Fire Protection in Shipyard Employment

Federal RegisterDec 11, 2002

Ask Donna

What actually matters in this document.

Text

DEPARTMENT OF LABOR

Occupational Safety and Health Administration

29 CFR Part 1915

[Docket S-051]

RIN 1218-AB51

Fire Protection in Shipyard Employment

AGENCY:

Occupational Safety and Health Administration (OSHA), U.S. Department of Labor.

ACTION:

Proposed rule.

SUMMARY:

The Occupational Safety and Health Administration (OSHA) is proposing fire protection standards for shipyard employment that were developed through a negotiated rulemaking process. This proposed standard is based on the recommendations of the Fire Protection in Shipyard Employment Negotiated Rulemaking Advisory Committee and is a comprehensive standard for the protection of shipyard employment workers from the hazards of fire on land side and on board vessels. The proposed standard reflects new technologies and current national consensus standards. The proposal collects all fire-related safety practices into a single subpart, which will make them more accessible and more easily understood by employers and employees. The standard will provide increased protection of shipyard employment workers from fire hazards.

DATES:

Comments must be submitted by the following dates:

Hard Copy: Your comments must be submitted (postmarked or sent) by March 11, 2003.

Facsimile and electronic transmission: Your comments must be sent by March 11, 2003. (Please see the

SUPPLEMENTARY INFORMATION

provided below for additional information on submitting comments.)

ADDRESSES:

Regular mail, express delivery, hand-delivery, and messenger service: You must submit three copies of your comments and attachments to the OSHA Docket Office, Docket No. H-011G, Room N-2625, U.S. Department of Labor, 200 Constitution Avenue, NW., Washington, DC, 20210. OSHA Docket Office and Department of Labor hours of operation are 8:15 a.m. to 4:45 p.m., e.s.t.

Facsimile: If your comments, including any attachments, are 10 pages or fewer, you may fax them to the OSHA Docket Office at (202) 693-1648. You must include the docket number of this notice, Docket No. H-011G, in your comments.

Electronic: You may submit comments through the Internet at

http://ecomments.osha.gov.

FOR FURTHER INFORMATION CONTACT:

For general information and press inquiries, contact Ms. Bonnie Friedman, OSHA, Office of Information and Consumer Affairs, N-3647, 200 Constitution Avenue, NW., Washington, DC 20210; telephone: (202) 693-1999. For additional copies of this

Federal Register

notice, contact OSHA, Office of Publications, U.S. Department of Labor, Room N-3101, 200 Constitution Avenue, NW., Washington, DC, 20210; telephone (202) 693-1888. Electronic copies of this

Federal Register

notice, as well as news releases and other relevant documents, are available at OSHA's web page on the Internet at

http://www.osha.gov.

SUPPLEMENTARY INFORMATION:

Submission of Comments on This Notice and Internet Access to Comments and Submissions

You may submit comments in response to this notice by (1) hard copy, or (2) FAX transmission (facsimile), or (3) electronically through the OSHA Webpage. Please note that you cannot attach materials, such as studies or journal articles, to electronic comments. If you have additional materials, you must submit three copies of them to the OSHA Docket Office at the address above. The additional materials must clearly identify your electronic comments by name, date, subject and docket number so we can attach them to your comments. Because of security-related problems there may be a significant delay in the receipt of comments by regular mail. Please contact the OSHA Docket Office at (202)-693-2350 for information about security procedures concerning the delivery of materials by express delivery, hand delivery and messenger service. All comments and submissions will be available for inspection and copying at the OSHA Docket Office at the address above. Comments and submissions posted on OSHA's Webpage are available at

http://www.osha.gov.

OSHA cautions you about submitting personal information such as social security numbers and birth dates. Contact the OSHA Docket Office at (202)-693-2350 for information about materials not available through the OSHA Webpage and for assistance in using the Webpage to locate docket submissions.

Table of Contents

This Preamble to the proposed standard is organized into the following sections:

I. Background

II. The Fire Protection in Shipyard Employment Negotiated Rulemaking Advisory Committee

III. Pertinent Legal Authority

IV. Summary and Explanation of Proposal

V. Summary of the Preliminary Economic and Initial Regulatory Flexibility Screening Analyses

VI. OMB Review under the Paperwork Reduction Act of 1995

VII. Public Participation

VIII State Plan Standards

IX. Federalism

X. Unfunded Mandates

XI. Authority and Signature

I. Background

Employees in shipyard employment are subject to a high risk of injury and death from fires and explosions during ship repair, shipbuilding, shipbreaking, and related work activities as well as firefighting activities. Many of the basic tasks involved in shipyard employment (also referred to as just “shipyards” hereafter), such as welding, grinding, and cutting metal with torches, provide an ignition source for fires. There are also many combustible sources on vessels and in shipyards, including flammable fuels and cargo on vessels, wood structures, building materials, and litter. When cutting torches are used in enclosed or confined spaces, accidental oxygen-enriched atmospheres can cause normally fire resistant-materials to readily burn. When fires do occur, employees are often working in confined or enclosed spaces that may make escape difficult or impossible, and result in atmospheres of combustible gases, toxic fumes, or oxygen-depleted air.

Shipyard employees are therefore at risk from fires that can result in burns, death, explosions, toxic gases and fumes, and asphyxiation from a lack of oxygen. Based on data collected by the Bureau of Labor Statistics, there is an annual average of one fatality, 110 lost-workday “heat/burn” injuries, and more than three times that many total injuries (Ex. 15).

In addition, employees are also at special risk when fighting fires in shipyards. Fighting fires at shoreside facilities in shipyards can be similar to structural firefighting at typical industrial manufacturing facilities. The usual firefighting hazards encountered include compressed gas cylinders, flammable liquid processes and storage, high-voltage electric switches and transformers, and high-density combustible materials storage.

Structures at shipyards can range from single-story office buildings to warehouses to massive fabrication shops. Fires can also be encountered in tunnel sections, rail cars, vessel components, and similar units under construction, repair, or demolition at the shipyard site.

However, firefighting on board vessels can be considerably different from structural firefighting. When traditional structural firefighting techniques are used on vessel fires, the result can be catastrophic. The potential is much greater for serious injury to firefighting personnel when tactics do not reflect the unique nature of ship firefighting. For example, there may be little or no ability to ventilate the heat, smoke, and gases produced by a fire. Typically, in structural firefighting, immediate steps are taken to open up the structure, vertically and horizontally, to remove smoke and heat. Hose lines are then used to attack the fire. When fighting a ship fire, one of the first steps that may be taken is to shut down ventilation systems to close off the fire's progression and starve it of oxygen. Hose lines are used to cool down surrounding metal decks and bulkheads. A defensive fire-fighting option for large or intense structural fires is to “surround and drown'; that is, position hose lines outside the structure and apply voluminous amounts of water until the fire goes out. Strategic options for vessel fires are very limited and nearly always require an aggressive interior attack. Small shipyards have outside fire responders. These municipal or other fire departments may not have much experience in fighting fires in shipyards or, especially, on vessels. Proper coordination, familiarization, and training is necessary to ensure the safety of outside firefighters who respond to shipyard fires.

Vessel fires are also more complicated because, in most cases, outside firefighters seldom have the opportunity to learn the layout of the vessel. Vessels under construction or modification have constantly changing structures. Firefighters, operating under adverse conditions caused by heat and smoke, can easily become disoriented or confused. Access to the vessel may be restricted by its location, such as within a dry dock, meaning that firefighters boarding the ship will have to converge on one or two access locations. This can lead to congestion of personnel and delays in locating and extinguishing the fire. Access can also be restricted by equipment, tools, vessel components, and structures. Staging platforms, scaffolding or rigging, cranes, and even mooring lines can hamper deploying hose lines and positioning apparatus, again causing delays and confusion. Even with unrestricted access to the vessel, deploying hose lines can be time-consuming and labor intensive. To attack a fire deep within a ship, firefighting hoses may have to be stretched hundreds of feet, a task that requires time and a lot of people.

Maintaining an adequate supply of air is another tactical problem for firefighting operations on ships. Firefighters will usually be equipped with self-contained breathing apparatus (SCBA) that optimally provide a 30-minute supply, after which the compressed air bottle will have to be refilled or replaced. Ship fire-fighting operations can last many hours; firefighters have to be rotated frequently to resupply their SCBA and counteract fatigue.

Ships' fires also present a problem firefighters do not often have to think about—introducing a large amount of water into the vessel, so much so that the vessel can become unstable and possibly capsize or sink. This potential problem requires consultation with experts (such as naval architects or U.S. Coast Guard engineers) to assure vessel stability.

Radio communication is another complicating factor common to fighting ship fires. Steel bulkheads and many compartments in ships effectively block and limit radio signal transmissions. To compensate, firefighters have to relay messages from within the ship by stationing personnel with radios close enough that transmissions can be sent and received. Other alternatives include using runners or deploying hard-wire communications systems. All possible solutions to this problem involve additional personnel, delays in establishing command and control, and increase the potential for mishaps.

Fires in shipyard employment present significant, serious hazards to those who work to control them. These hazards can be found in shipbuilding, as well as in shipbreaking and ship repair. Because firefighters must function on both land side and on board vessels, they need a single set of standards and training to do so safely. Likewise, other shipyard employees move from ship to shore frequently and need a single standard and training on alarms, evacuation, and the many other response actions.

OSHA's general industry standards for fire protection are in subpart L, CFR 1910.155 through 1910.165. The application of subpart L, CFR 1910.155(b), exempts maritime employments from coverage. Subpart L addresses typical land-side fire prevention and firefighting conditions (fire extinguishers, fixed extinguishing systems,

etc.

). OSHA compliance policy, set out in OSHA Instruction STD.2 addresses typical land-side fire hazards in shipyards. Since the Agency has no specific standards that address the risks of fire on board vessels and vessel sections, OSHA has used the General Duty Clause section 5 (a)(1) of the Occupational Safety and Health Act to cite fire safety hazards on both land-side facilities and on board vessels and vessel sections (also referred to as just “vessels” hereafter). To enforce the General Duty Clause, OSHA must show the existence of a hazard, that the hazard is recognized, that the hazard is causing, or is likely to cause serious physical harm to employees, and that a feasible means exists to abate the hazard. To demonstrate industry recognition and feasible abatement measures, OSHA has relied upon standards published by the Coast Guard and other branches of the Federal Government to identify hazards and abatement steps as well as guidelines developed by professional associations such as the National Fire Protection Association and the Marine Chemists Association.

The lack of a clear OSHA standard for fire protection on vessels, and the multiplicity of guidelines and standards from other sources that potentially apply to shipyards can result in uncertainty about, and gaps in, the safety requirements for employers in the shipyard industry. The Agency has preliminarily concluded that codifying relevant issues for fire protection in shipyards into a single subpart in CFR part 1915 will substantially clarify an employer's responsibilities in protecting shipyard employees from fire hazards. The Agency believes that this, in turn, will lead to better protection for these employees.

Simply extending application of the current general industry standards to shipyards would not be appropriate. First, most of the provisions in the general industry standards have been in effect since 1980. They would need revision to take into account technological advances that could improve fire protection in shipyard employment. These advances are recognized in the proposed new subpart P. Secondly, shipyard employment encompasses many tasks and worksites that are unique to the maritime industry. Employers, labor representatives and professional and trade associations have repeatedly asked OSHA to allow all shipyard employment to be covered by a single set of standards. They point out that the

work situations found within shipyard employment have more in common with each other than with those in general industry, and that the hazards and methods of controlling the hazards are similar throughout the shipyard. Finally, they point out that the work on land and aboard the vessels is located within the same area and performed by the same workforce. Fire protection services are usually provided by the same in-yard plant or out-of-yard fire crews to all areas of shipyard employment. OSHA's Negotiated Rulemaking Advisory Committee for subpart P (hereafter “the Committee”) concluded that when fire response crews find shipyard employment sites following the same standard, the crews are more effective in their fire response activities. OSHA agrees and has preliminarily concluded that a single new standard addressing fire hazards for all shipyard employment, on land and on board vessels, is reasonably necessary and appropriate to protect shipyard employees.

The Agency has also preliminarily concluded that there is a significant risk to employees of material impairment from fires, explosions, and fire-related accidents causing death, burns, and injuries related to fire and fighting fires. OSHA further concludes that the proposal's requirements for inspections before beginning hot work, fire watches, fire planning, training, and other provisions will help save lives and prevent injuries. Proposed subpart P will substantially reduce this risk of fire by recognizing and, in some cases, requiring new technology.

OSHA established the Shipyard Employment Standards Advisory Committee (SESAC) in 1990. SESAC was formed to guide OSHA in revising, consolidating, and modernizing the varying sets of rules that were being applied in the shipyard employment industry into what would ultimately become a single comprehensive set of standards for all shipyard employment. The new shipyard employment standards would apply to all shipyard employment, regardless of geographic location. In 1991 SESAC began work on standards on fire protection for all shipyard employment. The SESAC Subcommittee on Fire Protection, after reviewing pertinent federal regulations and guidelines issued by professional associations, drafted a shipyard employment fire protection standard (SESAC, Ex. 9). However, not all of its provisions were written in regulatory language and the provisions did not address all of the issues that need to be considered in an OSHA rulemaking.

The shipyard employment workgroup of the Maritime Advisory Committee on Occupational Safety and Health (MACOSH) briefly discussed fire protection and negotiated rulemaking at its September 1995 meeting in New Orleans, Louisiana. Members urged OSHA to proceed with a fire protection standard, although some members suggested the MACOSH shipyard employment workgroup take up the fire protection issues if OSHA was unable to do a fire protection negotiated rulemaking.

On June 6, 1996, OSHA announced its intent to establish a Fire Protection in Shipyard Employment Negotiated Rulemaking Advisory Committee under the Federal Advisory Committee Act (FACA) and the Negotiated Rulemaking Act (NRA)(61 FR 28824). The Committee would negotiate issues associated with developing a notice of proposed rulemaking to regulate fire hazards in shipyard employment. The Committee would be made up of representatives of the parties interested in, or affected by, the outcome of the proposed rule. OSHA asked interested parties to submit their nominations for membership or request representation on the Committee. The Agency planned public meetings for the Committee along the United States coastlines in an effort to provide small employers with the access they needed to participate in this rulemaking effort.

II. The Fire Protection in Shipyard Employment Negotiated Rulemaking Advisory Committee

Negotiated rulemaking is a process by which a proposed rule is developed through negotiation among a committee composed of representatives of all the interests that will be significantly affected by the rule. Negotiation allows interested parties to discuss possible approaches to various issues and arrive at jointly agreed or acceptable provisions for a standard. The negotiation process involves a mutual education of the parties on the reasons for different positions on the issues as well as on the concerns about the practical impact of various approaches.

The process is started by the Agency's identification of all interests potentially affected by the rulemaking under consideration. To help in this identification process, the Agency publishes a notice in the

Federal Register

, called “an intent to negotiate,” which identifies a preliminary list of interests and requests public comment. Also included in this notice is a statement that the Agency intends to negotiate and develop a proposed rule; a description of the subject and scope of the rule to be developed and the issues to be considered; a proposed agenda and schedule for completing the work of the committee; and even a possible list of persons who may be nominated.

After receiving comment, the Agency chooses an advisory committee of those nominated to represent these various interests. Representation on the committee may be direct, that is, each member represents a specific interest, or indirect, through coalitions of parties formed for this purpose. An Agency representative is a member of the committee, representing the Federal government's own set of interests. The negotiated rulemaking advisory committee is chaired by a mediator, who facilitates the negotiation process.

