ALL STANDARD TRIM NORMALLY
FURNISHED FOR FIXTURES. ALL ENAMEL SHALL BE ACID RESISTING. TRAPS, UNLESS OTHERWISE
NOTED SHALL BE 17 GAUGE BRASS TUBING, CHROME PLATED WHEN EXPOSED.
D. HOT AND COLD WATER SYSTEMS: DI-ELECTRIC UNIONS SHALL BE INSTALLED WHERE COPPER PIPE IS
CONNECTED TO GALVANIZED STEEL PIPING OR STUB OUTS. CONNECTIONS FROM COPPER PIPE TO
FIXTURE SUPPLY FITTINGS SHALL BE MADE WITH COPPER OR BRASS NIPPLES. ALL DOMESTIC WATER
PIPING SHALL BE KEPT CLEAR OF THE BUILDING STRUCTURE. WHERE IT IS WITHIN 1” OF THE BUILDING
STRUCTURE, IT SHALL BE WRAPPED WITH FELT (3/16” MINIMUM THICKNESS). TO THE GREATEST EXTENT
POSSIBLE, DOMESTIC COLD WATER PIPING SHALL BE KEPT SEPARATED FROM HOT PIPING AND WHERE
THERE IS A CHOICE SHALL BE RUN IN THE COOLEST PORTION OF THE AVAILABLE SPACE.
DWN BY DES BY CHK BY APP BY
PART 1 – GENERAL
E. PLUMBING FIXTURES: SPACE BETWEEN WALL MOUNTED FIXTURES AND WALL SURFACE SHALL BE
NEATLY POINTED UP WITH SILICONE RUBBER COMPOUND OF COLOR MATCHING FIXTURE.
1.3 COOPERATION WITH OTHER TRADES
A. STEEL PIPE UNIONS SHALL BE MALLEABLE IRON, 150LB., GROUND JOINT, GRINNELL FIG. 463.
A. COOPERATE FULLY WITH OTHER TRADES DOING WORK ON THE PROJECT AS MAY BE NECESSARY FOR
THE PROPER COMPLETION OF THE PROJECT. REFER TO THE STRUCTURAL, MECHANICAL, AND
ELECTRICAL DRAWINGS FOR DETAILS OF THE BUILDING STRUCTURE AND EQUIPMENT INSTALLATION
THAT WILL TEND TO OVERLAP, CONFLICT WITH OR REQUIRE COORDINATION WITH THE WORK OF THIS
SECTION, AND SCHEDULE THIS WORK ACCORDINGLY.
B. COPPER PIPE UNIONS SHALL BE SOLDERED JOINT, NIBCO SERIES 633 OR 733, MUELLER, OR EQUAL.
C. DIELECTRIC UNIONS SHALL BE EPCO OR EQUAL.
2.3 VALVES, SPECIALTIES
B. ANY WORK DONE WITHOUT REGARD FOR OTHER TRADES SHALL BE MOVED, REPLACED, OR REDONE
AS REQUIRED, WITHOUT EXTRA CHARGES TO OWNER.
B. EXCEPT AS OTHERWISE SHOWN, PROVIDE ¼” STEEL BACKING PLATES, 36” WIDE BY 12” HIGH MINIMUM
SIZE, SECURED TO A MINIMUM OF THREE STUDS BY WELDING, OR WITH ¼” X 2 ½” LAG SCREWS FOR
ALL WALL HUNG FIXTURES FOR WHICH NO OTHER MEANS OF SUPPORT IS SPECIFIED.
C. STOPS AND SUPPLIES: PROVIDE STOPS FOR ALL FIXTURES. UNLESS OTHERWISE SPECIFIED, STOPS
EXPOSED AT LAVATORIES AND SIMILAR FIXTURES SHALL BE CHICAGO #1016-ABCP, CHROME PLATED,
LOOSE KEY. CONCEALED STOPS SHALL BE CHICAGO #1771.
A. BALL VALVES, POTABLE WATER UP TO 2”: NIBCO T-585-80-LF, LEAD-FREE SILICON BRONZE BODY, “RING
BALL,” FULL PORT, TWO PIECE, LEVER HANDLE, 125 LB.
D. ALL FIXTURES SHALL MEET OR EXCEED THE REQUIREMENTS OF THE CALIFORNIA ADMINISTRATIVE
CODE, TITLE 24, PART 5.
B. BALL VALVES, POTABLE WATER OVER 2”: NIBCO T-580-80-LF, LEAD-FREE SILICON BRONZE BODY, “RING
BALL,” CONVENTIONAL PORT, TWO PIECE, LEVER HANDLE, 125 LB.
E. TRAP PRIMERS SHALL BE INSTALLED FOR ALL FLOOR DRAINS: PRECISION PLUMBING PRODUCTS MODEL
P2-500 AUTOMATIC TRAP PRIMER, CORROSION RESISTANT BRASS, PISTON OPERATED.
