Data Centers and Water:

Frequently Asked Questions

July 31, 2026

Congressional Research Service

https://crsreports.congress.gov

R49057

SUMMARY

Data Centers and Water:

Frequently Asked Questions

The expanding use of artificial intelligence and other trends in computing have contributed to

increased development of data centers. Simply, a data center is a physical facility that houses and

runs large computer systems. The increased number and size of these facilities have raised

concerns about the resources needed to support data center operation, including use,

consumption, and discharge of water. These concerns have garnered congressional attention.

Members of Congress and their constituents may have questions regarding a data center’s

potential impact on the quantity and quality of local water resources.

Data centers house equipment that processes, stores, manages, and disseminates digital

information, or data, in support of a variety of information technology (IT) services. Within a

data center, processing units and other computing and networking devices and systems generate

heat. Thermal regulation of the hardware can remove excess heat and maintain system function.

Systems that provide thermal regulation manage airflow, cooling, and other air-conditioning

needs. Generally, the cooling technologies used in data centers rely on either air cooling or liquid

cooling. Liquid-cooled systems generally use water to transfer heat. Data centers may rely on

several different types of cooling technologies, depending on facility characteristics such as size,

computing load, location, local climate conditions, thermal regulation needs of computing

equipment, and access and availability of water for cooling purposes.

R49057

July 31, 2026

Peter Folger, Coordinator

Section Research Manager

Elena H. Humphreys,

Coordinator

Specialist in Environmental

Policy

Nicole T. Carter

Specialist in Natural

Resources Policy

Corrie E. Clark

Specialist in Energy Policy

Laura Gatz

Specialist in Environmental

Policy

How local water resources are affected by data center water withdrawals and consumption (water

Anna E. Normand

consumption means water withdrawn and no longer available for reuse) depends on the water

Specialist in Natural

conditions and supply options available locally and/or regionally, as well as other demands for

Resources Policy

water. Currently, most operators of data centers acquire water from municipal water systems,

commonly referred to as public water systems. Other potential sources include treated wastewater

(commonly referred to as reclaimed water) and direct withdrawals from surface water or

Charles V. Stern

groundwater. Congress has generally deferred to the states’ primacy in intrastate water allocation.

Specialist in Natural

Resources Policy

State laws and regulations largely govern access to freshwater within a state. Despite this

deference to state primacy, the federal government has invested in infrastructure to assist in the

development of water resources through the U.S. Army Corps of Engineers and the Bureau of

Reclamation. These facilities may store water for various purposes, which could ultimately

include water used for data centers. In some instances, data centers may be using water from

these sources indirectly via public water systems or communities that have agreements with such federal agencies.

Data centers may generate different types of water-related discharges (i.e., effluents), including wastewater and stormwater

discharges. In addition, in some cases when land is developed to construct data centers, the development may include

discharges of dredged or fill material into wetlands or streams. The project proponent for data center development and the

owner/operator of the data center facility may need to comply with certain federal requirements, including obtaining Clean

Water Act permits or approvals, which aim to prevent or minimize water quality impacts from the data center’s discharges.

The pollutants that may be present in data center wastewater discharges depend upon several factors, including the source and

quality of the water being used for cooling, the cooling technology being used, site-specific operations, and whether the

discharges are from normal operations or from construction and commissioning phases. Currently, data centers most

commonly send their wastewater effluent to publicly owned treatment works.

To address data centers and water, some Members have introduced bills in the 119th Congress. These bills are identified in a

table in this report. Some of these bills include provisions to improve the available information about data center water use, to

incentivize certain practices (e.g., water reuse) at data centers, or to limit or facilitate data center construction.

Congressional Research Service

Data Centers and Water: Frequently Asked Questions

Contents

Introduction ..................................................................................................................................... 1

What Are Data Centers? .................................................................................................................. 2

Data Center Water Use .................................................................................................................... 2

How Do Data Centers Use Water? ............................................................................................ 2

What Are Some Potential Options to Reduce Water Used by Data Centers? ........................... 3

Water Sources and Authorities ........................................................................................................ 4

What Are the Potential Water Sources Available for Data Centers? ......................................... 4

What Drives a Data Center’s Water Demand? .......................................................................... 5

Do Data Center Operators Pay to Use the Water from Public Water Systems? What

Determines the Price They Pay? ............................................................................................ 6

Why Are Local Water Authorities and the States the Main Entities Determining If

Water Is Available for Data Centers? ..................................................................................... 7

Are There U.S. Data Centers That Directly Source Their Water? ............................................. 9

Are Federal Reservoirs and Infrastructure Providing Water to Data Centers? ........................ 10

How Does and Can the Federal Government Support State and Local Water Supply

Planning, Including for Data Centers? ................................................................................. 12

What Are the Available Data on Data Center Water Use? ...................................................... 13

What Is the Current Federal Role in Assessing Data Center Water Use and Its Effect

on Water Resources? ............................................................................................................ 14

What Is Water Reuse? ............................................................................................................. 16

Does the Federal Government Have a Role in Regulating Water Reuse? ............................... 16

Water Quality Impacts from Data Center Discharges ................................................................... 18

What Types of Water-Related Discharges Do Data Centers Generate? .................................. 18

Wastewater ........................................................................................................................ 18

Stormwater ........................................................................................................................ 19

Discharges of Dredged or Fill Material for Development ................................................ 19

What Types of Pollutants Do Data Centers Discharge in Their Wastewater? ......................... 20

How Are Water-Related Discharges from Data Centers Regulated at the Federal

Level? ................................................................................................................................... 21

Regulation of Discharges of Dredged or Fill Material...................................................... 21

Regulation of Stormwater ................................................................................................. 22

Regulation of Wastewater ................................................................................................. 23

Congressional Action .................................................................................................................... 26

Which Bills Have Been Introduced in the 119th Congress That Address Data Centers

and Water? ............................................................................................................................ 26

Tables

Table A-1. Selected Bills on Data Centers and Water Use in the 119th Congress.......................... 28

Congressional Research Service

Data Centers and Water: Frequently Asked Questions

Appendixes

Appendix. Selected Bills on Data Centers and Water Use in the 119th Congress.......................... 28

Contacts

Author Information........................................................................................................................ 38

Congressional Research Service

Data Centers and Water: Frequently Asked Questions

Introduction

The expanding use of artificial intelligence (AI) and other trends in computing and digital

consumption have contributed to increased development of data centers.1 Simply, a data center is

a physical facility that houses and runs large computer systems.

Data centers are not new, but their scale and incidence have changed due to various factors. The

rise of the internet has led to an increased need for computing power. Paired with the expansion

of computationally intensive portions of the economy (e.g., AI, cryptocurrency), these factors

have driven an increase in the number and scale of these facilities. This increase has raised

concerns about the resources needed to support data center operation, including water.2

Concerns over the water used by data centers have garnered congressional attention. Data centers’

direct water use (i.e., water used or consumed at the data center for thermal regulation, not

indirect use of water used for off-site power generation or further up the supply chain for

manufacturing computer hardware or building materials) is estimated to make up a relatively

small proportion (approximately 2%) of total U.S. water consumption.3 Individual communities

may have concerns about data centers contributing to constraints on their community’s water

supply. For example, the International Energy Agency estimates that a 100 megawatt (MW) U.S.

data center may directly consume roughly the same amount of water per day as 2,600

households.4 Communities where data centers are being considered or operated may have

questions about how the water is sourced. Currently, municipal water systems, commonly

referred to as public water systems, are estimated to supply 97% of the water provided to U.S.

data centers, with a few self-sourcing their water supplies (i.e., using surface water or

groundwater directly and not via a public water supply facility).5

Communities may have concerns over potential water quality impacts of discharges from data

centers into nearby waterbodies or into wastewater treatment systems. The quality of water

discharged from data centers may affect wastewater treatment processes or the receiving aquatic

ecosystem.

Data center water use is difficult to quantify comprehensively, and understanding of its potential

effects on local water resources is evolving. Some Members of Congress have shown interest in

improving understanding of the potential water-related effects of data centers on communities and

the environment. In the 119th Congress, some Members have introduced bills regarding water use

by data centers. Many of these bills are related to gathering and publishing data on data center

1 Adam Zewe, “Explained: Generative AI’s environmental impact,” Massachusetts Institute of Technology News,

January 17, 2025.

2 For more information about data centers’ energy consumption, see CRS Report R48646, Data Centers and Their

Energy Consumption: Frequently Asked Questions, by Martin C. Offutt and Ling Zhu.

3 American Water Works Association (AWWA), Cooling the Cloud: Water Utilities in a Data Driven World, October

28, 2025, https://www.awwa.org/wp-content/uploads/AWWA-Cooling-the-Cloud-Water-Utilities-in-a-Data-DriverWorld.pdf.

4 This estimate accounts only for direct water consumption and is averaged across the various cooling strategies. The

International Energy Agency (IEA) estimates water use of data centers to include 60% indirect (at power plants) and

40% direct water use, with the sum equal to the water consumption of 6,500 households. The direct water use would

thus be equivalent to the water consumption of 2,600 households. IEA, Energy and AI, World Energy Outlook Special

Report, April 2025, p. 242, https://iea.blob.core.windows.net/assets/34eac603-ecf1-464f-b8132ecceb8f81c2/EnergyandAI.pdf.

5 Bluefield Research, “U.S. Water-Related Expenditures for Data Centers to Exceed $41 Billion Through 2030,” press

release, June 23, 2025, https://www.bluefieldresearch.com/ns/u-s-water-related-expenditures-for-data-centers-toexceed-us4-1-billion-through-2030/.

Congressional Research Service

1

Data Centers and Water: Frequently Asked Questions

water use, as well as other approaches to incentivize certain practices at data centers. Others

would support or limit data center development.

The questions in this report pertain to direct water use by data centers; a discussion of indirect

use, such as the use of water in offsite power generation, is beyond the scope of this report.

What Are Data Centers?6

Data centers house equipment that processes, stores, manages, and disseminates digital

information, or data, for a computer network in support of a variety of information technology

(IT) services and associated infrastructure. They typically include server racks used for data

storage and processing. They can range in size from parts of rooms or individual rooms

(sometimes referred to as “server closets”) to entire buildings. These facilities generally

require dedicated uninterruptible power supplies and cooling systems. Large-scale stand-alone

facilities may have on-site backup power generation. Data centers may provide different services

or multiple services including traditional enterprise services (such as in-house IT system

infrastructure management, system security, or system administration), on-demand enterprise

services (such as flexible, scalable computational, storage, networking, and security services

often on a pay-as-you-go basis), high performance computing, internet facilities, and hosting

facilities.

Depending upon the size and computational needs of the facility, data center servers may

use different types of processing units. Many data centers use central processing units (CPUs) for

general-purpose workloads. Conventional servers may have single, dual, or multiple CPUs. Other

types of processors are used for specific tasks. For example, training of AI models primarily relies

on graphics processor units (GPUs), which were originally designed for video rendering. In

addition, many chip design firms offer custom logic chips designed for particular applications.

These chips are referred to as application-specific integrated circuits (ASICs). Such custom chips

are frequently used for cryptocurrency mining and increasingly used for AI applications. In

addition to server racks, data centers also include systems to thermally regulate the hardware.

Data Center Water Use

How Do Data Centers Use Water?7

Data centers may directly use water for multiple purposes. Processing units and other computing

and networking devices and systems within a data center generate heat. Thermal regulation of the

hardware removes excess heat and maintains system function. Systems that provide thermal

regulation manage airflow and air-conditioning needs. Some of these systems may use

water. Depending upon local climate conditions and data center operations, some data centers

may have on-site power generation, which may have separate systems for thermal regulation that

also could use water.

Data centers may rely upon several different types of cooling technologies depending upon

facility characteristics such as size, location, and thermal regulation needs of the computing

equipment. Generally, the cooling technologies used in data centers rely on either air cooling or

liquid cooling. (This report focuses on water as the liquid used in liquid cooling systems.) Air6 Corrie Clark, Specialist in Energy Policy, authored this entry.

7 Corrie Clark, Specialist in Energy Policy, authored this entry.

Congressional Research Service

2

Data Centers and Water: Frequently Asked Questions

cooled systems use chilled air to transfer heat from the computing equipment. Liquid-cooled

systems use liquids to transfer heat. Still other options exist including hybrid cooling systems,

which may combine multiple cooling technologies, and two-phase systems, which

can operate and transfer heat by changing between the liquid and vapor phases of the working

fluid. Small- or medium-sized data centers or co-located data centers typically rely upon direct

expansion systems, referred to as computer room air conditioners (CRACs).8 Larger data centers

may rely on other systems.

As computing demands increase for AI training and inference (inference is when the AI system

stops training and starts “doing” or producing output), cooling needs are also increasing. Some

companies have announced plans to retrofit existing data centers to operate with liquid cooling

systems, which can be more efficient than air-cooled systems but may not be cost-effective for

small- or medium-sized data centers. Other companies are exploring both immersion cooling, in

which components make contact with a thermally conducting fluid, and two-phase cooling.9

Different technologies for air management and thermal regulation have different water

requirements. Characteristics of a data center such as size, computing load, local climate

conditions, and access and availability of water for cooling purposes can influence the type of

technology or technologies selected for use. These and other factors influence the amount of

water used by a particular data center. These topics are further discussed in “What Are Some

Potential Options to Reduce Water Used by Data Centers?”

Overall, water use by data centers is increasing. One study estimates that in 2023, U.S. data

centers directly used approximately 17 billion gallons of water, compared with 5.6 billion gallons

in 2014.10

What Are Some Potential Options to Reduce Water Used by Data

Centers?11

A common metric that can be used to compare the water use of different data centers is water use

effectiveness (WUE), typically defined as the total water consumption of the data center divided

by the electricity demand of the IT equipment. Water consumption refers to the volume of water

withdrawn from a source and permanently removed from that original source due to evaporation

or other irreversible processes (such as deep-well injection of wastewater). WUE generally

measures direct water usage at the facility level and does not measure indirect water use, such as

water consumed during the off-site generation of electricity that powers data center operations.

A WUE metric that accounts for both facility-level water consumption and indirect water use

(e.g., the water consumed to generate electricity used to power the facility) may be more

comprehensive. Some consider that accounting for water consumed by both on-site cooling and

off-site electricity generation in a single, comprehensive WUE metric would be more appropriate

8 Arman Shehabi et al., 2024 United States Data Center Energy Usage Report, LBNL-2001637, December 19, 2024, p.

5, https://eta.lbl.gov/publications/2024-lbnl-data-center-energy-usage-report.