Once a negotiated rulemaking committee reaches consensus on the provisions of a proposed rule, the Agency, consistent with its legal obligations, uses this as the basis of its proposed standard, which is published in the

Federal Register

. This provides the required public notice and allows for a public comment period. Other participants and other interested parties retain their rights to comment, participate in an informal hearing (if requested), and seek judicial review. OSHA anticipates, however, that the pre-proposal consensus reached by the Committee will effectively narrow the number of controversial issues in the subsequent rulemaking.

The Negotiated Rulemaking Act of 1990 (5 U.S.C. 561

et seq.

) (NRA) allows OSHA to establish a negotiated rulemaking committee if it is determined that using the negotiated rulemaking procedure is in the public interest. As noted above, OSHA has made this determination for this rulemaking activity. Each committee member participates in resolving the interests and concerns of other members instead of leaving it up to OSHA to bridge different points of view. A key principle of negotiated rulemaking is that agreement is reached by consensus of all the interests. The NRA defines consensus as unanimous concurrence among the interests represented on a negotiated rulemaking committee, unless the committee itself unanimously agrees to use a different definition of consensus.

The Agency determined that the selection criteria listed in the NRA were met, and that there was a need to issue fire protection requirements that would apply to all shipyard employment. Finally, parties representing significant interests requested that OSHA use the negotiated rulemaking process on subpart P and acknowledged the need for a new standard.

The members of the Committee are: Chris Myskowski, U.S. Coast Guard; Paul Jensen, NIOSH; Joseph V. Daddura, Office of Maritime Standards, Occupational Safety and Health Administration; G. F. Hurley, Norfolk Naval Shipyard; Richard Duffy, International Association of Firefighters (AFL-CIO, CLC); E.P. Kaiser , South Tidewater Association of Ship Repairs, Inc.; Guy Colonna, National Fire Protection Association; Russ Sill, Portland Fire Bureau; Alton Glass, United Steel Workers of America (AFL-CIO, CLC), who was later replaced by John Molovich; George Broussard, Bollinger's Shipbuilding and Ship Repair, who was later replaced by Mark Duley, Walker Boat Yard, Inc.; Glenn Harris, Ingalls Shipbuilding; Donald Mozick, Atlantic Marine, who was later replaced by Terry Guidry, Bollinger's Shipbuilding and Ship Repair; Michael Buchet, United Brotherhood of Carpenters and Joiners of America, who was later replaced by Joseph Durst; J.D. Paulson, National Steel & Shipbuilding Co., Peter Schmidt, Office of Specialty Compliance Programs, Washington State Department of Labor and Industry.

The first meeting of the Committee was held in Portland, Oregon, on October 15, 16, and 17, 1996, and was open to the public, as were all subsequent meetings. (All minutes and documents from the Committee meetings can be found in Exs. 5-1 through 5-. Minutes were recorded by OSHA staff for the Committee.) During this organizational meeting, the members were charged with their duties and procedural matters were addressed. The members adopted ground rules for the Committee and set forth substantive issues that needed to be resolved. The rulemaking process was explained in depth to the Committee members, so that they would understand their role in the process. SESAC's proposal on fire protection in shipyards was given to the Committee.

Several examples of firefighting were given by members of the Committee and discussions were held after each example, including how small businesses contact outside fire departments for assistance with firefighting. Workgroups were established for the following areas: Fire Watch, Safe Work Practices, Fire Response, and Fire Protection. These workgroups were charged with producing a draft regulatory text and rationale for their parts of the safety standard. These drafts were to include definitions and several options in areas where the members of the workgroup did not agree. The Committee agreed to include sea trials in the scope of this regulation. Also at this meeting, an overview and history of the SESAC Draft Proposed Standard for Fire Protection was presented by a member of SESAC's workgroup. The draft, text, and rationale of SESAC's recommendations were reviewed. As was to become routine at meetings, the Committee and other participants toured nearby shipyards. They were MarCom Inc., Vancouver, Washington (small shipyard); Diversified Marine Incorporated, Portland, Oregon (small shipyard); and Cascade General, Portland, Oregon (large shipyard).

The second Committee meeting was held in Jacksonville, Florida on February 4, 5, and 6, 1997. The Committee discussed several key issues: Should subpart P—Fire Protection for Shipyard Employment—apply to all shipyard employment? How will the standard affect out-of-yard/plant firefighters such as those employed by a municipal fire department? What controls and work practices will provide adequate protection for workers? Should OSHA require hot work permits? Should OSHA require training for all firefighters? Should OSHA incorporate U.S. Coast Guard regulations in this standard? Is there any difference in controls and work practices on land-side verses on board vessels and vessel sections? Should OSHA require the employer to secure (deactivate) all firefighting systems on board vessels when they arrive in the yard? Should OSHA require each shipyard to have an in-yard/plant fire brigade? Should OSHA require written fire plans for land side and on board vessels? If so, what provisions need to be included in the plans? Should OSHA include a requirement for de-watering (removal of firefighting water from the vessel) of vessels when fighting a fire on board a vessel? What advances in fire technology have occurred since OSHA's general industry standards were published that should be incorporated into the shipyard employment standard? Should OSHA include technical information in an appendix or appendices? If so, should appendices be mandatory?

The Committee had a lengthy discussion about OSHA's jurisdiction. OSHA has no jurisdiction over municipal firefighters, but states and territories with OSHA-approved State Plans are required to have standards for state, county, and local government entities that are at least as protective as Federal OSHA's.

Small employer representatives included: T.L. James & Company, Houma, Louisiana; Halter Marine, New Orleans, Louisiana; and Alabama Shipyard/Atlantic Marine, Mobile Alabama. A Chicago municipal firefighter also attended. Committee members and the public participants at this meeting took a tour of Atlantic Marine (small shipyard).

A Fire Watch section workgroup met at Charleston, South Carolina, on March 18, 1997. The workgroup was tasked with developing proposals to be presented to the full Committee. Discussions included the Navy's NAVSEA 00907 Fire Prevention and Housekeeping standard of September 13, 1996. The workgroup agreed that NAVSEA 00907 was not applicable to the safety of workers because its focus was on the protection of property. The workgroup also agreed on two proposals to present to the full Committee: That an employee performing hot work should never be his or her own fire watch, and that training requirements should be performance oriented. For example, for training employers could use stand-up tool-box safety meetings or written training documents as a basis for appropriate training sessions. Suggestions for identifying a fire watch included: Stickers on hats, arm bands, and vests. The topic of live-fire training was raised as an issue for the full Committee to consider.

The third public meeting of the Committee was held in Lockport, Louisiana, on April 8, 9, and 10, 1997 (Ex. 5-3). The Committee's workgroups continued working on the issues of scope and application, controls and work practices, fire brigades, written fire plans, technological advances in fire protection, costs of fire protection, and appendices. There were discussions about small employer difficulties and on Coast Guard jurisdiction over vessels during sea trials. Preliminary drafts of proposed changes and preamble language were circulated among committee members for review and comment. At this meeting the Committee decided that issues upon which general agreement could not be reached would be raised for public comment in the proposal's preamble. By doing so, an issue, such as live fire training, would be considered by the public and OSHA and could become part of a final rule. Small employer representatives in attendance were: Walker Boat Yard; Halter Marine; Leevac Shipyard; Boland Marine; and Bollinger Shipyard. The Committee members and other participants toured the Bollinger Lockport facility and two other Bollinger facilities in the area (small shipyards).

The fourth public meeting of the Committee was held in Baltimore, Maryland on July 15, 16, and 17, 1997

(Ex. 5-6). During this meeting the Committee broke out into its workgroups and continued to develop proposed preamble and regulatory text on the issues that were identified in previous meetings. OSHA staff explained the economic feasibility issues that are brought into rulemaking and gave a briefing on “plain language.” Carryover discussion items from the previous meeting were OSHA's lack of jurisdiction over civilian guests on board vessels during sea trials, municipal fire departments, and volunteers. The discussions produced several examples of current practices from members of the Committee.

There was a discussion about the hazards of fixed extinguishing systems and members gave examples of current practices. A large West Coast shipyard disconnects the vessel's system because they do not want it to be accidentally activated. A representative from small shipyard on the inland waterways noted that he prefers not to deactivate a vessel's fixed extinguishing system, especially for a short-term repair job. For this type of short-term repair job, the Committee agreed that there are two options: Disconnect the entire system or train employees. Some members indicated that on some manned Navy vessels, deactivating the fixed extinguishing system is not an option. It was also noted that, on U.S. flag vessels the U.S. Coast Guard requires a time delay on fixed systems to allow employees to evacuate before the extinguishing agent is released or automatic locking doors are activated. There was an incident in Spain where a small fire on board a vessel was under control locally when another employee pulled the fixed fire system, causing fatalities. A presentation was given on a fire aboard the

Melvin H. Baker II,

which occurred during a hot work operation and caused a fatality.

There was also a discussion of how a fire watch can alert others before he or she exits the dangerous areas, which fire watch duties should be included in safe work practices, and the important role of the fire watch in preventing fires and loss of life. A workgroup was established to work on the definitions section of the standard. Small employers were represented by: Bollingers Shipyard, Lockport, Louisiana, and the National Shipbuilders Association, Arlington, Virginia.

The fifth meeting of the Committee was held in Paducah, Kentucky, on October 7, 8, and 9, 1997 (Ex. 5-4). At the request of the Shipbuilders Council of America (SCA), OSHA staff held a preliminary meeting on October 6. This meeting was open to the public and SCA invited small employers to be present. OSHA staff made presentations on the negotiated rulemaking process, OSHA's standards writing process, and the intent of the proposed Fire Protection standard. The OSHA Project Attorney reviewed the ground rules for negotiated rulemaking procedures, and answered more specific questions that the Committee had raised, such as regulating small businesses. Some workgroups presented their draft documents for discussion and approval by the full Committee. Those documents that were approved by the Committee were delivered to OSHA for further action. Some of the other topics of discussion were: Sliding/rolling fire doors, inadvertent activation of a ship's CO

2

system, and live fire training. Small employer representatives in attendance were: Bollinger's Shipyard, Lockport, Louisiana; James Marine, Inc., Paducah, Kentucky; Cascade General, Inc., Portland, Oregon; Newpark Shipbuilding & Repair, Houston, Texas; Missouri Dry Dock, Cape Girardeau, Missouri; Mid South Towing, Metropolis, Illinois; Sea River Maritime; and American Commercial Marine Service Co. Unions representatives were present from Firefighter Local 168, Paducah, Kentucky and IBEW Local 733, Pascagoula, Mississippi. Committee members and the public participants toured two small shipyards, Walker Boatyard and James Marine, Inc., Paducah, Kentucky.

The sixth public meeting of the Committee was held in San Diego, California, on February 24, 25, and 26, 1998 (Ex. 5-5). Discussions at this meeting included the Small Business Regulatory Enforcement Fairness Act (SBREFA), the general industry (29 CFR part 1910) regulations that apply to landside operations, and live fire training for fire watches. During this meeting, the Committee approved the regulatory text on hot work. Small employer representatives at this meeting included: Bollinger's Shipyard, Louisiana; Walker Boat Yard, Kentucky; Sea River Maritime; and South Tidewater Association of Ship Repairers (STASR), Hampton Roads, Virginia. The Committee member representing STASR noted that the negotiated rulemaking issues and products are shared by the member with 121 STASR members, who are mostly small employers. Committee members and the public participants at this meeting took a tour of the NASSCO and the NAVAL shipyards.

The seventh meeting of the Committee was held in Linthicum, Maryland on June 15, 16, and 17, 1998 (Ex. 5-9). The Committee decided that since MACOSH has supported the Committee and intends to review its products, the Committee's recommendation for a proposed standard will be made available to them. A lengthy discussion was held on shipboard fixed fire protection systems, during which the Committee members learned that only CO

2

systems have caused fatalities. This led to further discussion about whether or not an employer would rely on a vessel's fixed system as the primary source of fire protection., and prompted a page-by-page review of the fire response section. Topics discussed included the term “qualified instructor,” personal protective equipment, hose testing, and how long records must be kept.

During the second day of this meeting, the Acting Director of OSHA's Office of Regulatory Analysis presented an overview of what requirements OSHA's economic analysis must meet. A representative from the Small Business Administration (SBA), Office of Advocacy also answered questions from the Committee and public on issues related to small businesses. After a review, the Committee voted to accept the preamble of shipboard fixed systems. The Committee further agreed to not bring sections of 29 CFR part 1910 over into 29 CFR part 1915 for land-side fixed systems, because members prefer that fire extinguishers, stand pipes, or sprinklers conform to NFPA 10, Standard for Portable fire Extinguishers, 1998 Edition (Ex. 20-1) rather than the older OSHA general industry standards for this type of equipment.

The issue of records retention was reviewed. It was agreed that the proposal will state that records must be kept and made available for one year; however, an issue will be raised on one year versus three years retention. Large shipyards typically keep their records indefinitely, but in the opinion of several of their representatives, they would rather not be told how long records must be kept.

Small employer representatives at this meeting included: Bollinger's Shipyard, Louisiana; Walker Boat Yard, Kentucky; and South Tidewater Association of Ship Repairers, Hampton Roads, Virginia. A representative from National Shipbuilders Association, Arlington, Virginia, also attended.

The eighth meeting of the Committee was held in Biloxi, Mississippi, on September 9, 10, and 11, 1998 (Ex. 5-7). Topics of discussion included the progress that the definitions workgroup was making and the outreach programs previously completed. The public was polled about their expectations from

this negotiated rulemaking on fire protection. Other discussions were held on what to do with burning torches, what the extent of the standard was, where fire watches are not needed, and how to ensure that the 29 CFR part 1910 requirements are updated and that they cover the same work as subpart P.

The following list of issues was distributed and discussed by the Committee: Can a fire response count as a drill? Is the inspection required in the proposal's section 504(a) and (b) already covered in 1915.14, or does the proposal mandate that all areas—other than those that require a Marine Chemist or Shipyard Competent Person's inspection—be inspected before hot work? In section 505, Fire Response, should OSHA require proximity firefighting protective clothing for all yards and fire departments? Should an employee have the right to stop work if the employee felt he or she was placed in a dangerous situation? Does the committee want to require the employer to instruct on-site contractors on their fire plans? What is an “authorized area?” Is a welding shop, sheet metal shop, fabricating shop, or subassembly area to be considered an authorized area? If so, does the Committee want the employer to post signs to notify employees? How does the employer determine the authorized area? Is it the Committee's understanding that the employer is to survey his shipyard to determine and label all working areas? How is the issue of municipal fire departments' response to shipyard fires to be explained in the preamble? How can the Committee ensure that the public understands that this standard does not apply to state, county, or municipal fire departments?

Other issues discussed included: Proximity suits; a model training program for fire watches; employee participation; fire watch training; the requirements of subpart B, Confined and Enclosed Spaces and Other Dangerous Atmospheres in Shipyard Employment, that could apply in the hot work section; training requirements for all shipyard employees versus training only fire watches; liaisons between shipyards and outside fire responders; and the proposed requirement that all fire hoses used by the employer being labeled, tested, and maintained in accordance with NFPA 1962-1998 Standard for the Care, Use, and Service Testing of Fire Hose Including Couplings and Nozzles, 1998 Edition (Ex. 20-2). The Committee agreed on the regulatory text of proposed §§ 1915.505 and 1915.506.