C. CHECK VALVES, POTABLE WATER: NIBCO T-480-LF, LEAD-FREE SILICON BRONZE BODY, INLINE LIFT
TYPE, TEFLON SEAT, AND DISCS, SPRING ACTUATED, 125 LB. NIBCO T-413-Y-LF, LEAD-FREE SILICON
BRONZE BODY, Y-PATTERN LIFT TYPE, CLASS 200.
F.
F.
EXCAVATION AND BACKFILL: PROVIDE ALL EXCAVATION, TRENCHING, AND BACKFILL IN CONNECTION
WITH THE WORK OF THIS SECTION. EXCAVATION SHALL BE CARRIED TO 4” BELOW THE BOTTOM OF
PIPES. PROVIDE A SAND BEDDING FOR ALL SLOPED DRAINAGE PIPING, AND PROVIDE SMOOTH
UNIFORMLY GRADED BEDDING OF FIRM BUT YIELDING MATERIAL FOR ALL OTHER PIPING, CATCH
BASINS, AND SIMILAR STRUCTURES. BACKFILL MATERIAL SHALL BE NON-CORROSIVE AND FREE FROM
ALL FOREIGN MATERIAL THAT COULD DAMAGE PIPES. BACKFILL SHALL BE PLACED IN 6” LAYERS, EACH
LAYER TAMPED, AND COMPACTED TO 95% OF MAXIMUM DRY DENSITY (ASTM D-1557-64T (C)
COMPACTION TEST PROCEDURE).
3.6 TESTING, INSPECTIONS
1.4 AS-BUILT DRAWINGS
A. CONTRACTOR SHALL BE RESPONSIBLE FOR DELIVERY, STORAGE, PROTECTION, AND PLACING OF ALL
EQUIPMENT AND MATERIALS.
1.
2.
CONTRACTOR SHALL PROTECT THE WORK AND MATERIALS FROM DAMAGE DURING
CONSTRUCTION. EQUIPMENT STORED AT THE JOB SITE SHALL BE PROTECTED FROM DUST,
WATER, OR OTHER DAMAGE, AND BE COVERED IF EQUIPMENT IS EXPOSED TO WEATHER.
PROTECT INTERIORS OF NEW EQUIPMENT AND PIPING SYSTEMS AGAINST ENTRY OF FOREIGN
MATTER. CLEAN BOTH INSIDE AND OUTSIDE BEFORE PAINTING OR PLACING EQUIPMENT IN
OPERATION.
ANY ITEMS DAMAGED SHALL BE REPAIRED OR REPLACED, AT NO ADDITIONAL COST TO THE
OWNER.
F.
WATER PRESSURE REGULATING VALVES: WILKINS 500 YSBR SERIES. INSTALL WHERE PRESSURE TO
BUILDING EXCEEDS 70 PSI.
2.
3.
PIPING SYSTEMS SHALL BE FLUSHED, BLOWN, OR PIGGED AS NECESSARY TO DELIVER CLEAN
SYSTEMS.
CONTRACTOR SHALL BE FULLY RESPONSIBLE FOR ALL COSTS, DAMAGE, AND DELAY ARISING
FROM FAILURE TO PROVIDE CLEAN SYSTEMS.
A. CLEANOUTS IN MEMBRANE DAMP-PROOFED FLOORS SHALL HAVE FLASHING FLANGE AND MEMBRANE
CLAMPS. PLUGS SHALL BE BRONZE, WITH CAST IRON BODY FERRULE FOR CAST IRON PIPE.
B. FLOOR CLEANOUTS (FCO): ZURN ZN 1400-HD, “LEVEL-TROL” ADJUSTABLE CLEANOUTS, DURA-COATED
CAST IRON WITH GAS AND WATER-TIGHT ABS TAPERED THREAD PLUG, AND ROUND SCORIATED TOP,
ADJUSTABLE TO FINISHED FLOOR .
C. GRADE CLEANOUTS (GCO): ZURN Z-1474-IN OR EQUAL JR SMITH. HOUSING TO BE DURA-COATED CAST
IRON BODY WITH INTEGRAL ANCHOR FLANGE AND SCORIATED COVER WITH LIFTING DEVICE.
CLEANOUTS IN UN-PAVED AREAS SHALL BE SET IN 18” X 18” X 4” CONCRETE PADS.
D. WALL CLEANOUTS (WCO): CAST IRON PIPE: ZURN Z-1441, DURA-COATED WITH GAS AND WATER-TIGHT
BRONZE, TAPER THREAD PLUG AND ROUND SMOOTH STAINLESS STEEL ACCESS COVER WITH
SECURING SCREW.
A. SERVICE PIPE THROUGH EXTERIOR WALL, ROOFS: CRANE STYLE BC WALL AND CEILING PLATES;
CHROME PLATED AT FINISHED ROOMS.
B. PIPES THROUGH, UNDER FOOTINGS: 18 GAUGE IRON SLEEVES TWO DIAMETERS LARGER THAN PIPE,
CAST IN CONCRETE, ANNULAR SPACE FILLED WITH MASTIC OR PLASTIC BITUMINOUS CEMENT.