9 Sebastian Moss, “Nvidia Hiring for Immersion Cooling Technologist to Test Fluids and Materials,” Data Center

Dynamics, July 25, 2024, https://www.datacenterdynamics.com/en/news/nvidia-hiring-for-immersion-coolingtechnologist-to-test-fluids-andmaterials/.

10 Arman Shehabi et al., 2024 United States Data Center Energy Usage Report, LBNL-2001637, December 19, 2024,

pp. 55-56, https://eta.lbl.gov/publications/2024-lbnl-data-center-energy-usage-report (hereinafter Shehabi et al., LBNL

2024 Report).

11 Corrie Clark, Specialist in Energy Policy, authored this entry.

Congressional Research Service

3

Data Centers and Water: Frequently Asked Questions

when considering data center water use.12 However, a comprehensive WUE metric would add

complexity to comparisons of different cooling systems in data centers if the data centers used

different off-site sources of electricity (e.g., coal-fired versus natural-gas-fired versus nuclear

versus solar versus wind).

Different cooling technologies can use different amounts of water for the same amount of

cooling.13 Evaporative cooling, which uses energy (or waste heat) to change the state of water

from a liquid to a gas (and would increase the absolute humidity of the surrounding air), is an

effective method for dissipating internal heat loads from IT devices. Data centers that use watercooled chiller systems include cooling towers that make use of evaporative cooling. Water-cooled

chiller systems typically have the highest WUE (i.e., are less efficient at using water), which is

largely attributed to the substantial cooling tower water usage.

If cooling systems include economizers, which refer generally to heat-transfer technologies that

make use of “free cooling” from surrounding resources such as ambient air or water, the WUE for

a specific system can be reduced. For example, waterside economizers, which rely on water to

transfer heat, can reduce the use of a mechanical chiller and reduce WUE values by eliminating or

reducing heat from compressors. Another technology option to decrease WUE could include the

use of airside economizers, which rely on air to transfer heat. Airside economizers can allow for

the shutdown of chilled water systems during certain weather conditions, which can reduce water

consumption. Further reductions in water use can be achieved through operational and

management practices, such as elevating setpoint temperatures (the target temperature that a

thermostat or control system aims to maintain).

Trade-offs in water consumed and power usage exist between evaporation-based cooling systems

and air-cooled systems. Evaporation-based cooling systems are generally more energy efficient

than air-cooled chillers or other waterless systems. While air-cooled chillers use no water, they

use comparatively more energy.

Water Sources and Authorities

What Are the Potential Water Sources Available for Data Centers?14

Operators of data centers can acquire water from several sources. Commonly used sources

include municipal drinking water systems; treated wastewater, which can be referred to as water

reuse (for more information, see “What Is Water Reuse?”); and direct withdrawals from surface

water or groundwater. As of 2025, U.S. data centers relied on municipal water systems, so-called

public water systems, for an estimated 97% of their on-site water needs, according to one

analysis.15 (For information about self-sourced data centers, see “Are There U.S. Data Centers

That Directly Source Their Water?”)

12 Shehabi et al., LBNL 2024 Report, pp. 44-45.

13 For more information on data center cooling technologies, see Sijun Xu et al., “Thermal Management and Energy

Consumption in Air, Liquid, and Free Cooling Systems for Data Centers: A Review,” Energies, vol. 16, no. 3 (2023),

p. 1279, https://doi.org/10.3390/en16031279.

14 Elena Humphreys, Specialist in Environmental Policy, authored this entry.

15 Bluefield Research, “U.S. Water-Related Expenditures for Data Centers to Exceed $41 Billion Through 2030,” press

release, June 23, 2025, https://www.bluefieldresearch.com/ns/u-s-water-related-expenditures-for-data-centers-toexceed-us4-1-billion-through-2030/.

Congressional Research Service

4

Data Centers and Water: Frequently Asked Questions

Data centers require water that meets the required water quality parameters for cooling

technologies to operate, and water from water systems generally suffices.16 Regulated public

water systems are required to meet federal Safe Drinking Water Act (SDWA) regulations,17 and

some SDWA regulations pertain to maintaining disinfection and controlling the corrosivity of

water as it moves through the piped distribution system. As such, water from a regulated water

system may be less likely to detrimentally affect the cooling capacity of a data center, compared

with water that may cause corrosion, scaling of certain minerals, or growth of microbials on

equipment.18 Data centers that rely on direct withdrawals from surface water or groundwater or

on reclaimed water may have to install pretreatment systems to improve water quality and thus

limit potential impacts to cooling technologies.

Other factors may play a role in a data center’s water source selection. The proximity of a data

center to potential water sources is likely a key factor in source selection. In addition to water

from public water systems, for example, data centers located in areas with adequate wastewater

treatment for water reuse, as well as nonpotable pipe networks (commonly called purple pipe),

may be able to access such resources for cooling. Some areas with purple pipe may have

competing uses and demand for reclaimed water, possibly limiting the availability of this resource

for data centers. (For more information on water reuse, see “What Is Water Reuse?”)

Another factor regarding water source selection may involve the length of time required for a data

center to access a water supply. For direct withdrawals from groundwater or surface water bodies

(self-supply), a data center operator may have to apply for and be granted a permit from the state

and/or local government to withdraw the water, as well as to install infrastructure to deliver the

water to the center.19 (For more information about the state and local role, see “Why Are Local

Water Authorities and the States the Main Entities Determining If Water Is Available for Data

Centers?”) By comparison, connecting to an existing public water system may require fewer steps

and less time than developing a self-supply.

What Drives a Data Center’s Water Demand?20

As discussed in “How Do Data Centers Use Water?,” several factors drive a data center’s demand

for water, including the size of a facility and its specific cooling technology.21 Among the liquid

cooling technologies, open-loop water-based cooling systems require more water than closedloop water-based cooling systems.22 In addition, the ambient temperature of the data center’s

location influences the quantity of water needed for cooling. The water use patterns of data

16 AWWA, Cooling the Cloud: Water Utilities in a Data Driven World, October 28, 2025, https://www.awwa.org/wp-

content/uploads/AWWA-Cooling-the-Cloud-Water-Utilities-in-a-Data-Driver-World.pdf.

17 Safe Drinking Water Act (SDWA) regulations apply to water systems that serve more than 25 individuals. SDWA

regulations include standards or maximum contaminant levels to control harmful contaminants in public water supplies.

18 AWWA, Cooling the Cloud: Water Utilities in a Data Driven World, October 28, 2025, https://www.awwa.org/wpcontent/uploads/AWWA-Cooling-the-Cloud-Water-Utilities-in-a-Data-Driver-World.pdf.

19 Water Environment Federation (WEF), Water and Wastewater Utilities and Data Centers: Frequently Asked

Questions, April 16, 2026, https://water-ai-nexus.org/reports/water-and-wastewater-utilities-and-data-centersfrequently-asked-questions-faqs/ (hereinafter WEF, Water and Wastewater Utilities and Data Centers: Frequently

Asked Questions).

20 Elena Humphreys, Specialist in Environmental Policy, authored this entry.

21 WEF, Water and Wastewater Utilities and Data Centers: Frequently Asked Questions.

22 For open-loop water-based cooling systems, heat is directly transferred to water, which then may be directed to a

cooling tower to evaporate some of the water and transfer heat into the atmosphere. For closed-loop water-based

cooling systems, indirect cooling is used where two separate fluid systems are maintained such that heat is transferred

without direct fluid contact. Evaporative cooling or another type of cooling may be used for a closed-loop system.

Congressional Research Service

5

Data Centers and Water: Frequently Asked Questions

centers that rely on evaporative cooling parallel changes in daily temperature, as well as seasonal

changes. Data centers generally require more water for cooling during the hotter parts of the day

and of the year.

For data centers employing liquid cooling technologies, the initial quality of the water when it

arrives at a data center may play a role in the total water volume needed for cooling purposes.23

For example, water with levels of dissolved solids below a certain concentration can be reused

on-site, possibly cycling through an evaporative cooling technology multiple times. After a

certain number of uses, the concentration of dissolved solids in water will increase due to

evaporation. When the dissolved solids reach a specific threshold, the water can no longer be

used for cooling and is discharged. (For more information about discharges, see “Water Quality

Impacts from Data Center Discharges.”)

Do Data Center Operators Pay to Use the Water from Public Water

Systems? What Determines the Price They Pay?24

As discussed above, data centers obtain most of their water from public water systems. Generally,

these systems charge their customers, including data center operators, a rate to support the costs

to provide water service. This rate and the quantity of water used generally determine how much

a customer pays for water. For data centers, these rates, as well as the volume of water in

consideration, and other specifications, may be detailed in a water service agreement between a

municipality and the data center operator. Such agreements may include provisions that limit the

disclosure of this information.

Different water systems use different rate structures, and the water rates charged by public water

systems are not generally publicly available.25 These rate structures may have implications for

communities that have added water users, such as data centers, that require a larger volume of

water.

Some systems use a uniform rate, where all customers pay the same price per unit of water

regardless of the type of customer. Other systems may use a flat fee, where customers pay the

same price regardless of the amount of water used.26 Tiered rate structures may be used to

incentivize certain behavior. One type of tiered rate structure is an increasing block rate structure,

which involves charging an increasingly higher rate for increasingly greater amounts of water

use. Under this rate structure, a system would charge a higher rate for each specific portion of

water used than the previous portion, so that a user is incentivized to promote water

conservation. Another type of tiered rate structure is a decreasing block rate structure, which may

be designed to incentivize the development of certain industries.27 For example, under a

decreasing block rate structure, a system would charge a lower rate for each specific portion of

water used than the previous portion, providing a discount to customers, such as commercial

23 Alliance for Water Stewardship, Water Stewardship in Data Centres, North Berwick, Scotland, 2025,

https://a4ws.org/resource/water-stewardship-in-data-centres/.

24 Elena Humphreys, Specialist in Environmental Policy, authored this entry.

25 Some water rate information exists publicly. Specifically, the Environmental Finance Center at the University of

North Carolina, Chapel Hill, provides water rate information for utilities that voluntarily submitted such data from a

subset of states. Other states collect rate information for all or a subset of drinking water systems.

26 AWWA/Raftelis/University of North Carolina, Chapel Hill, Environmental Finance Center, Water and Wastewater

Rate Survey.

27 U.S. Environmental Protection Agency (EPA), Setting Small Drinking Water System Rates for a Sustainable Future,

April 2022, https://www.epa.gov/system/files/documents/202206/FINAL%20Sustainable%20Water%20Rate%20STEP%20Guide_508.pdf.

Congressional Research Service

6

Data Centers and Water: Frequently Asked Questions

customers, with high water usage.28 In addition to tiered rate structures where rates vary by

amount of water used, in some areas, commercial customers, as opposed to residents, may pay a

different rate per unit of water used.29

Some systems’ water rates may be regulated by a state public utility commission (PUC) or state

public service commission (PSC). The regulatory authority of PUCs and PSCs varies by state. All

states, except Georgia, Michigan, Minnesota, North Dakota, and South Dakota, regulate certain

private entities that own water systems through PUCs or PSCs.30 Some states regulate both public

and private water systems. For example, Wisconsin’s PSC regulates the rates of all water systems.

In addition to jurisdiction over private systems, the PUCs/PSCs in Alaska, Indiana, Maine,

Maryland, Mississippi, New Jersey, Pennsylvania, Rhode Island, and West Virginia have varying

jurisdiction over publicly owned water systems.31

PUCs/PSCs may apply different requirements to the systems they regulate. For example, some

PUCs/PSCs employ a key principle called full cost recovery, which is a pricing practice of setting

rates at a level so the water system can fully recover costs. In addition to full cost recovery,

PUCs/PSCs typically allow for some amount of return for investors (e.g., most commonly in the

case of privately operated water systems).32 Full cost recovery is intended to ensure that water

rate revenues are used to cover the water system’s costs, supporting operation and maintenance

and capital costs to ensure sustainable water service.

Why Are Local Water Authorities and the States the Main Entities

Determining If Water Is Available for Data Centers?33

Congress has generally deferred to the states’ primacy in intrastate water allocation.34 The Water

Supply Act of 1958 (72 Stat. 320; 43 U.S.C. §390b) states that Congress recognizes “the primary

responsibilities of the States and local interests in developing water supplies for domestic,

28 EPA, Setting Small Drinking Water System Rates for a Sustainable Future, April 2022,

https://www.epa.gov/system/files/documents/202206/FINAL%20Sustainable%20Water%20Rate%20STEP%20Guide_508.pdf.

29 EPA, Setting Small Drinking Water System Rates for a Sustainable Future, April 2022,

https://www.epa.gov/system/files/documents/202206/FINAL%20Sustainable%20Water%20Rate%20STEP%20Guide_508.pdf.

30 Janice A. Beecher, Potential for Economic Regulation of Michigan’s Water Sector: Policy Brief for the Incoming

2019 Gubernatorial Administration, Michigan State University Extension, East Lansing, MI, November 7, 2018,

https://www.canr.msu.edu/michiganpolicyguide/uploads/files/11-21%20waterecon%20beecher%20final.pdf.

31 Janice A. Beecher, Potential for Economic Regulation of Michigan’s Water Sector: Policy Brief for the Incoming

2019 Gubernatorial Administration.

32 Janice A. Beecher, Economic Regulation of Utility Infrastructure, Lincoln Institute of Land Policy, May 2013,

https://www.lincolninst.edu/app/uploads/legacy-files/pubfiles/economic-regulation-of-utility-infrastructure_0.pdf.

33 Nicole T, Carter, Specialist in Natural Resources, authored this entry.

34 This is generally not a question of what powers the federal government has and could exercise under the

Constitution. Rather, it is a recognition that Congress has often required that the United States defer to or comply with

state law in the construction and operation of federal facilities pertaining to allocation, control, or distribution of water

(see, for example, §8 of the Reclamation Act of 1902, 32 Stat. 390; 43 U.S.C. §§372, 383). Other laws recognizing

state primacy and their effects have been the subject of much judicial interpretation. At the same time, as owner of

hundreds of thousands of acres of public domain land, the federal government is the “owner of the right to use the

waters pertaining to the public domain lands, the right to use of which has not passed into private ownership under

authority of the U.S. or an earlier sovereign.” (Letter from Kent Frizzell, Assistant Attorney General, Land and Natural

Resources Division, Department of Justice, to the National Water Commission, January 11, 1973.) The federal

government also holds reserved water rights—although in many cases unquantified—for the purposes associated with

the reservations of federal lands withdrawn from the public domain (e.g., military lands, national forests, national park

lands, and wilderness areas).

Congressional Research Service

7

Data Centers and Water: Frequently Asked Questions

municipal, industrial, and other purposes.”35 Consequently, states may express concern when

federal government actions are seen as infringing on state primacy in water allocation or

controlling water management decisions within state boundaries.