A small shipyard representative requested that OSHA have an extended compliance date for employers with 250 or fewer employees. Shipyards with more than 250 employees typically have a full-time designated safety and health professional, based on the experience of the National Shipbuilders Association. A labor representative opposed the request for a delay in implementation for small employers. It was suggested that OSHA review the issue for its proposal.

Small employers were represented at this meeting by Bollinger Machine Shop & Shipyard, Inc., Louisiana; Walker Boat Yard, Kentucky, South Tidewater Association of Ship Repairers, Hampton Roads, Virginia; National Shipbuilders Association, Arlington, Virginia; First Wave Marine, Houston, Texas; Bender Shipbuilding, Mobile, AL; and Omega Shipyard, Moss Point, Mississippi.

The ninth meeting of the Committee was held in Houston, Texas, on February 5-7, 2002 (Ex. 5-8 ). OSHA staff incorporated the agreed upon changes made during this meeting into the Committee's working document. A motion was made for a full Committee vote on the document. The Committee unanimously approved, agreeing on all the issues and topics. A reworked package of the regulatory text including section number changes with training in its own section was mailed to the Committee March 2002.

Small employers were represented at this meeting by Bollinger Machine Shop & Shipyard, Inc., Louisiana and Texas; Walker Boat Yard, Kentucky; South Tidewater Association of Ship Repairers, Hampton Roads, Virginia; National Shipbuilders Council, Washington, D.C.; First Wave Marine, Houston, Texas; Trinity Marine Products; Moon Engineering, Co., Portsmouth, Virginia; and Atlantic Marine/Alabama Shipyard.

Informal meeting minutes were provided by OSHA staff for all meetings. These minutes were approved by the Committee and included in OSHA's Docket S-051 (Ex. 5). The Agency has taken the Committee's recommendations for a proposal for fire protection in shipyard employment and editorially revised them into the proposed standard that follows this preamble.

III. Pertinent Legal Authority

The purpose of the Occupational Safety and Health Act, 29 U.S.C. 651

et seq.

(“the Act”) is to “assure so far as possible every working man and woman in the nation safe and healthful working conditions and to preserve our human resources' (29 U.S.C. 651(b)). To achieve this goal, Congress authorized the Secretary of Labor to issue and enforce occupational safety and health standards. (

See

29 U.S.C. 655(a) (authorizing summary adoption of existing consensus and federal standards within two years of the Act's enactment), 655(b) (authorizing promulgation of standards pursuant to notice and comment), 654(b) (requiring employers to comply with OSHA standards).) A safety or health standard is a standard “which requires conditions, or the adoption or use of one or more practices, means, methods, operations, or processes, reasonably necessary or appropriate to provide safe or healthful employment or places of employment.” 29 U.S.C. 652(8).

A standard is reasonably necessary or appropriate within the meaning of section 652(8) if it substantially reduces or eliminates significant risk; is economically feasible; technologically feasible; cost effective; is consistent with prior Agency action or is a justified departure; is supported by substantial evidence; and is better able to effectuate the Act's purposes than any national consensus standard it supersedes. See 58 FR 16612-16616 (March 30, 1993).

A standard is technologically feasible if the protective measures it requires already exist, can be brought into existence with available technology, or can be created with technology that can reasonably be expected to be developed.

American Textile Mfrs. Institute

v.

OSHA

452 U.S. 490, 513 (1981) (“ATMI”),

American Iron and Steel Institute

v.

OSHA,

939 F.2d 975, 980 (D.C. Cir 1991) (“AISI”).

A standard is economically feasible if industry can absorb or pass on the cost of compliance without threatening its long term profitability or competitive structure.

See ATMI,

452 U.S. at 530 n. 55;

AISI,

939 F.2d at 980. A standard is cost effective if the protective measures it requires are the least costly of the available alternatives that achieve the same level of protection.

ATMI,

453 U.S. at 514 n. 32;

International Union, UAW

v.

OSHA,

37 F.3d 665, 668 (D.C. Cir. 1994) (“LOTO II”).

Section 6(b)(7) authorizes OSHA to include among a standard's requirements labeling, monitoring, medical testing and other information gathering and transmittal provisions. 29 U.S.C. 655(b)(7).

All standards must be highly protective.

See

58 FR 16614-16615; LOTO II, 37 F.3d at 668. Finally, whenever practical, standards shall “be expressed in terms of objective criteria and of the performance desired.” Id.

IV. Summary and Explanation of Proposal Rule

Section 1915.501 General Provisions

In paragraph (a), OSHA states that the purpose of this standard is to require employers to protect all employees from fire hazards in shipyard employment, including employees engaged in fire response activities.

Paragraph (b) describes the scope of the proposal, which is all shipyard employment work, including work on vessels and vessel sections and land-side operations, regardless of geographic location. The scope of this subpart is consistent with that in the maritime standards' subpart B Confined and Enclosed Spaces and Other Dangerous Atmospheres in Shipyard Employment and subpart I Personal Protective Equipment for Shipyard Employment. Fire response provided by the employer's workers, whether they be part of a fire brigade, shipyard fire department, or simply designated by the employer, is within the scope of this standard. There are several reasons for including all shipyard employment in the scope of this standard: (1) The requirements are tailored to the unique risks in shipyard employment; (2) subpart P will provide a single source of standards for fire protection that will be easier for training and to understand than multiple sources or sets of rules; (3) a comprehensive standard, referencing part 1910 where necessary, will be applicable throughout shipyard employment addressing hazards associated with fire watch situations, ship fire suppression systems, fire response procedures and landside fire operations.

OSHA has preliminarily concluded, and the Committee agrees, that a comprehensive standard applying to all shipyard employment operations will be highly protective of shipyard employment workers working on vessels, vessel sections, or landside operations and offer the best protection against fire hazards.

Shipyard employment can consist of shipbuilding, ship conversion, ship repairing or shipbreaking, and related employments. Shipyards may be dedicated to one type of work, such as new ship construction, or a shipyard may perform any or all types of shipyard work. The construction of a new vessel may be a single project or may involve separate fabrication of key components which are then joined together. Vessel sections may be fabricated on land within the shipyard, or may be built in specialty facilities inland of the shipyard and then transported to the yard. The scope must have broad coverage because shipyard employers increasingly engage in non-traditional shipyard employment such as steel fabrication of products not directly related to ships. This could include work such as construction of railroad cars, bridges, tunnel sections, smoke stacks, and boilers. It could also include operations performed during the final outfitting of vessels under construction or repair. Examples of such operations include technical support from the providers of shipboard electronic equipment as well as suppliers of internal furnishings. It does not include shoreside support services, such as those provided by vending equipment and mail delivery companies. The Agency is also proposing that any fire brigade, shipyard fire department, contracted outside fire response organization, or federal fire response organization be covered by this subpart if the responder is located at or responds to shipyard employment facilities. OSHA recognizes that a number of small employers perform vessel repair in non-traditional shipyards and intends to cover them.

Ship repair work could involve replacing damaged hull sections, outdated systems or components, or modifying a vessel to increase its capacity or change its designed purpose.

Shipbreaking could consist of the partial removal of vessel components or it could be the complete dismantling of a vessel (also known as “scrapping”) for the salvage value of its parts.

Shipyard employment can also consist of support operations necessary for vessel construction and repair. Metal fabrication, machine shops, electrical and paint shops are typical facilities that can be found within a shipyard. Many vessel sections and vessel components are built in these shops more easily than they can be built on board a vessel. The materials are the same and often the hazards encountered are similar.

Shipyard employment also occurs on vessels and vessel sections within the navigable waters of the United States. The provisions of the Longshore and Harbor Workers' Compensation Act (LHWCA), 33 U.S.C. 901

et seq.

, only applied to shipyards. Under the OSH Act, jurisdiction was extended to include workers wherever they were working.

1

1

See

29 CFR 1910.11(b). The LHWCA limitations on coverage that appear in the maritime standards were not adopted under section 6(a) of the OSH Act, 29 U.S.C. 655(a).

See also

the preamble for the rulemaking in which the shipyard employment standards were consolidated, 47 FR 16986 (April 20, 1982). This OSHA policy was accepted by the Occupational Safety and Health Review Commission in

Dravo Corporation,

10 BNA OSHC 1655 (No. 14818, 1982.)

Contra Dravo Corporation

v.

OSHRC & Marshall,

613 F.2d 1227 (3rd Cir. 1980).

OSHA has included the phrase “regardless of geographic location” in the scope so that protection is afforded employees wherever they work: On vessels, vessel sections, land side, or any other location they are sent to by their employers. This has been Agency policy on shipyard employment and is in the scope of both subparts B and I.

The Committee also urged OSHA to cover work in the traditional shipyard and dock as well as on vessels during sea trials or at anchor. At the Portland, Oregon, meeting, the Committee noted that most ships on sea trials are still under construction with shipyard workers on board. At the Baltimore, Maryland, meeting, Committee members reviewed OSHA Instruction CPL 2-1.20, “OSHA/U.S. Coast Guard Authority Over Vessels,” dated November 8, 1996. Particular attention was given to paragraph I which delineated geographical considerations for enforcement over all vessels. The CPL states that “OSHA only has authority over vessels when they are operating within the limits of State territorial waters.” It goes on to define those waters as extending three nautical miles seaward from the coast line of coastal States, “except for the Gulf Coast of Florida, Texas and Puerto Rico where the territorial waters extend for 3 marine leagues (approximately 9 nautical miles).”

The Committee concluded that the fire hazard exposure to workers is significant, whether a vessel or part is being constructed, repaired, or broken up and whether it is in the shipyard or dockside, at anchor, or underway for testing. Therefore, the requirements proposed in this subpart would apply broadly, including vessels underway within OSHA's jurisdictional boundaries, or at anchor, dockside, in dry dock, or on land.

In paragraph (c) of § 1915.501, OSHA seeks to encourage employee participation in shipyard safety and health program activities. OSHA proposes that the employer must provide ways for employees and employee representatives to participate in developing and periodically reviewing programs and policies adopted to comply with this standard. At the September 10, 1998, meeting held in Biloxi, Mississippi, the Committee recommended regulatory text regarding employee participation and involvement. The Committee saw this as a crucial component of the

proposed standard and OSHA agrees. This proposal is consistent with the Department of Labor's policy to involve employees in decision-making processes affecting safety and health at their worksites.

Paragraph (d) of the proposed fire protection rule sets minimum requirements for exchanging information and coordinating responsibilities for fire protection among host and contract employers. These requirements are fundamental to any effective fire safety program on a multi-employer worksite.

A multi-employer workplace is defined for the purposes of this rule as a workplace where there is a host employer and at least one contract employer. This proposed requirement is necessary because the existence of additional employers and their employees at a workplace makes addressing safety and health conditions at the workplace more complex. For example, at a multi-employer worksite, one employer may introduce hazards into the workplace that employees of other employers may not know about. All employers need information about hazards present at the worksite to enable them to fulfill their obligations to protect workers. For these reasons, communication and coordination among employers are essential.

Failure to communicate about hazards between employers and their employees can be tragic. For example, the 1989 explosion at a Phillips 66 chemical complex in Houston, which killed 23 people and injured more than 100 workers, resulted largely from the failure to coordinate safety and health activities on a multi-employer worksite. A Department of Labor/OSHA 1990 report to the President concerning this catastrophe concluded:

The catastrophe at the Phillips Complex not only emphasized the need for effective implementation of good safety management systems in the petrochemical industry but also raised questions about diffused responsibility for employee safety at worksites where one or more contractors are engaged in work for a company. OSHA had addressed this issue at construction sites, but not at petrochemical plants like the Phillips Complex, where a contractor was regularly employed to perform key maintenance operations and was directly involved in the October 1989 disaster (Ex. 10-5).

Events like the Phillips explosion and the increased reliance on using contractors throughout the shipyard industry have led OSHA to conclude that responsibility for fire safety must be specifically assigned to all employers, who must then be held accountable for discharging those responsibilities.

The need for and benefits of coordinating activities and exchanging information on multi-employer worksites are widely recognized, and requirements such as those being proposed here have been implemented in many workplaces throughout general industry, construction, and maritime industries. For example, the Chemical Manufacturers Association (now the American Chemistry Council) and the American Petroleum Institute state that improved occupational safety and health performance is one benefit that occurs when owners and contractors work together to enhance the management of contractor-related safety and health programs. Similarly, the National Safety Council has observed that “a strong partnership between [host and contract employers] can reduce or eliminate risks, injury, and illnesses; help control health and insurance costs; and improve employee production and morale.” In the shipyard industry it is common practice to hire contractors for nonroutine or specialized work situations. For example, painters, joiners, carpenters and scaffolding contractors are routinely used in shipyard employment.

The requirement for host and contract employer coordination and for the exchange of information about safety and health conditions on multi-employer worksites is consistent with Congress' desire that employees be informed of the hazards to which they are exposed. (Sections 6(b)(7) and 8(c)(1) of the OSH Act.) Employees can only be informed of the hazards to which they are exposed if information about such hazards is communicated among employers on multi-employer worksites. Such an exchange of information is also necessary to make sure that all hazards in the workplace are identified and that the responsibility for controlling them and protecting employees can be appropriately allocated among all employers on the site.

Under the proposal host employers must inform all employers at the work site about the contents of the host's fire safety plan—including hazards, controls, and emergency procedures—and assign any appropriate responsibilities for fire safety to other employers. The Committee is in agreement with this approach to multi-employer worksites (Ex. 5-8). The employer representatives on the Committee felt that the shipyard should not be responsible for training contractors.

In § 1915.509 Definitions, the host employer is defined as an employer who is in charge of coordinating work or hiring other employers to perform work at a multi-employer worksite. Proposed § 1915.501(d)(1) establishes the responsibilities of host employers. First, host employers must make sure that information about fire hazards, controls, safety and health rules, and emergency procedures is given to all the contract employers. The information includes whatever a contract employer must have to carry out his or her own duties as an employer under this rule. Contract employers need to inform employees of the fire hazards to which they are exposed at that worksite, the controls in place to reduce or eliminate those fire hazards, the safety and health procedures to be followed, and the steps to be taken in a fire emergency. Second, host employers must ensure appropriate fire safety and health responsibilities are assigned to contract employers at the worksite.

Contract employers must know about other hazards related to fire their employees may encounter at the workplace. Such knowledge allows contract employers to effectively plan and safely carry out their work and understand procedures, such as what to do when a fire alarm is sounded to evacuate a vessel. This information lessens the likelihood that accidents will occur. A host employer's workplace may have fire hazards of many kinds: toxic chemical, flammable or combustible liquids or dusts, electrical hazards, fall hazards, pressurized systems, confined spaces, and many more. Under this standard host employers must inform contract employers of the hazards related to fire they are likely to encounter to enable them, in turn, to protect their employees.

The Committee recognized that in the event of a fire emergency, contract employers must be able to take appropriate actions to protect their employees. Therefore, OSHA requires the host employer to make sure that all appropriate information about fire safety and evacuation procedures is conveyed to all contract employers working in shipyard employment.

