029(A) Accessibility of conduit bodies and boxes.
(1) Conduit bodies, junction, pull, and outlet boxes must be installed so that the wiring and devices contained in them is accessible without removing any part of the building structure, including insulation material.
023(H) Flexible cord connection of pendant boxes.
(2) The flexible cord and cord connection must comply with NEC 314.23(H) and the following:
(a) A suspended pendant box must not contain conduit "knockouts" and connection to a suspended box must utilize an integral threaded hub;
(b) The maximum length of the cord for a suspended pendant drop from a permanently installed junction box to a suitable tension take-up device above the pendant box must not exceed six feet;
(c) The flexible cord must be supported at each end with an approved cord grip or strain relief connector fitting/device that will eliminate all stress on the conductor connections;
(d) The flexible cord must be a minimum #14 AWG copper;
(e) The flexible cord ampacity must be determined using NEC Table 400.5(A) column A; and
(f) The flexible cord must be hard or extra hard usage.
027(C) Boxes at ceiling-suspended (paddle) fan outlets.
(3) For the purposes of NEC 314.27(C), locations acceptable for the installation of ceiling-suspended (paddle) fans include all ceiling areas of habitable rooms of dwelling occupancies except: Areas within four feet of walls, soffits, or fixed cabinetry; or areas directly above permanently installed island or peninsular countertop surfaces.

## Nearby sections

- [WAC 296-46B-010 WAC 296-46B-010. General](https://www.frixlaw.com/law-library/statutes/STATE_WA_ADC_296_46B_010.md)
- [WAC 296-46B-100 WAC 296-46B-100. General definitions](https://www.frixlaw.com/law-library/statutes/STATE_WA_ADC_296_46B_100.md)
- [WAC 296-46B-110 WAC 296-46B-110. General requirements for electrical installations](https://www.frixlaw.com/law-library/statutes/STATE_WA_ADC_296_46B_110.md)
- [WAC 296-46B-210 WAC 296-46B-210. Branch circuits not over 1,000 volts ac, 1,500 volts dc nominal](https://www.frixlaw.com/law-library/statutes/STATE_WA_ADC_296_46B_210.md)
- [WAC 296-46B-215 WAC 296-46B-215. Feeders](https://www.frixlaw.com/law-library/statutes/STATE_WA_ADC_296_46B_215.md)
- [WAC 296-46B-220 WAC 296-46B-220. Branch circuit, feeder, and service calculations](https://www.frixlaw.com/law-library/statutes/STATE_WA_ADC_296_46B_220.md)
- [WAC 296-46B-225 WAC 296-46B-225. Outside branch circuits and feeders](https://www.frixlaw.com/law-library/statutes/STATE_WA_ADC_296_46B_225.md)
- [WAC 296-46B-230 WAC 296-46B-230. Services](https://www.frixlaw.com/law-library/statutes/STATE_WA_ADC_296_46B_230.md)
- [WAC 296-46B-235 WAC 296-46B-235. Branch circuits, feeders, and services over 1,000 volts ac, 1,500 volts dc nominal](https://www.frixlaw.com/law-library/statutes/STATE_WA_ADC_296_46B_235.md)
- [WAC 296-46B-240 WAC 296-46B-240. Overcurrent protection](https://www.frixlaw.com/law-library/statutes/STATE_WA_ADC_296_46B_240.md)
- [WAC 296-46B-250 WAC 296-46B-250. Grounding and bonding](https://www.frixlaw.com/law-library/statutes/STATE_WA_ADC_296_46B_250.md)
- [WAC 296-46B-300 WAC 296-46B-300. General requirements for wiring methods and materials](https://www.frixlaw.com/law-library/statutes/STATE_WA_ADC_296_46B_300.md)
- [WAC 296-46B-314 WAC 296-46B-314. Outlet, device, pull, and junction boxes; conduit bodies; fittings; and handhole enclosures](https://www.frixlaw.com/law-library/statutes/STATE_WA_ADC_296_46B_314.md)
- [WAC 296-46B-334 WAC 296-46B-334. Nonmetallic-sheathed cable](https://www.frixlaw.com/law-library/statutes/STATE_WA_ADC_296_46B_334.md)

---

Source: Frix Law Library, https://www.frixlaw.com/law-library/statutes/STATE_WA_ADC_296_46B_314. Check the current official text before relying on it. Not legal advice.