As discussed above, state laws and regulations largely govern access to freshwater within a state.

Water rights and water supply regulations differ by state and often may differ for surface water

and groundwater access within a state.36 For data center owners and operators, these water rights

and access issues would mainly come into play for self-supply (i.e., constructing or operating an

intake from a river or lake, or operating wells) rather than obtaining water from a public water

system. Otherwise, conforming with state water rights and access requirements would be the

responsibility of the water service provider that delivers the water to the data center.

In the United States, municipalities and other water service providers have largely been

responsible for developing and distributing water supplies to serve the households, commercial

entities, and industries in their service areas. Congress has authorized federal agencies to assist

communities with municipal water supply development generally through the provision of

financial or technical assistance.37 Congress also has tasked federal agencies with protecting the

quality of drinking water derived from surface waters and groundwater, as well as protecting fish

and wildlife resources.38

State law often provides statutory authority related to the establishment and operation of water

utilities within the state. In many states, a public water system is required to provide water service

within its service area (i.e., a utility may have a duty to provide service if certain conditions, such

as capacity and water rights, are met and the utility is the exclusive provider of services in the

area). Some states may allow utilities to establish terms and conditions of service and may allow

utilities to decline to provide services to certain entities for particular uses or reasons. If a utility

has authority to establish terms and conditions and chooses to do so, it may be required to

establish and enforce those terms and conditions in a fair and impartial manner for customers in

generally similar circumstances.

Although Congress defers to states’ primacy in intrastate water allocation, the federal government

has invested in infrastructure to develop water resources, and these facilities may store water for

various purposes. For example, reservoirs and dams and other infrastructure operated by the

Department of the Interior’s (DOI’s) Bureau of Reclamation (Reclamation) and the U.S. Army

Corps of Engineers (USACE) may store water for irrigation and for municipal and industrial uses,

35 The act also states that the federal government should participate and cooperate in developing these supplies at

federal flood control, navigation, and irrigation projects.

36 Depending on individual state water resources and their historic development, states may use one or a hybrid of

various water rights doctrines for their surface and groundwater rights regimes. For example, under the riparian

doctrine, a person who owns land that borders a watercourse has the right to make reasonable use of the surface water

on that land. Traditionally, the only limit to users under the riparian system is the requirement of reasonableness in

comparison to other users. Under the prior appropriation doctrine, a person who diverts water from a watercourse

(regardless of his location relative thereto) and makes reasonable and beneficial use of the water may acquire a right to

use of the water, and priority is given in order of seniority (i.e., the first person to divert and use water gets first, or

senior priority, and persons following in sequence get next priority, or junior priority, according to when they diverted

and used the water). Many states east of the Mississippi River generally follow a riparian doctrine of water rights, while

many western states typically follow the prior appropriation doctrine. Under the states’ legal water rights regimes, some

states administer permit programs that require certain water users that withdraw large amounts of water resources to

register with the state. Other states have undertaken various planning and reporting programs to monitor water use, but

do not generally require a permit.

37 For more information about these authorities, see CRS Report R46471, Federally Supported Projects and Programs

for Wastewater, Drinking Water, and Water Supply Infrastructure, coordinated by Jonathan L. Ramseur.

38 For more information about the federal role in the protection of drinking water sources, see CRS Report RL31243,

Safe Drinking Water Act (SDWA): A Summary of the Act and Its Major Requirements, by Elena H. Humphreys.

Congressional Research Service

8

Data Centers and Water: Frequently Asked Questions

among other purposes. (For more on the role of federal projects in data center water supplies, see

“Are Federal Reservoirs and Infrastructure Providing Water to Data Centers?”)

Are There U.S. Data Centers That Directly Source Their Water?39

While the vast majority of U.S. data centers have largely met their water needs through municipal

water suppliers, various factors may shape the interest of data center developers and operators

looking to self-supply, and their interest in options other than municipal water systems and

locations outside municipal service areas.40

A few data centers reportedly use or have proposed to use groundwater withdrawals to directly

meet their water supply needs or to use as a backup for their primary supplies. For example, a

proposed data center in Richland Parish in Northeast Louisiana is planning to use groundwater

from the Mississippi River Alluvial Aquifer for its cooling.41 In the past, Congress generally has

deferred management of U.S. groundwater resources to the states, with a few exceptions related

primarily to protecting drinking water. Therefore, the states or entities of the state primarily

determine whether groundwater withdrawals require permits or other approvals.42 In the federal

congressional context, authorities have been proposed and enacted to facilitate state, local, and

private groundwater management efforts (e.g., management of federal reservoir releases to allow

for groundwater recharge by local utilities).43

Comprehensive, publicly available information on data center water sources is not available. To

date, CRS has not found sources that identify currently operating U.S. commercial data centers

that self-source using surface water. That said, interest in meeting water supply needs other than

through municipal water suppliers may increase as commercial data center developers look to

sites outside municipal boundaries and service areas (e.g., in unincorporated areas or on federal

lands), and as communities respond to local concerns about data center impacts. One way that

data center developers may attempt to access surface water without going through municipal

water systems is through irrigation districts.44 How direct water withdrawals and consumption for

39 Nicole T. Carter, Specialist in Natural Resources Policy, authored this entry.

40 Local (or state) restrictions on data centers seem to reflect community concerns about data centers on local utilities

and resources. These are likely factors shaping interest by data center developers and operators in siting data centers

outside local municipal service areas, such as in rural and unincorporated areas.

41 According to local reporting, the data center is “registered to consume more than 23 million gallons of water per day,

or 8.4 billion gallons per year, according to state records and the company itself.... But Meta says those limits are

substantially higher than what it will actually use annually. According to the company, the data center will use between

500 to 600 million gallons per year once it is up and running in 2028, or an average of 1.5 million gallons per day”

(Josie Abugov, “How Much Water Will Data Center Use?” Richland Beacon News, January 1, 2026,

https://www.therichlandbeaconnews.com/article/1024,how-much-water-will-data-center-use).

42 State requirements can vary. For example, the Missouri Department of Natural Resources (Missouri DNR) data

centers and water website states: “There are no regulatory restrictions on the amount of water that can be used or for

what purposes. Consequently, while the department regulates water quality, it does not regulate water amount or usage,

beyond exporting water out of state and requiring annual reports of major water users. Major water users refers to any

facility or individual with the capability to withdraw at least 100,000 gallons per day (70 gallons per minute) from any

water source in Missouri.” (Missouri DNR, “Data Centers,” https://dnr.mo.gov/data-e-services/centers.)

43 For more information about groundwater management, see CRS Report R45259, The Federal Role in Groundwater

Supply, by Peter Folger et al.

44 Two reported examples of data center developers seeking water from irrigation districts are as follows. In December

2024, the Town of Marana, AZ, adopted an ordinance amending the town code to state, “The Marana water department

will not provide potable water to a data center (principal or accessory use) for its cooling system, humidity control, and

other similar operations” (Town of Marana, Marana Ordinance No. 2024.029, p. 6). For a proposed data center in the

town, the Cortaro Marana Irrigation District is expected to provide nonpotable water for industrial, irrigation, and fire

(continued...)

Congressional Research Service

9

Data Centers and Water: Frequently Asked Questions

data centers could affect local water resources depends on the water conditions and supply

options available locally or regionally, as well as other demands for water. That is, the amount of

water available, its condition, its seasonal and weather-dependent availability, as well as other

uses (such as households, industries including the energy and power industries and agriculture,

and environmental and species needs and conditions) can factor into the relative significance of a

new water demand from data centers. Similarly, the timing of peak water demand for data centers

(e.g., hot days) may also be a factor if it occurs simultaneously to other users’ peak demands, or

when supplies are particularly constrained. Further, direct withdrawals would be subject to state

groundwater and surface water laws and regulations, pursuant to the prevailing water rights

doctrine in each state (i.e., riparian, prior appropriation, right of capture, or some hybrid).45

Are Federal Reservoirs and Infrastructure Providing Water to Data

Centers?46

Most large-scale federal water resource projects are owned and managed by the two principal

federal water resource agencies: Reclamation, which operates facilities in the 17 western

reclamation states,47 and USACE. Reclamation owns and operates reservoirs, dams, and other

infrastructure that are used to store and deliver water for various purposes, including primary

project purposes of irrigation and municipal and industrial (M&I) uses. DOI typically acquires

water rights in the respective states for these projects as needed and contracts with water users

(typically irrigation districts and municipalities) for delivery of project water supplies.48

USACE dams typically have not focused on water supply storage as a principal project purpose;

instead, water supply storage is often a secondary purpose of multipurpose dams. The role of

USACE in water storage nonetheless can be locally significant. Because most USACE reservoirs

store water for nonconsumptive purposes (like navigation and flood control), the agency

generally does not hold state water rights for its projects. USACE may store water for municipal

and industrial uses at its reservoirs; the entity requesting a water supply agreement to withdraw

stored water from a USACE-operated reservoir is responsible for securing water rights through

the state.

Based on research conducted in early July 2026, CRS did not identify data center developers or

operators that have directly entered into a water supply agreement with Reclamation or USACE

for withdrawal of water stored at federal facilities.49 Nonetheless, existing or planned data centers

suppression purposes (Charles Borla, “Rezoning Approved for Marana Data Center Campus,” Arizona Daily Star,

February 18, 2026). In an unincorporated area of Imperial County, CA, reportedly a data center developer claims to

have attempted to fallow agricultural land in order to transfer (through a change of purpose application) the conserved

water to the data center’s operations. The local irrigation district denied the application for the untreated irrigation canal

water to be used for industrial cooling water; the developer subsequently filed suit against the irrigation district (Betty

Miller, “Data Center Developer Sues IID Over Water Service Denial,” The Desert Review, June 18, 2026).

45 See footnote 36.

46 Nicole T. Carter, Specialist in Natural Resources Policy, and Charlie Stern, Specialist in Natural Resources Policy,

authored this entry.

47 The 17 reclamation states are Arizona, California, Colorado, Idaho, Kansas, Montana, Nebraska, Nevada, New

Mexico, North Dakota, Oklahoma, Oregon, South Dakota, Texas, Utah, Washington, and Wyoming.

48 For more information on the Bureau of Reclamation, see CRS Report R46303, Bureau of Reclamation: History,

Authorities, and Issues for Congress, by Charles V. Stern and Anna E. Normand.

49 For a discussion of U.S. Army Corps of Engineers (USACE) authorities for water supply storage agreements, see

CRS Report RL30478, Federally Supported Water Supply and Wastewater Treatment Programs, coordinated by

Jonathan L. Ramseur.

Congressional Research Service

10

Data Centers and Water: Frequently Asked Questions

may indirectly receive water through water utilities or communities that have such agreements

with federal agencies. For example, CRS identified two USACE facilities related to data centers:

1. The Project Turbo data center (which was paused as of December 2025) near

Gainesville, GA, reportedly had planned to meet its water needs through the City

of Gainesville’s water system; the city withdraws water from USACE’s Lake

Lanier as its primary water source.50

2. Amazon’s project in Caddo and Bossier parishes in Louisiana, associated with

land acquisition by STACK Infrastructure (an industrial site developer), has

planned water service through Blanchard Utilities of the Town of Blanchard, LA.

Blanchard draws its water supply from Caddo Lake, which is formed by a dam

operated by USACE.51

Some data centers in the 17 western states where Reclamation owns and operates water resource

facilities appear to be indirectly receiving water from Reclamation projects through entities that

have agreements with federal facilities. For instance, a 2026 study found that 66 data centers were

completed or under construction in Central Arizona.52 This figure included data centers in the

areas serviced by municipal water suppliers for Tucson (9), Phoenix (25), Scottsdale (5), and

Mesa (8). All of these municipalities receive a significant portion of their water supplies from the

federally managed Colorado River, through the Central Arizona Project.53 Phoenix, Scottsdale,

and Mesa also receive significant shares of their water supplies from the federally owned Salt

River Project. Some data centers may also pursue the conversion of federal project water for

irrigation uses to M&I uses.54

The Water Resources Development Act of 2026 (H.R. 9497) as ordered to be reported in July

2026 includes a provision that may provide information relevant to data centers and USACE

projects. The provision would direct the Secretary of the Army within one year of enactment to

report on impacts of “new commercial and industrial water users” on USACE water resources

development projects that are authorized for the purpose of water supply or water conservation.55

50 USACE and the City of Gainesville, GA, entered into an agreement in June 1953 to compensate the city for property

taken to construct the Buford Dam and its Lake Lanier reservoir. Pursuant to the agreement, Gainesville was granted

the right to remove up to 8 million gallons of water per day from the lake without payment to USACE. Clyde Morris,

“Project Turbo Data Center: Is LLA Aware and Involved?” Lake Lanier Association Newsletter, 2025.

51 Liz Swain, “Blanchard Nears First Public Meeting on Contentious Data Center,” The Shreveport-Bossier City

Advocate, March 2, 2026. Unlike most other USACE dams, whose operation remained a federal responsibility after

construction, according to USACE, the agency was not transferred authority over the reservoir or the real estate at

Caddo Lake, when in 1976 Congress directed USACE to assume responsibility for dam operations. Therefore,

Blanchard’s water withdrawals from the reservoir are not subject to a water supply agreement with USACE, and an

easement to access the lake is not required of USACE. (USACE, personal communication with CRS, May 20, 2026.)

Other federal permits and authorizations may be required. Caddo Lake is a 25,400-acre lake and wetland in Texas and

Louisiana.

52 Arizona State University, Morrison Institute for Public Policy, “From Copper, Cattle and Cotton to Chips and Cloud

Computing: Large Water Uses in Central Arizona,” February 2026, https://morrisoninstitute.asu.edu/copper-cattle-andcotton-chips-and-cloud-computing-large-water-uses-central-arizona.

53 For more information, see CRS Report R45546, Management of the Colorado River: Water Allocations, Drought,

and the Federal Role, by Charles V. Stern, Pervaze A. Sheikh, and Kristen Hite.

54 For example, see the Marana and Imperial proposals in discussed in footnote 44.

55 USACE’s authorities have typically used “municipal and industrial” to broadly capture nonagricultural water uses,

including commercial uses. More generally data centers have often been classified as commercial facilities (e.g., see

discussion in “What Is the Current Federal Role in Assessing Data Center Water Use and Its Effect on Water

Resources?”) and also at times could be considered as industrial facilities (e.g., some local zoning requirements).