OSHA is also requiring in paragraph (d)(1)(ii) that the host employer make sure that fire protection responsibilities are specifically assigned to the various employers working at a multi-employer worksite. The host employer must make sure that fire safety and health responsibilities are assigned as appropriate to other employers at the worksite. Some of these responsibilities include fire hazard abatement, informing employees of fire hazards before exposure, and stopping work because of an imminent danger

situation. A host employer might assign a contract employer the responsibility of preventing employees (other than the contract employer's employees) from being exposed to a hazard generated by the contract employer. For example, the host employer might require the contract employer to control the area around a painter to ensure that hot work is not permitted while painting is in progress. More generally, the host employer must, in conjunction with the contract employers, decide who is to train employees and control which hazards. The need to coordinate across organizational lines on a multi-employer worksite makes the clear assignment of responsibilities across those lines essential to achieve the overall goal of reducing employee exposure to potential fire hazards.

The proposed definition of “contract employer” in § 1915.509 Definitions is an employer who performs work under contract for a host employer or to another employer under contract to the host employer at the worksite. This definition specifically excludes employers who provide incidental services that do not influence shipyard employment (such as mail delivery or office supply services). The Agency recognizes that many vendors who work under contract to host employers do not engage in work that exposes their employees to the job-related hazards present at the site and do not themselves introduce new hazards to the site. This definition also makes sure, however, that contract employees engaged in work operations that do place them at risk, such as temporary labor (

e.g.

tank cleaners), blasting, and paint contractors are protected by the proposed provisions regarding multi-employer worksites.

As noted in this discussion, OSHA has provided additional definitions of “host employer” and “contractor employer” in order to help clarify multi-employer worksite provisions. In other places, the term “employer,” which is already defined in 29 CFR part 1915, is used to describe duties that are generally the host employer's as the employer with control of the overall worksite. We believe the intent of this approach is clear. The host employer has overall responsibility for fire protection at the worksite. However, in order to have effective fire protection, all employees on the site need to be aware of the hazards and the procedures established to deal with fires, regardless of who employs them. And all of the hazards on the site need to be identified and controlled, regardless of which employer has introduced the hazard to the workplace. Thus the provisions of the standard anticipate that an exchange of information will be required to ensure that fire protection is handled in a comprehensive and effective manner, and any necessary coordination of activities will occur. The Agency invites input on these terms and the way they are used in the proposed rule. Is it clear which employer is responsible in all of the proposed provisions? Is there another way to define or clarify which employer has responsibility for implementing the requirements?

The Agency is considering dropping the phrase “safety and health rules,” in paragraph (d)(i) that refers to the contents of the fire safety plan and dropping the phrase “safety and health” in reference to contract employers' responsibilities for fire protection activities in paragraph (d)(ii). The Agency has concluded that the reference to “health” or “safety and health” rules or responsibilities is confusing and vague in the fire safety proposal and that the scope of issues should be confined to fire safety.

Paragraph (d)(2) of § 1915.501, sets forth the proposed responsibilities for contract employer's. The contract employer must inform the host employer of any fire hazards that could be created by the work being performed by his or her employees, and what steps the contract employer must take to address those hazards. In addition, OSHA proposes that any hazards that were not identified by the host employer, but were identified by the contract employer, must be shared with the host employer.

Proposed paragraph (d)(2)(i) requires contract employers to make sure that the host employer is aware of the fire related hazards presented by the contract employer's work and how the contract employer is addressing them. The work performed by contract employers is commonly beyond the knowledge and expertise of the host employer and typically is not a part of the host employer's routine work. Contract employers are often hired precisely because they have special expertise. They offer a wide range of services, such as equipment repair and maintenance, blasting, painting, atmospheric testing of spaces, tank cleaning, and selected scaffold erection. Consequently, their work can present a set of hazards that are unfamiliar to the host employer. For these reasons, OSHA believes that the proposed rule must include minimum requirements for contract employers on multi-employer workplaces to report fire hazards to host employers. Proposed paragraph (d)(2)(ii) requires that contract employers advise host employers of any fire hazards unidentified by the host employer. In the course of his or her work, the contract employer may create or uncover fire hazards. The host employer must be made aware of all of the hazards, regardless of who created them, to enable him or her to coordinate the management of safety and health at a given multi-employer worksite.

Section 1915.502 Fire Safety Plan

The requirements for fire safety plans contained in this section were developed by the Committee based upon their combined professional experience and current industry practices. OSHA concurs with these recommendations. OSHA does not have any requirements for fire safety plans in its current standards.

The Committee recommended a program that would establish the location, type, and capacity of firefighting equipment such as extinguishers, fire hose and stand pipes, smoke detectors, automatic sprinklers, and other fixed firefighting systems in accordance with applicable fire codes. The plan must provide for the routine inspection, maintenance, and replacement of this equipment and mandate training for new workers and refresher training for all shipyard employment workers. Routine fire prevention inspections would be conducted by knowledgeable personnel with authority to correct deficiencies. The program would establish: Effective fire prevention measures for control of flammable and non-flammable compressed gases; identification and the control of ignition sources; the control of combustible materials; welding and hot work procedures and designated locations covering all operations (in addition to locations where hot work is authorized); and designated emergency evacuation routes and procedures.

The Committee felt that such a plan must be written. A written plan would enable employers and employees to see how the employer intends to protect workers; enable employers to readily exchange information; provide continuity of procedures; and would provide a practical means of communication to fire response organizations. Updating the plan to reflect changing fire control technology or changing the plan to reflect different fire hazards in different work situations is readily accomplished with a written plan. The Committee rejected the notion of verbal exchange as the equivalent of an established written fire safety plan.

In paragraph (a) of § 1915.502, OSHA proposes that the employer develop and implement a written fire safety plan that covers all the actions that employers

and employees must take to ensure employee safety in the event of a fire. OSHA is also proposing to include a note to the paragraph referring readers to a model fire safety plan that is included as Appendix A, a non-mandatory appendix to this subpart.

Appendix A contains a suggested outline for a model fire safety plan that employers could follow. Members of the small business community who participated in Committee negotiations strongly recommended that OSHA offer guidance for developing a fire safety plan. The purpose of the proposed appendix is to give guidance to any employers who may not have the expertise available to develop their own plan. If an employer chooses to use the model plan for a specific worksite, following the outline and addressing particular conditions at his or her specific worksite would meet the minimum requirements of this section.

In paragraph (b) of § 1915.502, OSHA sets forth the elements that the employer must include in the fire safety plan. They are: The identification of significant potential fire risks; procedures for recognizing and reporting unsafe conditions; alarm procedures; procedures for notifying employees of a fire emergency; procedures for notifying fire response organizations of a fire emergency; procedures for evacuation; procedures to account for all employees after an evacuation; and the names, job titles, or departments for individuals who can be contacted for further information about the plan. The Committee identified these elements as essential components that every effective plan must have. The Committee was particularly anxious for the alarm procedures to address the distinctive signaling devices and how they will be used to alert employers of fire and evacuation in a particular shipyard. The Committee and OSHA recognized that each shipyard may have its own unique alarm systems (

e.g.

, steam whistles, intercom, bells).

In paragraph (c) of § 1915.502, OSHA proposes that the employer must review the fire safety plan with each affected employee within 90 days of the effective date of this standard for employees who are currently working; upon initial assignment for new employees; and whenever the actions the employee must take under the plan change because of a change in duties or a change in the plan.

Paragraph (d) of § 1915.502 reflects the recommendations of the Committee. Consistent with that, OSHA proposes that the employer must also keep the plan readily accessible for review by employees, their representatives, and OSHA; review and update the plan whenever necessary but at least annually; certify in writing that each affected employee has been informed of the plan; and give a copy of the plan to any outside fire response organization that the employer expects to respond to fires at a worksite, regardless of geographic location. These requirements are necessary in order for the plan to be effective in protecting employees.

In paragraph (e) of § 1915.502, OSHA proposes as additional responsibilities for contract employers, compliance with the host employer's fire safety program. At any given time, because of the nature of the work, there may be many employers within one particular shipyard. The additional employers and employees cause an increase in safety and health hazards in the worksite. OSHA's intent with this paragraph is that all employers take responsible actions to reduce these hazards when possible, and to alert other employers when hazards exists. Recognition of hazards and response to emergencies in a safe manner requires all employers on the site to follow the host employer's fire safety plan.

Section 1915.503 Precautions for Hot Work

The purpose of this section is to reduce the potential of fire hazards and to reduce the frequency and severity of any fires resulting from hot work. Three elements are normally present for a fire to occur: an ignition source, oxygen, and a fuel source. If one element is removed, then a fire will not occur. The proposed requirements in this paragraph are intended to prevent the combination of these three elements from occurring at the same time.

The Committee's proposal focused on reducing the hazards associated with both the fuel sources as well as the ignition sources for fires. The Committee advocated removing any fuel source from the area where hot work was to be performed. If that is not possible, then isolating the fuels, using protection (shielding), or posting a fire watch can be used to comply with the provision. These requirements reflect current industry practices and the requirements associated with § 1915.14 for flammable and combustible materials within confined and enclosed spaces and other dangerous atmospheres. The Committee also identified other materials that may be present that have properties that may increase the hazards associated with a fire, such as oxidizers and water reactive chemicals. The Committee's proposal would require the employer to perform a hazard assessment as part of the decision-making process in authorizing hot work. The Committee concluded that fires resulting from hot work can be prevented through an authorization procedure and proper inspection of the worksite before hot work. This would involve identifying fire hazards and implementing appropriate control measures that include removing hazards, inerting spaces, shielding combustibles, or posting fire watches. The Committee believed this would be an innovative approach that protects shipyard workers from fire hazards while reflecting the best practices of the industry.

Following the Committee's recommendations, OSHA proposes that the requirements of this standard apply to all hot work operations in shipyard employment except those covered in subpart B of this part. The purpose of OSHA's proposed requirement is to make sure that the employer identifies all fire hazards in a hot work area. This section is also based upon requirements adapted from the existing § 1915.52 Fire Prevention, § 1910.252 Welding, Cutting and Brazing, and from an industry consensus standard, NFPA 51B-1998, Standard for Fire Prevention in Use of Cutting and Welding Processes (Ex. 20-3).

In paragraph (a)(1) of § 1915.503, OSHA is proposing that the employer, in designating areas for hot work, must determine that such areas do not contain potential fire hazards. The Committee recognized that there are areas within the shipyard that may not require an inspection before each hot work operation. These areas may, in fact, be designed for hot work. They include fabricating shops, sub-assembly areas, and welding and burning areas within shops, such as pipe, boiler, and sheet metal shops. These areas are examples of what the Committee considered to be “Designated Areas” along with certain areas on board vessels and vessel sections. In “designated areas” the hot work operations are regular and continuous as opposed to incidental operations occurring throughout the yard. Nonetheless, such areas must be initially inspected to establish them as “designated areas” and then maintained as such, as proposed in paragraph (b)(1) of this section.

The requirement for authorization of hot work in nondesignated areas is addressed in paragraph (a)(2) of this section. In paragraph (a)(2)(i) of § 1915.503, OSHA proposes that before authorizing hot work in non-designated area, the employer must visually inspect the area where hot work is to be performed, including adjacent spaces, to

identify potential fire hazards, unless a Marine Chemist's certificate or shipyard Competent Person's log is used for the authorization. The Committee recommended that this section include any area not covered by subpart B of this part. As mentioned earlier, OSHA is not addressing hot work in areas covered by subpart B Confined and Enclosed Spaces and Other Dangerous Atmospheres in Shipyard Employment. This subpart already covers the hazards of performing hot work in these areas. Addressing them again in this subpart would be duplicative. OSHA believes that by requiring authorization before hot work in the non-designated areas, the employer will pre-plan the operation and thereby identify and control the hazards associated with hot work.

OSHA notes that although Marine Chemists and Shipyard Competent Persons have specific functions to perform under subpart B, this paragraph recognizes that the employer may also use them to assess and inspect both designated and nondesignated hot-work areas for potential fire hazards.

The Committee considered whether the authorization of hot work issued by the employer should be in a written form or whether a verbal authorization would give equivalent safety. Currently all shipyards handling repair or overhaul-type U.S. Navy contracts have written authorization procedures because Navy work requires authorization (hot work permits) as a standard item. On the other hand, shipyards that do not handle Navy contracts allow employees to perform hot work following either verbal or written authorizations. The Committee decided that shipyard employers should have the flexibility to decide what type of authorization is best suited for their hot-work operations. For example, in many cases associated with new construction, hot work is done with an authorization specifying that no special precautions are required and no written authorization (permit) is issued. The intent here is to enable the employer to perform the steps and to assess the hazard each time before authorizing the hot work, but not necessarily introduce the specification that requires a formal written permit. Therefore, in this paragraph OSHA does not specify what form of authorization must be issued.

In paragraph (a)(2)(ii) of § 1915.503, OSHA proposes that the employer be allowed to authorize employees to do hot work only in areas that have been visually inspected and found to be free of fire hazards or in inspected areas where fire hazards are controlled by physical isolation, fire watches, or other positive means such as inerting.

In developing the proposed language above, the Committee discussed under what circumstances the employer may authorize hot work on board vessels and vessel sections. Everyone on the Committee agreed that decisions about authorizing hot work on board vessels and vessel sections must be based on the inspection. When the inspection shows that there are no uncontrolled combustible or flammable materials in the area, then authorization for hot work is appropriate. The Committee also recognized that most of the mid-to large-size yards pre-outfit ship sections with electrical cables and fixtures, insulation, and other combustible materials requiring the employer to decide for each section what type of fire protection should be provided when hot work is to be done.

The likelihood of the hot work areas containing combustible materials during ship repair is greater than in shipbuilding. During ship repair, as in other work the employer must control the fire hazards prior to authorizing the hot work. Control, as required in paragraph (a)(2)(ii), can be by physical isolation, posting fire watches, or other positive means. For example, an employer can achieve physical isolation of combustibles by simply moving them to an area at least 35 feet away from the hot work (

see

definition of “physical isolation”). The Committee discussed the 35-foot vertical and horizontal distance and found it to be consistent with current industry practice. Where combustibles can not be moved or otherwise physically isolated, the employer can post a fire watch to control the fire hazard. Additionally, when flammable atmospheres are found adjacent to the hot work area, the employer can control the fire hazard by inerting the adjacent space with a non-reactive substance that will not support combustion. For further information on controlling spaces (flammable atmospheres) adjacent to where hot work is being performed,

see

subpart B of this part.

Members of the public and shipyard representatives on the Committee commented during negotiations that the individual performing the hot work is usually expected to conduct his or her own final visual survey of the hot work area to make sure that conditions are safe for hot work. This is a common practice whether identified on a written permit or as part of the verbal authorization/assignment to the work. If the survey discovers unsafe conditions (

e.g.

, appreciable combustibles in an area, leaking lines of combustible liquids—hydraulic fluid, oil), then the worker will not initiate the work and will contact the individual authorizing the work for further instruction. It is also expected that work would not start until the situation was corrected. As explained by a Committee member, the employer is ultimately responsible for making sure that areas are inspected before hot work and that safe conditions are maintained throughout the hot work area. This may be done by requiring frequent inspection, training, or warning signs even when the employer has delegated the responsibilities for the inspections. OSHA has not proposed to require the hot worker to conduct a survey as the Agency believes the employer has the responsibility for determining if the area is safe. An employer may, of course, have such a survey as part of his or her work practices.