A. EQUIPMENT WARRANTIES SHALL BE PROVIDED FOR ALL EQUIPMENT, WITH ALL NECESSARY
INFORMATION FILLED IN, EXCEPT PURCHASE DATE, IN FAVOR OF THE OWNER.
B. THE CONTRACTOR SHALL GUARANTEE THAT ALL WORK UNDER THIS SECTION IS FREE FROM DEFECTS
IN MATERIAL AND WORKMANSHIP FOR A PERIOD OF ONE YEAR FROM THE DATE OF FILING THE NOTICE
OF COMPLETION. REPLACEMENT OF DEFECTIVE WORK AND DAMAGE CAUSED TO WORK OF OTHER
TRADES AS A RESULT OF SUCH DEFECTIVE WORK SHALL BE THE RESPONSIBILITY OF THE
CONTRACTOR, AND SHALL BE MADE AT NO COST TO THE OWNER.
1.8 ALTERNATIVE MATERIALS AND METHODS
A. THESE PLANS AND SPECIFICATIONS DESCRIBE THE GENERAL SCOPE OF THE MECHANICAL SYSTEMS.
THESE PLANS AND SPECIFICATIONS DO NOT PRECLUDE THE SUBMITTAL OF ALTERNATIVE METHODS OR
MATERIALS. MANUFACTURER’S NAMES AND CATALOG NUMBERS ARE STATED TO IDENTIFY THE TYPE
AND QUALITY OF THE EQUIPMENT OR MATERIALS REQUIRED FOR THE PROJECT.
B. THE CONTRACTOR MAY SUBMIT SHOP DRAWINGS AND/OR TECHNICAL INFORMATION ON ALTERNATIVE
EQUIPMENT, MATERIALS OR INSTALLATION DETAILS TO ACCOMPLISH THE INTENT OF THE PLANS AND
SPECIFICATIONS. APPROVAL OF THE ALTERNATIVE EQUIPMENT, MATERIALS OR INSTALLATION DETAILS
SHALL NOT RELIEVE THE CONTRACTOR OF ANY RESPONSIBILITY FOR COMPLYING WITH THE INTENT OF
THE PLANS AND SPECIFICATIONS. SUBMIT THE MANUFACTURERS' TECHNICAL INFORMATION, SHOP
DRAWINGS, AND/OR WRITTEN DESCRIPTION OF ALTERNATIVE METHODS FOR EACH ITEM DESCRIBED BY
MANUFACTURER'S NAME AND CATALOG NUMBER AND FOR EACH COMPONENT, EQUIPMENT, MATERIAL,
OR INSTALLATION DETAIL REQUIRED.
A. THIS CONTRACTOR SHALL BE HELD TO HAVE EXAMINED THE SITE AND COMPARED IT WITH THE
CONTRACT DOCUMENTS, AND TO ADEQUATELY UNDERSTAND THE CONDITIONS UNDER WHICH THE
WORK IS TO BE PERFORMED. IN THE EVENT OF DISCREPANCY, THIS CONTRACTOR SHALL NOTIFY THE
ARCHITECT AND PROCEED AS DIRECTED. THIS CONTRACTOR SHALL BE HELD RESPONSIBLE FOR ALL
EXISTING CONDITIONS, WHETHER OR NOT ACCURATELY DESCRIBED, AND NO ALLOWANCE SHALL
SUBSEQUENTLY BE MADE ON HIS BEHALF FOR ANY ERROR, OMISSION, OR EXTRA EXPENSE DUE TO
FAILURE OR NEGLECT TO MAKE SUCH EXAMINATION AND NOTIFICATION.
1.
THIS CONTRACTOR SHALL MAKE ALL TESTS REQUIRED BY ALL LOCAL, STATE, AND FEDERAL LAWS,
CODES, ORDINANCES, AND REGULATIONS HAVING JURISDICTION OVER THIS WORK.
2.
FURNISH ALL NECESSARY LABOR, MATERIALS, AND EQUIPMENT FOR CONDUCTING TESTS, AND PAY
ALL EXPENSES IN CONNECTION THEREWITH. SHOULD LEAKS DEVELOP WHILE TESTING, REPAIRS
SHALL BE MADE, AND TESTS SHALL BE REPEATED UNTIL A SATISFACTORY TEST IS OBTAINED.
3.
WATER PIPING SHALL BY HYDROSTATICALLY TESTED FOR 6 HOURS AT 150 PSI. ALL EQUIPMENT
SHALL BE TESTED WATER TIGHT AT UTILITY PRESSURE.
4.
DRAINAGE AND VENT PIPING SHALL BE TESTED FOR 1 HOUR BY PLUGGING ALL OUTLETS AND
FILLING THE PIPES WITH WATER TO THE TOP OF VERTICAL SECTIONS OF PIPES. NO LOSS OF
WATER SHALL BE PERMITTED.
