Electric Power Storage

Congressional research reportSep 8, 2009

Ask Donna

What actually matters in this document.

Text

Electric Power Storage

-name redactedSpecialist in Energy and Environmental Policy

September 8, 2009

Congressional Research Service

7-....

www.crs.gov

R40797

CRS Report for Congress

Prepared for Members and Committees of Congress

Electric Power Storage

Summary

Unlike natural gas or fuel oil, electricity cannot be easily stored. However, interest in electric

power storage (EPS) has been growing with technological advancements that can make storage a

more practical means of integrating renewable power into the electricity grid and achieving other

operating benefits.

This report summarizes the technical, regulatory, and policy issues that surround implementation

of EPS. Electricity storage is one of several non-traditional technologies and methods of meeting

power demand that are of current congressional interest (others include distributed generation,

renewable power, and demand response). EPS and these other alternatives do not fit the

traditional power industry paradigm, which involves reliance on large-scale central power plants

and long-distance transmission lines to meet demand. This raises the question of how quickly and

effectively the power industry and its regulators will be willing to pursue and deploy new

approaches. Electricity storage is also currently a relatively high-cost technology, another factor

that could delay its deployment.

The report identifies several areas for possible congressional oversight, including:

•

Power industry and state regulator acceptance of storage technologies.

•

Integration of storage into transmission system planning, including integration of

renewable power into the electricity grid.

•

Federal executive agency focus on EPS as a solution to power system needs.

•

The application of incentives for electric power storage development included in

the American Recovery and Reinvestment Act of 2009 (ARRA; P.L. 111-5).

The report discusses how the provisions of several pending bills relate to the development of

electric power storage, including S. 1091, the Storage Technology of Renewable and Green

Energy Act of 2009 (STORAGE Act); H.R. 2454, the American Clean Energy and Security Act of

2009 (ACES); and S. 1462, the American Clean Energy Leadership Act of 2009 (ACELA).

This report will be updated as warranted.

Congressional Research Service

Electric Power Storage

Contents

Introduction ................................................................................................................................1

Purpose and Organization......................................................................................................1

Notes on Key Power System Concepts ..................................................................................1

Power Plants and Power Lines ........................................................................................1

Capacity and Energy .......................................................................................................2

Storage Technologies and Applications........................................................................................2

Centralized Bulk Power Storage............................................................................................5

Distributed Power Storage.....................................................................................................7

Batteries..........................................................................................................................8

Flywheels ..................................................................................................................... 10

Solar Thermal Storage................................................................................................... 11

Residential Electricity Storage....................................................................................... 13

Commercial-Scale Cooling Storage............................................................................... 14

Storage and the Smart Grid ................................................................................................. 16

Barriers and Issues in Deploying Electric Power Storage ........................................................... 17

Environmental and Cost Factors.......................................................................................... 18

Regulatory Issues ................................................................................................................ 20

Regulatory Background................................................................................................. 20

Power Market Regulation and Electric Power Storage ................................................... 21

Transmission Planning as an Institutional Issue ................................................................... 23

Issues for Congressional Consideration ..................................................................................... 24

Industry and Regulator Acceptance of Storage..................................................................... 24

Executive Agency Focus ..................................................................................................... 25

Current Legislation and Incentives ...................................................................................... 28

STORAGE Act ............................................................................................................. 28

ACES and ACELA ....................................................................................................... 29

Figures

Figure 1. Elements of the Electric Power System.........................................................................2

Figure 2. Hydroelectric Pumped Storage .....................................................................................5

Figure 3. Compressed Air Energy Storage ...................................................................................6

Figure 4. Japanese 34 MW Battery Facility for Use with a Wind Plant.........................................8

Figure 5. Flywheel Electricity Storage....................................................................................... 10

Figure 6. Schematic of a Solar Thermal Power Plant with Molten Salt Storage .......................... 12

Figure 7. Schematic of Peak Shaving and Load Shifting ............................................................ 15

Tables

Table 1. Electric Power Storage Technology Summary ................................................................4

Congressional Research Service

Electric Power Storage

Table 2. Electric Power Research Institute Estimates of Capital Costs for Electric Power

Storage Technologies ............................................................................................................. 18

Contacts

Author Contact Information ...................................................................................................... 31

Congressional Research Service

Electric Power Storage

Introduction

Purpose and Organization

Unlike natural gas or fuel oil, electricity cannot be easily stored. However, interest in electric

power storage (EPS) has been growing with technological advancements that can make storage a

more practical means of integrating renewable power into the electricity grid and achieving other

operating benefits.

This report summarizes the technical, regulatory, and policy issues that surround implementation

of EPS. The report is organized as follows:

•

This introductory section concludes with a brief discussion of certain key power

system concepts.

•

The next section describes EPS technology. This is followed by an analysis of

barriers to the deployment of storage systems.

•

The concluding section discusses areas of potential congressional interest,

including oversight and current legislation.

Notes on Key Power System Concepts

Power Plants and Power Lines

In addition to electric power storage, this report refers to power plants, transmission lines, and

distribution lines. These facilities, which constitute the major components of the existing electric

power system, are briefly described and illustrated below (Figure 1):

•

Generating plants produce electricity, using either combustible fuels such as

coal, natural gas, and biomass; or non-combustible energy sources such as wind,

solar energy, and nuclear fuel.

•

Transmission lines carry electricity from power plants to demand centers. The

higher the voltage of a transmission line the more power it can carry. Current

policy discussions focus on the high-voltage network (230 kilovolts (kV) rating

and greater) used to move large amounts of power long distances.

•

Near customers a step-down transformer reduces voltage so the power can be

carried by low-voltage distribution lines for final delivery.

As discussed later in this report, EPS can be used throughout the power system, depending on the

technology employed and the application.

Congressional Research Service

1

Electric Power Storage

Figure 1. Elements of the Electric Power System

Simplified Schematic

Source: CRS, based on graphic found at https://reports.energy.gov/BlackoutFinal-Web.pdf (p. 5).

Capacity and Energy

References will made in this report to megawatts and megawatt-hours. These are related but

different concepts. A megawatt is a measure of a storage or generating unit’s capacity, while a

megawatt-hour is a measure of the unit’s energy output.

Capacity is the potential instantaneous output of a generating or storage unit, measured in watts.

Energy is the actual amount of electricity generated by a power plant or released by a storage

device during a time period, measured in watt-hours. The units are usually expressed in thousands

(kilowatts and kilowatt-hours) or millions (megawatts and megawatt-hours). For example, the

maximum amount of power a 1,000 megawatt (MW) power plant can generate in a year is 8.76

million megawatt-hours (Mwh), calculated as:

1,000 MW x 8,760 hours in a year = 8.76 million Mwh.

EPS systems are sometimes discussed in terms of their capacity to energy ratios; that is, the ratio

of peak instantaneous output (MW) to total energy released (Mwh) before the unit must be

recharged. A high ratio indicates that the unit discharges rapidly, while a low ratio indicates that

the unit releases its energy over a longer period of time.

Storage Technologies and Applications

Perhaps paradoxically, the storage of electricity does not usually involve the storage of the

electric energy itself. Rather, the storage device converts the electricity to another form—such as

Congressional Research Service

2

Electric Power Storage

the kinetic energy in a spinning flywheel or the potential energy in water that has been pumped to

a higher elevation—and then later converts the energy from the new form back to electricity.

With the exception of hydroelectric pumped storage, EPS technologies are still in various stages

of development. This section of the report discusses the storage technologies and their

applications. The technologies are summarized in Table 1.

Congressional Research Service

3

Electric Power Storage

Table 1. Electric Power Storage Technology Summary

Technology

Representative

Applications

Energy Discharge

Time Span

Status

Capacity

Hydroelectric

Pumped Storage

Bulk power storage for

peak shaving and load

shifting, energy arbitrage,

possible future

applications supporting

wind and solar generation.

Hours.

Commercial; 37

facilities are currently

in operation in the

United States.

Tens to hundreds

of megawatts.

Compressed

Air Energy

Storage

Bulk power storage for

peak shaving and load

shifting, energy arbitrage,

possible future

applications supporting

wind and solar generation.

Hours.

Commercial but with

older technology

(one unit apiece in

Germany and

Alabama); improved

technology has been

proposed.

Tens to hundreds

of megawatts.

Stationary

Batteries

Depending on the

technology, batteries can

be employed for

frequency regulation, peak

shaving and load shifting,

backup power supply

(islanding).

Milliseconds to

minutes to a few

hours, depending on

the technology and

application.

Pilot projects being

installed, some

without government

funding, for sodium

sulfur batteries.

Research and

development is

continuing for this

and other

technologies.

Currently up to

about one MW per

unit. Multiple units

can be combined

to produce a larger

installation, such as

an existing 34 MW

facility in Japan.

Plug-In Hybrid

and Pure

Electric Vehicles

Primary purpose is to

power vehicles, but the

stored power could also

be used by power

companies to meet

emergency and peak

demands

Hours.

Research and

development.

Individually

kilowatt scale, but

cumulatively could

amount to

thousands of

megawatts on a

utility system.

Flywheels

Frequency regulation;

spinning (emergency

backup) reserve.

Milliseconds to

minutes, depending

on the application.

Pilot projects being

installed.

About 25 KW per

unit. Multiple units

can be combined

to produce larger

installations, such

as 20 MW facilities

Solar Thermal

Storage

Bulk storage of energy

produced by an integrated

solar thermal plant. The

stored energy can be

employed to run the solar

facility as a baseload,

dispatchable station.

Hours.

Advanced

development,

including a project in

Spain.

Tens to hundreds

of megawatts.

Cooling Storage

Peak shaving and load

shifting.

Hours.

Commercial.

Kilowatt-scale, but

multiple units can

be bundled by an

aggregator for sale

as a load

management

package to utilities.

Source: CRS.

Congressional Research Service

4

Electric Power Storage

EPS technologies can be broadly categorized into two groups, each of which is discussed below:

centralized bulk power storage and distributed storage. This section also discusses the

relationship between EPS and the smart grid.