While subpart B has a requirement that a record be prepared by the Marine Chemist, Coast Guard Authorized Person, or Shipyard Competent Person allowing the hot work to be authorized as defined by § 1915.14, not all hot work areas need to be certified by a Marine Chemist or inspected by a Coast Guard Authorized Person or Shipyard Competent Person before the employer's authorization for hot work to begin. The employer may assign the authorization responsibility to other individuals who are knowledgeable in the hazards associated with hot work.

In paragraph (b) of § 1915.503, OSHA is proposing that the employer keep all hot work areas free of hazards that may cause or contribute to the spread of fire. This proposed paragraph summarizes the Committee's belief that fires cannot occur if the hazards contributing to them are controlled. This requirement is to prevent the introduction of combustible or flammable materials during the performance of hot work. Often, safe conditions exist at the start of the hot work process; however, over the duration of the work, these materials may be brought to the site thereby creating a fire hazard. For example, one worker may be performing hot work at the same time another worker from another job introduces combustible or flammable materials within 35 feet of the hot work operation. The worker's safety can be further compromised by the fact that the worker doing the hot work is wearing a face shield that obstructs vision, preventing that worker from seeing the entrance of the second worker. It is the intent of this requirement that hazard assessment be a continual process and not a singular, one-time event. Therefore any measures

used by the employer to control fire hazards must be maintained.

Fuel gas and oxygen burning lines and torches are typically used in shipyard employment as follows. A burner (an employee engaged in burning or brazing) is trained and becomes qualified in the safe operation and testing of his equipment; namely the burning torch, gauges, care and use of the fuel gas and oxygen hose lines and proper connection to the supply manifold. Only qualified employees are issued this equipment from the tool room. After being issued his equipment, a burner working on a vessel will proceed to the manifold on the fantail of the vessel. Assigned to work in the lower level of the machinery space (enclosed space) 200 feet from the manifold, he will connect four 50 foot sections of hose together and to his torch. Next, he will connect this assembly to the gauges that he, in turn, attaches to the supply manifold. He then charges the entire burning rig by opening the oxygen and fuel supply lines. He then tests the torch and lines for compression integrity using his gauges first having turned off the supply valves. If the gauges indicate compromised integrity, the burner will then re-tighten all of the connections and test again. Once the integrity of the burning rig is established, he then proceeds to roll out the lines on the deck to his assigned worksite. Upon reaching his worksite, he then returns to the supply manifold, energizes the system, and proceeds to secure his hose lines elevated and out of walkways to eliminate tripping hazards. Finally, he returns to his worksite and begins burning.

In paragraph (b)(2)(i) OSHA proposes that the employer must make sure that no unattended fuel gas and oxygen hose lines or torches are left in confined spaces. The proposed language in this paragraph has been adapted from 29 CFR 1910.252; § 1915.52; and NFPA 312-2000, Standard for Protection of Vessels During Construction, Repair, and Lay-up (Ex. 20-4). The Committee and participants from the public attending the Committee's meetings agreed with the proposed requirement in paragraph (b)(2)(i). This requirement reflects the current practice in the industry.

The potential danger associated with unattended fuel gas and oxygen hoses or torches in confined spaces is apparent and universally accepted. Leaking fuel gas and oxygen from unattended hoses or torches can accumulate rapidly in confined spaces leading to several hazardous conditions such as increased fire hazards, oxygen-enriched atmospheres, explosive atmospheres, and similar conditions. This proposed paragraph seeks to eliminate the hazards associated with unattended fuel gas and oxygen hoses or torches in confined spaces.

In paragraph (b)(2)(ii) of § 1915.503, OSHA is proposing that employers must not allow unattended charged fuel gas and oxygen hose lines or torches in enclosed spaces for more than 15 minutes. The proposed language in this paragraph has also been adapted from 29 CFR 1910.252; § 1915.52; and NFPA 312-2000, Standard for Protection of Vessels During Construction, Repair, and Lay-up (Ex. 20-4). The Committee agreed with this proposed requirement following extensive discussion and analysis. They felt that the potential for fire or explosion caused by unattended charged lines in enclosed spaces far outweighs the burden of pulling to open air or disconnecting.

In paragraph (b)(2)(iii) of § 1915.503, OSHA is proposing that the employer must disconnect all fuel gas and oxygen hoses at the supply manifold at the end of each shift. The fact that paragraph (b)(2)(iii) does not propose a hose removal requirement needs to be further discussed in rulemaking. The Agency seeks comment on this subject. Some shipyard employers indicated that at shift change fuel gas and oxygen hoses are rolled back to the manifold and disconnected at the supply end, while other shipyard employers found this to be impractical. They noted that at a large shipyard work can be done on a vessel as long as 800 feet with as many as seven decks. For this work, employees need to connect burning rigs on the fantail supply manifold and string 700 feet of fuel gas and oxygen hose lines through a number of enclosed spaces to reach a worksite. Adding more lines to this supply manifold with additional manifolds also located on the fantail creates the problem of unstringing and rolling back literally miles of hose lines to disconnect them. The potential for confusion exists when these lines are disconnected and then need to be reconnected. The Committee agreed that the hoses should be removed from the confined spaces, but there remained a question about whether this was necessary for enclosed spaces.

The concern is not necessarily about leaking hoses and their potential for creating a hazardous space. Rather, the bigger concern seems to be with the possibility of hooking up, at the supply manifold, a different (wrong) hose whose torch end was left hanging in an enclosed space. Because it is the wrong hose, it may now be dispensing gas (oxygen and fuel gas) into an space without anyone knowing, a space that is not involved in the intended work. The contaminated space may not be discovered until much later, thus creating a fire/explosion hazard. Additionally, leaking fuel gas and oxygen may create a flammable or oxygen-enriched atmosphere that may reach an ignition source.

OSHA deals with these hazards in proposed paragraphs (b)(2)(iii)(A) and (B) of § 1915.503. When fuel gas and oxygen lines are to be disconnected, the employer has two options. One is to completely roll the lines back to the supply manifold (open air) and then disconnect the torch. The other is, where a positive means of identification on the fuel gas and oxygen hose lines has been given before rolling out or extending the line, the employee can leave the lines extended, disconnect them at the supply manifold, and then disconnect the torch. This would assure that, not only would the proper extended lines be disconnected, but also that the proper lines will be reconnected, thus eliminating the hazards discussed above. Also, because the torch must be removed from the enclosed space after disconnecting the extended line from the supply manifold, the potential for the build-up of a hazardous atmosphere is greatly reduced.

Selecting the positive means of identification for the fuel gas and oxygen hose lines is left, by this performance type requirement, to the discretion of the employer. Examples of the positive means of identification include stenciling both ends of the line, color coding, stamped brass tags, and so forth. It is clear however, that the lines must be identified at both ends regardless of how many sections are joined, creating the run.

The Committee felt that extended lines could be reconnected safely provided that certain measures were followed: positively identifying hose line ends and maintaining the integrity of the complete burning rig. The former has already been discussed. The Committee recognized that maintaining the integrity of the burning rig can be accomplished in a number of ways. The preferred way is the drop test using gauges which has already been discussed. Another way is the use of a lockout device (Ex. 16b). Still another is testing a pressurized system, using soapy water at all connections. The Committee concluded—and OSHA agrees— that using such performance language as an alternative to specifications will help to nurture developing technology in these areas.

Section 1915.504 Fire Watches

The requirements of this section, as recommended by the Committee, apply to fire watch activity designated by the employer in shipyard employment. The requirements are proposed in three parts: (a) the employer's written policy on fire watches, (b) the posting of a fire watch, and (c) fire watch assignments.

The existing subpart in § 1915.52 Fire Prevention in Welding, Cutting and Heating is a 35-year-old standard. It was identified by SESAC in 1992 as needing updating and extension of its scope to cover all the situations in shipyard employment regardless of geographic location. The Committee has recommended, and OSHA agrees, that the existing requirements in § 1915 that address fire protection be replaced by the proposed requirements of this subpart.

Paragraph (a) of § 1915.504 requires employers to create and keep current a written policy on fire watches specifying the requirements for the training, duties, equipment, and PPE necessary for fire watches in the workplace. The PPE that fire watches will need is specified in to 29 CFR subpart I Personal Protective Equipment. No specific format is proposed for the written policy. The Committee determined the employer was in the best position to determine how the requirement can be met, and OSHA agreed. OSHA recognizes that the employer needs the discretion to tailor the plan to his or her workplace.

Paragraph (b) of § 1915.504 proposes that the employer must determine the need for and post a fire watch if during hot work: (1) Slag, weld splatter, or sparks might pass through an opening and cause a fire; (2) fire-resistant guards or curtains are not used to prevent ignition of combustible materials during work on or near decks, bulkheads, partitions, or overheads; (3) combustible material closer than 35 ft. (10.7m) horizontally and vertically cannot be removed, protected with flame-proof covers, or otherwise shielded with metal or fire-resistant guards or curtains, so that the material will not be ignited by the hot work; (4) on or near insulation, combustible coatings, or sandwich-type construction on either side cannot be shielded, cut back, or the materials removed. In the latter case, if removal is impracticable, the space affected by the hot work must be inerted; if that cannot be done, then a fire watch must be posted. A fire watch must also be posted when: (5) Combustible materials adjacent to the opposite sides of bulkheads, decks, overheads, metal partitions, or of sandwich-type construction may be ignited by heat conduction or radiation; (6) hot work on pipes or other metal is close enough to cause ignition through heat radiation or conduction if contact is made with insulation, combustible coatings, or combustible decks, bulkheads, partitions, or overheads; (7) hot work is close enough to unprotected combustible pipe or cable runs to cause ignition from exposure to the hot work; or (8) a watch is required by a Marine Chemist, a Coast Guard authorized person, or a shipyard Competent Person. The Committee identified these eight probable cases where a fire watch is needed for any size shipyard employment. OSHA's proposed requirements for this paragraph are based on their recommendations.

Paragraph (b)(1) of § 1915.504 proposes controlling ignition sources for work processes that generate slag, weld splatter, or sparks that might pass through an opening and cause a fire. It has been adapted from NFPA 51B-1999, Standard for Fire Prevention in Use of Cutting and Welding Processes (Ex. 19-3) and 1910.252(a)(2)(iii)(A)(3). During the meetings, the Committee discussed the size of the openings. The Committee considered whether the size needs to be specified. The provision's intent as proposed is to leave the requirement performance oriented. If a spark can get through an opening and cause a fire, then the area should be protected. The Committee preferred to not be specific, but to leave it to the employer to determine which openings need to be protected.

Paragraph (b)(2) of § 1915.504 proposes to recognize that ignition sources can be controlled through the use of fire-resistant guards or curtains. Where the combustible materials cannot be protected from a possible ignition source, the employer must post a fire watch. The Committee recognized that combustible materials can be protected through the use of fire-resistant guards or curtains. For example, a sandwich-type bulkhead could be safely protected from ignition of the combustible materials during hot work by using a fire-resistant guard or curtain.

Paragraph (b)(3) of § 1915.504 reflects the 35 ft. requirement (minimum distance of combustible materials from hot work) from the 1910.252(a)(2)(vii), subpart Q Welding, Cutting and Brazing and NFPA 51B-1999, Standard for Fire Prevention in Use of Cutting and Welding Processes (Ex. 19-3). In this paragraph OSHA proposes to require that an employer post a fire watch unless combustible materials are relocated to at least 35 feet beyond the hot work area or are protected by shielding. The Committee discussed the 35-foot distance at length during the course of the meetings and agreed that if the possibility exists that hot work materials could make contact with the combustible material in any way, a fire watch must be posted. No specific reasons or evidence to change the distance was suggested by any of the members or representatives from the public. The Committee's proposal kept the 35-foot distance. The Committee believes that the distance has been in regulatory requirements and national consensus standards for many years and reflects the current industry practice. The Agency concurs that such protection is reasonable and necessary.

Paragraph (b)(4) of § 1915.504 addresses the hazards associated with combustible coatings, sandwich-type construction, or other insulating materials. Besides shielding, cutting back, removing the materials and posting a fire watch, an industry practice for the acoustic foams that are commonly found in inaccessible voids is to inert the areas to make them safe for hot work. Industry practice, in these situation, has been to also provide charged fire hoses or portable extinguishers as fire protection measures for fire watches. Polyurethane and other organic foams are increasingly used on vessels because of their excellent insulating and lightweight properties. When properly installed and protected against fire, organic foams present no more fire hazard than other combustible materials. However, when organic foams (including those described as self-extinguishing, non-burning, fire resistant, flame resistant, and by similar terms) are exposed to fire or heat, they may ignite and burn with rapid flame spread, high temperatures, toxic gases, and voluminous quantities of smoke.

Paragraph (b)(5) of § 1915.504 addresses the potential hazards of adjacent spaces. This paragraph is adapted from § 1915.52(a)(3). It is an important part of the hazard assessment “since direct penetration of sparks or heat transfer may introduce a fire hazard to an adjacent compartment, the same precautions shall be taken on the opposite side as are taken on the side on which the welding is performed.” During hot work on or near insulation, combustible coatings, or sandwich-type construction on either side, if the employer cannot cut back or remove the materials or inert the space, a fire watch must also be posted on the opposite side of the hot work. This requirement is intended to address the increased fire hazard potential (noted in the explanation above for paragraph (b)(4))

that results from hot work conducted in areas with or adjacent to polyurethane or other organic foams.

In cases where hot material from hot work could involve more than one level, as in trunks and machinery spaces, a fire watch must be stationed at each affected level unless positive means are available to prevent the spread or fall of hot material. Positive means could be accomplished by placing barriers or by physically isolating an area. The same is true for adjacent spaces; a fire watch must be stationed at each affected work area.

Paragraph (b)(6) of § 1915.504 requires a fire watch during hot work when performed on pipes or other metal in contact with insulation, combustible coatings or combustible materials on or near decks, bulkheads, partitions, or overheads if the work is close enough to cause ignition by radiation or conduction. The fire watch workgroup discussed at length the term “bulkhead and deck.” Because the scope of subpart P is for shipyard employment, the subgroup discussed the fact that bulkheads and decks refer to vessels and vessel sections and although these terms could be used for structures and buildings, that is not the norm. Normally on landside structures the terms “walls and floors” are commonly used. Would use of “bulkhead and deck” in this provision cause confusion as to the applicability throughout shipyard employment, both on land side and aboard vessels? The Agency invites comment on this issue.

Paragraph (b)(7) of § 1915.504 requires a fire watch if hot work is conducted close enough to combustible pipe or cable runs to cause ignition (unless the pipe or cable runs are protected from exposure to the hot work). This provision takes into account the large amount of cable runs through vessel compartments. Although these cables must be tested to low flame spread and smoke production rates, they are still combustible and have been responsible for the spread of fire in many cases. Also, the use of combustible piping is increasing, and although required to meet strict flame spread and smoke production criteria, the potential for fire spread through pipe runs is the same as through cable runs and should therefore be safeguarded.

Paragraph (b)(8) of § 1915.504 proposes to add a provision for posting a fire watch when required by a Marine Chemist, a Coast Guard authorized person, or a shipyard Competent Person. These individuals are trained to know when a fire hazard requiring a fire watch exists even in circumstances not set forth in paragraphs (b)(2) through (b)(7) above. In one of the areas of biggest concern-where flammable and combustible liquids are present, for example, in vessel construction— the regulations already require a competent individual to determine where a fire watch will be required. An employer is already required to designate a shipyard Competent Person in accordance with applicable requirements of 29 CFR 1915.7. These requirements, coupled with the time-tested recommendations of NFPA 51B-1999 and 29 CFR 1915 subpart B, were considered adequate by the Committee.