3.2 VIBRATION AND SOUND CONTROL
A. MAKE ALL NECESSARY PROVISIONS TO PREVENT THE TRANSMISSION OF VIBRATION TO THE BUILDING
STRUCTURE, INCLUDING FLEXIBLE PIPE CONNECTIONS TO MOTOR DRIVEN EQUIPMENT, RESILIENT
MOUNTING FOR PIPING, AND SEALING OFF PIPE AND DUCT PENETRATIONS OF WALLS AND ROOF.
3.3 INSULATION
A. INSULATION SHALL BE APPLIED IN COMPLETE ACCORDANCE WITH THE MANUFACTURER’S PUBLISHED
INSTALLATION INSTRUCTIONS. ALL INSULATION SHALL BE APPLIED ON CLEAN, DRY SURFACES AND
SHALL BE CONTINUOUS THROUGH WALL AND CEILING OPENING AND SLEEVES. ALL JOINTS SHALL BE
FIRMLY BUTTED TOGETHER AND LONGITUDINAL JACKET LAPS AND BUTT STRIPS SHALL BE SMOOTHLY
SECURED. SPECIFIED ADHESIVES, MASTICS, AND COATINGS SHALL BE APPLIED AT THE
MANUFACTURER’S RECOMMENDED MINIMUM COVERAGE PER GALLON.
3.4 PIPING INSTALLATION, GENERAL REQUIREMENTS
C. PIPES THROUGH FIRE RATED WALLS SHALL BE PROTECTED WITH FIRE RETARDANT MASTIC AS
DETAILED ON THE DRAWINGS. INSTALLATION SHALL BE IN FULL ACCORDANCE WITH THE
REQUIREMENTS OF THE UL SYSTEM NUMBER. HILTI OR APPROVED EQUAL.
D. WALL AND CEILING PLATES: CRANE STYLE BC OR EQUAL; CHROME PLATED AT FINISHED ROOMS.
4.
1.7 WARRANTIES
DESCRIPTION
B. TESTS
3.1 SURFACE CONDITIONS
2.5 SLEEVES, WALL PLATES
EXERCISE CARE IN STORAGE AND HANDLING OF EQUIPMENT AND PIPING MATERIAL TO BE
INCORPORATED IN THE WORK. REMOVE DEBRIS ARISING FROM CUTTING, THREADING, AND
WELDING OF PIPING.
PART 3 – EXECUTION
2.4 CLEANOUTS
B. CLEANLINESS OF PIPING AND EQUIPMENT SYSTEMS
1.
A. CHRISTY #F-08, COMPLETE WITH CONCRETE COVER AND REQUIRED EXTENSIONS. INDEX ALL COVERS
“GAS” OR “WATER” AS REQUIRED FOR SERVICE USE.
E. PIPES THROUGH FLOORS, INTERIOR CONCRETE WALLS, AND THROUGH FIRE RATED WALL AND SMOKE
STOP PARTITIONS: 18 GAUGE IRON SLEEVES, TWO DIAMETERS LARGE THAN PIPE, ANNULAR SPACE
FILLED WITH 3M BRAND FIRE BARRIER CP-25 CAULK.
F.
PIPES THROUGH 1-HOUR WALLS SHALL BE PROTECTED WITH FIRE RETARDANT MASTIC AS DETAILED
ON THE DRAWINGS. INSTALLATION SHALL BE IN FULL ACCORDANCE WITH THE REQUIREMENTS OF THE
UL SYSTEM NUMBER. HILTI OR APPROVED EQUAL.
2.6 ACCESS DOORS
A. WHERE CONSTRUCTION IS NOT INHERENTLY ACCESSIBLE, PROVIDE ADEQUATELY SIZED AND
CONVENIENTLY LOCATED ACCESS DOORS IN CEILING, WALLS, AND FURRING FOR SERVICING VALES,
EQUIPMENT, ETC.
B. ACCESS DOORS SHALL BE KARP, MILCOR, OR EQUAL, PRIME COATED STEEL FOR ALL SURFACES
EXCEPT CERAMIC TILE, 12” X12” MINIMUM SIZE AS REQUIRED. LOCKS SHALL BE FLUSH, SCREWDRIVER
OPERATED.
1.
2.
3.
4.
5.
STYLE KDW FOR GYPSUM BOARD SURFACES.
STYLE PL FOR PLASTER SURFACES.
STYLE 210 FOR ACOUSTIC TILE SURFACES.
STYLE DSC 214-M SATIN FINISH STAINLESS STEEL AT CERAMIC TILE SURFACES.
STYLE “FIRE RATED” AT RATED CEILINGS AND WALLS.
A. ALL PIPING SHALL BE CONCEALED IN FINISHED ROOMS, INSTALLED IN FURRED WALLS AND PARTITIONS.
WHERE FURRED OR SUSPENDED CEILINGS OCCUR, PIPING SHALL BE INSTALLED IN THE CONCEALED
SPACE AT POINTS ADJACENT TO BEAMS AND/OR OTHER STRUCTURAL MEMBERS, AND COORDINATED
WITH DUCTWORK AND EQUIPMENT. WHERE EXPOSED PIPING OCCURS, IT SHALL BE INSTALLED
PARALLEL TO OR AT RIGHT ANGLES TO BUILDING WALLS, UNLESS SPECIFICALLY SHOWN OTHERWISE
ON THE DRAWINGS.