Centralized Bulk Power Storage

Centralized bulk power storage facilities are relatively large and complex installations designed to

store large amounts of electricity. Capacities range from tens to hundreds of megawatts, and the

units can supply power to the grid for hours at a time. The primary form of centralized bulk

power storage—and in fact the only form of EPS of any type in commercial and widespread

use—is hydroelectric pumped storage (HPS). In an HPS system, pumps are used during off-peak

periods, when surplus cheap electricity can be generated elsewhere on the power system, to move

water to a reservoir at a higher elevation than the water source. During peak periods, when power

is scarce and expensive, the water in the reservoir is released to move backward through the

system, where it drives hydraulic turbines to produce electricity. About 70% of the power used to

pump the water up into the reservoir is recovered when the process is reversed (see Figure 2).

Figure 2. Hydroelectric Pumped Storage

Source: http://richard-rowland-perkins.com/professional/renewable-tech-hydropower/.

There are currently 37 operational HPS facilities in the United States with a total capacity of

19,696 MW. By comparison, total generating capacity in the United States is about 1 million MW.

Of the 37 operational HPS facilities, 34 plants with 89% of the total capacity were built prior to

1991. The last facility was completed in 1995.1 While plans have been discussed for additional

projects it is unlikely that many more HPS facilities will be built. This is because the number of

1

An additional HPS facility at the Richard B. Russell Dam and Lake in Georgia entered service in 2002 but the project

was essentially complete years earlier. The situation at Russell is discussed later in the report.

Congressional Research Service

5

Electric Power Storage

suitable sites is limited and there are environmental objections to the construction of large

hydroelectric projects.

The other form of centralized bulk power storage is compressed air energy storage (CAES). In

this system compressors are used to inject air into a cavern developed within a salt dome or into

another suitable geologic formation. To recover the power the compressed air is released, heated

using a natural gas-fired combustion turbine, and used to help drive a turbine generator. A

schematic of a CAES system is shown below (Figure 3).

Figure 3. Compressed Air Energy Storage

Source: CRS, based on a diagram at http://blogs.chron.com/newswatchenergy/archives/2007/07/

power_for_when.html (citing Ridge Energy Storage and Grid Services).

Notes: For an animated version of this graphic, see http://ridgeenergystorage.com/.

Congressional Research Service

6

Electric Power Storage

Prototype CAES plants were built in 1978 in Germany (290 MW) and in 1991 in Alabama (the

McIntosh plant, 110 MW). There are reportedly many sites in the United States suitable for

construction of CAES units,2 and because the units have a relatively small above-ground footprint

they may face less public opposition than HPS developments. New projects have been announced

but construction has not started.3 The CAES technology is still evolving. For instance, the

designers of the 1991 plant in Alabama are now seeking to build units using an improved “second

generation” technology.4

One use of centralized bulk power storage systems is displacement of peaking generation. The

cheap power captured in the facility during low-demand hours, such as the evening, can be used

during the day to meet high loads in place of expensive-to-operate peaking power plants. An

operationally related concept is price arbitrage, in which the cheap power stored at night is sold at

a high price during the day.

A new potential use for centralized bulk storage would be to compensate for the variability in

output from wind and solar plants. For example, in some parts of the country the strongest and

most consistent winds blow at night when demand is low. This surplus wind power can be

captured in a storage facility and then used to meet demand during the day. Stored electricity

(captured from any generating source) can also be used to backstop wind and solar power if

weather conditions are unfavorable. As discussed later in this report, the degree to which wind

power in particular needs backup storage is disputed.

Distributed Power Storage

Distributed multipurpose power storage includes facilities dispersed through the power system

and used to meet specific, local needs for power. The facilities can be located at generating plants,

on the power transmission or distribution systems, or at an end-user site. The facilities are

typically small but this may change as technologies mature. All of these technologies are still in

the developmental stage.

The following distributed power storage technologies 5 and applications are discussed below:

2

Steve Blankinship, “Intermittent Wind: Problems and a Possible Solution,” Power Engineering, June 2008. The

article is available on-line by searching at http://pepei.pennnet.com/.

3

This includes projects in Ohio, Iowa, California, and Texas. Samir Succar and Robert H. Williams, Compressed Air

Storage: Theory, Resources, and Applications for Wind Power, Princeton University Environmental Institute, April 8,

2008, pp. 24-26, http://www.princeton.edu/~cmi/research/Capture/Papers/

SuccarWilliams_PEI_CAES_2008April8.pdf. For information on the Iowa project, including an animated description

of the proposed facility, see http://www.isepa.com/index.asp. Most recently, on August 26, 2009, Pacific Gas &

Electric Co. in California announced it was seeking $25 million in federal stimulus funding to help fund a 300 MW,

$356 million CAES facility in Kern County. The project would take five years to design and build, and would have 10

hours of capacity. The primary source of stored electricity would be wind power. For more information see the posting

at the utility’s website, http://www.next100.com/, and Tracy Seipel, “PG&E to Build Plant to Store Wind Energy,” San

Jose Mercury News, August 27, 2009.

4

See the website for Energy Storage and Power LLC at http://www.energystorageandpower.com/home.html.

5

Other technology options include ultracapacitors and superconducting magnetic energy storage devices. These are

still in an early developmental stage and reportedly not ready for utility-scale power system applications (Rahul

Walawalkar, Jay Apt, and Rick Mancini, “Economics of Electric Energy Storage for Energy Arbitrage and Regulation

in New York,” Energy Policy, April 2007). For additional information on these technologies see American Physical

Society, Challenges of Electricity Storage Technology, May 2007, http://www.aps.org/policy/reports/popa-reports/

upload/Energy-2007-Report-ElectricityStorageReport.pdf.

(continued...)

Congressional Research Service

7

Electric Power Storage

•

Batteries.

•

Flywheels.

•

Solar thermal storage.

•

Residential electricity storage.

•

Commercial-scale cooling storage.

•

Storage and the smart grid.

Batteries

Although battery technology is still under development, commercial applications exist in the

United States and elsewhere. Figure 4 shows a 34-MW battery facility in Japan used in

conjunction with a 51-MW wind farm. The facility uses sodium sulfur (NaS) batteries produced

by a Japanese manufacturer, NGK Insulators.

Figure 4. Japanese 34 MW Battery Facility for Use with a Wind Plant

Source: http://www.ngk.co.jp/english/products/power/nas/installation/index.html.

American Electric Power (AEP), a large domestic power company, deployed a 1-MW NaS

battery (the size of a double-decker bus and weighing 77 tons) in 2006 in Charleston, WV. The

project was funded in part by the Department of Energy (DOE). The battery was connected to the

distribution system and is charged in the evening when demand is low; by providing power as

needed during higher-demand daytime periods it alleviates an overloading problem and defers the

(...continued)

Congressional Research Service

8

Electric Power Storage

need to build a new substation. In 2008 AEP installed two 1-MW batteries near Milton, WV, to

relieve another distribution system overloading problem. 6

Other existing or planned battery installations include:

•

AES Energy Storage, an affiliate of the large power project developer AES Inc.,

has connected a 1-MW array of batteries carried in a truck trailer to the grid in

Pennsylvania, and a similar 2-MW array at a wind farm it owns in California.

These projects use lithium ion technology supplied by A123Systems in

Massachusetts.

•

Xcel Energy, a Midwestern utility, is testing a trailer-carried 1-MW NaS battery

at a wind farm it owns in Minnesota. The project has government and university

partners.7

•

AEP installed three facilities of 2 MW each at sites in Ohio, West Virginia, and

Indiana in 2008, and a 4-MW facility in Texas in 2009. The company reportedly

aims to install 1,000 MW of battery capacity throughout its system by 2020.8

•

The New York Metropolitan Transit Authority installed a 1-MW NaS battery in

January 2009. The battery stores inexpensive off-peak power in the evening to

run natural gas compressors used for refueling buses during the day. The

installation is a demonstration project funded in part by the state and federal

governments and industry trade associations.9

Batteries can provide several different services to the power system. Depending on the

technology,10 batteries can provide a local source of power for several hours, displacing or

deferring the need for additional generating, transmission, or distribution capacity; provide a

backup source of power to a local area if other parts of the grid fail (referred to as “islanding”);

and provide grid “regulation,” a service described immediately below in the flywheel discussion.

6

Statement of Larry Dickerman, Director, Distribution Engineering Services, American Electric Power, before the

House Committee on Science and Technology, Subcommittee on Energy and Environment, October 3, 2007; George

Hohmann, “Utility Installs Giant Batteries in Milton; Devices Can Store Enough Energy to Supply 760 Households for

Six to Seven Hours,” Charleston (West Virginia) Gazette, December 18, 2008.

7

“News Briefs: Xcel Energy,” Platts Electric Utility Week, April 20, 2009.

8

Jeff Ryser, “Electricity Storage Technology Moves Forward with Support by Grid Operators,” Platts Electric Utility

Week, April 6, 2009; Ali Nourai, AEP, “Massive Electricity Storage: A Utility Perspective,” Congressional briefing for

the Energy Storage Association, Washington, DC, June 16, 2009, slide 3; AEP, “Electric Transmission Texas Signs

Contract for Largest Utility-scale Battery in the U.S.,” press release, September 1, 2009, http://www.aep.com/

newsroom/newsreleases/?id=1560.

9

New York Metropolitan Transit Authority, “MTA LI BUS And NYPA Install First Sodium Sulfur Battery Energy

Storage System In State,” press release, January 9, 2009, http://www.mta.info/mta/news/releases/?en=090109-HQ2.

10

Battery technology continues to evolve and designs other than the NaS and lithium ion systems mentioned above are

under development. For additional information on battery technologies see the website of the Energy Storage

Association at http://www.electricitystorage.org/site/technologies/; American Physical Society, Challenges of

Electricity Storage Technology, May 2007, http://www.aps.org/policy/reports/popa-reports/upload/Energy-2007Report-ElectricityStorageReport.pdf; and Jonathan Shieber, “Producers – Building a Better Battery,” The Wall Street

Journal, November 17, 2008.

