- **Location:** Title 49—Transportation > Subtitle B—Other Regulations Relating to Transportation > CHAPTER I—PIPELINE AND HAZARDOUS MATERIALS SAFETY ADMINISTRATION, DEPARTMENT OF TRANSPORTATION > SUBCHAPTER D—PIPELINE SAFETY > PART 193—LIQUEFIED NATURAL GAS FACILITIES: FEDERAL SAFETY STANDARDS > Subpart B—Siting Requirements

## Text

Each LNG container and LNG transfer system must have a thermal exclusion zone in accordance with section 2.2.3.2 of NFPA-59A-2001 (incorporated by reference, see § 193.2013) with the following exceptions:
(a) The thermal radiation distances must be calculated using Gas Technology Institute's (GTI) report or computer model GTI-04/0032 LNGFIRE3: A Thermal Radiation Model for LNG Fires (incorporated by reference, see § 193.2013). The use of other alternate models which take into account the same physical factors and have been validated by experimental test data may be permitted subject to the Administrator's approval.
(b) In calculating exclusion distances, the wind speed producing the maximum exclusion distances shall be used except for wind speeds that occur less than 5 percent of the time based on recorded data for the area.
(c) In calculating exclusion distances, the ambient temperature and relative humidity that produce the maximum exclusion distances shall be used except for values that occur less than five percent of the time based on recorded data for the area.
[Amdt. 193-17, 65 FR 10958, Mar. 1, 2000, as amended by Amdt. 193-18, 69 FR 11336, Mar. 10, 2004; Amdt. 193-22, 75 FR 48604, Aug. 11, 2010; Amdt. 193-25, 80 FR 182, Jan. 5, 2015]

## Nearby sections

- [49 CFR § 193.2001 § 193.2001 Scope of part.](https://www.frixlaw.com/law-library/statutes/ecfr-49-193.2001.md)
- [49 CFR § 193.2005 § 193.2005 Applicability.](https://www.frixlaw.com/law-library/statutes/ecfr-49-193.2005.md)
- [49 CFR § 193.2007 § 193.2007 Definitions.](https://www.frixlaw.com/law-library/statutes/ecfr-49-193.2007.md)
- [49 CFR § 193.2009 § 193.2009 Rules of regulatory construction.](https://www.frixlaw.com/law-library/statutes/ecfr-49-193.2009.md)
- [49 CFR § 193.2011 § 193.2011 Reporting.](https://www.frixlaw.com/law-library/statutes/ecfr-49-193.2011.md)
- [49 CFR § 193.2013 § 193.2013 What documents are incorporated by reference partly or wholly in this part?](https://www.frixlaw.com/law-library/statutes/ecfr-49-193.2013.md)
- [49 CFR § 193.2017 § 193.2017 Plans and procedures.](https://www.frixlaw.com/law-library/statutes/ecfr-49-193.2017.md)
- [49 CFR § 193.2019 § 193.2019 Mobile and temporary LNG facilities.](https://www.frixlaw.com/law-library/statutes/ecfr-49-193.2019.md)
- [49 CFR § 193.2051 § 193.2051 Scope.](https://www.frixlaw.com/law-library/statutes/ecfr-49-193.2051.md)
- [49 CFR § 193.2057 § 193.2057 Thermal radiation protection.](https://www.frixlaw.com/law-library/statutes/ecfr-49-193.2057.md)
- [49 CFR § 193.2059 § 193.2059 Flammable vapor-gas dispersion protection.](https://www.frixlaw.com/law-library/statutes/ecfr-49-193.2059.md)
- [49 CFR § 193.2067 § 193.2067 Wind forces.](https://www.frixlaw.com/law-library/statutes/ecfr-49-193.2067.md)
- [49 CFR § 193.2101 § 193.2101 Scope.](https://www.frixlaw.com/law-library/statutes/ecfr-49-193.2101.md)
- [49 CFR § 193.2301 § 193.2301 Scope.](https://www.frixlaw.com/law-library/statutes/ecfr-49-193.2301.md)

---

Source: Frix Law Library, https://www.frixlaw.com/law-library/statutes/ecfr-49-193.2057. Check the current official text before relying on it. Not legal advice.