Congressional Research Service

11

Data Centers and Water: Frequently Asked Questions

How Does and Can the Federal Government Support State and

Local Water Supply Planning, Including for Data Centers?56

As noted above, most data centers are not currently sourcing their water directly (referred to as

self-supply) and instead receive water from public water supplies, which generally source from

surface water bodies (e.g., Lake Michigan for Mount Pleasant, WI, data centers, or the Potomac

River for Loudoun County, VA, data centers) or local groundwater. As previously noted, state

laws and regulations generally determine access to water sources within state borders. For some

shared resources, however, interstate compacts and associated river basin organizations may play

a role in determining access to state water resources, as well as in considering potential impacts

on other states (e.g., upstream withdrawals may affect availability of water for downstream

states).

Congress has authorized some federal support, including technical assistance for water planning

efforts in selected states, and state and local drought planning and water resource planning (e.g.,

USACE technical assistance for states and local water resource planning authorized by 42 U.S.C.

§1962d-16 or USACE watershed studies authorized by 33 U.S.C. 2267a).57 For example, DOI,

through Reclamation’s Drought Response Program, has the authority to provide support for the

development of comprehensive drought plans for state and local entities in the 17 western

Reclamation states, and also may support projects that build long-term resiliency to drought. To

date, this assistance has been limited to state and local governments and entities with water or

power delivery authorities. Some federal legislative proposals, such as S. 3737 in the 119th

Congress (see Table A-1 in the Appendix), would expand this Reclamation authority to include

data centers, among other entities, as eligible applicants for project support.

Some states, such as California, Texas, and Florida, have undertaken their own planning efforts.

In some cases, it is unclear whether or how these recent planning efforts may have incorporated

data center water demands.

While the federal government has continued some support for state planning efforts, at times

prior to the mid-1980s there were broader federal water resource planning efforts. For a brief

history of federal water planning since 1965, see the text box “Federal Water Planning Since

1965” below.

In 2022, Congress established in statute the Interagency Committee on Water Management and

Infrastructure (P.L. 117-316; 15 U.S.C. §9708). Congress directed the committee to work toward

improving interagency coordination in water-related matters, including water storage and

supplies, and to identify needs for cross-agency research and coordination. Since enactment,

various groups have advocated implementing the committee as Congress directed in the law.58

56 Nicole T. Carter, Specialist in Natural Resources Policy, and Charlie V. Stern, Specialist in Natural Resources

Policy, authored this entry.

57 The House-introduced Water Resources Development Act of 2026 (H.R. 9497) would amend the water supply

purposes for which the Secretary of the Army can produce a watershed assessment that includes water supply for

“projected water supply needs for municipal, domestic, industrial, and agricultural purposes.”

58 Coalition letter from Julie Ufner, National Waterways Conference, et al. to President Donald J. Trump, regarding

Executive Order 13956, “Modernizing America’s Water Resource Management and Water Infrastructure,” September

30, 2025, https://icwp.org/wp-content/uploads/2026/03/Coalition-Water-Subcabinet-Committee-Letter_Sept-2025.pdf.

Congressional Research Service

12

Data Centers and Water: Frequently Asked Questions

Federal Water Planning Since 1965

At times, concern about the availability and use of water to support the nation’s people, economy, and

environment has bolstered interest in federal water supply planning. While many support better coordination of

federal water activities and federal financial support, states often react to proposals of a greater federal role in

water supply as attempts to exert federal control over what may be considered state and local matters. Congress

has not enacted overarching water policy legislation since the 1965 Water Resources Planning Act (P.L. 89-80; 42

U.S.C. §1962). The Water Resources Planning Act was the direct result of recommendations of the Senate Select

Committee on National Water Resources, a congressional committee established to review national water

resources policy. The 1965 act, among other things, created the interagency Water Resources Council (WRC).

Following the 1965 act, the federal government supported federal, state, and river basin planning in numerous

ways. By the late 1970s, federal watershed and river basin commission planning was both positively received and

criticized for its costs and usefulness. Federal funding for state planning efforts declined. The early-1980s

disbandment of the WRC (with re-formation for a few specific decisions in the mid-2010s), and of most river basin

commissions, shifted federal project planning away from coordinated watershed-based decisionmaking. Since then,

most federal agency planning has been project-specific, with some exceptions.

Although an assessment of the nation’s water resource conditions was last conducted in 1975 and several entities

have studied selected aspects of water policy and management, the most recent systematic and comprehensive

review of nationwide federal water policy was the National Water Commission’s 1973 Water Policies for the Future.

The National Water Commission was created by Congress in 1968 for a five-year term to provide a review of

national water resource problems and programs (P.L. 90-515; 82 Stat. 868) and ended in 1973.

Since 1983, coordination of federal water resources efforts has largely been ad hoc. In 2022, Congress established

in statute the Interagency Committee on Water Management and Infrastructure (P.L. 117-316) after two years of

its operating informally. The committee includes the Administrators of the National Oceanic and Atmospheric

Administration and Environmental Protection Agency, and the Secretaries of the Interior, Agriculture, Commerce,

Energy, and the Army, and others, as appropriate. The committee's purpose is to “ensure” the federal government

engages in water-related matters, including water storage and supplies, water infrastructure, and water forecasting,

among other topics, where agencies have joint or overlapping responsibilities.

What Are the Available Data on Data Center Water Use?59

The availability of sector-specific or facility-specific water usage data (e.g., that of a data center)

is limited. Water utilities may collect water usage data and, when required, report the data to state

or local agencies; such data are not always shared publicly.60 Water usage data for facilities that

rely on public supplies are typically combined with water usage data from all the other users

within the service area.61 Thus, effects from individual facilities may be difficult to identify and

quantify. Facilities that self-supply often have fewer reporting requirements than a utility,

depending on state or local laws and/or regulations.62

Some states or localities may pursue more information on current or anticipated water use by data

centers. For example, the Texas state legislature directed the Public Utility Commission of Texas

to conduct an Energy and Water Use Survey for Data Center and Virtual Currency Mining

59 Anna Normand, Specialist in Natural Resources Policy, and Elena Humphreys, Specialist in Environmental Policy,

authored this entry.

60 M. Y. Naseri and L. T. Marston, “United States Water Withdrawals Database,” Scientific Data, vol. 12, article no.

2022 (2025), https://doi.org/10.1038/s41597-025-06300-1; L. Medalie et al., Water Use Across the Conterminous

United States, Water Years 2010–20, Chap. D of U.S. Geological Survey Integrated Water Availability Assessment—

2010–20, USGS Professional Paper 1894–D, 2025, https://doi.org/10.3133/pp1894D (hereinafter Medalie et al., Water

Use Across the Conterminous United States, Water Years 2010–20).

61 C. L. Luukkonen et al., Data and Knowledge Gaps of a Water Bottling Facility Inventory and Select Water-Use

Dataset, United States, USGS Scientific Investigations Report 2024–5106, 2024, https://doi.org/10.3133/sir20245106

(hereinafter Luukkonen et al., Data and Knowledge Gaps).

62 Medalie et al., Water Use Across the Conterminous United States, Water Years 2010–20.

Congressional Research Service

13

Data Centers and Water: Frequently Asked Questions

Facilities; the commission is required to submit a resulting report to the Legislative Budget Board

and the governor by the end of 2026.63

What Is the Current Federal Role in Assessing Data Center Water

Use and Its Effect on Water Resources?64

To date, the federal government has not conducted a systematic assessment of water use by data

centers. For the past 70 years, the United States Geological Survey (USGS) has compiled

national-, state-, and county-level estimates of water withdrawals across the nation based on

reporting from various water use sectors.65 The USGS historically appears to have classified data

centers as commercial for purposes of its water withdrawal estimates through 1995.66 The USGS

has not provided separate water withdrawal estimates for the commercial sector since 1995.67

More recently, to fulfill mandates from the Secure Water Act, the USGS Water Availability and

Use Science Program developed statistical models using AI and machine learning for estimating

water withdrawals and consumptive use.68 These models rely heavily on information provided by

state and local governments, as well as federal datasets.69 In 2025, the USGS Water Availability

and Use Science Program produced the USGS Integrated Water Availability Assessment—201020, which provided estimates of surface water and groundwater withdrawals for public supply,

irrigation, and thermoelectric generation cooling on a subwatershed scale at monthly intervals

over a decade.70 For public supply, the models produced separate estimates for domestic

63 Public Utility Commission of Texas, “Frequently Asked Questions: Energy and Water Use Survey for Data Center

and Virtual Currency Mining Facilities (Project No. 59281),”

https://www.puc.texas.gov/industry/water/utilities/energy-and-water-use-survey/faq/#dcvcmf-g; Public Utility

Commission of Texas, Memorandum Project No. 59181, Data Collection to Study the Water Use of Dam Centers and

Virtual Currency Mining Facilities (General Appropriations Act of the 89th Legislative Session at Vlll-57 (“Rider 6”)

Staff Update, April 2, 2026, https://interchange.puc.texas.gov/Documents/59281_2_1615402.PDF.

64 Anna Normand, Specialist in Natural Resources Policy, authored this entry.

65 Through 2015, the United States Geological Survey (USGS) published estimates for one year every five years.

USGS, “Accessing Water Use Data,” June 17, 2026, https://www.usgs.gov/mission-areas/waterresources/science/accessing-water-use-data.

66 The commercial sector included computing infrastructure providers, data processing, web hosting, and related

services. See the two-digit North American Industrial Classification System (NAICS) 2022 code 518210 and Office of

Management and Budget’s 1987 Standard Industrial Classification code 7371-7379. U.S. Census Bureau, “North

American Industry Classification System,” https://www.census.gov/naics/?input=&year=2022; USGS, Guidelines for

Preparing U.S. Geological Survey Water-Use Estimates in the United States for 1995, Appendix B,

https://water.usgs.gov/usgs/watuse/1995compilation/1995guidelines/appb.html.

67 USGS, “Changes in Water Use Categories,” August 3, 2018, https://www.usgs.gov/mission-areas/waterresources/science/changes-water-use-categories.

68 The Secure Water Act is Title IX, Subtitle F of the Omnibus Public Land Management Act of 2009 (P.L. 111-11).

Section 9508 directed the Secretary of the Interior to produce regular, comprehensive assessments of water use and

availability in the United States. USGS, “Water Use,” November 1, 2023, https://www.usgs.gov/mission-areas/waterresources/science/water-use (hereinafter USGS, “Water Use”); A. Alzraiee et al., “Next Generation Public Supply

Water Withdrawal Estimation for the Conterminous United States Using Machine Learning and Operational

Frameworks,” Water Resources Research, 60, e2023WR036632 (2024), https://doi.org/10.1029/2023WR036632.

69 To support improved collection of water use data by states, the Secure Water Act authorized the USGS Water-Use

Data and Research Program to provide financial assistance through cooperative agreements with state water resource

agencies. USGS, “Water Use.”

70 The USGS is aiming for a future release of additional categories of use. Subwatershed scale refers to the 12-digit

hydrologic units code (HUC-12) watershed areas in the USGS Watershed Boundary Dataset; it is the scale often used

for localized studies. USGS, “National Water Availability Assessment Data Companion,” https://water.usgs.gov/nwaadata/; Medalie et al., Water Use Across the Conterminous United States, Water Years 2010-20; USGS, U.S. Geological

(continued...)

Congressional Research Service

14

Data Centers and Water: Frequently Asked Questions

deliveries and for combined commercial, industrial, and institutional deliveries.71 In 2026, the

USGS released a dataset covering 2020 self-supply industrial water use by county and

subwatershed scale.72 The facilities in the self-supply industrial water use dataset are based on a

manufacturing categorization.73

Federal funding has also supported the development of a water use database.74 In 2025,

researchers from the Virginia Polytechnic Institute and State University (Virginia Tech) published

the United States Water Withdrawals Database, a standardized compilation of water withdrawal

data and estimates for 42 states, which included public supply, industrial, and commercial water

use.75 The database provides water withdrawal values reported by states from water users that are

required by state law to periodically report their withdrawals from surface water and/or

groundwater. The new USGS water availability assessments are different in that they supplement

state-reported values with modeled estimates to fill in spatial, temporal, and sectoral gaps, and do

not include self-supply commercial water use.76

The USGS’s Water Availability and Use Science Program also may investigate with partners the

effect of water use in specific sectors or geographic regions on water resources.77 Appropriated

cooperative matching funds have supported partnerships with nonfederal entities to investigate

how hydrologic systems are affected by increasing demand and competition for limited regional

water resources.78 In addition, Congress directed the program to conduct a nationwide assessment

of water withdrawals for a specific industrial sector—water bottling—and its effect on water

resource availability.79 Similar to data centers, there is no comprehensive national inventory of

water bottling facilities that includes the volume of water extracted and associated water source.80

Survey Integrated Water Availability Assessment—2010-20, USGS Professional Paper 1894, 2025,

https://doi.org/10.3133/pp1894. USGS, “Hydrologic Units of the United States,”

https://water.usgs.gov/themes/hydrologic-units/.

71 J. D. Larsen et al., “Public Supply Water Delivery Analysis and Estimation for the Conterminous United States,”

Water Resources Research, vol. 61, e2024WR039271 (2025), https://doi.org/10.1029/2024WR039271.

72 USGS, “Industrial Water Use for 2020 by County, HUC12, Month, and Year for the Conterminous United States,”

April 22, 2026, https://www.usgs.gov/data/industrial-water-use-2020-county-huc12-month-and-year-conterminousunited-states.

73 The USGS provided data based on NAICS codes 31-33: the manufacturing sector “comprises establishments

engaged in the mechanical, physical, or chemical transformation of materials, substances, or components into new

products.” U.S. Census Bureau, “North American Industry Classification System,”

https://www.census.gov/naics/?input=&year=2022.

74 M. Y. Naseri and L. T. Marston, “United States Water Withdrawals Database,” Scientific Data, vol. 12, article no.

2022 (2025).

75 The dataset published by the study authors does not provide further specific facility information under these water

uses. M. Y. Naseri and L. T. Marston, “United States Water Withdrawals Database,” Scientific Data, vol. 12, article no.

2022 (2025).

76 M. Y. Naseri and L. T. Marston, “United States Water Withdrawals Database,” Scientific Data, vol. 12, article no.

2022 (2025).

77 USGS, “Water Use.”

78 USGS, “Cooperative Projects,” https://www.usgs.gov/programs/water-availability-and-use-scienceprogram/cooperative-projects.

79 Explanatory statements accompanying Division G of the Consolidated Appropriations Act, 2021 (P.L. 116-260) and

Division G of the Consolidated Appropriations Act, 2022 (P.L. 117-103) directed a total of $2.75 million of funding for

the USGS to research the hydrologic impact of extraction of water for bottling on water tables, water availability, and

water quality. USGS, “Withdrawals for Bottled Water,” December 2, 2024, https://www.usgs.gov/mission-areas/waterresources/science/withdrawals-bottled-water.