Congressional Research Service

9

Electric Power Storage

Flywheels

A flywheel stores electricity in the form of mechanical energy in a spinning wheel or tube. In

storage mode power is used by a motor to spin-up the flywheel. To recover power, the flywheel

drives a generator (Figure 5). About 85% to 90% of the stored power can be recovered.11

Figure 5. Flywheel Electricity Storage

Source: CRS, based on a schematic at http://www.dg.history.vt.edu/ch2/storage.html.

With current technology individual flywheel units have a capacity of about 25 kilowatts (kw).

These can be deployed in integrated arrays to produce megawatt-scale installations. Beacon

Power, a Massachusetts firm, is currently operating a 2-MW pilot facility in that state and hopes

to expand to 5 MW by the end of 2009. The firm has also received a $2 million grant from New

York State and tentative approval for a $43 million federal loan guarantee to help support

construction of a 20-MW plant in New York. 12 A 1-MW facility is being planned in conjunction

with AEP for installation in Ohio. 13

These projects are intended to provide regulation service to the power grid, a service which, as

noted above, can also be provided by battery facilities. In this context “regulation” refers to the

need for power grid operators to precisely match, moment to moment, the supply and demand for

electricity. If supply and demand go too far out of synch, the power system can become unstable,

11

For more information on flywheel technology, see Ed Douglas, “New Generation Flywheels,” Power Engineering,

May 2009 and Steve Blankinship, “Megawatt-Scale Flywheel Nears Market Readiness,” Power Engineering, April

2007 (the articles can be found on-line by searching at http://pepei.pennnet.com/); and American Physical Society,

Challenges of Electricity Storage Technology, May 2007.

12

See press releases on the Beacon Power website at http://www.beaconpower.com/company/news.asp.

13

“Beacon Power Building Energy Storage Facility at AEP Site,” The Energy Daily, February 24, 2009.

Congressional Research Service

10

Electric Power Storage

consumer electrical equipment and appliances can be damaged, and ultimately the grid can fail.

Because demand is constantly changing, the output of some power plants on a power system is

constantly varied, up and down, to match demand. Because power plants generally operate most

efficiently at a steady state, constant small-scale adjustments increase fuel costs and wear and tear

on the generators.

Although current flywheels can provide power for up to 15 minutes, regulation depends on their

moment-to-moment ability to move power on and off of the grid. The need for regulation service

may increase in the future as more wind and solar power with variable, weather-dependent output

is connected to the power system. 14 Regulation service from conventional generators has worked

reliably for decades, but in principle a storage device such as a flywheel or battery could provide

the service more efficiently. Flywheels and some types of batteries are EPS options for providing

this capability.

Another service that is essential to maintaining the stability of the grid is reactive power supply.

As explained by the Federal Energy Regulatory Commission (FERC):

Almost all bulk electric power in the United States is generated, transported and consumed in

an alternating current (AC) network. Elements of AC systems produce and consume two

kinds of power: real power (measured in watts) and reactive power (measured in voltamperes reactive, or var). Real power accomplishes useful work (e.g., running motors and

lighting lamps). Reactive power supports the voltages that must be controlled for system

reliability.

Reactive power supply is essential for reliably operating the electric transmission system.

Inadequate reactive power has led to voltage collapses and has been a major cause of several

recent major power outages worldwide. And while the August 2003 blackout in the United

States and Canada was not due to a voltage collapse as that term has been traditionally used,

the final report of the U.S.-Canada Power System Outage Task Force (April 2004) said that

“insufficient reactive power was an issue in the blackout.” Dynamic capacitive reactive

power supplies were exhausted in the period leading up to the blackout.15

Although generating plants produce real and reactive power, additional reactive power must be

injected at various points throughout a power grid. This is currently accomplished by specialized

devices, but flywheels are another potential option.

Solar Thermal Storage

Solar thermal and photovoltaic power are alternative means of harnessing sunlight to produce

electricity. Photovoltaic power, probably the better-known technology, uses solar cells to directly

convert sunlight to electricity. Solar thermal plants, also referred to as concentrated solar power

(CSP), concentrate sunlight to heat a working liquid, such as water, to produce steam that drives a

power-generating turbine. 16 Several parabolic trough-type CSP installations have operated

14

Richard Fioravanti, Khoi Vu, and Walter Stadlin, “Large Scale Solutions,” IEEE Power and Energy, July/August

2009, p. 50.

15

FERC, Principles for Efficient and Reliable Reactive Power Supply and Consumption, Staff Report, Docket AD05-1000, February 4, 2005, p. 3, http://www.ferc.gov/eventcalendar/files/20050310144430-02-04-05-reactive-power.pdf.

16

The two major types of solar thermal systems are parabolic trough and power tower technologies. Parabolic trough

plants use an array of mirrors to focus sunlight on liquid-carrying tubes integrated with the mirrors. The power tower

technology uses a mirror field to focus sunlight on a central tower, where the heat is used to produce steam for power

(continued...)

Congressional Research Service

11

Electric Power Storage

successfully in California since the 1980s, and the 64-MW Nevada Solar One plant began

operating in 2007.

Several new solar thermal projects, with capacities in the hundreds of megawatts, are in

development. A potential advantage of solar thermal systems is the ability to produce electricity

when sunlight is weak or unavailable by storing solar heat, such as in the form of molten salt. In

such a system the concentrated solar energy is used to melt salts (such as sodium and potassium

chloride). A heat exchanger (also referred to as a steam generator) is used to capture heat from the

salt to produce steam, which then drives a power turbine (Figure 6). Reportedly up to 93% of the

stored energy can be recaptured for steam production. 17

Figure 6. Schematic of a Solar Thermal Power Plant with Molten Salt Storage

Source: CRS, based on a diagram at http://thefraserdomain.typepad.com/energy/2005/09/aabout_solar_to.html.

Notes: A heliostat is a mirror that reflects solar rays onto a central receiver. A heliostat automatically adjusts its

position to track daily or seasonal changes in the sun's position. The arrangement of heliostats around a central

receiver is also called a solar collector field. (Definition from http://www.eia.doe.gov/glossary/index.html.)

(...continued)

generation. A research power tower, the Solar One/Two plant, operated for several years in the 1980s and 1990s in

California. A power tower plant has recently been constructed in Spain and projects have been proposed for the United

States. For more information see CRS Report RL34746, Power Plants: Characteristics and Costs, by (name reda

cted).

17

For additional information on CSP and thermal storage technology see David Bello, “How to Use Solar Energy at

Night,” Scientific American, February 18, 2009, http://www.scientificamerican.com/article.cfm?id=how-to-use-solarenergy-at-night.

Congressional Research Service

12

Electric Power Storage

Molten salt storage was used at the test Solar One/Two plant in the United States, and is being

used now at the 50-MW Andasol 1 plant in Spain (a second 50-MW block is under construction

and a third is planned). The Spanish plant can run at full load for 7.5 hours using stored heat. The

disadvantage of adding molten salt storage to a CSP plant is the additional cost and complexity.

For example, the developer of the 400-MW Ivanpah CPS project in California decided not to use

molten salt storage in the project in order to reduce costs and make the project “commercially

viable by getting rid of the extras.” The decision on whether to add storage to a project pivots on

the balance between the incremental costs and the additional revenues available by being able to

provide firm service over an extended operating day.

Residential Electricity Storage

Batteries can be used to store electricity in individual homes, either in battery banks or in the

battery packs of plug-in hybrid electric vehicles (PHEV), or at small sites serving a group of

homes. Each approach has different technical and economic issues.

Fixed in-home storage involves installing a bank of batteries in the house, and is often discussed

in conjunction with installing a home solar photovoltaic (PV) system. The idea is that surplus PV

power generated during the day can be stored and used when less sunlight is available or home

demand is high. With current battery technology these systems can be bulky, require power

conversion electronics, and require significant maintenance and replacement time and expense. 18

More advanced battery technology could reduce costs and improve performance.

PHEVs have battery packs that can be charged through a home’s power system. As with fixed inhome battery banks, the notion is to use off-peak power to charge the battery. These systems and

the vehicles that would use them are still under development but have garnered a great deal of

interest and government and industry attention.19

The interaction between in-home storage and the power system is complex. The electricity stored

in the batteries can be viewed as a resource only for and under the control of the homeowner. An

alternative concept, which is closely tied to the notion of a smart grid (discussed below), is that

the utility would have control over the operation of the batteries. For example, utility control of a

large network of distributed batteries could allow the utility to rely on power stored in the

batteries during off-peak hours, such as the evening, to meet daily peak demands. This approach

requires less construction of transmission and generation facilities than with traditional utility

methods. However, it also means that the utility and not the homeowner would have control over

charging and discharge cycles.

Utility control may be problematic in particular for PHEVs, since a homeowner planning a

relatively long late afternoon trip may not want the utility taking power out of his or her vehicle’s

battery pack to meet mid-day system peaks. On the other hand, some degree of utility control

18

National Renewable Energy Laboratory, “Battery Power for Your Residential Solar Electric System,” October 2002,

http://www.nrel.gov/docs/fy02osti/31689.pdf.

19

For additional information see the discussion of “Economics of Plug-In Hybrid Electric Vehicles” in EIA, Annual

Energy Outlook 2009, pp. 31-35, http://www.eia.doe.gov/oiaf/aeo/index.html. A recent DOE study notes that “PHEVs

are unlikely to play a significant role as a storage mode or as a distributed generator in the near term due to cost

considerations.” DOE, Smart Grid System Report, July 2009, p. 20, http://www.oe.energy.gov/DocumentsandMedia/

SGSRMain_090707_lowres.pdf.

Congressional Research Service

13

Electric Power Storage

and/or government regulation will be needed to prevent situations where homeowners try to

charge PHEV batteries during peak periods, which would increase system costs and perhaps

degrade system reliability.

In-home storage also competes with the concept of “net metering.” Net metering provides for a

utility to buy surplus power generated by the home PV system (or other generating system).20 The

system owner then receives either a cash payment or electricity in kind when home demand

exceeds PV output. Net metering arrangements vary by locality and may provide superior

economics to home power storage. 21

Multi-home electricity storage involves a small battery facility that would serve several homes,

perhaps half-a-dozen, with several hours of storage. The facility would be owned, controlled, and

maintained by the local utility, and would be used for peak shaving, as a backup power supply,22

and for power quality control.23 This kind of centralized facility would presumably benefit from

economics of scale compared to individual home battery banks, but the homeowner would also

lose control of the storage. Additional metering, wiring, and billing enhancements would be

needed for a centralized facility to be used to collect surplus power from a home’s PV system and

send it back when needed.