B. INSTALLATION OF PIPING SHALL BE SUCH THAT DAMAGE CANNOT RESULT, THROUGH THERMAL
EXPANSION OR CONTRACTION, TO PIPING, BUILDING, OR PIPE HANGERS AND SUPPORTS. ANCHORS
SHALL BE INSTALLED AT MIDPOINTS OF ALL RUNS IN MAIN PIPING FOR THE PURPOSE OF LOCALIZING
PIPE EXPANSION OR PREVENTION OF CREEPAGE.
3.7 DOMESTIC WATER SYSTEM STERILIZATION
A. UPON COMPLETION OF THIS WORK, THE DOMESTIC WATER SYSTEM SHALL BE THOROUGHLY FLUSHED,
STERILIZED, AND REFLUSHED. STERILIZATION AND REFLUSHING SHALL BE PERFORMED USING THE
FOLLOWING PROCEDURE.
1.
ALL WORK SHALL BE PERFORMED IN THE PRESENCE OF THE INSPECTOR.
2.
INTRODUCE CHLORINE OR A SOLUTION OF SODIUM HYPOCHLORITE, FILLING THE LINES SLOWLY
AND SUPPLYING THE STERILIZATION AGENT AT A RATE OF 50 PARTS OF CHLORINE PER MILLION, AS
DETERMINED BY RESIDUAL CHLORINE TESTS AT THE ENDS OF ALL BRANCHES. OPEN AND CLOSE
ALL VALVES WHILE THE SYSTEM IS BEING CHLORINATED TO INSURE UNIFORM DISTRIBUTION.
3.
AFTER THE STERILIZING AGENT HAS BEEN APPLIED FOR 24 HOURS, TEST FOR RESIDUAL CHLORINE
AT THE ENDS OF THE BRANCHES. IF LESS THAN 5 PPM IS INDICATED, REPEAT THE STERILIZATION
PROCEDURE.
4.
WHEN TESTS SHOW AT LEAST 5 PPM OF RESIDUAL CHLORINE, FLUSH OUT THE SYSTEM UNTIL ALL
TRACES OF THE CHEMICAL ARE REMOVED.
B. AFTER A PERIOD OF 48 HOURS MINIMUM, BACTERIOLOGICAL TESTS, USING SAMPLES FROM AT LEAST 3
REPRESENTATIVE POINTS SHALL BE MADE BY RECOGNIZED TESTING AGENCY, WHO SHALL CERTIFY TO
THE ARCHITECT THAT THE SYSTEM IS BACTERIOLOGICALLY SAFE AND AT LEAST EQUAL IN SAFETY TO
THAT OF THE PRINCIPAL WATER SUPPLY. THE LABORATORY REPORT AND CERTIFICATION SHALL BE
TRANSMITTED TO THE ARCHITECT AND OWNER.
END OF SECTION
C. ALL PIPE LINES SHALL BE INSTALLED FREE FROM TRAPS AND AIR POCKETS, TRUE TO LINE AND GRADE,
WITH SUITABLE SUPPORTS PROPERLY SPACE. ALL PIPING SHALL BE INSTALLED WITHOUT UNDUE
STRESSES AND WITH PROVISION FOR EXPANSION AND CONTRACTION.
D. ALL PIPING SHALL BE NEW AND FREE FROM FOREIGN SUBSTANCES. AMERICAN STANDARD PIPE
THREADS SHALL BE USED FOR IPS THREADED WORK. JOINTS IN THREADED PIPING SHALL BE MADE UP
WITH TEFLON TAPE APPLIED TO THE MALE THREADS ONLY. NO SCREWED PIPE JOINTS SHALL BE
CAULKED OR PACKED WITH ROPE OR OTHER PACKING MATERIALS. PIPE SHALL BE FREE FROM TOOL
MARKS, THREADS CUT ACCURATELY WITH NOT MORE THAN TWO (2) THREADS SHOWING BEYOND
FITTING. FRICTION WRENCHES SHALL NOT BE USED WITH PLATED, POLISHED, OR SOFT METAL PIPING.
ALL CHANGES IN PIPE SIZE SHALL BE MADE WITH REDUCING FITTING. BUSHINGS WILL NOT BE
PERMITTED.
DATE
1.6 DELIVERY, STORAGE, AND HANDLING
E. BACKFLOW PREVENTERS (WHERE SHOWN ON THE DRAWINGS OR REQUIRED BY LOCAL CODE):
REDUCED PRESSURE TYPE: ¼” TO 2” – WILKINS #975-XLMS SERIES, 2 ½” TO 10” – WILKINS #375 SERIES.