80 C. L. Luukkonen et al., Data and Knowledge Gaps.

Congressional Research Service

15

Data Centers and Water: Frequently Asked Questions

The water bottling study may be useful as a possible analogue to any study on water use at data

centers, in that any such effort might likely face similar challenges in obtaining comprehensive

water use information.

What Is Water Reuse?81

Water reuse, also commonly referred to as water recycling or water reclamation, is the process of

capturing wastewater, stormwater, saltwater, or graywater and treating it as needed for a specific

beneficial purpose.82 Such purposes may include industrial processes, agriculture, landscape

irrigation, surface or groundwater replenishment, or even drinking water.83 The extent of

treatment depends upon the intended use and any potential risk to human health or the

environment.

Amid growing concerns about data centers’ water consumption and potential impacts on

municipal potable water supplies and other freshwater resources, some data centers are

incorporating water reuse into their operations.84 These practices include installing on-site

treatment systems that treat and recycle wastewater for reuse in cooling processes and accessing

reclaimed water from nearby wastewater treatment facilities. According to the U.S.

Environmental Protection Agency (EPA), many data center operators are interested in

transitioning to recycled water for cooling purposes but face an unclear permitting pathway for

this specific use.85

Does the Federal Government Have a Role in Regulating Water

Reuse?86

At the federal level, there are no laws or regulations governing water reuse.87 Generally, states

maintain primary regulatory authority in allocating and developing water resources. According to

EPA, “Some states have established programs to specifically address reuse, and some have

incorporated water reuse into existing regulatory frameworks.”88 Treatment and monitoring

requirements may vary depending upon the source of recycled water and the end use.

Accordingly, states with water reuse regulations, guidelines, or policies may create separate

treatment specifications based on the source of reclaimed water and the end use.89 EPA data

81 Laura Gatz, Specialist in Environmental Policy, authored this entry.

82 WateReuse, “Water Reuse 101,” https://watereuse.org/educate/. EPA, “Basic Information about Water Reuse,”

https://www.epa.gov/waterreuse/basic-information-about-water-reuse#basics.

83 WateReuse, “Water Reuse 101,” https://watereuse.org/educate/. EPA, “Basic Information about Water Reuse,”

https://www.epa.gov/waterreuse/basic-information-about-water-reuse#basics. EPA, “Water Reuse Resource Hub by

End-Use Application,” https://www.epa.gov/waterreuse/water-reuse-resource-hub-end-use-application.

84 Association of Clean Water Administrators (ACWA) and EPA, “Water Reuse for Data Centers,” https://www.acwaus.org/wp-content/uploads/2025/12/ACWA-EPA_webinar_data_center_and_reuse_12032025.pdf.

85 EPA, “Water Reuse Action Plan: Online Platform,” Action 3.10: Support States in Expanding the Use of Recycled

Water for Industrial and Data Center Cooling Applications, https://www.epa.gov/waterreuse/water-reuse-action-planonline-platform?action=3.10.

86 Laura Gatz, Specialist in Environmental Policy, authored this entry.

87 EPA, “Basic Information About Water Reuse,” https://www.epa.gov/waterreuse/basic-information-about-waterreuse#basics.

88 EPA, “Basic Information About Water Reuse,” https://www.epa.gov/waterreuse/basic-information-about-waterreuse#basics.

89 EPA, “Basic Information About Water Reuse,” https://www.epa.gov/waterreuse/basic-information-about-waterreuse#basics.

Congressional Research Service

16

Data Centers and Water: Frequently Asked Questions

indicate that as of February 2024, 20 states had developed guidelines or regulations for industrial

water reuse.90

At the federal level, EPA has taken steps, in collaboration with federal agencies and other

partners, to help support the adoption of water reuse and address barriers across a range of

technical, institutional, and financial topics.91 In 2020, EPA published a National Water Reuse

Action Plan (WRAP), in coordination with federal agencies, state and tribal partners, and the

water utility sector and associations, among other stakeholders.92 The WRAP identified 37 actions

with over 200 implementation milestones to be undertaken by a variety of stakeholders, aimed at

supporting consideration and implementation of water reuse as a water resource management

strategy. As part of its efforts under the WRAP, EPA and partners developed the Regulations and

End-Use Specifications Explorer (REUSExplorer), a web-based tool that summarizes over 185

state reuse regulations, searchable by state, sources of water, and reuse application.93 The

REUSExplorer tool aims to help clarify the regulatory landscape, ensure that interested parties

have information on water reuse treatment standards, and help support states as they develop

reuse regulations and guidelines.94

Enacted in 2021, the Infrastructure Investment and Jobs Act (IIJA; P.L. 117-58) required EPA to

take certain actions related to water reuse. Section 50218 of the IIJA directed EPA to establish a

Water Reuse Interagency Working Group to develop and coordinate water reuse activities and

resources through the implementation of a National Water Reuse Action Plan.

In April 2026, EPA released the Water Reuse Action Plan 2.0 (WRAP 2.0), which the agency

characterizes as a renewed initiative, expanding upon the original plan and emphasizing water

reuse for “industry, the technology sector, and energy dominance.”95 In a press release for the

plan, EPA specified that WRAP 2.0 is not a federal regulatory mandate; that EPA and federal

partners recognize that states and local leaders understand their water resources and needs best;

and that the initiative leans on collaborative partnerships to advance reuse.96 WRAP 2.0 has a

number of actions aimed at advancing the use of recycled water for data centers. Among these is

an action, to be undertaken by EPA, “to work with states and the regulated community to compile

and share best practices relevant for industrial cooling systems so states can readily permit the use

of recycled water for data centers.”97 Other new data-center-related actions, to be undertaken by

EPA and a number of partner stakeholders, include identifying and proposing solutions to the

90 Based on a CRS search of EPA’s Regulations and End-Use Specifications Explorer (REUSExplorer), for “industry”

under “reuse application,” https://www.epa.gov/waterreuse/regulations-and-end-use-specifications-explorerreusexplorer.

91 EPA, “National Water Reuse Action Plan,” https://www.epa.gov/waterreuse/national-water-reuse-action-plan.

92 EPA, National Water Reuse Action Plan, EPA-820-R-20-001, February 2020,

https://www.epa.gov/sites/default/files/2020-02/documents/national-water-reuse-action-plan-collaborativeimplementation-version-1.pdf.

93 EPA, “Regulations and End-Use Specifications Explorer (REUSExplorer),”

https://www.epa.gov/waterreuse/regulations-and-end-use-specifications-explorer-reusexplorer.

94 EPA, “Basic Information about Water Reuse,” https://www.epa.gov/waterreuse/basic-information-about-waterreuse#basics. EPA and the Association of Clean Water Administrators (ACWA), Water Reuse for Data Centers,

December 2025, https://www.acwa-us.org/wp-content/uploads/2025/12/ACWAEPA_webinar_data_center_and_reuse_12032025.pdf.

95 EPA, “Water Reuse Action Plan 2.0,” https://www.epa.gov/waterreuse/water-reuse-action-plan-20.

96 EPA, “EPA Launches Water Reuse Action Plan 2.0 to Advance Agency's Core Mission and Strengthen US Industry,

AI, and Energy Dominance,” press release, April 16, 2026, https://www.epa.gov/newsreleases/epa-launches-waterreuse-action-plan-20-advance-agencys-core-mission-and-strengthen-us.

97 EPA, “Water Reuse Action Plan 2.0 Booklet,” https://www.epa.gov/system/files/documents/2026-04/wrap-2.0booklet.pdf, p. 10.

Congressional Research Service

17

Data Centers and Water: Frequently Asked Questions

“regulatory hurdles” associated with using recycled water for data center cooling, hosting a

collaborative water and wastewater utility forum on data centers, establishing a Center of

Excellence to advance the use of recycled water for AI, and advancing development of on-site

water reuse through the Building Infrastructure Locally for Decentralized Water Systems (BILD)

initiative.98

Water Quality Impacts from Data Center Discharges

What Types of Water-Related Discharges Do Data Centers

Generate?99

Data centers may generate different types of water-related discharges (i.e., effluents), including

wastewater and stormwater discharges. In addition, in some cases when land is developed to

construct data centers, the development may include discharges of dredged or fill material into

wetlands or streams.

Wastewater

Data centers generate two main types of wastewater discharges: (1) effluent from water-based

cooling systems used for thermal regulation of computing equipment, and (2) domestic

wastewater.100 Cooling-water-related discharges, the predominant discharges, may include

noncontact cooling water, cooling-system blowdown (i.e., the intentional discharge of water from

a system), and discharges associated with construction, commissioning, or maintenance.101

Domestic wastewater flows are generally more limited discharges generated from employee

facilities (e.g., toilets). If the data center has on-site treatment (either for source water prior to its

use for cooling or for wastewater prior to discharge) there may be additional wastewater streams

from these systems.102

The frequency and volume of cooling-water-related discharges vary depending upon a number of

factors, such as the cooling technology being used, site-specific operations (including size and

facility design), and geographic location (e.g., seasonal air temperature and humidity affect

cooling needs and related discharges).103 Discharges also vary between the construction and

commissioning phase and the operation phase.

The type of cooling technology is a key factor affecting the frequency and volume of discharges.

For example, open-loop water-based cooling systems (i.e., evaporative cooling systems) typically

generate higher volumes of effluent during operations. Water may be cycled through the system

multiple times prior to discharge (i.e., blowdown). Closed-loop cooling systems, which circulate

98 EPA, “Water Reuse Action Plan 2.0 Booklet,” p. 10, https://www.epa.gov/system/files/documents/2026-04/wrap-

2.0-booklet.pdf.

99 Laura Gatz, Specialist in Environmental Policy, authored this entry.

100 Rasheed Ahmad, “Keeping Data Centers Cool,” Civil Engineering, March 2024, https://www.asce.org/publicationsand-news/civil-engineering-source/civil-engineering-magazine/issues/magazine-issue/article/2024/03/engineers-oftenneed-a-lot-of-water-to-keep-data-centers-cool (hereinafter Ahmad, “Keeping Data Centers Cool,” Civil Engineering,

March 2024).

101 WEF, Water and Wastewater Utilities and Data Centers: Frequently Asked Questions, April 16, 2026, https://waterai-nexus.org/reports/water-and-wastewater-utilities-and-data-centers-frequently-asked-questions-faqs/ (hereinafter

WEF, Water and Wastewater Utilities and Data Centers: Frequently Asked Questions).

102 WEF, Water and Wastewater Utilities and Data Centers: Frequently Asked Questions.

103 WEF, Water and Wastewater Utilities and Data Centers: Frequently Asked Questions.

Congressional Research Service

18

Data Centers and Water: Frequently Asked Questions

water within a sealed system without direct exposure to the environment, may generate more

limited wastewater discharges during normal operational phases.104 Both open- and closed-loop

systems also generate wastewater during maintenance and during data center construction and

commissioning.105 Other types of cooling technologies, such as air-cooled systems, may generate

little to no wastewater effluent, while immersion cooling (i.e., submersion of equipment in fluid)

or hybrid cooling (i.e., a blend of air and liquid cooling) systems may reduce cooling water needs

and related effluents.106

Data center construction, including commissioning of a facility, involves processes such as

cleaning, passivation (i.e., a chemical process that enhances the corrosion resistance of metals),

and flushing.107 These processes involve chemical treatment of the cooling system components

(e.g., cooling system loops) to clean and degrease equipment, remove impurities, and improve

corrosion resistance.108 These processes can generate short-term, high-volume discharges with

higher pollutant concentrations than those generated during operational phases.109 Due to the

multiphase nature of data center development, these commissioning phases are not limited to one

initial event, but rather may occur with each phase of site development.110

Stormwater

Stormwater discharges generated by data centers include runoff during construction phases of a

data center site, as well as runoff associated with any industrial activities on the site. As discussed

previously, data center development sometimes involves multiple phases of construction rather

than a single construction period. This may therefore result in multiple periods during which a

site may generate construction-stormwater-related discharges. During operational phases, data

centers may generate stormwater runoff associated with industrial activities and equipment on the

site, such as generators, fuel and chemical storage tanks, outdoor equipment storage, or material

loading areas.111

Discharges of Dredged or Fill Material for Development

If a data center is constructed on a site that requires development of a parcel of land, in some

cases, that development may involve discharges of dredged or fill material into wetlands or

surface waters within that parcel.

104 WEF, “Advancing Understanding of Data Center Effluent,” https://www.wef.org/events--

education/webcasts/upcoming-webcasts/understand-data-center-effluent/ (hereinafter WEF, “Advancing Understanding

of Data Center Effluent”).

105 WEF, “Advancing Understanding of Data Center Effluent.”

106 WEF, Water and Wastewater Utilities and Data Centers: Frequently Asked Questions.

107 WEF, Water and Wastewater Utilities and Data Centers: Frequently Asked Questions.

108 Allegheny Surface Technology, “Passivation for Data Centers: Protecting Stainless Steel Cooling Systems from

Corrosion and Contamination,” https://alleghenysurface.com/2025/10/passivation-for-data-centers-protecting-stainlesssteel-cooling-systems-from-corrosion-and-contamination/.

109 WEF, Water and Wastewater Utilities and Data Centers: Frequently Asked Questions.

110 WEF, “Advancing Understanding of Data Center Effluent.”

111 Ohio Environmental Protection Agency, “Fact Sheet for National Pollutant Discharge Elimination System (NPDES)

General Permit for Discharges from Data Center Facilities,”

https://dam.assets.ohio.gov/image/upload/epa.ohio.gov/Portals/35/permits/Data_Centers/OHD000001_Draft.fs.pdf

(hereinafter Ohio EPA, “Fact Sheet for NPDES General Permit for Discharges from Data Center Facilities”).

Congressional Research Service

19

Data Centers and Water: Frequently Asked Questions

What Types of Pollutants Do Data Centers Discharge in Their

Wastewater?112

The pollutants that may be present in data center wastewater discharges depend upon a number of

factors, including the source and quality of the water being used for cooling, the cooling

technology being used, site-specific operations, and whether the discharges are from normal

operations or from construction and commissioning phases.

For example, in water-cooled data centers that use evaporative cooling systems, the evaporation

processes consume some of the water and concentrate any pollutants that were present in the

source water.113 Such concentrated pollutants commonly include total dissolved solids and may

also include chlorine if the source water is treated public water or another chlorinated source.114

Water may be cycled through the cooling system multiple times before it is discharged as

blowdown. Data centers vary in the number of times they circulate cooling water prior to

discharge. The number of cycles, sometimes referred to as cycles of concentration, can affect how

much these pollutants concentrate.115 In some data centers, fresh water may be added to dilute the

concentrated cooling water and allow for additional cycles.

Data center operators may also use various types of chemical treatment for their cooling systems.