Commercial-Scale Cooling Storage

Cooling storage devices use electricity during non-peak hours, such as the evening, to turn water

to ice. During the day and particularly at times when electricity demand would normally be at its

peak, such as midday or the afternoon on a summer business day, the ice can be used to cool air,

displacing air conditioning load. This type of storage is currently economical for commercial and

industrial establishments, such as office buildings. Cooling storage is a commercial technology

sold by several vendors.

Cooling storage affects the power system by shaving peak demand and shifting load. As shown

below in Figure 7, by cutting air conditioning load during the day the cooling storage cuts peak

demand. This reduces the need to operate, or even to build, some relatively high-priced natural20

Net metering is defined more fully at the Database of State Incentives for Renewables & Efficiency

(http://www.dsireusa.org/glossary/): “For electric customers who generate their own electricity, net metering allows for

the flow of electricity both to and from the customer—typically through a single, bi-directional meter. With net

metering, during times when a customer’s generation exceeds the customer’s use, electricity from the customer flows

back to the grid, offsetting electricity consumed by the customer at a different time. In effect, the customer uses excess

generation to offset electricity that the customer otherwise would have to purchase at the utility’s full retail rate. Net

metering is required by law in most U.S. states, but some of these laws only apply to investor-owned utilities – not to

municipal utilities or electric cooperatives.”

21

For state level implementation information, see the Database of State Incentives for Renewables & Efficiency at

http://www.dsireusa.org/summarytables/rrpre.cfm. For a brief comment on home storage versus net metering, see

http://energyoutlook.blogspot.com/2009/03/storing-sunlight.html.

22

According to AEP, just four hours of storage would cover about 90% of the utility’s power outages. Martin

LaMonica, “Utility AEP Plans Backyard Energy Storage,” CNET News: Green Tech, March 7, 2009,

http://news.cnet.com/8301-11128_3-10191231-54.html.

23

AEP is reportedly planning to install multi-home storage systems, perhaps using lithium ion battery technology.

“AEP to Install Residential Energy Storage,” Pennwell Power Group On-Line Article, March 19, 2009,

http://pepei.pennnet.com/Articles/Article_Display.cfm?Section=ARTCL&PUBLICATION_ID=6&ARTICLE_ID=

356711&C=INDUS&dcmp=rss; and “FERC Examining First-Ever Comprehensive Storage Pricing Policy,” Energy

Washington Week, July 29, 2009.

Congressional Research Service

14

Electric Power Storage

gas-fired peaking plants. However, the load is not eliminated, but shifted to the non-peak hours

when the storage system makes ice.

Figure 7. Schematic of Peak Shaving and Load Shifting

Source: CRS, based on a diagram at http://oee.nrcan.gc.ca/publications/infosource/pub/cipec/efficiency/2_04.cfm?

attr=20.

The effect of the load shifting and peak shaving is likely to be a reduction in total costs to

consumers. This is for three reasons:

•

The shifted load would be met in most utility systems by coal or natural gas

combined cycle plants that are under-utilized in the evening. These are cheaper to

operate than peaking plants. However, to the extent that carbon dioxide emissions

are a concern, shifting more load to coal-fired plants may be an issue.

•

In restructured markets,24 power prices for all generators are set by the price of

the marginal—that is, highest priced—generating unit to operate during a certain

time period, such as hourly. By reducing the peak load on generating units, and

24

In restructured power markets, retail rates for electricity reflect daily market bids for electricity supply in the

wholesale market. In traditional markets, rates are set by state utility commissions. Neither market is deregulated, but

the forms of regulation are much different. Many states in the Midwest, Northeast, New England, Texas, and California

have adopted various forms of restructured markets while other parts of the county, particularly the Southeast and

Northwest, continue to rely on traditional rate regulation. For additional background see DOE, Keeping the Lights on in

a New World, January 2009, pp. 18-23, http://www.oe.energy.gov/eac.htm.

Congressional Research Service

15

Electric Power Storage

therefore the need to operate higher-cost peaking units, peak shaving can have a

substantial impact on total power costs.25

•

Making ice during relatively cooler evening hours is somewhat more efficient

than running air conditioning during the hottest daytime hours. This efficiency

gain can essentially eliminate any power losses in the storage process.26

The economics of cooling storage can be improved by a load management “aggregator.” The

aggregator is a kind of broker that combines the capacity of multiple cooling storage installations

into a block that can be sold to a utility as a single, guaranteed load management resource.

Cooling storage is limited to the cooling season and by the amount of capacity that can be

installed, which is a function of the amount of air conditioning load in suitable buildings. In

climates that experience high summer and winter demand it would be preferable to have storage

that can shave peaks year-round.

Storage and the Smart Grid

Power grid modernization proposals are often made under the rubric of the “smart grid,” a term

that encompasses technologies that range from advanced meters in homes to advanced software

in transmission control centers. There is no standard definition of the smart grid.27 For the

purposes of this report, the smart grid can be viewed as a suite of technologies that give the grid

the characteristics of a computer network, in which information and control flows between and is

shared by individual customers and utility control centers. The technologies would allow

customers and the utility to better manage electricity demand, and include self-monitoring and

automatic-protection schemes to improve the reliability of the system.28 Although grid technology

has not been static over the years,29 the smart grid concept would implement capabilities well

beyond any existing electric power system. 30

The smart grid involves integrated operation of the power system from the home to the power

plant and could encompass management of centralized and distributed EPS. In principle a smart

grid system would optimize the full range of available resources—including the various kinds of

distributed storage and net metering distributed generation—to meet multiple needs, including

25

Storage units like batteries and CAES can supply during peak hours relatively inexpensive electricity stored in the

evening, putting further downward pressure on peak-hours prices. See Motion to Intervene and Comments of Xcel

Energy Services Inc., Before the Federal Energy Regulatory Commission, Docket No. ER09-1126-000, June 2, 2009,

p. 14 (available through FERC docket search at http://elibrary.ferc.gov/idmws/docket_search.asp).

26

Michael T. Burr, “Storage Goes Mainstream,” Public Utilities Fortnightly, April 2009, p. 29.

27

DOE’s Electricity Advisory Committee noted that “there are many working definitions of a Smart Grid.” Electricity

Advisory Committee, Smart Grid: Enabler of the New Economy, U.S. Department of Energy, Washington, DC,

December 2008, p. 1.

28

Other descriptions of the smart grid emphasize its environmental benefits through reducing fossil-fueled electric

generation and air pollution emissions. See the comments of FERC Commissioners Moeller and Spitzer in Federal

Energy Regulatory Commission, “FERC Accelerates Smart Grid Development with Proposed Policy, Action Plan,”

press release, March 19, 2009, http://www.ferc.gov/news/news-releases/2009/2009-1/03-19-09.asp.

29

Scott Gawlicki, “Demonstrating the Smart Grid,” Public Utilities Fortnightly, June 2008, p. 51; and Kenneth Martin

and James Carroll, “Phasing in the Technology: Phasor Measurement Devices and Systems for Wide-Areas

Monitoring,” IEEE Power and Energy, September/October 2008.

30

For additional information on the smart grid and the transmission system generally see CRS Report R40511, Electric

Power Transmission: Background and Policy Issues, by (name redacted).

Congressional Research Service

16

Electric Power Storage

peak shaving, backup power in the case of outages, electricity regulation, and ensuring that

distributed battery systems are charged during non-peak hours.

The close relationship between the development of storage and the smart grid is reflected in the

smart grid policy statement recently promulgated by FERC. The policy identifies EPS as one of

“four key functionalities” that the smart grid must implement.31 A recent DOE report finds that:

The ability to accommodate a diverse range of generation types, including centralized and

distributed generation as well as diverse storage options, is central to the concept of a smart

grid. Through these generation and storage types, a smart grid can better meet consumer load

demand, as well as accommodate intermittent renewable-energy technologies. Distributed

resources can be used to help alleviate peak load, provide needed system support during

emergencies, and lower the cost of power provided by the utility.32

The report also observes that many technical challenges remain before the smart grid and

associated technologies can be fully deployed, noting that “accommodating a large number of

disparate generation and storage resources requires anticipation of intermittency, unavailability,

while balancing costs, reliability, and environmental emissions.”33

Like electricity storage, the smart grid is for the most part a developmental rather than operational

technology. Other than installation of smart meters in some localities (which permit interactive

communication and in some cases appliance control between homes and utility control centers)

deployment of the “full” smart grid, which would include optimization of storage and other

resources, has not progressed beyond pilot projects.

Barriers and Issues in Deploying Electric Power

Storage

EPS does not fit neatly into traditional utility planning, or current regulatory and financing

structures, which have approached power system needs with central station power plants and

large transmission projects. As one analysis notes:

We know from years of operating pumped hydroelectric facilities that incorporating them

into market and grid operations is a nontrivial task. Optimally scheduling the use of these

facilities in a market with dynamic pricing can be a complicated problem. There are not so

many of these facilities in use, however, that the problems have had to be generally solved

for scale application. Today, though, we can foresee a future with many electric storage

systems out there—at wind farms and other generation sites, grid-connected at transmission

and distribution substations, and deployed along distribution feeders and behind the meters.

Storage will represent a new class of electric infrastructure apparatus and will require that we

develop new algorithms, tools, protocols, and regulatory paradigms for planning, financing,

31

The others are wide-area situational awareness, demand response, and electric-powered transportation. The policy

also identifies two “cross-cutting issues,” cybersecurity and a common information model. For additional information

see the proposed and final policy statements (dated, respectively, March 19 and July 16, 2009), available by searching

for Docket No. PL09-4-000 at http://elibrary.ferc.gov/idmws/docket_search.asp.

32

DOE, Smart Grid System Report, July 2009, p. 18, http://www.oe.energy.gov/DocumentsandMedia/

SGSRMain_090707_lowres.pdf.

33

Ibid.