2.9 VALVE BOXES
REV
B. THE CONTRACTOR SHALL REVIEW AND COMPARE THE ARCHITECTURAL, STRUCTURAL, PLUMBING,
MECHANICAL, AND ELECTRICAL DRAWINGS AND ALL OWNER SUPPLIED EQUIPMENT DRAWINGS, AND
ADJUST THEIR WORK TO BE IN CONFORMITY WITH THE CONDITIONS INDICATED THEREON.
DISCREPANCIES BETWEEN DRAWINGS, BETWEEN DRAWINGS AND ACTUAL FIELD CONDITIONS, OR
BETWEEN DRAWINGS AND SPECIFICATIONS, SHALL PROMPTLY BE BROUGHT TO THE ATTENTION OF
THE ARCHITECT FOR A DETERMINATION OF THE MODIFICATIONS TO BE EFFECTED. IN THE EVENT THAT
A MAJOR MODIFICATION IS REQUIRED, A CHANGE ORDER WILL BE PREPARED.
D. RELIEF VALVES: WATER HEATER TEMPERATURE/PRESSURE RELIEF VALVE, WATTS, M&M, OR EQUAL
WITH ASME RATING, AND AGA CERTIFIED DESIGN. SET AT 125 PSI AND 210°F.
THIS CONTRACTOR SHALL NOT ALLOW OR CAUSE ANY WORK OF THIS SECTION TO BE COVERED OR
ENCLOSED UNTIL IT HAS BEEN INSPECTED, TESTED, AND APPROVED BY THE ARCHITECT AND THE
AUTHORITIES HAVING JURISDICTIONS OVER THE WORK. SHOULD ANY OF THIS WORK BY ENCLOSED
OR COVERED UP BEFORE SUCH INSPECTION, TESTING, AND APPROVAL, THIS CONTRACTOR SHALL
UNCOVER THE WORK, HAVE THE NECESSARY INSPECTIONS, TESTS, AND APPROVALS MADE AND,
AT NO EXPENSE TO THE OWNER, MAKE ALL REPAIRS NECESSARY TO RESTORE BOTH HIS WORK
AND THAT OF OTHER CONTRACTORS THAT MAY HAVE BEEN DAMAGED, TO BE IN CONFORMITY WITH
THE CONTRACT DOCUMENTS.
E. NO WATER OR DRAINAGE PIPING SHALL PASS OVER ELECTRICAL EQUIPMENT UNLESS ADEQUATE
PROTECTION IS PROVIDED TO PREVENT DAMAGE BY LEAKS OR CONDENSATION.
F.
ALL COPPER TUBING SHALL BE FORMED IN A WORKMANLIKE MANNER, IN ACCORDANCE WITH THE PIPE
AND TUBE BENDING HANDBOOK OF THE COPPER AND BRASS RESEARCH ASSOCIATION. A TUBE
BENDER GIVING SUPPORT TO THE PERIPHERY OF THE TUBE SHALL BE USED. THE TUBING SHALL
BE PROTECTED AGAINST FLATTING OR OTHER INJURY.
G. ALL COPPER CONNECTIONS AND JOINTS SHALL BE MADE IN ACCORDANCE WITH THE COPPER TUBE
HANDBOOK, COPPER AND BRASS RESEARCH ASSOCIATION. NO SWAGED CONNECTIONS WILL BE
PERMITTED. ALL VALVES, PUMPS, AND SIMILAR EQUIPMENT SHALL BE CONNECTED TO COPPER PIPING
THROUGH UNION OR FLANGE ADAPTER FITTINGS.
H. SHUT OFF VALVES SHALL BE PROVIDED IN ALL MAIN SERVICES, AND WHERE REQUIRED TO PERMIT
PROPER SERVICING OF EQUIPMENT. VALVES OF ONE TYPE SHALL BE OF ONE MANUFACTURER.
I.
J.
ALL VALVES SHALL BE OF THE SAME SIZE AS THE PIPELINES IN WHICH THEY ARE INSTALLED, UNLESS
SPECIFICALLY SIZED ON THE DRAWINGS. ALL HAND CONTROLLED LINE VALVES SHALL BE BALL VALVES,
EXCEPT WHERE THROTTLING CONTROL OR FREQUENT OPERATION IS REQUIRED, IN WHICH CASE
GLOBE OR ANGLE VALVES SHALL BE USED. GLOBE VALVES IN HORIZONTAL LINES SHALL BE INSTALLED
WITH STEM IN HORIZONTAL TO PERMIT LINE DRAINING. ALL GLOBE AND ANGLE VALVES SHALL BE
INSTALLED TO CLOSE AGAINST PRESSURE. DISC VALVES SHALL HAVE DISCS SUITABLE FOR THE
SERVICES FOR WHICH THEY ARE TO BE USED.
PROVIDE PRIME COATED ESCUTCHEON PLATES AT ALL POINTS WHERE EXPOSED PING PENETRATES
FINISHED WALL CEILINGS OR FLOORS.