The types of chemicals used vary and are sometimes considered proprietary, but may include

acids, disinfectants, dispersants, corrosion inhibitors (to reduce corrosion and scaling in cooling

loops), or biocides (to control bacteria, algae, fungi, and biofilm).116 Typically, some of these may

be used to help increase the number of cycles of concentration or to help inhibit corrosion. Data

center discharges, therefore, may include these chemicals, particularly during maintenance

operations or during commissioning and start-up of a facility.

Wastewater discharges may also contain pollutants that are products of metal pipe corrosion, such

as copper, nickel, and chromium. In addition, during commissioning and start-up of a data center,

the passivation and cleaning of the cooling loops before the system is put into service may

involve use of chemicals to clean the metal and make it more corrosion resistant, which can lead

to discharges that include treatment chemicals as well as metals.117 Metals may also leach from

piping materials during extended stagnation or initial system start-up, even when the operator

does not intentionally add chemicals.118

Other water quality parameters in data center wastewater discharges that can be considered

pollutants under the Clean Water Act (CWA) include pH (which can either be acidic or alkaline

based on the cooling system’s treatment processes), as well as elevated temperature.119

112 Laura Gatz, Specialist in Environmental Policy, authored this entry.

113 WEF, Water and Wastewater Utilities and Data Centers: Frequently Asked Questions.

114 Ohio EPA, “Fact Sheet for NPDES General Permit for Discharges from Data Center Facilities.” Ahmad, “Keeping

Data Centers Cool,” Civil Engineering, March 2024.

115 WEF, “Advancing Understanding of Data Center Effluent.”

116 WEF, “Advancing Understanding of Data Center Effluent.” WEF, Water and Wastewater Utilities and Data

Centers: Frequently Asked Questions.

117

WEF, “Advancing Understanding of Data Center Effluent.”

118 WEF, Water and Wastewater Utilities and Data Centers: Frequently Asked Questions.

119 33 U.S.C. §1362(6). 40 C.F.R. §401.16.

Congressional Research Service

20

Data Centers and Water: Frequently Asked Questions

How Are Water-Related Discharges from Data Centers Regulated at

the Federal Level?120

The project proponent for data center development and the owner/operator of the data center

facility may need to comply with certain federal requirements, including obtaining CWA permits

or approvals, which aim to prevent or minimize water quality impacts from the data center’s

discharges. The relevant permits or approvals that may be needed will vary depending upon

factors, including site-specific characteristics of the data center development site, facility, and

operations; the destination of a facility’s discharge (e.g., sewer system, surface water, other); and

varying state and local requirements.

Regulation of Discharges of Dredged or Fill Material

If the construction of a data center requires the development of a site that contains waters of the

United States (e.g., certain wetlands, streams, or other jurisdictional waters), and if the

development would require placement of dredged or fill material into those waters, the project

proponent would need to obtain a CWA Section 404 permit. In most states, the USACE

administers Section 404 permits.121 USACE may authorize such discharges through either

individual (i.e., site-specific) permits, or through general permits that authorize discharges for

categories of activities that are similar in nature. USACE or states issue individual permits for

individual projects or applicants, typically when the project’s discharge may cause more than

minimal individual or cumulative impacts. USACE and states may issue general permits for

proposed activities that will result in only minimal individual and cumulative adverse

environmental effects. These permits are issued on a nationwide, regional, or state basis for

particular categories of activities that are similar in nature.

USACE may issue general permits on a nationwide, regional, or statewide basis. Every five years,

USACE issues nationwide permits (NWPs), which are general permits applicable nationwide to

authorize categories of similar activities that the agency has determined will result in no more

than minimal adverse impacts, individually and cumulatively, to waters of the United States.122 In

USACE’s 2026 reissuance of its NWPs, the agency clarified that one of its existing permits, NWP

39, applies to data centers.123 NWP 39 authorizes “discharges of dredged or fill material into nontidal waters of the United States for the construction or expansion of commercial and institutional

building foundations and building pads and attendant features that are necessary for the use and

maintenance of the structures.”124 To qualify for NWP 39, the discharge of dredged or fill material

must not cause the loss of greater than half an acre of nontidal waters of the United States.

120 Laura Gatz, Specialist in Environmental Policy, authored this entry.

121 Two states, Michigan and New Jersey, administer their own Section 404 permitting programs; however, USACE

retains permitting jurisdiction in certain waters in those states—typically those that are navigable in fact.

122 USACE, “Regulatory Request System: Do I Need a Permit?” https://rrs.usace.army.mil/rrs/home/permitting.

123 USACE, “Reissuance and Modification of Nationwide Permits,” 91 Federal Register 768, January 8, 2026. In the

preamble, USACE explained that commenters recommended adding data centers to the list of examples of commercial

and institutional developments within the nationwide permit (NWP). USACE further explained that while the list is not

intended to be all-encompassing, they added data centers to the list of examples. In July 2025, President Trump issued

E.O. 14318, “Accelerating Federal Permitting of Data Center Infrastructure,” which directed USACE to review its

NWPs and determine whether a specific NWP is needed “to facilitate the efficient permitting of activities” related to

certain data center projects. The preamble to the 2026 NWP regulation does not reference the executive order.

124 USACE, Decision Document: Nationwide Permit 39,

https://usace.contentdm.oclc.org/utils/getfile/collection/p16021coll9/id/3187.

Congressional Research Service

21

Data Centers and Water: Frequently Asked Questions

USACE may also authorize discharges of dredged or fill material into jurisdictional waters and

wetlands through individual permits, which require site-specific evaluation. According to publicfacing USACE data, as of July 2026, the agency has issued 21 individual permits for data centers

(between 2009 and 2026) and has additional permits pending.125 The agency does not have

public-facing data on the number of data centers with discharges authorized through general

permits.

If a data center needs a CWA Section 404 permit, that also often triggers a requirement to obtain a

CWA Section 401 water quality certification from the state or authorized tribe where the

discharge would occur.126 CWA Section 401 water quality certifications are required for any

federal permit or license for an activity that may result in a discharge to waters of the United

States.127

Regulation of Stormwater

Data center developers and owners/operators may also need to obtain National Pollutant

Discharge Elimination System (NPDES) permits for stormwater discharges. The CWA authorizes

both EPA and delegated states to administer NPDES permits, which authorize discharges of

pollutants from point sources (i.e., discrete conveyances) to waters of the United States. 128 Most

states (47 states) and one territory (the Virgin Islands) are authorized to administer their own

NPDES permits.129 EPA administers NPDES permits in Massachusetts, New Hampshire, New

Mexico, the District of Columbia, the remaining territories, and on Indian lands. Similar to CWA

Section 404 permits, NPDES permits can also be issued as individual or general permits.

Any construction project, including a data center development project, that disturbs one or more

acres of land and discharges stormwater to waters of the United States must obtain coverage

under an NPDES permit. Often, a project proponent can seek coverage under a general permit for

construction activities, which establishes pollution prevention and sediment and erosion control

requirements for stormwater discharges to waters of the United States.

A data center may also need an NPDES permit for industrial stormwater for the site during

operations. Typically, NPDES industrial stormwater permits are required for discharges from

specific categories of industrial activity, as designated in EPA regulations.130 It is unclear whether

data centers fall under any of these specific sectors, but the permitting authority may still

designate a facility that generates stormwater discharges as needing a permit even when it does

not fall under any of the specified sectors.131 As an example, at least one state has proposed a

draft general permit for data centers that would include coverage for discharges of pollutants in

125 Data is based on a search of USACE, “USACE Regulatory and Section 408 Publicly Available Data,”

https://permits.ops.usace.army.mil/orm-public, for the term “data center,” filtered by “all districts” and “all years.”

Issuance dates for these permits range from 2009 to 2026.

126 EPA is the certifying authority on lands of exclusive federal jurisdiction or on Indian lands where tribes have not

received authorization for treatment as a state for purposes of Clean Water Act (CWA) Section 401.

127 For more on CWA Section 401 water quality certification, see CRS Report R46615, Clean Water Act Section 401:

Overview and Recent Developments, by Laura Gatz and Kate R. Bowers.

128 33 U.S.C. §1342.

129 EPA, “NPDES State Program Authority,” https://www.epa.gov/npdes/npdes-state-program-authority. States,

territories, and tribes may administer their own National Pollutant Discharge Elimination System (NPDES) permits if

they seek and receive approval from EPA to assume the program. To date, no tribe has assumed administration of an

NPDES permitting program.

130 40 C.F.R. §122.26(b)(14). See also EPA, “Stormwater Discharges from Industrial Activities,”

https://www.epa.gov/npdes/stormwater-discharges-industrial-activities.

131 40 C.F.R. §122.26(a)(9)(i)(C)-(D).

Congressional Research Service

22

Data Centers and Water: Frequently Asked Questions

stormwater runoff on the site during operations from generators, fuel and storage tanks, outdoor

equipment storage, material loading/unloading areas, or other activities.132

Regulation of Wastewater

The water-related permits that a data center may need to obtain for its wastewater discharges

depend on what is in the discharge and where a data center sends its discharge—a municipal

sewer system, a surface water body, or an alternative disposal method.

Municipal Sewer Systems

According to available sources, data centers most commonly send their wastewater effluent to

publicly owned treatment works (POTWs).133 The POTW then treats the water prior to

discharging to nearby surface waters. If that POTW discharges to a water of the United States,

then that facility would operate under an NPDES permit for wastewater, and the data center

would be considered an indirect discharger.134 Indirect dischargers are subject to regulation under

the National Pretreatment Program.

The National Pretreatment Program, a component of the CWA’s NPDES program, is intended to

prevent the introduction of pollutants into a POTW that will interfere with its operations or pass

through the treatment process.135 Local municipalities are mostly responsible for implementing

and enforcing pretreatment requirements.136 EPA and states authorized to act as the approval

authority for POTWs in their states may approve a POTW’s pretreatment program. If approved,

the POTW is the control authority responsible for ensuring compliance with pretreatment

standards. If a POTW does not have an approved pretreatment program, the control authority is

the approved state authorized to act as the approval authority or, in unapproved states, the EPA

acts as the control authority.137

Typically, a control authority establishes pretreatment standards that may include general and

specific prohibitions, categorical pretreatment standards, and local limits.138 The control authority

determines which standards are applicable to each industrial discharger, also referred to as an

132 Ohio EPA, “Fact Sheet for NPDES General Permit for Discharges from Data Center Facilities,” pp. 2, 6.

133 EPA, “Water-Related Permits for Data Centers,” accessed May 20, 2026, https://www.epa.gov/watersense/water-

related-permits-data-centers#discharge. See also American Society of Civil Engineers (ASCE), “Engineers Often Need

a Lot of Water to Keep Data Centers Cool,” March 4, 2024. A publicly owned treatment works (POTW) is defined in

40 C.F.R. §403.3(q) to mean a treatment works as defined by Section 212 of the CWA, which is owned by a state or

municipality. This includes devices and systems used in the storage, treatment, recycling, and reclamation of municipal

sewage or industrial wastes of a liquid nature; sewers, pipes, or other conveyances if they convey wastewater to a

POTW; and also the municipality that has jurisdiction over the indirect discharges to and from such a treatment works.

See also Joint Legislative Audit and Review Commission, Data Centers in Virginia, Report to the Governor and the

General Assembly of Virginia, December 2024, p. 133, https://jlarc.virginia.gov/pdfs/reports/Rpt598.pdf.

134 40 C.F.R. Part 403.

135 40 C.F.R. §403.2. EPA, “National Pretreatment Program Overview,” https://www.epa.gov/npdes/nationalpretreatment-program-overview.

136 EPA, “National Pretreatment Program Implementation,” https://www.epa.gov/npdes/national-pretreatment-programimplementation.

137 40 C.F.R. §403.3.

138 40 C.F.R. §§403.5-403.6. EPA, “National Pretreatment Program Overview,” https://www.epa.gov/npdes/nationalpretreatment-program-overview.

Congressional Research Service

23

Data Centers and Water: Frequently Asked Questions

industrial user (IU), based on whether the IU is subject to national categorical pretreatment

standards (a categorical industrial user) or meets the criteria for a significant industrial user.139

•

•

•

General and specific prohibitions are national standards that apply to all IUs who

discharge to a POTW.140 The general prohibitions forbid the discharge of any

pollutants to a POTW that can cause pass through or interference.141 Specific

prohibitions forbid the discharge of eight categories of pollutants that are

potentially hazardous or likely to cause pass through or interference.142

EPA establishes national categorical pretreatment standards (as well as

limitations that apply to direct dischargers) through federally promulgated

regulations called Effluent Limitation Guidelines and Standards (ELGs) on an

industry-by-industry basis.143

Local limits, which are site specific, aim to protect the POTW (including the

collection system infrastructure), receiving waters, worker health and safety, and

the POTW’s sewage sludge disposal practices.144 Local limits can be numeric or

narrative effluent discharge limits and may include best management practices.

EPA has not established ELGs for data centers, so categorical pretreatment standards do not

apply. Some public-facing information also indicates that data centers are not typically classified

as significant industrial users because CWA regulations exclude cooling system blowdown from

flow-based thresholds, even though those flows may still affect treatment processes.145

Accordingly, data centers must comply with the general and specific prohibitions, and the control

authority may develop local limits. POTWs impose local limits at the point of connection to the

POTW’s collection system.

Some control authorities report challenges in implementing their pretreatment programs to

address data centers, due to the nature of data center discharges.146 Data centers often have

intermittent, high-volume “slug” loads during construction and maintenance phases and relatively

low-strength discharges during routine operations.147 In addition, some control authorities report

insufficient information about the quality and quantity of the discharges they receive from data

centers.148 In some areas with higher densities of data centers, POTWs may not have the capacity

to handle the flows sent to the facility by all the data centers within the sewershed.149

139 EPA, “Pretreatment Standards and Requirements—Applicability,” https://www.epa.gov/npdes/pretreatment-

standards-and-requirements-applicability.

140 EPA, “Pretreatment Standards and Requirements—General and Specific Prohibitions,”

https://www.epa.gov/npdes/pretreatment-standards-and-requirements-general-and-specific-prohibitions.

141 40 C.F.R. §403.5(a).

142 40 C.F.R. §403.5(b).

143 EPA, “Learn about Effluent Guidelines,” https://www.epa.gov/eg/learn-about-effluent-guidelines.

144 40 C.F.R. §403.5(c). EPA, “Pretreatment Standards and Requirements—Local Limits,”

https://www.epa.gov/npdes/pretreatment-standards-and-requirements-local-limits.