Congressional Research Service

17

Electric Power Storage

and operating these assets. The greatly increased flexibility that storage brings to the electric

system will best be exploited only when we have the right new methods and understanding

in place.34

This section of the report discusses environmental, cost, regulatory, and institutional issues which

may impede the deployment of EPS systems.

Environmental and Cost Factors

The only EPS technology that is both technically mature and widely used is hydroelectric pumped

storage. However, there will probably be few opportunities to build more HPS plants in the

United States. Two limiting factors are lack of suitable site and high cost. As shown in Table 2,

the estimated cost of building a new HPS facility is $2,500 to $4,000 per KW of capacity,

exclusive of financing (which can be very significant) and certain other costs (see the notes to the

table). This is, roughly speaking, in the range of costs for building a new coal plant at the low end

($2.5 billion) and a new nuclear power plant at the high end ($4 billion). Perhaps even more

important than the cost of HPS are the perceived environmental impacts, including flooding of

valleys to create reservoirs and damage to wildlife habitats. Environmental objections to HPS are

so severe that they have delayed the operation of completed plants. For example, an HPS facility

at the Richard B. Russell Dam and Lake in Georgia was essentially completed in the mid-1980s,

but did not enter service until 2002 due to environmental litigation and related testing. 35 The HPS

capacity at the Harry S. Truman Dam and Reservoir in Missouri has never been used

commercially for environmental reasons.36

Table 2. Electric Power Research Institute Estimates of Capital Costs for Electric

Power Storage Technologies

Current or Projected

Cost

Estimated Total Capital

Cost, $ per Kilowatt of

Capacity

Technology

Technology Detail

Compressed Air Energy

Storage

100 to 300 MW facility;

underground salt dome

storage

Current

$600 to $750

Hydroelectric Pumped

Storage

1000 MW

Current

$2,500 to $4,000

Battery—Conventional

Sodium Sulfur

Projected

$1,850 to $2,150

Battery—Advanced

Flow Battery

Projected

$1,545 to $3,100

Flywheel

10 MW facility

Current

$3,695 to $4,313

Source: Dan Rastler, “The Electric Storage Landscape: Renewables Integration and Smart Grid,” presentation,

Platts Power Storage Conference, January 15-16, 2009.

34

Ralph Masiello, “Bottling Electricity,” IEEE Power and Energy, July/August 2009, p. 24.

Southeastern Power Administration, “Hydropower Pump-back Projects/Perspectives,” presentation, Southwestern

Federal Hydropower Conference, June 10, 2009, http://www.swpa.gov/PDFs/2009Conference/Pumpback-PMAPerspective-Nadler.pdf; and http://www.sjrdotmdl.org/Meeting_info/mW6s3bb.doc.

36

General Accounting Office, Power Marketing Administrations: Cost Recovery, Financing, and Comparison to

Nonfederal Utilities, September 1996, p. 34, http://www.gao.gov/archive/1996/ai96145.pdf.

35

Congressional Research Service

18

Electric Power Storage

Notes: The EPRI source material notes (1) all figures are rough order-of-magnitude estimates; (2) total capital

costs include power conditioning system and all equipment necessary to supply power to the grid; (3) not

included are battery replacement costs, site permitting, interest during construction and substation costs; and (4)

the cost estimates are for mid-2008.

Other storage technologies do not have the same environmental issues as HPS (although issues

may arise if storage systems become more common37), but they appear to share the HPS issue of

high cost. The Electric Power Research Institute (EPRI) capital cost estimates shown in Table 2

are roughly comparable to those of the current range of conventional fossil and nuclear generating

technologies.38 However, the operating times of conventional power plants are, with the exception

of peaking units, measured in days and months, rather than the hours and minutes of storage

technologies. Also, storage systems generally return to the grid less power than they store.

Consequently, storage devices have fewer kilowatt-hours of output to spread their costs over than

conventional generators, which increases the cost per kwh. The Table 1 estimates, which EPRI is

planning to update in a more comprehensive form by the end of 2009,39 also do not account for

maintenance, battery replacement, and financing expenses.

Storage technology continues to evolve and with more advanced systems and economies of scale

from mass production the costs could decline. Nonetheless, for the time being it seems fair to

treat EPS as generally a high-cost suite of technologies. There are current federal incentives and

grants that can help to compensate for these high costs, as discussed later in the report. But for a

long-term and sustainable role in the power system, it appears that storage will need revenue from

premium applications, and revenue from multiple value streams that reflect the many uses to

which storage can be put. For example, a flywheel facility might provide:

•

Regulation service, which according to one analyst may produce system benefits

5 to 10 times greater than peak shaving and load shifting.40

•

Emergency backup reserve power to the grid (referred to as “spinning reserve”)

for short periods.

•

Reactive power to the grid for voltage support.

Batteries can be used for distribution system support to maintain reliability and defer investments

in new power lines and substations, voltage regulation, as a form of spinning reserve, for

generating unit “black start,”41 and to provide power to a local area in the event of a blackout. A

CAES plant can be used for price arbitrage, load leveling, and voltage regulation. Other examples

can be added. However, to monetize these services the highly regulated electric market must have

37

See for example the discussion in Elisabeth A. Gilmore, et al., The Air Quality And Human Health Effects Of

Integrating Utility-Scale Batteries Into The New York State Electricity Grid, Carnegie Mellon Electricity Industry

Center Working Paper CEIC-09-04, 2009, http://wpweb2.tepper.cmu.edu/ceic/papers/ceic-09-04.asp.

38

For additional information on power plant costs see CRS Report RL34746, Power Plants: Characteristics and Costs,

by (name redacted).

39

Telephone conversation with Dan Rastler, EPRI, August 27, 2009.

40

Dr. Robert B. Schainker, EPRI, “Emerging Technologies to Increase Penetration and Availability of Renewables:

Energy Storage – Executive Summary,” presentation, California Energy Commission Integrated Energy Policy

Workshop, July 31, 2008, slide 3, http://www.swsolartech.com/pdf/EPRI-July2008Report.pdf.

41

In the event of a blackout, generating units that have shut down need an outside source of power to restart. These

emergency generators are referred to as black start units. Examples are diesel generators and some types of combustion

turbines. Storage units might also serve this role.

Congressional Research Service

19

Electric Power Storage

rates and payment arrangements that account for the benefits from EPS. As discussed below, this

regulatory framework is still evolving.

Regulatory Issues

This section begins with a background review of electric power regulation in the United States,

and then discusses regulatory issues as they pertain to electric power storage.42

Regulatory Background

The regulation of electric power in the United States is a patchwork quilt of federal and state

authorities. The most important distinction to make is between traditional and restructured state

markets. As explained by DOE, in the many states that continue to operate traditional markets,

many investor-owned utilities (IOUs), municipal, and cooperative utilities:

still provide electric service under a traditional vertically integrated business model, owning

and operating generation, transmission, and distribution facilities and measures while selling

“bundled” retail service to their end-use consumers. These utilities provide retail service

under a “cost-of-service” model; thus, their rates reflect their costs of providing service plus

a reasonable return (or in the case of not-for-profit co-ops and public power systems, a

financial reserve).43

In these traditional markets, allowable costs, retail rates, and operating practices are monitored

and controlled by a state public utility commission. New investments, such as in power plants,

power lines, or EPS facilities, must be approved by the state commission. Traditional regulation

continues to be predominant in the Southeast, Northwest, and other western states outside of

California.

Beginning in the 1990s, restructured markets developed in many states in the Northeast, New

England, much of the Midwest, Texas, and California.44 For the most part these were areas with

high electric prices where the state governments concluded that introducing more competition

into the power markets could drive down rates and improve service.

There is no standard form of restructured market, but some typical elements include:

•

Vertically integrated utilities sold their power plants to independent power

producers. The utilities are now “wires” companies that buy power wholesale

from the generating companies.

42

A full discussion of the competitive restructuring of the electric power market is beyond the scope of this report. For

summaries of these developments, see The Electricity Advisory Committee, Keeping the Lights on in a New World,

U.S. Department of Energy, Washington, DC, January 2009, sections 1.7 to 1.10, http://www.oe.energy.gov/eac.htm;

and Federal Energy Regulatory Commission, Order No. 890, Final Rule, issued February 16, 2007, pp. 6-21,

http://www.ferc.gov/legal/maj-ord-reg.asp.

43

DOE, Electric Advisory Committee, Keeping the Lights on in a New World, January 2009, p. 20,

http://www.oe.energy.gov/DocumentsandMedia/adequacy_report_01-09-09.pdf.

44

The American Public Power Association (APPA) website maintains state-by-state information on power market

regulation; see http://www.appanet.org/aboutpublic/staterestructurlist.cfm.

Congressional Research Service

20

Electric Power Storage

•

Wholesale electricity prices not covered by contracts are set daily or hourly by a

bidding process managed by a centralized market maker, the regional

transmission organization (RTO).

•

The RTO also establishes market rules and tariffs generally, including tariffs for

setting the prices of “ancillary services” such as voltage regulation and spinning

reserve. RTOs also take over operation of the transmission network in a region or

large state, although utilities continue to own their systems, and set rules for how

the grid is managed. 45

In the restructured markets, state commissions continue to set the framework for retail rates. But

since these rates must reflect, at least over the long term, the wholesale cost of power, consumers

are more exposed to market fluctuations than in traditional states. Additionally, because RTO

markets set wholesale prices based on the marginal—that is, highest cost—bid, consumers in

restructured states pay rates that reflect these marginal prices rather than the retail rates based on

average costs that are set by commissions in traditional markets.

Both the traditional and restructured markets are subject, in important respects, to federal

regulation. Wholesale electricity rates and transmission rates are under the aegis of FERC.

Although FERC has moved over the years from cost-of-service regulation to encouraging marketbased rates, the operation of these markets, if not individual rates and prices, remains tightly

regulated. All tariffs for market-based rates, other rules and regulations of RTOs, and generally

any activity by RTOs and jurisdictional utilities that impact operation of the interstate power

markets require FERC approval. 46

Power Market Regulation and Electric Power Storage

Restructured and traditional power markets pose different challenges to EPS projects.