Paragraph (c) of § 1915.504 outlines the assignment of fire watch duty. Originally, the Committee's Fire Watch Workgroup had recommended language for this paragraph that specifically states that the employer is responsible for a worker's assignment to fire watch duty. However, the Committee felt that this should be understood throughout the regulations that the employer is ultimately responsible for workplace fire safety, and thus it does not need to be repeated. OSHA agrees.

Paragraph (c)(1) of § 1915.504 states that an employee must not be assigned other duties when designated as fire watch by the employer. The Committee wanted to be very clear on this requirement, because although fire watch as an exclusive assignment is recognized as industry practice, the fire watch posting is crucial to maintaining safe working areas. For example, welders with their shields down rely totally on the fire watch's observations. This watch should not be distracted by having other duties assigned at the same time.

The provision in paragraph (c)(2)(i) requires that a fire watch must have a clear view of all areas assigned. This requirement effectively precludes a worker acting as his or her own fire watch. The workgroup told the Committee that if hot work workers,

i.e.

, welders and burners, were, in fact, acting as their own fire watch, the requirement for a clear view of those areas affected could not be met. They noted that when a welder's shield is down, the immediate area where the arc hits is the only area the welder is concentrating on, and the welder is oblivious to the surrounding work area affected. The Committee agreed and wanted to note specially that a worker performing hot work, such as a welder, cannot be his or her own fire watch under any circumstances.

The Committee was concerned that a fire watch be able to do his or her job. This means that a fire watch must be physically capable of accessing the necessary area and wearing the appropriate PPE. For example, a fire watch may have to climb ladders to access tanks or other structures, carry fire extinguishers, pull hoses, see the assigned area, pull alarm stations, and communicate the alarm verbally. Although there was much discussion, the Committee did not include a requirement stating that the employer must make sure that personnel who are expected to stand fire watch will perform and are capable of carrying out the duties of fire watch. The logic, after discussions, was that the employer would be the best judge of physical capability and mental alertness of the fire watch.

Paragraph (c)(2)(ii) of § 1915.504 proposes that employees assigned to fire watch duty must be able to communicate with workers exposed to hot work. As addressed later in the preamble for paragraph (c)(2)(x) of § 1915.508 Training, there was considerable discussion within the workgroup about current industry practices for the fire watch's contact with other workers. The Committee decided that communication is important because a fire watch may not be able to see a hot worker when, for example, the fire watch is on the other side of a compartment from the hot worker. The Committee did not want to limit the means of communication. For example, in the case of a fire watch on the other side of the bulkhead from the employee doing hot work, the means may be as simple as tapping on the bulkhead to signal whether the hot worker can continue or must stop, or it could be a more electronic communication system such as radio communication.

Paragraph (c)(2)(iii) of § 1915.504 specifies that the fire watch must remain in the hot work area at least 30 minutes after hot work is completed. A provision has been added that permits the fire watch to be relieved sooner if the employer or the employer's representative surveys the exposed areas, conducts a post-work hazard assessment, and determines that no further fire hazard exists. Obviously, this determination can only be made after a hazard assessment is completed. The fire watch workgroup carried forth this requirement from SESAC's recommendation that the NFPA and industry-accepted practice be used as the rationale for the 30 minute requirement unless the employer surveys the affected work area(s) and determines that there is no further fire hazard. The workgroup recommended to the Committee that when the work area was protected before the hot work was done, the employer or the

employer's representative could resurvey the affected area and determine the area was safe from fire hazards without the need for a fire watch for 30 minutes after completion of the hot work. The Committee agreed. The intent of this provision is to encourage employers or their representative to use the hazard assessment process throughout the work—beginning, middle (to see if conditions change), and at the end (to determine how long the fire watch may be needed).

OSHA invites comment on whether the fire watch remaining in the hot work area for at least 30 minutes after completion of the hot work is the equivalent to the employer's immediate survey of the exposed area to making a determination that there is no further fire hazard.

Paragraph (c)(2)(iv) of § 1915.504 proposes that the employer must ensure that employees assigned to fire watch duty are trained to detect fires that occur in areas exposed to the hot work. (For a further explanation,

see

the Training section at § 1915.508.)

Paragraph (c)(2)(v) of § 1915.504 requires that the fire watch must attempt to extinguish any incipient stage fires in the assigned work area that are within the available equipment's capacity and within the fire watch's training qualifications as defined in 1915.508 Training. The term “incipient stage fire” is defined in the General Industry Fire Protection Standard § 1910.155(c)(26): Incipient stage fire means a fire which is in the initial or beginning stage and which can be controlled or extinguished by portable fire extinguishers, class II standpipe or small hose systems without the need for protective clothing or breathing apparatus. Although the maritime industry asked for a single standard, this definition is an example where the general industry standard is referenced to reduce regulatory duplication. OSHA seeks comment on whether the definition needs to be included in this standard.

Paragraph (c)(2)(vi) of § 1915.504 proposes the requirement that the fire watch alert employees of any fire that goes beyond the incipient stage. The method the fire watch uses to alert other employees is not specified. The fire watch can alert in the way most suited to the worksite and conditions. Whether this is accomplished by shouting, waving of arms, or hand signals is left up to the employer to instruct the fire watch. In a noisy working environment, it might be most appropriate to tap hot workers on the shoulder and then motion to them to follow or exit the area. In a smokey situation, vocal communication would be more appropriate.

Paragraph (c)(2)(vii) of § 1915.504 provides that if fire watches are unable to extinguish fire in the areas exposed to the hot work, they must activate the alarm and start the evacuation procedure as trained according to § 1915.508(c)(2)(xi) and the employer's fire safety plan, § 1915.502.

Section 1915.505 Fire Response

In this section OSHA proposes specific requirements for fire response in shipyard employment. At present, OSHA does not have any specific requirements for fire response in shipyard employment.

Responders to shipyard fires encounter a complex set of fire hazards involving buildings, vessels in dry-dock or on ways, afloat, or alongside a quay. Fire responders need to be prepared to suppress a wide range of fire scenarios from a flammable liquid storage room in a shipyard building to oil-soaked rags in an engine room on a ship. Types of fires could include ordinary combustible materials (such as wood, paper or cloth), flammable or combustible liquids (such as oil, fuels, paints or chemicals), insulation and other materials that give off toxic gases and smoke, electrical fires (involving energized motors, circuit controls, transformers or wiring) or even a rare combustible metal fire (such as magnesium or titanium).

Shipyard firefighting as defined in section 1915.509 Definitions may be provided by:

1. Members of a fire brigade established by the shipyard, consisting of employees who have primary duties other than firefighting;

2. Workers of the shipyard employed as full-time firefighters; or

3. Public, private, governmental, or military units providing rescue, firefighting, and other related services.

As expressed by one Committee member, when firefighters respond to a shipyard fire, the safety of the shipyard workers rests with those firefighters; therefore, that member noted, the safety of all firefighters should be addressed by this standard and these rules should apply to them as well. In fact, the Committee expressed concern that whoever provides fire response to shipyard employment must meet certain minimum standards. The Committee's consensus was that designated workers (whether employed by the shipyard or by another employer) must be trained and equipped to fight fires in shipyard employment as safely as possible to reduce worker deaths or injuries related to these fires.

To ensure that this happens when firefighters are not shipyard workers, the Committee decided to require a liaison be established between the shipyard employer and the outside organization providing response services. Consistent with the recommendations of the Committee, OSHA is proposing that the shipyard liaison's communication with an outside fire response organization must include addressing facility and layout familiarization and coordination protocols. Public fire departments in those states with approved section 18b State Plans that respond to shipyard facilities will be covered by similar requirements through their respective states. Federal OSHA does

not

have jurisdiction over state and municipal fire departments or volunteers. Federal firefighters are covered under Executive Order No. 12291. OSHA believes that the safety of all firefighters is a major concern and intends the broadest coverage possible under the Act regardless of the shipyard employer's fire response arrangements. The Committee was in full agreement that anyone responding to a shipyard employment fire to actually extinguish a fire should be covered by this proposed rule to the extent possible. The proposed coverage of this standard, for fire responders has to exclude state and municipal fire departments and volunteers even though they will benefit from the requirement to establish a liaison with them.

Shipyard fire responders do not include support personnel responding at or near fires who have only limited support functions to perform. The Committee agreed that the shipyard employment workers who might respond to provide support services but are not exposed to the hazards of the fire, should not be covered. Such support services include electricians, utility workers, and facility management representatives. As explained by one Committee member, the requirements of this proposal are not intended to apply to employees responding to a shipyard employment fire to open or close valves, turn off electric service, or disconnect gas supplies. “Support personnel,” as the Committee called them, are designated persons not put into harm's way but performing such tasks as shutting down or isolating gas lines and disconnecting electrical service. They are not fire response personnel since they are not exposed to the hazards of firefighting. Members of the public, including Vincent Galattli from Bender Shipbuilding and Michael Davis from Halter Marine, noted that some shipyard

employment workers join community fire departments as volunteers. These volunteers are sometimes used in shipyard employment to pull hoses but do not fight fires. Committee member Buck Hurley from the Norfolk Naval Shipyard noted that crane operators could be used to provide supplies, water, or chemicals, but not perform actual firefighting.

This proposed section consolidates the requirements of 29 CFR 1910.156 Fire Brigades with some of the provisions in NFPA 1500-2002, Fire Department Occupational Safety and Health Program (Ex. 20-5), creating a standard that specifically addressees shipyard fire response.

A Committee workgroup consisting of representatives of the fire service, government, labor, and employers developed the initial proposed language for this section. In addition to using the SESAC recommended proposal and current industry practice, the workgroup relied heavily on NFPA 1500-2002. The workgroup also discussed and reviewed NFPA 600-2000, Standard on Industrial Fire Brigades (Ex. 20-6).

NFPA completely revised NFPA 600 in 2000 to be consistent with OSHA's Fire Brigade Standard. In 2000, NFPA further revised the document to include industrial fire departments that were previously covered in NFPA 1500.

The workgroup chose to rely more heavily on NFPA 1500-2002 rather than NFPA 600-2000 because of the need to make sure that response from outside the yard would be compatible with response from inside the yard. In many communities, particularly where there are small employers, the shipyard must rely on and coordinate fire response with the local fire authority. Through this section, OSHA intends to assure the coordination between the yard and the outside fire response organization so that they can work together safely.

There is one general distinction that OSHA wants to make clear with respect to fire response in shipyard employment. As recommended to OSHA by the Committee, shipyard support personnel are not considered members of the shipyard fire brigade or fire department when they respond to fires on board vessels or vessel sections. The Committee agreed that additional shipyard personnel, usually yard maintenance or temporary service employees, can and do react to fire alarms on board vessels and vessel sections. However, when these employees respond to the fire location, they do so with the understanding that they will not put themselves at risk by attempting to fight fires. Rather, their only responsibility is to offer skilled support to fire brigade or fire department responders by securing certain utilities (

i.e.

, electrical, ventilation, compressed air, and oxy-fuel lines suppling the vessel or vessel section) when necessary during fire suppression activities. Because they have detailed knowledge of the vessel's or vessel section's layout of temporary services and the locations within the yard for controlling these services, they can also serve as an information resource for firefighters responding to the fire.

For example: A large cargo ship is tied up at a pier. Manifolds provide fuel gas and oxygen for hot work located on the main deck of the vessel. The manifolds are fed from the pier. A fire is discovered below decks and the fire alarm sounds throughout the vessel. The employees leave their work stations and proceed off the vessel to a waiting area. The yard's fire brigade arrives and boards the vessel. The outside or municipal fire department is alerted and initiates its response plan. As part of the yard's fire safety plan, the temporary service and yard maintenance departments respond to the pier alongside the vessel. Representatives of the yard's fire brigade meet with the temporary service employees and they communicate with the firefighters on board the vessel to identify the location of the fire. Based upon the information received from the firefighters on board the vessel, the temporary service employees will begin to secure utilities that provide service to the fire area. Once the utilities have been secured to prevent hazards to the firefighters, the temporary service employees will return to the staging area and await further requests from the yard's fire brigade.

In this scenario, the temporary service employees did not enter the vessel's compartments with the intent to fight the fire. They responded to give skilled, technical support to the responding fire departments. OSHA wants to make it clear that in shipyard employment, the shipyard support personnel, such as temporary service employees, are not considered part of the shipyard's fire brigade or fire response department. Shipyard fire response department or brigade employees who participate in the actual role of fire suppression and control are the only employees covered by this section. These employees must be trained for the duties and functions they are expected to perform. The shipyard employees who are not part of the shipyard's fire brigade or fire department, including skilled support employees, are not covered by this section. Their protection is provided by other standards in this part.

In paragraph (a)(1) of § 1915.505, the shipyard employer is required to determine who will perform fire response in the shipyard and what type of response will be provided. The Committee recommended this approach based on the diverse fire response capabilities it found throughout the industry. Some shipyard employers, those with very large facilities, employ full-time shipyard firefighters and provide them with response apparatus and equipment. At the other end of the spectrum are the employers at small shipyards who must rely totally on public fire protection. One Committee member indicated that his shipyard fire response personnel constitute the superior fire protection expertise in his community. This is with regard not only to shipyard fires but also to the fire response operations of the local public fire department to which he offers support and back-up. Yet, at another meeting, a public fire official indicated his department provides all of the fire protection for the shipyards located in his district. The Committee consensus is that the deciding factors are so many and so varied that each shipyard employer must take responsibility for determining who will provide fire response services and what those services will be.

OSHA proposes in paragraph (a)(2) of § 1915.505 that the employer must create and maintain an updated written statement or policy that describes the internal and outside fire response organizations that the employer will use. In complete agreement with the Committee, OSHA is promoting the idea of pre-planning throughout this proposed fire response section.

Paragraph (a)(3) of § 1915.505 proposes that the employer create, maintain, and update a written statement or policy that defines what evacuation procedures employees must follow if the employer chooses to require a total or partial evacuation of the worksite at the time of a fire.

The Committee stated strongly that once the shipyard employer decides how to protect employees from the hazards of fire, the methods of protection must be pre-planned and documented regardless of the type of response the employer chooses. Accordingly, in paragraph (b) of § 1915.505, OSHA proposes the information that must be included in the written policy statement required by this section. These written policy statements should set forth the basis for operating a fire response service. A key point is to set out clearly the specific

functions the fire response service is authorized and expected to perform. Employers must assert their authority to set the specific functions and the limits of the functions the fire response service will provide. The employer also must furnish the necessary resources for delivering the designated services. Such services might include structural fire response, emergency medical services, hazardous materials response, high-angle rescue, heavy rescue, and others.

OSHA proposes in paragraph (b)(1) of § 1915.505 that, if the employer chooses to provide internal fire response, then the employer must create, maintain, and update a written statement or policy that defines the fire response to be provided. The information would include the organizational structure of the fire response service; the number of trained fire response employees; the minimum number of fire response employees necessary, the number and types of apparatus, and a description of the fire suppression operations established by written standard operating procedures for each type of fire response at the employer's facility; training requirements; expected functions that may need to be carried out; and procedures for use of protective clothing and equipment. Spelling out the specific parameters of services to be provided allows the fire response service to plan, staff, equip, train, and deploy members to perform these duties.