145 WEF, Water and Wastewater Utilities and Data Centers: Frequently Asked Questions. 40 C.F.R. §403.3(v).

146 InsideEPA, “Data Center Discharges Strain Wastewater Treatment Systems in Boom Areas,” March 31, 2026

(hereinafter InsideEPA, “Data Center Discharges Strain Wastewater Treatment Systems”). WEF, Water and

Wastewater Utilities and Data Centers: Frequently Asked Questions.

147 WEF, Water and Wastewater Utilities and Data Centers: Frequently Asked Questions.

148 InsideEPA, “Data Center Discharges Strain Wastewater Treatment Systems.” WEF, “Advancing Understanding of

Data Center Effluent.”

149 InsideEPA, “Data Center Discharges Strain Wastewater Treatment Systems.” EPA defines sewershed as the

geographic area from which all the sewer flows to a single endpoint.

Congressional Research Service

24

Data Centers and Water: Frequently Asked Questions

Slug discharges may lead to pass through or interference at a POTW if the facility does not have

the capacity to handle the volume of the slug or if unanticipated pollutants in the discharge

interfere with or pass through the treatment operations at the facility. If slug loads include

pollutants that impact the effectiveness of a POTW’s treatment processes, the load may lead to an

upset (i.e., temporary noncompliance) at the POTW.150 Slug discharges may also affect a POTW’s

ability to comply with its permit limitations for sewage sludge, a byproduct of the treatment

process. For example, slugs following start-up or maintenance activities may include higher

concentrations of metals compared with discharges from routine operations, which may lead to

higher concentrations of metals in the POTW’s sewage sludge.151 Some control authorities also

report that slug loads containing certain chemicals may corrode the POTW’s infrastructure.152

Some control authorities report that with clearer communication and information from data

centers about the quantity and quality of the effluent being sent to the POTW, they can take steps

to help ensure compliance.153 Options may include anticipating and adjusting treatment at the

POTW to ensure pass through and interference do not occur; requiring the data center to treat its

effluent before sending it to the POTW; requiring the data center to establish on-site storage to

accommodate fluctuations in flow; or requiring the data center to dispose of the effluent through a

different means, such as having it hauled off for disposal in an appropriate facility.154

Surface Waters

Some data centers discharge directly into nearby surface waters. If the receiving water is a water

of the United States, then that data center, considered a direct discharger, would need to obtain an

NPDES permit for its wastewater discharges. According to EPA, discharging directly to a surface

water body is less common for data centers than for other industrial sectors, but may occur in

locations without access to municipal wastewater infrastructure.155 NPDES permits for data

center wastewater discharges may include limits and monitoring requirements for a variety of

pollutants and metrics depending upon the characteristics of the source water and site-specific

operations. Examples include flow, temperature, pH, nutrients (such as phosphorus or nitrogen),

chlorine, treatment additives, and metals.156 Because EPA has not established ELGs for data

centers (which, in addition to pretreatment standards, include technology-based-effluent

limitations for direct dischargers), permit writers typically establish discharge limits for data

centers based on their best professional judgment.157

Any data center with discharges authorized by an NPDES permit that is designed to withdraw at

least 2 million gallons per day from waters of the United States for cooling purposes must also

comply with technology-based performance requirements specified in CWA Section 316(b) for

150 WEF, “Advancing Understanding of Data Center Effluent.” An upset (defined at 40 C.F.R. §122.41(n)) is an

exceptional incident in which there is unintentional and temporary noncompliance with NPDES permit limitations

because of factors beyond the reasonable control of the permittee.

151 InsideEPA, “Data Center Discharges Strain Wastewater Treatment Systems.” WEF, “Advancing Understanding of

Data Center Effluent.” WEF, Water and Wastewater Utilities and Data Centers: Frequently Asked Questions.

152 InsideEPA, “Data Center Discharges Strain Wastewater Treatment Systems.”

153 InsideEPA, “Data Center Discharges Strain Wastewater Treatment Systems.” WEF, “Advancing Understanding of

Data Center Effluent.” WEF, Water and Wastewater Utilities and Data Centers: Frequently Asked Questions.

154 WEF, “Advancing Understanding of Data Center Effluent.” WEF, Water and Wastewater Utilities and Data

Centers: Frequently Asked Questions.

155 EPA, “Water-Related Permits for Data Centers,” https://www.epa.gov/watersense/water-related-permits-datacenters#discharge, accessed May 20, 2026.

156 Ohio EPA, “Fact Sheet for NPDES General Permit for Discharges from Data Center Facilities.”

157 EPA, “Learn About Effluent Guidelines,” https://www.epa.gov/eg/learn-about-effluent-guidelines.

Congressional Research Service

25

Data Centers and Water: Frequently Asked Questions

cooling water intake structures.158 These standards aim to ensure that the location, design,

construction, and capacity of the structures reflect the best technology available to minimize

harmful impact on the environment. Specifically, the standards aim to reduce injury and death of

fish and other aquatic life caused by cooling water intake structures through impingement or

entrainment.159

Alternative Disposal Methods

Data centers may also use alternative disposal methods that have the potential to trigger other

regulatory frameworks, some of which may be at the state or local level. At the federal level, any

facility that injects wastewater or treatment residuals into subsurface formations would need to

obtain authorization under the Safe Drinking Water Act’s Underground Injection Control

program.160 A data center with on-site storage or treatment systems (e.g., impoundments or

lagoons) may need to comply with design, construction, operation, and permit standards, which

may be federal or state standards, to protect groundwater and surface water quality.

Congressional Action

Which Bills Have Been Introduced in the 119th Congress That

Address Data Centers and Water?

In the 119th Congress, some Members have introduced bills and proposed amendments that

address data centers and a range of topics related to water availability, use, and discharge, among

others.161 As of July 30, 2026, at least one relevant provision had been enacted. Section 1531 of

the National Defense Authorization Act for Fiscal Year 2026 (P.L. 119-60) expands the

Department of Defense’s “High Performance Computing Roadmap” to include estimates of

additional electricity and water usage, and associated anticipated effects on the surrounding

community, from the construction or expansion of data centers on military installations, to the

extent that such estimates do not delay the roadmap’s triennial updates.162

In both chambers, some Members have introduced bills that address data centers, and the bills

have been referred to multiple committees. Most of these bills have not moved past the

introduction stage. The measures with specific water provisions generally are bills that address

data centers more broadly, and in some instances focus on data centers’ energy consumption.

The identified bills propose to address data centers and water through a variety of mechanisms.

Some of these bills include provisions to improve the available information about data center

water use, to incentivize certain practices (e.g., water reuse) at data centers, or to limit or facilitate

data center construction.

Table A-1 lists a selection of these bills and includes the legislation number and related bill(s);

title; long title, relevant provision(s), and additional excerpts as needed; relevant federal agencies

or other entities; House and Senate committees; and last action and date.

158 33 U.S.C. §1326(b). See also EPA, “Cooling Water Intakes,” https://www.epa.gov/cooling-water-intakes.

159 EPA, “Cooling Water Intakes,” https://www.epa.gov/cooling-water-intakes.

160 40 C.F.R. Part 144.

161 CRS identified this and other legislation on this topic by searching Congress.gov using the terms data center(s),

datacenter(s), and water.

162 Section 1531 of amends Title 10, Section 4001 note, of the U.S. Code.

Congressional Research Service

26

Data Centers and Water: Frequently Asked Questions

In addition to the bills listed in Table A-1, some Members have introduced legislation that relates

to “industrial” or “commercial” water use. While these bills may not specifically refer to data

centers in their text, data centers may fall under these terms depending on the legislative text or

agency interpretation. For example, as discussed in “Are Federal Reservoirs and Infrastructure

Providing Water to Data Centers?,” the Water Resources Development Act of 2026 (H.R. 9497),

as ordered to be reported, would direct USACE to report on impacts of “new commercial and

industrial water users” on USACE water resources development projects.

Congressional Research Service

27

Appendix. Selected Bills on Data Centers and Water Use in the 119th Congress

Table A-1. Selected Bills on Data Centers and Water Use in the 119th Congress

(as of July 30, 2026)

Legislation

No.

(Related

Bill)

Committee(s)

Latest Action

(Date)

—

House Committee

on Ways and

Means

Referred to

committee

(4/17/2025)

To conduct a study on the impact of artificial intelligence and data center site

growth on energy supply resources in the United States, and for other purposes.

Section 2 states that “The Secretary of Energy shall designate a National

Laboratory to conduct a study on the impact of artificial intelligence and

data center site growth on energy supply resources in the United States”;

and that the study should include “The impact of the co-location of artificial

intelligence and data center sites on energy costs, energy supply, energy

supply reliability, land-use, water-use, and cost to consumers.”

Department

of Energy

(DOE)

House Committee

on Science, Space,

and Technology

Referred to

committee

(9/9/2025)

To direct the Comptroller General of the United States to conduct a technology

assessment focused on liquid-cooling systems for artificial-intelligence compute

clusters and high-performance computing facilities, require the development of

Federal Government-wide best-practice guidance for Federal agencies, and for

other purposes.

Section 3 directs the U.S. Government Accountability Office (GAO) to

initiate a review of liquid cooling research and development needs to

include, among other topics, “An evaluation of coolant options, including

water, water‑glycol, and engineered fluids, materials compatibility, corrosion

control, bio growth mitigation, filtration, deaeration, and fluid monitoring

and management.“

GAO

House Committee

on Science, Space,

and Technology;

House Committee

on Energy and

Commerce

Referred to

committees

(9/11/2025)

Short Title

Long Title and Selected Excerpts

H.R. 2940

Advancing

Water Reuse

Act

To amend the Internal Revenue Code of 1986 to allow an investment credit for

certain water reuse projects.

Section 2 authorizes a 30% tax credit of the investment for any qualifying

water reuse project, which, as defined by the bill, includes “a project which

installs, replaces, or modifies an onsite water recycling system within an

industrial, manufacturing, data center, or food processing facility.”

H.R. 5227

Unleashing LowCost Rural AI

Act

H.R. 5332

(§3 of H.R.

5332 is

similar to §2

of S. 3269)

Liquid Cooling

for AI Act of

2025

CRS-28

Relevant

Agencies

or Entities

Legislation

No.

(Related

Bill)

Short Title

Long Title and Selected Excerpts

H.R. 6900

(see also

H.R. 2940)

American

Affordability Act

of 2025

To amend the Internal Revenue Code of 1986 to address the nation’s cost-of-living

crisis.

Among other provisions, Section 24001 authorizes a 30% tax credit of the

investment for any qualifying water reuse project, which, as defined by the

bill, includes “a project which installs, replaces, or modifies an onsite water

recycling system within an industrial, manufacturing, data center, or food

processing facility.”

—

House Committee

on Ways and

Means; House

Committee on

Education and

Workforce;

House Committee

on Energy and

Commerce

Referred to

committees

(12/18/2025)

H.R. 6984

Data Center

Transparency

Act

To require reports on the effects of data centers on air quality and water quality,

and on electricity consumption by data centers.

Section 2 requires the U.S. Environmental Protection Agency (EPA), within

six months of enactment, and then every three months after, to submit to

Congress and post on its website a report that includes, among other

elements, “(1) the total amount of water consumed by data centers located

in the United States; (2) how such data centers reuse water, and the amount

of such reused water; (3) how such data centers affect local water systems,

including with respect to—

(A) the availability of potable water; (B) whether the data center increased

demand on local water utilities; (C) any potential data on service disruptions

for other customers of local water utilities; (D) any changes in residential

rates for water services; and (E) the type and amount of pollutants (as such

term is defined in section 502(6) of the Federal Water Pollution Control

Act (33 U.S.C. 1362(6))) discharged into water by data centers…”

EPA

House Committee

on Energy and

Commerce

Referred to

committee

(1/8/2026)

H.R. 7858

Data Center

Community

Impact Act

To require the Secretary of Energy to conduct a study on the effect of data centers

on communities of color and low-income communities, and for other purposes.

Section 3 requires DOE, in coordination with EPA, the Department of

Commerce (Commerce), the Federal Energy Regulatory Commission

(FERC), and the Council on Environmental Quality (CEQ) to conduct a

study on “communities of color and low-income communities.” Among

other information, this study is to include “The amount of water consumed

by data centers, including how such consumption affects local water supplies

and drought-prone regions,” and “How the cooling processes used by data

centers affect wastewater systems.”

CEQ,

Commerce,

DOE, EPA,

FERC

House Committee

on Energy and

Commerce

Referred to

committee

(3/5/2026)

CRS-29

Relevant

Agencies

or Entities

Committee(s)

Latest Action

(Date)

Legislation

No.

(Related

Bill)

Short Title

Long Title and Selected Excerpts

H.R. 8033

(see also §2

of H.R.

9629)

No Harm Data

Centers Act

To ensure that American families are protected from the impacts of data centers

on the electric grid, and for other purposes.

Section 5 directs EPA to seek to enter an agreement with the National

Academies (NAS). Through this agreement, NAS shall “conduct an

assessment of the impacts of data centers on the environment and public

health,” including on water consumption and water supply, among other

topics; develop recommendations to mitigate such impacts; and submit the

report and assessment to the relevant congressional committees.

H.R. 8037

Protect

American AI

Act of 2026

To limit the effect of litigation on the environmental application process for data

centers and associated infrastructure.

Section 3(a) states, “A civil action relating to an environmental review under

… the Federal Water Pollution Control Act (33 U.S.C. 1251 et seq.) …

with respect to a data center or covered infrastructure shall not affect the

validity of a permit, license, or approval issued for the data center or

covered infrastructure that is the subject of the civil action.” Section 3(b)

states, “If, in a civil action described in subsection (a), the environmental

review for a permit, license, or approval issued to the data center or

covered infrastructure that is the subject of the civil action is found by the

applicable court to violate … the Federal Water Pollution Control Act (33

U.S.C. 1251 et seq.) … (1) notwithstanding chapter 5 or 7 of title 5, United

States Code (commonly referred to as the ‘Administrative Procedure Act’),

the applicable court shall not set aside or vacate the permit, license, or

approval issued for the data center or covered infrastructure but instead

remand the matter to the relevant Federal agency to resolve the violation;

and (2) the relevant Federal agency shall continue to process all covered

applications.”

CRS-30

Relevant

Agencies

or Entities

Committee(s)

Latest Action

(Date)

EPA, NAS

House Committee

on Energy and

Commerce

Referred to

committee

(3/20/2026)

—

House Committee

on Energy and

Commerce;

House Committee

on the Judiciary

Referred to

committees

(3/24/2026)

Legislation

No.

(Related

Bill)

Relevant

Agencies

or Entities

Long Title and Selected Excerpts

H.R. 9372

Data

Infrastructure

Energy

Measurement

and Standards

Act

To direct the Director of the National Institute of Standards and Technology to

develop best practices for measuring data center energy use, study data availability

for the purpose of improving energy demand forecasting capabilities, and for other

purposes.