Restructured markets by design expose and put a price on the multiple services that compose the

power market, including the ancillary services that storage can provide, such as regulation and

spinning reserve. This can allow storage projects, which can be expensive, to exploit multiple

revenue streams. The constantly changing market prices in restructured markets also provide

additional opportunities to use EPS for price arbitrage. Countering these advantages, restructured

markets operate using complex rules that have probably not been designed to accommodate the

specific characteristics of electricity storage, such as the ability of a single facility to serve

transmission and generation functions or the short discharge duration of some storage

technologies.

45

RTOs also ensure open access to the grid, coordinate transmission planning, establish mechanisms to pay for new

transmission lines. and in some cases operate capacity markets which arrange for new power plants to be built. Similar

in function to RTOs are independent system operators (ISOs) and the terms are sometimes used interchangeably.

However, the only ISOs to be qualified as RTOs under the terms of FERC’s Order 2000 are ISO-New England, PJM,

the Midwest ISO, and the SPP RTO.

46

This said, the scope of FERC’s authority is primarily limited to IOUs located outside of Texas, Alaska, and Hawaii.

FERC does not have economic regulatory authority over public power entities, most cooperatives, and most of Texas.

(Most of Texas is covered by the ERCOT RTO. The entities which eventually formed ERCOT severed non-emergency

connections with outside grids in August 1935, when the Federal Power Act became effective, in order to avoid falling

under the ratemaking jurisdiction of the Federal Power Commission (FERC’s predecessor) by maintaining a purely

intrastate system.) The primary exception to these limitations is FERC’s authority over the reliability of the bulk power

system, which covers the entire contiguous United States.

Congressional Research Service

21

Electric Power Storage

An example of the regulatory complications that can ensnare EPS projects is the Lake Elsinore

Advanced Pumped Storage (LEAPS) project, a rare case of a proposed new HPS facility. In 2006

FERC designated LEAPS as an advanced transmission technology, but the California ISO

(CAISO, the organization that runs the power market in most of the state) concluded it should be

treated as a generating unit. This ruling was eventually upheld by FERC, “effectively leaving

[the] storage [project] in a state of limbo.”47

It may seem odd that an HPS project, using the one storage technology with a long track record,

should fall between the cracks in the regulatory system. However, HPS projects were for the most

part constructed years ago in a different and much simpler regulatory environment, and although

the technology has been used for decades the handful of HPS facilities has not produced an

extensive or definitive set of regulatory precedents.48 The quandary is summarized by one

analysis:

Transmission owners with assets managed by independent system operators (ISO) can't put

storage assets in their [regulated] rate base, because those assets also provide [deregulated]

generation services. Similarly, distribution utilities frequently can't justify the cost of energy

storage only on the basis of its distribution-system benefits. And generation companies

struggle to make energy storage pay off, because the market hasn't yet developed bilateral

contracts that value the full range of energy storage services.49

In 2008 and 2009, RTOs began to change their rules, procedures, and operating software systems

to account for electricity storage. ISO New England, the New York ISO, and the Midwest ISO

(MISO) have all adopted temporary or permanent rules changes to facilitate the use of EPS for

regulation services.50 However, these changes do not address other storage services or the

potential contribution of large-scale storage projects. For example, one power company has asked

FERC to require MISO to begin discussing “with stakeholders potential modifications to its Tariff

or business practices to allow the incorporation of the long-term storage technologies.”51 In a

development that may prove significant, a FERC commissioner stated in July 2009 that the

agency is exploring whether to adopt a national EPS pricing policy that would address such issues

as the ability of storage devices to act as both generation and transmission facilities.52

Traditional markets, where rates for vertically integrated utilities are set for a bundle of services

by state utility commissions, present a simpler but still problematic environment for storage

projects. Because in these markets separate prices are often not exposed for individual services,

47

Michael T. Burr, “Storage Goes Mainstream,” Public Utilities Fortnightly, April 2009, p. 28. This project is also

dealing with other legal and financial challenges; see the grand jury report and reply at http://www.evmwd.com/depts/

admin/public_affairs/leaps/informational_materials.asp.

48

Electricity Advisory Committee, DOE, Bottling Electricity: Storage as a Strategic Tool for Managing Variability

and Capacity Concerns in the Modern Grid, December 2008, p. 15, http://www.oe.energy.gov/DocumentsandMedia/

final-energy-storage_12-16-08.pdf.

49

Michael T. Burr, “Storage Goes Mainstream,” Public Utilities Fortnightly, April 2009, p. 27.

50

Craig Cano, “ISO-NE Can Conduct Pilot To Get Regulation Services From New, Alternative Technologies,” Platts

Inside FERC, September 22, 2008; Lisa Lawson, “NYISO Seeks Tariff Revisions to Integrate Energy Storage

Technologies into Market,” Platts Inside FERC, March 23, 2009; Craig Cano, “MISO Files Further Revisions to Make

Better Use of Stored Energy Resources,” Platts Inside FERC, May 18, 2009;

51

Motion to Intervene and Comments of Xcel Energy Services Inc., Before the Federal Energy Regulatory

Commission, Docket No. ER09-1126-000, June 2, 2009, p. 16 (available through FERC docket search at

http://elibrary.ferc.gov/idmws/docket_search.asp).

52

“FERC Examining First-Ever Comprehensive Storage Pricing Policy,” Energy Washington Week, July 29, 2009.

Congressional Research Service

22

Electric Power Storage

such as spinning reserve, it can be difficult to decide how to value a storage project. EPS may

also compare unfavorably with alternative technologies with more cost and technical certainty.

For example, quick-start combustion turbines are a mature technology that can be used for

spinning reserve, regulation, and black start. They do not have other capabilities that storage can

provide, such as price arbitrage, but this may be outweighed in the eyes of utility commissions by

the fact they are known commodities. One utility executive said that:

“if the cost of that [electricity storage] solution for now is 30% higher than a traditional

solution, then you've got to have a willingness on the part of regulators or governmental

agencies to either go ahead and put things in rate base that are a little more expensive for

now, knowing that what we're doing is incubating a new technology.” Alternatively,

incentives must be found “that enable you to make up that cost differential—in the case of

storage it seems like it's coming up around 30%.”53

On the other hand, utility commissioners may be reluctant to spend ratepayer money on what they

view as technological experiments. Another consideration are the economic incentives utilities

face in traditional markets. In these markets the allowed rate of return is in part a function of the

size of the utility’s “rate base”—that is, the amount of capital invested in plant and equipment.

Other things being equal, the larger a utility company’s capital investments the more money it

will be allowed to earn in rates. This incentive can make public utility commissions skeptical of

utility plans to invest in expensive new technologies.

Transmission Planning as an Institutional Issue

Many analysts have identified a need to expand the national transmission system. The objectives

of system expansion include renewable energy development, transmission line congestion relief,

and reliability improvement. 54 Proposals for how to plan and implement transmission grid

expansion can be categorized as follows:

•

National transmission “interstate highway” system. This concept envisions

multi-billion-dollar development of a new network of high-voltage transmission

lines spanning the continent. Planning has not proceeded past general concepts.55

•

Major interregional projects. These projects involve long-distance, interregional

transmission construction, though not at the scale of the national system

discussed above. 56

•

Regional development. This concept would rely on local and nearby renewable

resources rather than distant resources. An example is serving Northeastern

53

Larry Dickerman, director of AEP's distribution engineering services, quoted in Paul Ciampoli, “AEP Executive

Urges Attention To Systemic Benefits, ‘Game Changing’ Potential Of Storage” Platts Electric Utility Week, February

23, 2009.

54

For additional information see CRS Report R40511, Electric Power Transmission: Background and Policy Issues, by

(name redacted).

55

For alternative views of this concept see Bracken Hendricks, Center for American Progress, Wired for Progress:

Building a National Clean-Energy Smart Grid, February 2009, http://www.americanprogress.org/issues/2009/02/pdf/

electricity_grid.pdf; and Kevin Bullis, “A Costly and Unnecessary New Electricity Grid,” Technology Review, July 14,

2009, http://www.technologyreview.com/energy/22997/.

56

An example is the Joint Coordinated System Plan proposal for developing a new network of transmission lines to

move wind power from the Midwest to the Northeast and Southeast; see http://www.jcspstudy.org/.

Congressional Research Service

23

Electric Power Storage

demand for renewable power with PV generation, off-shore wind farms, and

hydroelectric power imports from Quebec.

•

Integrated Solutions. This approach aims to give full attention to nontransmission and non-generation alternatives, in addition to large-scale

transmission projects. These alternatives include small-scale transmission

projects, local renewable resources, demand response and energy efficiency, and

EPS. Although this is the most comprehensive planning approach, it also makes

transmission planning into something much more akin to development of a

complete electric system plan for a region. Integrated planning implies

involvement of a large range of stakeholders, complex analyses, consideration of

long-term economic objectives, and perhaps a time-consuming process.

Electricity storage potentially fits into all of these approaches to transmission planning, but in

perhaps different ways. For example, large centralized storage facilities might play a role in

national or regional transmission projects intended to bring large amounts of wind power from the

northern plains to cities; distributed storage could be used in the regional planning approaches.

But one question is to what extent will EPS be considered at all.

These varying approaches to transmission planning reflect major divides in views of the future of

the power system. One divide is between those who believe that major, long-distance

transmission development is unavoidable, largely to access new sources of renewable power, and

the alternative view that local resource development can obviate much of the need for new

transmission lines. A second, perhaps even more fundamental divide, is between traditional utility

approaches to resolving power systems issues—which focus on central station power plants and

large transmission projects—and new approaches which rely on diverse resources. EPS is an

example of an alternative resource that does not fit easily into the traditional utility paradigm.

This is in part because many storage technologies are distributed rather than centralized, and in

part because single storage technologies can serve multiple purposes—it is a peg that fits into

several holes, round and square, of different sizes.

Which transmission planning approach—or approaches—are ultimately adopted will be the result

of policy decisions informed by many technical, cost, and political considerations. The degree to

which EPS plays a role in these planning decisions and planning processes may be influenced in

part by federal policy, as discussed in the next section of the report.