Similarly, OSHA proposes in paragraph (b)(2) of § 1915.505 that if the employer chooses to use an outside fire response organization, then the employer must include specific information in the employer's policy statement. The policy statement should include the following: (1) The types of fire suppression incidents to which the fire response organization is expected to respond at the employer's facility or worksite; (2) the liaison which would presumably be by individual name or job title, between the employer and the outside fire response organization; (3) a plan for fire response functions that discusses using or getting help from other organizations, and familiarizes the external fire response organization with the layout of the employer's facility or worksite, including access routes to controlled areas, and site-specific operations, occupancies, vessels or vessel sections, and hazards; and how hose and coupling connection threads are to be made compatible and where the adapter couplings are kept; or have a statement saying that they will not allow the use of incompatible hose connections.

OSHA further proposes in paragraph (b)(3) of § 1915.505 that if the employer chooses to use a combination of an internal and an outside fire response organization, then the employer must define the fire response services in addition to the requirements in (b)(1) and (2) above, that will be provided by each fire response organization. Specifically, the following information must be included: The basic organizational structure of the combined fire response; the number of combined trained fire responders; the fire response functions that need to be carried out; the minimum number of fire response employees necessary, the number and types of apparatus, and a description of the fire suppression operations established by written standard operating procedures for each particular type of fire response at the worksite; and the type, amount, and frequency of joint training that must be given to fire response employees.

As an alternative to providing active fire response, the Committee recognized in paragraph (b)(4) of § 1915.505, OSHA's longstanding policy that employers may also ensure employee safety in case of fire through the means of evacuation. Accordingly, paragraph (b)(4) of § 1915.505 would require that the employer's evacuation policy statement include the following: Emergency escape procedures; procedures to be followed by employees who may remain longer in the worksite to perform critical shipyard operations before they evacuate; procedures to account for all employees after emergency evacuation is completed; the preferred means of reporting fires and other emergencies; and names or job titles of the employees or departments who may be contacted for further information or explanation of duties. These requirements are based on similar requirements found in employee emergency plans and fire prevention plans (29 CFR 1910.38).

Emergency escape procedures in shipyard employment can vary greatly depending upon whether the worksite is located on a vessel or vessel section or in a landside facility. For example, on a vessel at anchorage, escape routes from the vessel may be more difficult to identify than those found in a landside machine shop, carpenter's shop, welding shop, cafeteria, employment office, or similar worksite. This paragraph also requires procedures to protect employees who must remain behind to perform critical shipyard operations before they evacuate. Critical shipyard operations may include shutting down a vessel's power plant, securing utilities to the fire area, or similar activities. Additionally, accountability procedures for all employees following emergency evacuation must be established. For example, employees could be directed to report to a specific location after evacuation. Another important element of the evacuation policy is the preferred means of reporting fires or other emergencies. Examples include telephone or radio communications, fire alarms, steam whistles, verbal communication, or other tactile, visual, or audible means of communication at the employer's discretion. Finally, as a means to administer the evacuation policy effectively, the statement must indicate the key individuals by name, job title, or department to be contacted for further information or explanation of duties under the policy.

In paragraph (b)(5) OSHA is proposing a requirement that the employer must include a description of the emergency rescue procedures and names or job titles of the employees who are assigned to perform rescue and emergency response. The Committee recommended this requirement and OSHA agrees.

In paragraph (c) of § 1915.505, OSHA, following the recommendation of the Committee, proposes the physical and medical qualifications shipyard employees must meet to be a part of the fire response. In paragraph (c)(1) of § 1915.505, OSHA requires that all fire response employees receive medical examinations to assure that they are physically and medically fit for the duties they are expected to perform. This approach is consistent with NFPA 600-2000, NFPA 1500-2002, and other OSHA standards, such as in 29 CFR 1910.156 and 29 CFR 1910.120. OSHA recognizes that firefighting is one of the most hazardous occupations and that those who perform fire response activities must be able to perform them properly without jeopardizing the safety and health of themselves and other firefighters. Of particular concern to OSHA are such conditions as emphysema, heart disease, and epilepsy. While these conditions do not preclude participation in fire response, they may preclude participation in certain fire response activities. For that reason, OSHA proposes to require the employee's physical and mental fitness be in accord with the duties the employee will perform.

In paragraph (c)(2) of § 1915.505, OSHA is proposing that fire response employees who are required to wear respirators while performing their duties must meet the medical requirements of 29 CFR 1915.154 Respiratory protection. This

requirement is consistent with the language of 29 CFR 1910.134 (c)(1) that requires employers whose employees use respirators to develop and implement a respiratory protection program. One of the elements of a respiratory protection program is implementing medical evaluation for employees who use respirators. Paragraphs (g)(3) and (g)(4) of 29 CFR 1910.134 require firefighters who perform interior structural firefighting or who enter atmospheres that are immediately dangerous to life and health ( IDLH atmospheres) to wear self-contained breathing apparatus.

In paragraph (c)(3) of § 1915.505, OSHA proposes to require that the employer make sure that all fire response employees have an annual medical examination. Further, in paragraph (c)(4), medical records of fire response employees must be kept according to 29 CFR 1915.1020 Access to Employee Exposures and Medical records. These proposed requirements are consistent with existing regulations found in 29 CFR 1910.156 and 29 CFR 1910.134.

In paragraph (d) of § 1915.505, OSHA addresses the procedures the employer would have to follow for organizing internal fire response functions. Paragraph (d)(1) proposes that the employer must organize the employer's fire response functions to make sure that there are enough resources to safely conduct emergency operations at the site. This language is consistent with the goals and language of paragraph 4.1.1 of NFPA 1500-2002 addressing the fire department's organizational statement. The Committee believes organization of the internal fire response functions is critical to its success in a fire emergency.

In paragraph (d)(2) of § 1915.505, OSHA proposes that the employer must set up written administrative regulations, standard operating procedures, and departmental orders for fire response functions. This proposed language is also consistent with the language of Chapter 4 in NFPA 1500-2002 addressing the organization of fire response providers.

In paragraph (d)(3) of § 1915.505, OSHA proposes that the employer must set up an Incident Management System (IMS) to coordinate and direct fire response functions. It is proposed that this system must include specific fire emergency responsibilities; how the employer will account for all fire response employees during an emergency operation; and what resources would be offered by outside organizations. This proposal is consistent with the goals and language found in paragraph 8.1 of NFPA 1500-2002. The IMS is an improved fire department management and control system, based on actual experience with the Incident Command System (ICS) recognized in other OSHA standards such as 29 CFR 1910.156 Fire Brigades and 29 CFR 1910.120 Hazardous Waste Operations and Emergency Response. Incident command is now a subset of incident management. The new system recognizes that command at an incident is only part of the overall management necessary to safely respond to emergency situations.

In paragraph (d)(4) of § 1915.505, OSHA proposes that employers provide this information (of paragraph (d)) the outside fire response organization to be used. The Committee believes that providing this information will improve coordination and ease pre-planning efforts to ensure a safe overall fire response. These proposed provisions are consistent with existing OSHA requirements (29 CFR 1910.156 Fire brigades and 29 CFR 1910.120 Hazardous Waste Operations and Emergency Response).

Paragraph (e)(1) of § 1915.505, addresses the personal protective equipment of fire response employees. OSHA proposes the employer must provide hazard specific personal protective clothing and equipment, at no cost, to fire response employees. It is also proposed that the employer must make sure that each employee wears the personal protective clothing and equipment that offers protection from the hazards to which that employee is likely to be exposed. This general requirement was recommended by the Committee and is consistent with the language found in chapter 7 of NFPA 1500-2002. It is specifically consistent with existing OSHA standards and with paragraph 7.1.2 of NFPA 1500-2002.

In paragraph (e)(2) of § 1915.505, OSHA proposes the requirements for protective clothing's thermal stability and flame resistance. It is proposed in paragraph (e)(2)(i) that the employer would have to make sure that each fire response employee exposed to the hazards of flame does not wear clothing that, when exposed to flames, could increase the extent of injury that the fire response employee would sustain. Proposed paragraph (e)(2)(ii) specifically prohibits wearing clothing made from acetate, nylon, or polyester, either alone or in blends, unless it could be shown that the fabric can withstand the flammability hazard that could be encountered, or that the clothing is worn in such a way to eliminate the flammability hazard that may be encountered. This language is consistent with the language in existing OSHA standards and in paragraph 7.1.6 of NFPA 1500-2002.

In paragraph (e)(3) of § 1915.505, OSHA proposes the requirements for respiratory protection for shipyard fire response employees. The proposed requirements in paragraph (e)(3) are consistent with current industry practice as discussed by the Committee.

In paragraph (e)(3)(i) of § 1915.505, OSHA proposes that the employer provide self-contained breathing apparatus (SCBA) to all shipyard fire response employees who are involved in emergency operations in an atmosphere that is immediately dangerous to life or health (IDLH), may become IDLH, or is unknown. This language is consistent with existing OSHA standards and paragraph 7.8.7 of NFPA 1500-2002.

In paragraph (e)(3)(ii) of § 1915.505, OSHA proposes that the employer provide SCBA to fire response employees performing emergency operations during hazardous chemical emergencies that will expose them to known chemicals in vapor form or to unknown chemicals. OSHA recognizes that there may be a potential for employee exposure to hazardous chemicals during fire response emergencies due to the nature of shipyard employment. As proposed, this requirement would limit employers to the use of SCBAs for this type of chemical exposure.

In paragraph (e)(3)(iii) of § 1915.505, it is proposed that the employer must provide either SCBA or respiratory protective devices. The SCBA or respiratory device must be certified by NIOSH under 42 CFR part 84 as suitable for the specific chemical environment, to fire response employees who perform or support emergency operations that will expose them to chemicals in liquid form. In this proposal, OSHA recognizes that the hazard to employees because of liquid chemical exposure is such that respirators other than SCBAs, such as cartridge respirators, may provide appropriate protection and be less costly to provide and maintain.

In paragraph (e)(3)(iv) of § 1915.505, OSHA also proposes that the employer must ensure that additional outside air supplies used in conjunction with SCBA be positive pressure systems and certified by NIOSH under 42 CFR part 84. Again, this proposal is consistent with existing OSHA standards and paragraph 7.10.1.1 of NFPA 1500-2002.

In paragraph (e)(3)(v) of § 1915.505, OSHA proposes that the employer must provide only SCBA that meets the requirements of NFPA 1981-1997, Standard on Open-Circuit Self-

Contained Breathing Apparatus for Firefighters (Ex. 20-7). The fire response members of the committee, stated that this has been a long standing recommendation and has become standard equipment for all fire response organizations throughout the country.

In paragraph (e)(3)(vi) of § 1915.505, OSHA proposes that the employer establish a respiratory protection program and use respiratory protective equipment according to 29 CFR 1915.154 Respiratory Protection. The Committee based this proposal on the language found in 29 CFR 1910.156, and 29 CFR 1910.134(g).

In paragraph (e)(4) of § 1915.505, OSHA proposes that the employer must supply at no cost to all fire response employees who are exposed to the hazards of interior structural firefighting within shipyard employment, either protective coats and trousers, or protective coveralls; helmets; gloves; footwear; and protective hoods that meet the applicable requirements of NFPA 1971-2000, Standard on Protective Clothing Ensemble for Structural Firefighting (Ex. 20-8). This proposal is based upon chapter 7 of NFPA 1500-2002.

In paragraph (e)(5) of § 1915.505, OSHA proposes that the employer must supply, at no cost to all fire response employees who are exposed to the hazards of proximity firefighting, the appropriate protective proximity clothing that would have to meet the applicable requirements of NFPA 1976-2000, Standard on Protective Clothing for Proximity Firefighting (Ex. 20-9).

It is the intent of this section to require that only the shipyard employees who will be engaged in operations that will expose them to the intense radiant heat of a proximity firefighting incident (the proximity hot zone) be equipped with specialized proximity firefighting protective clothing.

Employee protection from the hazards of proximity firefighting situations should be viewed in a similar manner to hazardous materials operations. That is, employees must be fully encapsulated to protect them from the unique hazards associated with both situations. The employer should know the locations where such potential exposure to high radiant heat hazards exists, such as bulk flammable liquid or bulk flammable gas facilities. By determining what operations employees could undertake and what the potential exposure will be for those employees conducting fire response operations, the employer will know which employees need proximity firefighting clothing.

At an incident, the employer must establish the boundaries of the proximity hot zone for that incident and require all who must operate within those boundaries to be protected from the intense radiant heat. Intense radiant heat may cause injury to the employees or damage or destroy their structural firefighting protective clothing. The employer could make the decision to evacuate the area and protect employees from such exposures. Then the employer can summon mutual aid that is equipped with the appropriate equipment and proximity protective clothing to handle the proximity hot zone of the incident. The employer could also use fixed protection systems available at the facility to apply extinguishing agents (master streams, water deluge, foam,

etc.

) into the proximity hot zone. Alternatively, the employer could train and equip his or her own response employees to be able to fully deal with these incidents.

Not every employee needs to be included in the proximity hot zone operations unless the employer's written statement or policy requires these resources. For example, the employer may plan fire response operations that would contain and control the fire without the need for employees' operating within the proximity hot zone. Therefore, the employer would not need to provide proximity firefighting protective clothing. Using other protective strategies (including but not limited to physical shields or barriers, or large volume water stream applications that are sustained over the entire duration of the incident) could protect employees who otherwise would need proximity firefighting protective clothing. This language is consistent with the language in paragraph 7.3 of NFPA 1500-2002.

In paragraph (e)(6) of § 1915.505, OSHA proposes that the employer provide a Personal Alert Safety System (PASS) device to each fire response employee involved in firefighting operations. The PASS devices must meet the requirements of NFPA 1982-1998, Standard on Personal Alert Safety Systems (PASS) for Firefighters (Ex. 19-10). This language is consistent with the language in paragraph 7.13.1 of NFPA 1500-2002.

A PASS is a device that is attached to or is an integral part of self-contained breathing apparatus (SCBA). It automatically sounds a distinctive alarm (some units also display a flashing strobe light) if a fire response employee becomes immobile for a pre-determined period of time (usually 30-40 seconds). For example, the device would be activated in the event a fire responder becomes incapacitated from structural collapse or runs out of breathing air. It can also be activated manually by the fire response employee. Fire response employees who might become trapped or lost, but are not unconscious, can also activate the device to help searchers locate them. The shrill alarm allows rescuers to locate the wearer quickly in dark or heavy smoke conditions. The alerting sound of a PASS can easily be distinguished from a low air supply alarm emitted by a SCBA. The Committee agreed that it is every fire fighter's nightmare to be in a fire situation and hear both alarms coming from a comrade's position. This means the comrade has run out of air and is motionless. All incidental fire response activities will immediately stop until the disabled fire fighter is located and pulled to safety. PASS devices are now considered standard issue and are recommended by NFPA Standard No. 1982-1998. It is also industry practice.

Section 1915.505(e)(7) addresses life safety ropes, body harnesses, and hardware. The workgroup, based on their experience, proposed this requirement to the Committee. Their recommendation is consistent with current practice in the fire service. The committee accepted the workgroups recommendations.

In paragraph (e)(7)(i) of § 1915.505, OSHA proposes that all life safety ropes, body harnesses, and hardware used by fire response employees for emergency operations must meet the applicable requirements of NFPA 1983-2001, Standard on Fire Service Life Safety Rope, Harnesses, and Hardware (Ex. 19-11). This is consistent with subpart I of this part and paragraph 7.14.1 of NFPA 1500-2002.