DATE OF ISSUE:
7/12/2023
SCALE:
PROJECT NO:
427.11
DRAWING NO:
P1.1
1/2"
1"
2"
HUMBOLDT COUNTY, CALIFORNIA
A. THE DRAWINGS INDICATE DIAGRAMMATICALLY THE GENERAL LAYOUT OF THE PLUMBING SYSTEMS AND
OTHER RELATED WORK. FIELD VERIFICATION OF SCALED DIMENSIONS TAKEN FROM THE DRAWINGS IS
REQUIRED.
1.
ZURN, “SHOKTROL,” OR EQUAL JR SMITH, STAINLESS STEEL BELLOWS. INSTALL WITH GATE VALVE
SHUT-OFF AND ACCESS DOOR AT ALL FLUSH VALVES OR OTHER AUTOMATIC VALVES. A SINGLE UNIT
SIZED IN ACCORDANCE WITH THE MANUFACTURER’S RECOMMENDATIONS MAY SERVE BATTERIES OF
VALVES.
PLUMBING SPECIFICATIONS
1.5 DRAWINGS
A. GENERAL
TRINIDAD RANCHERIA
INTERPRETIVE CENTER
TRINIDAD, CA. 95570
A. A COMPLETE SET OF CONTRACT DRAWINGS SHALL BE MAINTAINED AT THE WORK SITE, AND ALL
CHANGES IN THE WORK SHALL BE RECORDED ON THIS SET, ON A DAILY BASIS. THE FINAL AS-BUILT
DRAWINGS SHALL BE SUBMITTED TO THE OWNER’S REPRESENTATIVE FOR APPROVAL.
TRINITY VALLEY CONSULTING ENGINEERS, INC.
TVCE
67 WALNUT WAY
PO BOX 1567
WILLOW CREEK, CA 95573
P:(530)629-3000
F:(530)629-3011
KEYED NOTES:
1 2" WASTE DOWN IN WALL, 1-1/2" VENT UP IN WALL,
PROVIDE WITH 2" WALL CLEAN OUT.
2 1-1/2" VENT UP IN WALL. IF APPLICABLE, CONNECT
VENT PIPES IN WALL 6" ABOVE RIM OF TALLEST
PLUMBING FIXTURE SERVING VENT PIPING.
3 2" VENT UP IN WALL. IF APPLICABLE, CONNECT VENT
PIPES IN WALL 6" ABOVE RIM OF TALLEST PLUMBING
FIXTURE SERVING VENT PIPING.
4 ROUTE CONDENSATE OR INDIRECT DRAIN LINE
DOWN TO MOP SINK AND DISCHARGE WITH 1" GAP.
5 3/4" CDO FROM AHU-1. DISCHARGE UNDER EAVES
DWN BY DES BY CHK BY APP BY
1-1/4" CW SEE CIVIL
FOR CONTINUATION
1-1/4" CW BG
3/4" CW
1
P3.0
4
2
ET-1
1" HW
WH-1
HB-1
ACCESS DOOR,
SEE ARCH DWG
MS-1
WH-1
3/4" HW
ACCESS DOOR,
SEE ARCH DWG
RCP-1
3" FCO
1-1/4" CW UIW
1
TP-1
TMV-1
1" CW
2
3/4" CW BS
1/2" CW BS
TO TP-1
FS-1
5
1-1
1-1
1-1/4" CW SOV IN
GRADE BOX
3/4" CW UIW TO
ESPRESSO MACHINE
WITH BFP-1
AHU-1
2
2
DESCRIPTION
3/4" CD
2" VTR
3/4" CW DIW
FD-1
FS-1
DATE
1/2" CW/HW DIW
REV
3" GW TO (E) GREASE INTERCEPTOR, 3" GW
SEE CIVIL FOR CONTINUATION
4" SS, SEE CIVIL FOR CONTINUATION
4" SS
ST
ST
ST
ST
3/4" HW
3/4" HWR
TR
TR
2" VTR
ST
ST
3
WC-1
1
WC-1
4" FCO
2
P2.0
L-1
PLUMBING FLOOR PLAN - DWV
1/4" = 1'-0"
TMV-1
L-1
1
P2.0
PLUMBING FLOOR PLANS
TR
TRINIDAD RANCHERIA
INTERPRETIVE CENTER
TRINIDAD, CA. 95570
TR
PLUMBING FLOOR PLAN - WATER & GAS
1/4" = 1'-0"
DATE OF ISSUE:
7/12/2023
SCALE:
1/4" = 1'-0"
PROJECT NO:
427.11
DRAWING NO:
P2.0
1/2"
1"
2"
HUMBOLDT COUNTY, CALIFORNIA
3/4" CW
TRINITY VALLEY CONSULTING ENGINEERS, INC.
TVCE
67 WALNUT WAY
PO BOX 1567
WILLOW CREEK, CA 95573
P:(530)629-3000
F:(530)629-3011
NOTES:
1.
2.
ALL PIPES TO BE INSULATED.
PLACE ONE RESTRAINT STRAP AT 2/3
HEIGHT OF WATER HEATER, AND ONE
STRAP AT 1/3 HEIGHT OF WATER HEATER.