Issues for Congressional Consideration

As noted above, EPS faces regulatory, economic, and institutional barriers to widespread

acceptance. This concluding section of the report discusses oversight and legislative approaches

to addressing these barriers that may be of interest to Congress.

Industry and Regulator Acceptance of Storage

Electricity storage is one of several technologies and methods of meeting power demand that are

of current congressional interest (including distributed generation, renewable power, and demand

Congressional Research Service

24

Electric Power Storage

response57) which do not fit the traditional power industry paradigm. That paradigm involves

reliance on large-scale central power plants and long-distance transmission lines to meet demand.

As noted above, this raises the question of how quickly and effectively the power industry and its

federal and state regulators will be willing to pursue and deploy new approaches that are costeffective. 58 A DOE study sums up the adoption issue:

A utility that is guaranteed [by regulators] to receive cost recovery of either a transmission or

generation project, or both, may have little incentive to put an energy storage project in

place. Rather than invest in energy storage technology, a utility may simply opt to construct

a transmission and/or generation facility, the costs of which are more likely to be approved

and recovered. In addition, state utility regulators may be reluctant to allow cost recovery for

an innovative energy storage technology. State utility regulators may instruct the utility to

rely on proven technology to address issues that could be solved through energy storage

technology. 59

As discussed above, efforts are underway at the state and federal level to address the regulatory

issues. But because utility regulation is decentralized in the United States, this is likely to be a

lengthy process that Congress may want to monitor.

Executive Agency Focus

Another possible issue for congressional oversight is whether executive agencies are taking

appropriate cognizance of EPS in studies and actions. This is part of the larger issue of whether

executive agencies, like their counterparts in industry and the states, are considering the full range

of non-traditional solutions (when they are cost-effective) to power systems needs.

Two recent studies of electric power issues, one by DOE and another by FERC, illustrate

potential oversight issues. In 2008 DOE published 20% Wind Energy by 2030: Increasing Wind

Energy’s Contribution to U.S. Electricity Supply, a major study that “examines some of the costs,

challenges, and key impacts of generating 20% of the nation’s electricity from wind energy in

2030.”60 A major issue in integrating large amounts of wind capacity into the power system is the

variability of wind power. Large-scale wind integration requires steps to compensate for the times

when wind power is either reduced or unavailable due to weather conditions. To date this has not

57

Demand response involves creating incentives or controls that cause the demand for power to change in response to

power prices and/or availability. It reverses the historical method of operating a power system, in which power plant

output response to changes in demand. Demand response in the industrial and commercial sectors in a growing

resource available to grid operators in some parts of the country, and the smart grid is seen as the technological

component that may be necessary to bring demand response to the residential sector. The issue is complex and

somewhat controversial when proposed demand response programs involve changes to utility economic incentives and

residential rates.

58

While utilities and their regulators are sometimes described as technically conservative organizations, the level of

conservatism seems, at least in some cases, to have more to do with how far a new approach varies from traditional

operating practices than how new the technology is. An example is how readily much of the power industry and its

regulators adopted nuclear power in the 1960s and 1970s. The technology fit the central station paradigm, but it was

largely untested and proved to be vastly more expensive and operationally challenging than expected.

59

Electricity Advisory Committee, DOE, Bottling Electricity: Storage as a Strategic Tool for Managing Variability

and Capacity Concerns in the Modern Grid, December 2008, p. 16, http://www.oe.energy.gov/DocumentsandMedia/

final-energy-storage_12-16-08.pdf.

60

DOE, 20% Wind Energy by 2030: Increasing Wind Energy’s Contribution to U.S. Electricity Supply, July 2008, p.2,

http://www1.eere.energy.gov/windandhydro/pdfs/41869.pdf.

Congressional Research Service

25

Electric Power Storage

been a major issue because few areas have sufficient wind power to create integration issues, but

this is expected to change in the future.

The conventional approach to wind integration is to install quick-start natural gas-fired

combustion turbine power plants to back up wind power. Other options that have been proposed

include geographic dispersion of wind farms, improved wind power forecasting techniques,

implementation of demand response and smart grid technologies and procedures, aggregation of

utility control areas, and EPS. However, DOE’s study essentially disregards the EPS option. 61

There is no unanimity of opinion on the extent to which EPS will be needed, if at all, to integrate

large amounts of wind and other renewable power capacity into the grid. The American Wind

Association, for example, believes that electricity storage is too costly and is unnecessary for

wind integration.62 However, this opinion is not universally held. For example, a recent North

American Electric Reliability Corp. (NERC)63 study of renewable integration concluded that

“Additional flexible resources, such as demand response, plug-in hybrid electric vehicles, and

storage capacity, e.g., compressed air energy storage (CAES), may help to balance the steep

ramps associated with variable generation.”64 A white paper issued by the American Society of

Chemical Engineers concluded that large-scale electricity storage “is the critical technology

needed by renewable power if it is to become a major source of baseload dispatchable power to

eventually replace fossil/nuclear plants.”65 The chief of the PJM Interconnection, the operator of

the power grid in much of the Middle Atlantic and Midwest, believes that 1,000 MW or more of

CAES will be needed on the PJM system to support growing wind capacity, and two utilities in

California have recently announced proposed CAES and battery projects to facilitate wind power

integration.66 With this diversity of opinions, it is unclear why the DOE study would not take

more cognizance of options like EPS and demand response as part of the suite of tools available

to integrate wind into the power system.

Another example of a perhaps narrow agency focus is a recent FERC study, A National

Assessment of Demand Response Potential. 67 In response to a mandate included in the Energy

61

The DOE study’s brief discussion of storage is on pages 80 and 81. The modeling performed for the study could

incorporate only storage located at a wind plant site, by some estimates an inefficient and expensive approach (Jeff

Anthony, American Wind Energy Association, “Wind Energy & Energy Storage,” Platts Power Storage Conference,

Las Vegas, NV, June 15, 2009, slide 29; Jonathan Fahey, “Hold that Electron!,” Forbes, November 24, 2008), and it is

not clear if this option was actually implemented in the model runs (see the DOE report, page 191). Demand response

is not mentioned in the DOE report and the smart grid is discussed only in passing.

62

Jeff Anthony, American Wind Energy Association, “Wind Energy & Energy Storage,” Platts Power Storage

Conference, Las Vegas, NV, June 15, 2009, slide 38. For a similar perspective see National Academies, Electricity

From Renewable Resources, prepublication copy, 2009, pp. 78, 79, and 84. On the notion that wind power may be

more suitable for storage than solar power see http://energyoutlook.blogspot.com/2009/03/storing-sunlight.html.

63

NERC is an industry association that has been designated by FERC as the official electric reliability organization for

the United States.

64

NERC, Accommodating High Levels of Variable Generation, April 2009, p. iii, http://web.ta-alberta.ca/downloads/

IVGTF_Report_041609(1).pdf.

65

Bernard Lee and (name redacted), American Institute of Chemical Engineers White Paper,Massive Electricity Storage,

June 2008, pp. 2-3, http://www.aiche.org/uploadedFiles/About/DepartmentUploads/PDFs/

MES%20White%20Paper%20submittal%20to%20GRC%206-2008.pdf.

66

Jeff Ryser, “Electricity Storage Technology Moves Forward with Support by Grid Operators,” Platts Electric Utility

Week, April 6, 2009; Tracy Seipel, “PG&E to Build Plant to Store Wind Energy,” San Jose Mercury News, August 27,

2009; Poornima Gupta, “Utility Wants To Deploy Largest Grid Battery Ever,” Reuters, August 26, 2009,

http://www.reuters.com/article/GCA-GreenBusiness/idUSTRE57P4PJ20090826.

67

FERC, A National Assessment of Demand Response Potential, June 2009, http://www.ferc.gov/legal/staff-reports/06(continued...)

Congressional Research Service

26

Electric Power Storage

Independence and Security Act of 2007,68 the report assesses the demand response potential, state

by state, for the period 2010 through 2019. The estimates are made for several scenarios which

incorporate varying levels of technological advancements and changes to rate structures,

including:

•

Dynamic rates, in which the rates charged for electricity vary daily or in real time

to reflect wholesale power prices and scarcity in electricity supplies. This is a

substantial departure from the average price rates typically charged to residential

customers.

•

Dynamic rates combined with “enabling technologies” that automatically

respond to high power prices by reducing a home’s electricity demand.

•

Direct load control of consumer equipment, such as air conditioners, by the

utility.

•

Interruptible tariffs, in which large industrial and commercial customers agree to

reduce demand under certain conditions in return for a financial incentive.

•

Other programs aimed at reducing demand as needed from large industrial and

commercial customers.

Some of these approaches to demand response are currently routine or can be easily implemented,

such as interruptible tariffs and direct load control. Dynamic rates, as noted, would represent a

substantial change for residential customers and have been controversial. 69 The enabling

technologies that can augment dynamic rates have been pilot tested at a residential scale but not

widely deployed. Depending on the scenario, the study assumes up to universal installation of

smart meters, 60% to 70% customer participation in dynamic pricing, and 60% of customers

using enabling technologies.70

A potential oversight issue is whether FERC has been unnecessarily restrictive in the choice of

technologies and options it examined for reducing and shifting peak demands (a central goal of

demand response programs). The report states that:

Other examples [of currently high-cost options] include battery storage and thermal energy

storage. Both items hold the potential to significantly reduce peak demand on a permanent

basis by shifting it to off-peak periods. As in the case of photovoltaic arrays, cost is a

significant barrier to their rapid market penetration today. Another example is behind-themeter generation which includes a diverse set of technologies including small conventional

generation units that are used as back-up generation during emergencies and cogeneration

systems that combine heat and power, largely in industrial process applications.71

(...continued)

09-demand-response.pdf.

68

P.L. 110-140, section 529.

69

Tom Tiernan, “Utilities Sometimes in the Middle as Enthusiasm, Wariness Circle Each Other in Smart Grid Push,”

Platts Electric Utility Week, November 3, 2008.

70

An additional scenario assumes, for example, mandatory dynamic pricing for all customers, but this scenario is used

simply to determine the hypothetical upper limit of energy savings from demand response.

71

FERC, A National Assessment of Demand Response Potential, June 2009, p. 48, http://www.ferc.gov/legal/staffreports/06-09-demand-response.pdf.