In paragraph (e)(7)(ii) of § 1915.505, OSHA proposes that only class I body harnesses may be used to attach fire response employees to ladders and aerial devices. This is consistent with NFPA 1983-2001.

In paragraph (e)(7)(iii) of § 1915.505, OSHA proposes that only class II and class III body harnesses may be used by fire response employees for fall arrest and repelling operations. This is consistent with NFPA 1983-2001.

In paragraph (f) of § 1915.505, OSHA addresses equipment maintenance.

In paragraph (f)(1) of § 1915.505, OSHA proposes that the employer must inspect and maintain personal protective equipment used to protect fire response employees to make sure that it provides the intended protection. Such inspection and maintenance is consistent with OSHA's personal protective equipment standards.

In paragraph (f)(2) of § 1915.505, OSHA addresses the maintenance of fire response equipment. The requirements for testing and maintaining fire response equipment are consistent with sound safety practices and the requirements for tools and equipment found in chapter 7 of NFPA 1500-2002.

In paragraph (f)(2)(i) of § 1915.505, the employer is required to keep fire response equipment in a state of readiness.

In paragraph (f)(2)(ii) of § 1915.505, OSHA proposes that the employer must make sure that all fire hose coupling and connection threads are standardized throughout the facility and on vessels and vessel sections by providing the same type of hose coupling and connection threads for hoses of the same or similar diameter. It is important to stress the need for standardized or compatible threads in couplings and connections. The Committee heard testimony from fire department personnel stressing the need for compatibility and standardization. Those fire department representatives indicated for example, that many 1

1/2

-inch hoses have threads that look very similar but cannot be connected.

In paragraph (f)(2)(iii) of § 1915.505, OSHA proposes that if the employer uses an outside fire organization for fire response and the employer expects them to use the employer's facility's or vessel's or vessel section's fire response equipment, then the employer must make sure that either all the facility's or vessel's or vessel section's hose and coupling connection threads are the same as those used by the outside fire authority or that suitable adapter couplings are supplied. This language is consistent with the language found in paragraph 9.3 of NFPA 14-2000 (Ex. 20-12).

Section 1915.506 Hazards of Fixed Extinguishing Systems on Board Vessels and Vessel Sections

This section addresses the hazards associated with fixed extinguishing systems on board vessels and vessel sections that could create a hazardous atmosphere when activated in shipyard employment, regardless of geographic location. Of particular concern is the incorrect or inadvertent activation of these systems. Fixed fire extinguishing systems found on land side are covered by the next section of this proposed subpart, § 1915.507 Land side Fire Protection Systems.

The hazards associated with the use of fixed extinguishing systems on board vessels and vessel sections have long been recognized by the United States Coast Guard (USCG) as evidenced by Coast Guard Commandant Notices and Instructions that date to 1978. The International Maritime Organization

2

(IMO) has also addressed this issue by issuing regulations that are part of the International Convention for the Safety of Life at Sea (SOLAS).

2

The International Maritime Organization is the United Nations' specialized agency responsible for improving maritime safety and preventing pollution from ships.

Testing these ships' fixed extinguishing systems has led to several fatalities. In October, 1996, aboard the Italian flag liquid natural gas (LNG) carrier SNAM PORTVENERE, an American Bureau of Shipping (ABS) surveyor and five shipyard technicians were killed when carbon dioxide (CO

2

) was released accidently from a fixed fire extinguishing system that was being tested. On May 3, 1993, aboard the M/V CAPE DIAMOND, while a contractor was testing a low pressure CO

2

system that protected the ship's engine room, CO

2

was discharged accidently, causing the deaths of a Coast Guard marine inspector and a shipyard contractor. Additionally, an intentional activation of a manual CO

2

extinguishing system aboard the Australian naval vessel HMS APPLELEAF, caused the death of four persons. These incidents were attributed to human error in which the discharge of CO

2

extinguishing systems protecting spaces aboard vessels was allowed to occur while employees were working inside.

The Committee recognized and OSHA agrees that although the casualty history reveals problems with only CO

2

systems, the potential exists for the use of new extinguishing agents and application methods to produce hazards similar to CO

2

. Therefore, the proposed employer's responsibilities in paragraph (a) of § 1915.506 apply to all fixed extinguishing systems aboard vessels and vessel sections, regardless of geographic location, that may result in a hazardous atmosphere if discharged. It is very likely that the only systems that may be affected by this regulation will be those that employ gaseous or two-phase (gaseous/liquid) extinguishing agents. However, by including all systems that may create a hazardous atmosphere when activated, the Committee believes that the regulation will be broad enough to cover future systems and/or extinguishing agents that are currently unforeseen. Examples of future possibilities include systems employing dry chemical extinguishing agents (these systems currently exist but are not typically installed on vessels), combination dual water/dry chemical systems, or systems using Halon alternative agents.

While developing this proposal, the Committee discussed whether to include requirements for other systems that do not cause hazardous atmospheres when activated, such as foam and automatic water sprinkler systems. After extensive discussion, the Committee decided that a standard for these systems was not necessary because they are not typically relied upon on board vessels and vessel sections, and they do not pose a significant safety and health threat to employees.

In proposed paragraph (b) of § 1915.506, the Committee agreed to require that systems, whether designed to be activated automatically or manually, be physically isolated or be provided with other positive means to prevent discharge of the systems before any work is done in a space equipped with fixed extinguishing systems. The Committee recognized the increased hazard posed by systems that are activated by either pneumatic, electronic, or other means, with no human action necessary to set them into operation. However, even if a system also has a manual means of activation, it would have to be physically isolated or provided with other positive means to prevent discharge. Examples of other positive means can be found in paragraph (c) of this section. Systems that are activated automatically are normally located in typically unoccupied spaces such as paint lockers and storage lockers, but can also be found in normally occupied spaces such as engine rooms and pump rooms.

In paragraphs (b), (d), and (e) of § 1915.506, the term physically isolated refers to physically preventing the extinguishing agent from entering the work area. This is typically done by installing a blank (a flat piece of metal between two flanges) in the supply line of the extinguishing system so that the extinguishing agent can not possibly be released into the protected area.

Paragraph (b) of § 1915.506 sets forth the provisions that must be completed before any work is done in a space equipped with such fixed fire extinguishing systems. In paragraph (b)(1) of § 1915.506, OSHA proposes that systems must be physically isolated or have other positive means to prevent discharge.

Proposed paragraph (b)(2) of § 1915.506 requires employee training to ensure recognition of systems discharge and evacuation alarms, and recognition of the appropriate escape routes. This training consists of making sure that employees recognize the discharge and

evacuation alarms and escape routes in accordance with § 1915.508 of this subpart.

Proposed paragraph (b)(3) of § 1915.506 was included as a result of Coast Guard information about a casualty at sea. The United States Coast Guard recognized the need to ensure adequate means of escape from spaces protected by CO

2

systems. In this incident, the chief engineer inadvertently discharged CO

2

into a space with an inward opening door. Members of the crew were unable to open the door until pressure in the space subsided. During that time some crew members were asphyxiated. As a result of this incident the Coast Guard recommended that during inspections, CO

2

storage provisions and means of escape should be evaluated. The Coast Guard stated further that protective measures should be provided, such as making sure that doors open outward, that there are kick-out panels in doors or bulkheads, that doors are blocked open when the space is occupied, or that there are sufficient vent openings to the atmosphere. These recommendations are also recognized in COMDTINST 16000.7, MSM, Vol. II (Ex. 17) and SOLAS 74/78 (Ex. 18) which require outward opening access doors in CO2 protected spaces aboard vessels.

Proposed § 1915.506(b)(4) addresses the Committee's concern with inward opening doors, hatches, scuttles, and other potential barriers that may close off escape routes as a result of system activation. The Committee recognized that fully opening or removing doors may cause unacceptable exposures of equipment or employees to the elements (

e.g.

freezing, precipitation, etc.) and, therefore, proposed that this concern may be satisfied by placing a blocking device between the door and door frame to make sure that in the event of system discharge escape routes will not be impaired.

OSHA recognizes that placing a blocking device in a fire door is normally an unacceptable practice. However, in this case, because of the hazard of asphyxiation, OSHA would allow the doors to be blocked open, as long as the blocks are removed before the system is relied upon to provide fire protection.

Proposed paragraph (b)(5) of § 1915.506 requires employee training in the hazards associated with extinguishing systems, such as how to avoid disturbing system components and equipment that are located within spaces. Such components and equipment include piping, cables, linkages, detection devices, activation devices, and alarm devices. Typically in shipyard employment, employees rig materials and equipment in and out of vessel and vessel sections, using chain falls and come-alongs. Employees untrained about the dangers of disturbing system components could accidently activate the system while in the process of rigging.

The Committee recognized that the majority of current CO

2

systems are not equipped with components and instrumentation that would allow a simple method for physically isolating the system. Therefore, the Committee proposed paragraph (c) of 1915.506 to allow work in a space protected by a system activated solely by manual means without the need to physically isolate. Although the safest method is to physically isolate the system, OSHA believes that the requirements included in paragraphs (b)(1) through (5) of § 1915.506 provide an acceptable level of safety. One reason for these options is the impracticality of physically isolating the system for routine and short-duration maintenance and repairs. The Committee wanted to encourage manufacturers, standards writing agencies, and end users to work to develop a simple and practical means for physically isolating existing and future systems.

Proposed paragraph (c) of § 1915.506 is intended to minimize the risk of intentional or accidental activation of a manual system during sea trials by requiring that all activation stations, whether remote or local, must be secured under lock and key or an attendant posted. The intent is to prevent unauthorized persons access to the activation controls of a manual system.

Proposed paragraphs (d) and (e) of § 1915.506 address system testing and system maintenance operations. These have been demonstrated to be the most likely causes of accidental system activation. The Coast Guard currently requires fixed fire extinguishing systems to be disconnected when undergoing any testing or maintenance. The need for these requirements is demonstrated clearly by the fatalities that occurred while testing the fixed system on the M/V CAPE DIAMOND mentioned above. As a result of this incident the Coast Guard recommended that personnel in spaces protected by CO

2

systems be evacuated during testing, unless suitable safeguards are instituted, such as isolating the CO

2

supply from the protected space or providing personnel with self-contained breathing apparatus (SCBA).

The Committee considered the Coast Guard recommendation for employees doing testing to have the option of using SCBAs or using emergency escape breathing devices (EEBD). But the Committee concluded that, because the potential for accidental discharge is so great during testing and maintenance of the system, it is necessary to physically isolate the system during testing and maintenance. The Committee further proposed requiring evacuation of the space by all personnel not directly involved in testing. The reason for proposing both to physically isolate the system and to evacuate non-essential personnel during testing is that testing of the system typically results in alarm activation and discharge of extinguishing agent. Therefore all indications of a test gone awry may be ignored as a false or nuisance alarm by non-essential employees until it is too late to evacuate the space safety. OSHA agreed that the proposal to evacuate all personnel not involved in testing the system best protects the safety of shipyard employees.

Several members of the Committee noted that during sea trials, the employer may expect employees to rely on the on board fixed extinguishing system in the event of a fire. In proposed paragraph (f) of § 1915.506, OSHA addresses the hazards associated with using fixed fire extinguishing systems by proposing that employees be trained and designated as necessary to operate and activate the system properly. Further, OSHA proposes that all employees be evacuated from protected spaces, affected areas, and accounted for before the discharge of the system.

Two serious incidents resulting in ten fatalities were caused by intentional activation of a manual CO

2

extinguishing system protecting an engine room while personnel were trapped inside. One incident occurred on the SNAM PORTOVENERE. Lloyd's Register reported on November 7, 1996, that “an autopsy on the victims revealed that carbon dioxide was the cause of death, rather than the fire or smoke from the blaze which had been reported in the engine room. Sources said the fire was small and was being put out with hand extinguishers when the carbon dioxide plant was activated, saturating about 85% of the engine room within 2 minutes, according to one of the technicians who survived the incident.” (Ex. 10-1). OSHA therefore proposes in paragraph (f)(1) of § 1915.506 to require that employees be trained and designated to operate fixed manual systems when the employer expects these systems to be relied on in the event of a fire.

As reported in the London Guardian, the second incident occurred aboard the

HMS APPLELEAF, when, “an Australian naval captain ordered that the engine room be sealed off and the compartment flooded with carbon dioxide—with four crew members inside.” (Ex. 10-2). Although the report was not clear as to whether or not the cause of the deaths in this case was from asphyxiation by the carbon dioxide or from fire and smoke exposure, the incident illustrates the hazards associated with discharging a lethal concentration of an extinguishing agent into an occupied, enclosed space. The Committee strongly recommended and OSHA agreed to propose in paragraph (f)(2) of § 1915.506 to require that the protected space and affected areas must be evacuated completely and all employees accounted for before discharge of the fixed manual extinguishing system.

Section 1915.507 Land Side Fire Protection Systems

While developing these provisions, the Committee examined existing OSHA regulations for fire protection. Currently there are several OSHA requirements for land side portable and fixed fire protection systems in part 1915. For flammable liquids, § 1915.36(a)(6) requires “Suitable fire extinguishing equipment shall be immediately available in the work area and shall be maintained in a state of readiness for instant use.” For welding, cutting and heating operations, § 1915.52(a)(2) requires, “If the object to be welded, cut or heated cannot be moved and if all the fire hazards including combustible cargoes cannot be removed, positive means shall be taken to confine the heat, sparks, and slag, and to protect the immovable fire hazards from them.” For all hot work § 1915.52(b)(2) requires “Suitable fire extinguishing equipment shall be immediately available in the work area and shall be maintained in a state of readiness for instant use.” For all hot work § 1915.52(b)(4) requires that “Vaporizing liquid extinguishers shall not be used in enclosed spaces.”

Additionally, for ship breaking operations only, § 1915.52(c) requires “In all cases, suitable fire extinguishing equipment shall be immediately available in the work area and shall be maintained in a state of readiness for instant use. Personnel assigned to contain fires within controllable limits shall be instructed as to the specific anticipated fire hazards and how the firefighting equipment provided is to be used.” For general working conditions, § 1915.91(d) requires, “Free access shall be maintained at all times to all exits and to all fire alarm boxes or fire extinguishing equipment.” While these standards apply specifically to fire protection in shipyard employment, the Committee recognized that there are also additional standards in the part 1910 General Industry Standards that are currently used as guidelines in shipyard employment and are accepted industry practice. The Committee has recommended, and OSHA agrees, that the existing requirements in § 1915 that address fire protection will be replaced by the requirements of this subpart.

Subpart L of part 1910 contains the general industry standards for portable and fixed fire suppression systems. The specific types of equipment and systems regulated include portable fire extinguishers, standpipe and hose systems, automatic sprinkler systems, and fixed extinguishing systems using liquid, solid, or gaseous extinguishing agents. There are also requirements for fire detection and fire alarm systems. The current standards in subpart L were developed in 1980 (45 FR 60710) as a major revision to the original 6(a) standards adopted in May, 1971. While subpart L of part 1910 does not apply to the maritime industry (29 CFR 1910.155), many of these standards are used voluntarily as guidelines to control hazards to shipyard employees working in shipyard employment.

In addition to reviewing cu

This text is long and has been trimmed here. Open the source document for the complete record.