As introduced, Section 2 directs the National Institute of Standards and

Technology (NIST), with DOE, to carry out a measurement research

program “to inform the development or improvement of best practices,

definitions, methodologies, procedures, and technical standards for the

measurement of … water use by data centers … including the measurement

of … water use resulting from training and inference of artificial intelligence

models or other compute intensive information processes.” This section

further details specific activities to be included in the NIST program.

National

Institute of

Standards

and

Technology,

DOE

House Committee

on Science, Space,

and Technology

Ordered to be

reported in the

nature of a

substitute

(amended)

(6/25/2026)

H.R. 9419

(§201 of

H.R. 9419 is

similar to

H.R. 2940

and H.R.

6900)

Power and

Water for

Families Act of

2026

To facilitate the responsible development of data centers and related

infrastructure, to protect existing ratepayers from the shifting of incremental

infrastructure costs attributable to large-load facilities, to encourage investment in

water reuse, and for other purposes.

Section 201 authorizes a 30% tax credit of the investment for any qualifying

water reuse project, which, as defined by the bill, includes “a project which

installs, replaces, or modifies an onsite water recycling system within an

industrial, manufacturing, data center, or food processing facility, replaces

the use of freshwater, such as groundwater, with recycled water from a

municipal water provider for the production of goods or provision of

services by the taxpayer, or builds or expands a municipal water recycling

system for the purpose of securing recycled water for the production of

goods or provision of services.”

—

House Committee

on Ways and

Means; House

Committee on

Energy and

Commerce

Referred to

committees

(6/24/2026)

H.R. 9442

(see also

S.4214)

Artificial

Intelligence

Data Center

Moratorium Act

To impose a moratorium on the construction of new data centers until legislation is

enacted that safeguards the public from the dangers of artificial intelligence.

Section 3 includes a requirement for DOE to submit quarterly reports on AI

data centers that “shall include … the water usage of the artificial

intelligence data center … the wastewater discharge and thermal outputs of

the artificial intelligence data center.”

DOE

House Committee

on Energy and

Commerce;

House Committee

on Foreign Affairs

Referred to

committees

(6/24/2026)

CRS-31

Committee(s)

Latest Action

(Date)

Short Title

Legislation

No.

(Related

Bill)

Short Title

Long Title and Selected Excerpts

H.R. 9629

(see also §5

of H.R.

8033)

Protecting

Communities

from Data

Center Impacts

Act of 2026

To require an assessment of the environmental and public health effects of data

centers, and for other purposes.

Section 2 directs EPA to seek to enter an agreement with the National

Academies (NAS). Through this agreement, NAS shall “conduct an

assessment of the impacts of data centers on the environment and public

health,” including on water consumption and water supply, among other

topics; develop recommendations to mitigate such impacts; and submit the

report and assessment to the relevant congressional committees.

H.R. 9777

Protecting

Ratepayers Act

To require that new and existing data centers use off-grid power and water

supplies, and for other purposes.

Section 3 prohibits private companies or private entities that own, operate,

or maintain a data center or have plans to, from building, owning, operating,

or maintaining a new data center or existing data center, unless the data

center derives all “water, including back-up water, from an on-site water

source, or some other water source or combination of sources separate

from, and not deriving water from, the public water system.”

CRS-32

Relevant

Agencies

or Entities

Committee(s)

Latest Action

(Date)

EPA, NAS

House Committee

on Energy and

Commerce

Referred to

committee

(7/9/2026)

—

House Committee

on Energy and

Commerce

Referred to

committee

(7/20/2026)

Legislation

No.

(Related

Bill)

H.R. 9825

(see also

S.4213)

CRS-33

Short Title

Long Title and Selected Excerpts

Data Center

Water and

Energy

Transparency

Act of 2026

To require data center operators to submit to States or the Administrator of the

Environmental Protection Agency and the Secretaries of Energy and Agriculture

reports on data center energy and water use, and for other purposes.

Section 3 states that “each data center operator with 1[one] or more data

centers [with a peak demand of not less than 25 megawatts] in a State shall

submit to that State an annual report that” describes “total water use and

the source of that water during each month of that calendar year; and

annual average power usage effectiveness and water usage effectiveness;

projected on-site energy use and water use for not less than the following 5

calendar years, which shall include proposals for reducing the energy use

and water use of the data center and the increases in efficiency that are

anticipated to result from those proposals.” This section also requires new

or expanded data centers to report to the state (or to DOE and EPA in

areas where the state does not have the authority to collect such

information) on “the projected energy use and water use and the sources of

energy and water of the new data center during the first 5 calendar years

after the data center begins operation; or (II) the projected increase in

energy use and water use as a result of the expansion of a data center

during the first 5 calendar years after completion of the expansion; and (ii)

proposals for reducing the energy use and water use of the data center and

the increases in efficiency that are anticipated to result from those

proposals,” and requires EPA and DOE to report annually on specified

information, including water sources, supply, and associated community

impacts, submitted by new and expanded data centers.

Relevant

Agencies

or Entities

EPA, DOE

Committee(s)

Latest Action

(Date)

House Committee

on Energy and

Commerce

Referred to

committee

(7/22/2026)

Legislation

No.

(Related

Bill)

Relevant

Agencies

or Entities

Long Title and Selected Excerpts

P.L. 119-60

(see also

§1625 of the

Senatepassed

National

Defense

Authorizatio

n Act for

Fiscal Year

2026 (S.

2296))

National

Defense

Authorization

Act for Fiscal

Year 2026

To authorize appropriations for fiscal year 2026 for military activities of the

Department of Defense, for military construction, and for defense activities of the

Department of Energy, to prescribe military personnel strengths for such fiscal

year, and for other purposes.

Section 1531 expands the Department of Defense’s (DOD’s) “High

Performance Computing Roadmap” to include estimates of additional

electricity and water usage, and associated anticipated effects on the

surrounding community, resulting from the construction or expansion of

data centers on military installations, to the extent that such estimates do

not delay the roadmap’s triennial updates.

DOD

Senate Committee

on Veterans’

Affairs; Senate

Committee on

Armed Services;

House Committee

on Armed

Services; House

Committee on

Rules

Became Public

Law

(12/18/2025)

S. 3269

(§2 of S.

3269

requires a

similar but

broader

GAO

review as

compared

with §3 of

H.R. 5332)

Liquid Cooling

for AI Act of

2025

To direct the Comptroller General of the United States to conduct a technology

assessment focused on liquid cooling systems for artificial intelligence compute

clusters and high-performance computing facilities, and for other purposes.

Section 2 directs GAO to initiate a review of liquid cooling research and

development needs to include, among other topics, “An evaluation of

coolant options, including water, water‑glycol, and engineered fluids,

materials compatibility, corrosion control, bio growth mitigation, filtration,

deaeration, fluid monitoring and management, single-phase and 2-phase

engineered fluids, testing for total thermal performance, heat transfer

capacity, and energy efficiency.”

GAO

Senate Committee

on Energy and

Natural Resources

Referred to

committee

(4/15/2026)

S. 3737

GROW SMART

Act

To amend the Reclamation States Emergency Drought Relief Act of 1991 to

provide financial and technical assistance to eligible entities for the conduct of

innovative approaches to voluntary water partnership agreements among multiple

water users and projects conducted by individual agricultural entities, and for other

purposes.

Section 2 defines “Qualified applicants” for the voluntary water partnership

agreements to include, “1 [one] or more agricultural entities (including

irrigation districts)”; and “1 [one] or more industrial or commercial entities,

including data centers.”

Bureau of

Reclamation

Senate Committee

on Energy and

Natural Resources

Committee

hearings held

(3/17/2026)

CRS-34

Committee(s)

Latest Action

(Date)

Short Title

Legislation

No.

(Related

Bill)

S. 3852

CRS-35

Short Title

GRID Act

Long Title and Selected Excerpts

To impose certain requirements on data centers to ensure the prioritization of

residential ratepayers, and for other purposes.

Section 3 defines “utility” to include “a public water system (as defined in

section 1401 of the Safe Drinking Water Act (42 U.S.C. 300f)); a treatment

works (as defined in section 212 of the Federal Water Pollution Control Act

(33 U.S.C. 1292)); and any other regulated utility that provides water,

energy, or other essential services to a data center.” Section 5 requires

DOE to establish requirements for data centers to provide to the public

estimates of utility usage for new and existing data centers, and publicly

disclose any utility transaction or agreement, and utilities are to publicly

disclose any transaction or agreements with data centers.

Relevant

Agencies

or Entities

DOE

Committee(s)

Latest Action

(Date)

Senate Committee

on Energy and

Natural Resources

Referred to

committee

(2/11/2026)

Legislation

No.

(Related

Bill)

Short Title

Long Title and Selected Excerpts

S. 4213

Data Center

Water and

Energy

Transparency

Act of 2026

To require data center operators to submit to States or the Administrator of the

Environmental Protection Agency and the Secretaries of Energy and Agriculture

reports on data center energy and water use, and for other purposes.

Section 3 states that “each data center operator with 1[one] or more data

centers [with a peak demand of not less than 25 megawatts] in a State shall

submit to that State an annual report that” describes “total water use and

the source of that water during each month of that calendar year; and

annual average power usage effectiveness and water usage effectiveness;

projected on-site energy use and water use for not less than the following 5

calendar years, which shall include proposals for reducing the energy use

and water use of the data center and the increases in efficiency that are

anticipated to result from those proposals.” This section also requires new

or expanded data centers to report to the state (or to DOE and EPA in

areas where the state does not have the authority to collect such

information) on “the projected energy use and water use and the sources of

energy and water of the new data center during the first 5 calendar years

after the data center begins operation; or (II) the projected increase in

energy use and water use as a result of the expansion of a data center

during the first 5 calendar years after completion of the expansion; and (ii)

proposals for reducing the energy use and water use of the data center and

the increases in efficiency that are anticipated to result from those

proposals,” and requires EPA and DOE to report annually on specified

information, including water sources, supply, and associated community

impacts, submitted by new and expanded data centers.

S. 4214

Artificial

Intelligence

Data Center

Moratorium Act

To impose a moratorium on the construction of new data centers until legislation is

enacted that safeguards the public from the dangers of artificial intelligence.

Section 3 includes a requirement for DOE to submit quarterly reports on AI

data centers that “shall include … the water usage of the artificial

intelligence data center … the wastewater discharge and thermal outputs of

the artificial intelligence data center.”

CRS-36

Relevant

Agencies

or Entities

Committee(s)

Latest Action

(Date)

EPA, DOE,

Department

of

Agriculture

Senate Committee

on Energy and

Natural Resources

Referred to

committee

(3/25/2026)

DOE

Senate Committee

on Commerce,

Science, and

Transportation

Referred to

committee

(3/25/2026)

Legislation

No.

(Related

Bill)

Relevant

Agencies

or Entities

Committee(s)

Latest Action

(Date)

Short Title

Long Title and Selected Excerpts

S. 4784

National

Defense

Authorization

Act for Fiscal

Year 2027

An original bill to authorize appropriations for fiscal year 2027 for military

activities of the Department of Defense, for military construction, and for defense

activities of the Department of Energy, to prescribe military personnel strengths for

such fiscal year, and for other purposes.

Section 1632 amends the DOD’s “High Performance Computing Roadmap”

(last amended by Section 1531 of P.L. 119-60) to expand the data centers

for which DOD is required to estimate water and other resource usage to

include those supporting military operations as well as data centers to be

built or expanded. It also increases the frequency of the updates to the

roadmap from triennial to annual, among other provisions.

DOD

Senate Committee

on Finance

Motion to

proceed to

consideration of

measure made

in Senate

(7/27/2026)

S. 5054

Data Center

Tax

Accountability

and Disclosure

Act of 2026

A bill to exempt AI data centers from bonus depreciation and require data center

operators to submit certain information relating to electricity and water use by

data centers, and for other purposes.

Among other provisions, Section 3 defines a covered data center to “mean a

data center, including a dual-use data center and a data center that is colocated or otherwise shares commercial space with a dedicated Federal data

center, the power demand of which is 25 megawatts or more,” excluding

federal data centers. This section requires new and existing covered data

centers to report annually on water quantity used during that year, the

source of the water used, the annual average “water use effectiveness,” and

“any water rights, permits, or long-term supply agreements” held by the

data center operator. This section authorizes states to elect to receive such

reports (so-called “electing states”) and authorizes EPA and DOE to receive

such reports for covered data centers in states that do not elect to do so.

This section requires “electing states” to share that information with EPA

and DOE, annually. This section also requires EPA and DOE to make these

reports publicly available on the agencies’ websites. This section also directs

the Office of Management and Budget to develop standards for water

source, quantity, water use effectiveness, and supply agreements reporting

for data centers that provide service “to both the Federal Government and

1 or more non-Federal interests.”

EPA, DOE,

Office of

Management

and Budget

Senate Committee

on Finance

Referred to

committee

(7/21/2026)

Source: Compiled by CRS using Congress.gov, https://www.congress.gov/quicksearch/legislation?wordsPhrases=%28%22data+center%22+OR+%22data+centers%22+OR+datacenter+OR+datacenters%29+AND+water&include=on&wordVariants=on&congres

sGroups%5B0%5D=0&congresses%5B0%5D=119&legislationNumbers=&legislativeAction=&sponsor=on&representative=&senator=&s=6.

Note: Kezee Procita, Head of Research and Library Services, compiled this table.

CRS-37

Data Centers and Water: Frequently Asked Questions

Author Information

Peter Folger, Coordinator

Section Research Manager

Laura Gatz

Specialist in Environmental Policy

Elena H. Humphreys, Coordinator

Specialist in Environmental Policy

Anna E. Normand

Specialist in Natural Resources Policy

Nicole T. Carter

Specialist in Natural Resources Policy

Charles V. Stern

Specialist in Natural Resources Policy

Corrie E. Clark

Specialist in Energy Policy

Disclaimer

This document was prepared by the Congressional Research Service (CRS). CRS serves as nonpartisan

shared staff to congressional committees and Members of Congress. It operates solely at the behest of and

under the direction of Congress. Information in a CRS Report should not be relied upon for purposes other

than public understanding of information that has been provided by CRS to Members of Congress in

connection with CRS’s institutional role. CRS Reports, as a work of the United States Government, are not

subject to copyright protection in the United States. Any CRS Report may be reproduced and distributed in

its entirety without permission from CRS. However, as a CRS Report may include copyrighted images or

material from a third party, you may need to obtain the permission of the copyright holder if you wish to

copy or otherwise use copyrighted material.

Congressional Research Service

R49057 · VERSION 2 · NEW

38