RCP-1
BALL VALVE, TYP.
CHECK VALVE, TYP.
HW RECIRC
CW
MAY EXTEND AS A
WASTE OR VENT
FACE OF WALL
CW INLET WITH BALL
AND CHECK VALVE
WALL
TAIL PIECE
TRAP PRIMER
EXPANSION TANK, SEE
SCHEDULE FOR ET-1
DIELECTRIC UNIONS (TYP.)
STAINLESS STEEL
COVER SCREWED TO
THREADED C.O. PIPE
ESCUTCHEON
PLUGGED TEE
WITH CLEANOUT
DWN BY DES BY CHK BY APP BY
LAV
HW
PRESSURE AND
TEMP. RELIEF VALVE
1/2"
SEAL WATERTIGHT
FLOOR LINE
FIN. FLOOR
FD
SECURE WITH 2" 16 GA. SHEET METAL
STRAPS TO BLOCKING WITH #10 WS
SET WATER HEATER TO 140°F,
SEE SCHEDULE FOR WH-1
COPPER RELIEF DISCHARGE
TO MOP SINK
1/2" PIPING BELOW FLOOR.
SLOPE TOWARD DRAIN
MOP SINK
P-TRAP
NOTES:
1. POSITION PIPE TO AVOID OBSTRUCTIONS TO CLEAN-OUTS.
2. PROVIDE C.O. AT ALL VERTICAL SANITARY/VENT STACKS.
NOTE: INSTALL FLOOR DRAIN TRAP PRIMERS ON ALL FLOOR DRAINS.
FLOOR DRAIN TRAP PRIMER DETAIL
2
WALL CLEAN-OUT DETAIL
1
ELECTRIC WATER HEATER DETAIL
P3.0
NOT TO SCALE
P3.0
NOT TO SCALE
P3.0
NOT TO SCALE
REV
DATE
3
DESCRIPTION
CONNECT 1/2" CW
TO TRAP AS REQ'D
EQ
EQ
2" x 2" x 1/4" STL.
ANGLE, 3" LONG
3/8" THRU BOLT WITH
NUT AND LOCK WASHER
NUT AND WASHER
(TOP & BOTTOM)
3/8" ALL-THREAD ROD
UNION
CLEAN OUT
NUT (TOP & BOTTOM)
WASHER (TOP & BOTTOM)
DRAIN PAN
THE DRAIN PIPE SHALL BE
AT LEAST THE SAME SIZE AS
THE NIPPLE ON THE DRAIN
PAN BUT NO LESS THAN 3/4"
PIPE
SEE PLAN FOR
CONTINUATION
INSULATION PROTECTIVE
SHEETMETAL SHIELD
5
HVAC CONDENSATE DRAIN DETAIL
4
PIPE HANGING DETAIL
P3.0
NOT TO SCALE
P3.0
NOT TO SCALE
PLUMBING DETAILS
INSULATION, IF REQUIRED
DATE OF ISSUE:
7/12/2023
SCALE:
1/8" = 1'-0"
PROJECT NO:
427.11
DRAWING NO:
P3.0
1/2"
1"
2"
HUMBOLDT COUNTY, CALIFORNIA
CLEVIS HANGER
TRINIDAD RANCHERIA
INTERPRETIVE CENTER
TRINIDAD, CA. 95570
4"
CLEAN OUT
4" MIN.
PITCH DOWN TOWARD DRAIN
T24.1
Trinidad Interpretive Center
Trinidad
T
i id d Pier
Pi
Trinidad, CA 95570
TITLE 24 BUILDING ENERGY REPORT
1125 16th St., Ste. 216 Arcata, CA 95521
707.826.1433
admin@abbaytechnicalservices.com
Abbay Technical Services
Building Energy Consultants
T24.2
Trinidad Interpretive Center
Trinidad
T
i id d Pier
Pi
Trinidad, CA 95570
TITLE 24 BUILDING ENERGY REPORT
1125 16th St., Ste. 216 Arcata, CA 95521
707.826.1433
admin@abbaytechnicalservices.com
Abbay Technical Services
Building Energy Consultants
T24.3
Trinidad Interpretive Center
Trinidad
T
i id d Pier
Pi
Trinidad, CA 95570
TITLE 24 BUILDING ENERGY REPORT
1125 16th St., Ste. 216 Arcata, CA 95521
707.826.1433
admin@abbaytechnicalservices.com
Abbay Technical Services
Building Energy Consultants
T24.4
Trinidad Interpretive Center
Trinidad
T
i id d Pier
Pi
Trinidad, CA 95570
TITLE 24 BUILDING ENERGY REPORT
1125 16th St., Ste. 216 Arcata, CA 95521
707.826.1433
admin@abbaytechnicalservices.com
Abbay Technical Services
Building Energy Consultants
T24.5
Trinidad Interpretive Center
Trinidad
T
i id d Pier
Pi
Trinidad, CA 95570
TITLE 24 BUILDING ENERGY REPORT