Congressional Research Service

27

Electric Power Storage

It is not clear why universal roll-out of smart meters (itself a multi-billion-dollar expense),

widespread deployment of thermostats that respond to power prices, or large-scale

implementation of dynamic pricing (a ratemaking approach currently almost unknown in the

residential sector) would be more likely than deployment of EPS systems by 2019. Also unclear is

the treatment of distributed generation—which in the industrial and commercial sectors has been

used routinely for decades72—as a developmental option.

FERC perhaps had to limit the range of options it could consider in its demand response report,

but this study and the DOE wind report also reflect the risks of not giving fuller attention to the

full range of options available to meet power system needs. As discussed below, two major pieces

of proposed legislation before the 111th Congress both treat EPS as a demand response option for

managing peak loads. To the degree that Congress is interested in the advancement of EPS

technology, it may want to monitor how this option is being considered in agency studies and

programs.

Current Legislation and Incentives

This section of the report reviews the treatment of electric power storage in three current

legislative proposals:

•

S. 1091, the Storage Technology of Renewable and Green Energy Act of 2009

(STORAGE Act).

•

H.R. 2454, the American Clean Energy and Security Act of 2009 (ACES).

•

S. 1462, the American Clean Energy Leadership Act of 2009 (ACELA).

This section also summarizes the financial incentives available to EPS projects in the American

Recovery and Reinvestment Act of 2009 (ARRA; P.L. 111-5).

STORAGE Act

The STORAGE Act would amend the tax code to create incentives for EPS deployment. These

incentives include:

•

A 20% business investment tax credit for investments in EPS systems that deliver

stored power for sale, and have a minimum output capacity of 0.5 MW during a

four-hour delivery period.

•

A 20% business investment tax credit for investments in EPS systems located at

the consumer site, and used primarily to store and deliver renewable energy

generated onsite that is used to reduce onsite peak power demand. These can be

small systems: the minimum required output is five kilowatts during a four-hour

delivery period.

72

The predominant form of distributed generation is combined heat and power, also referred to as cogeneration. For

more information see Oak Ridge National Laboratory, Combined Heat and Power: Effective Energy Solutions for a

Sustainable Future, December 1, 2008, http://www1.eere.energy.gov/industry/distributedenergy/.

Congressional Research Service

28

Electric Power Storage

•

A 30% residential tax credit for an EPS system installed in a home, and used

primarily to store and deliver renewable energy generated onsite that is used to

reduce onsite peak power demand. No minimum size requirements are specified.

•

The bill would allow government and cooperative power agencies to issue Clean

Renewable Energy Bonds73 for storage projects.

The STORAGE Act was introduced on May 20, 2009, and referred to the Finance Committee. As

of late August 2009 no further action had been taken on the bill.

ACES and ACELA

ACES is a climate change and energy policy act passed by the House on June 26, 2009, and

referred to the Senate. 74 Many of the objectives of the bill, including increased use of renewable

power, peak demand reductions, and reductions in carbon emissions, might be facilitated by costeffective EPS. With respect to transmission planning, the bill would establish a national

transmission planning policy that takes:

into account all significant demand-side and supply-side options, including energy

efficiency, distributed generation, renewable energy and zero-carbon electricity generation

technologies, smart-grid technologies and practices, demand response, electricity storage,

voltage regulation technologies, high capacity conductors … superconductor technologies,

underground transmission technologies, and new conventional electric transmission capacity

and corridors.75

The bill’s peak demand reduction section also specifies EPS as one of the technologies that can be

used to meet reduction goals. 76

ACELA is an energy bill that was introduced on July 16, 2009, when it was reported out of the

Senate Energy Committee. The bill includes a peak reduction and load shifting goal that would be

met through the “widespread implementation” of several demand response technologies,

including dynamic pricing, smart grid technology, distributed generation, and electricity storage. 77

The bill would also establish a multi-faceted national transmission policy. The first principle

listed is “support for the development of new renewable energy generation capacity,” but there

are numerous other objectives, including cost savings, reliability enhancement, reduced power

plant emissions, and maximizing “the contribution of demand side management (including energy

efficiency and demand response), energy storage, distributed generation resources, and smart grid

investments.” Transmission planning would be required to reflect these policy objectives. 78

Both ACES and ACELA therefore anticipate transmission planning processes that would take the

integrated approach discussed earlier in this report. Both bills also include electricity storage

73

For more information on this bond program see http://www.dsireusa.org/incentives/incentive.cfm?Incentive_Code=

US45F&re=1&ee=1.

74

For more information on ACES see CRS Report R40643, Greenhouse Gas Legislation: Summary and Analysis of

H.R. 2454 as Passed by the House of Representatives, coordinated by (name redacted) and (name redacted).

75

H.R. 2454, Title I, Subtitle F, section 151.

76

H.R. 2454, Title I, Subtitle D, section 295.

77

S. 1462, Title II, Subtitle D, section 295.

78

S. 1462, Title I, Subtitle B, section 121.

Congressional Research Service

29

Electric Power Storage

among the demand response technologies that can be used to meet goals for reducing peak

demand. If either bill becomes law, Congress may want to monitor whether storage and other

non-traditional approaches actually receive appropriate attention from industry, regulators, and

executive agencies.

The American Recovery and Reinvestment Act of 2009 (ARRA; P.L. 111-5) added or expanded

funding and incentives for electricity storage. 79 However, many of the programs seem to be

focused primarily on one application, battery technology for pure electric and plug-in hybrid

electric vehicles. 80

•

ARRA provides $6.0 billion that is expected to leverage more than $60 billion in

federal loan guarantees for transmission grid construction that supports

renewable energy projects. These guarantees can presumably be used to support

applicable EPS projects. This new loan guarantee program expands the existing

innovative technology loan guarantee program created by the Energy Policy Act

of 2005 (EPACT05).81 Although the EPACT05 program is limited to supporting

“pre-commercial” innovative technology, the new program can also support

commercial technology. Qualifying projects must be capable of starting

construction no later than September 30, 2011.

•

ARRA provides $300 million for a Department of Defense “Near Term Energy

Efficiency Technology Demonstrations and Research” program. According to the

conference committee report, electricity storage is one of the applications to

which this money can be applied.82

•

The act provides $4.5 billion to DOE’s Office of Electricity Delivery and Energy

Reliability for grid modernization and related technologies, such as electricity

storage. 83

•

The law establishes a tax credit that can be used to re-equip, expand, or establish

a facility that is designed to manufacture equipment that is used to produce, for

example, electricity storage systems for electric/hybrid vehicles, renewable

energy systems, fuel cells, and other specified technologies. The law allows for

up to $2.3 billion in credits. 84

•

ARRA establishes a new program of $2.0 billion for facility funding grants to

manufacturers of advanced battery and battery system components. Covered

activities include the production of lithium ion batteries, hybrid electrical

systems, system components, and software.85

79

For additional information see CRS Report R40412, Energy Provisions in the American Recovery and Reinvestment

Act of 2009 (P.L. 111-5), coordinated by (name redacted).

80

On August 5, 2009, President Obama announced $2.4 billion in ARRA grants to “accelerate the development of U.S.

manufacturing capacity for batteries and electric drive components as well as the deployment of electric drive

vehicles.” For more information see the DOE press release at http://www.energy.gov/news2009/7749.htm.

81

For further information on the loan guarantee program see 42 USC §16511 et seq and the DOE website at

http://www.lgprogram.energy.gov/. The $6 billion in funding would be directed to renewables and transmission by a

new section 1705 added to EPACT05.

82

P.L. 111-5, Division A, Title III; and H.Rept. 111-16, pp. 422-423.

83

P.L. 111-5, Division A, Title IV.

84

P.L. 111-5, Division B, Title I, Subtitle D, section 1302.

85

P.L. 111-5, Division A, Title IV.

Congressional Research Service

30

Electric Power Storage

•

ARRA modifies an existing tax credit for the purchase of new plug-in vehicles

(plug-in hybrids and pure electric vehicles) to cap the per-vehicle credit at $7,500

for light-duty vehicles and heavy-duty vehicles up to 14,000 pounds gross

weight. 86

•

The law adds $2.4 billion to an existing $800 million Energy Conservation Bond

program. The bonds can be applied to many purposes, including advanced

automobile batteries and advanced battery manufacturing technology. 87

To the extent that Congress is interested in widespread adoption of cost effective EPS

technologies, it may want to oversee the extent to which these incentives are committed to

electricity storage devices other than vehicle battery systems.

Author Contact Information

(name redacted)

Specialist in Energy and Environmental Policy

[redacted]@crs.loc.gov, 7-....

86

87

P.L. 111-5, Division B, Title I, Subtitle B.

P.L. 111-5, Division B, Title I, Subtitle B.

Congressional Research Service

31

EveryCRSReport.com

The Congressional Research Service (CRS) is a federal legislative branch agency, housed inside the

Library of Congress, charged with providing the United States Congress non-partisan advice on

issues that may come before Congress.

EveryCRSReport.com republishes CRS reports that are available to all Congressional staff. The

reports are not classified, and Members of Congress routinely make individual reports available to

the public.

Prior to our republication, we redacted names, phone numbers and email addresses of analysts

who produced the reports. We also added this page to the report. We have not intentionally made

any other changes to any report published on EveryCRSReport.com.

CRS reports, as a work of the United States government, are not subject to copyright protection in

the United States. Any CRS report may be reproduced and distributed in its entirety without

permission from CRS. However, as a CRS report may include copyrighted images or material from a

third party, you may need to obtain permission of the copyright holder if you wish to copy or

otherwise use copyrighted material.

Information in a CRS report should not be relied upon for purposes other than public

understanding of information that has been provided by CRS to members of Congress in

connection with CRS' institutional role.

EveryCRSReport.com is not a government website and is not affiliated with CRS. We do not claim

copyright on any CRS report we have republished.

This is a copy of a public record, reproduced as it was published. It is not legal advice, and it may not be the version a court would rely on. Check the official source before you cite it.

A word about cookies

We need a few to keep you signed in and the library working. The rest help us see which pages people use and where they get stuck. They stay off unless you say yes.