# WAC 296-46B-110: WAC 296-46B-110. General requirements for electrical installations

> Washington · Regulations · In force

URL: https://www.frixlaw.com/law-library/statutes/STATE_WA_ADC_296_46B_110

## Section

- **Citation:** WAC 296-46B-110
- **Heading:** WAC 296-46B-110. General requirements for electrical installations
- **Jurisdiction:** Washington
- **Kind:** Regulations
- **Status:** In force
- **Text as of:** August 14, 2026
- **Source:** Compiled text
- **Location:** Washington Administrative Code / Title 296 / Chapter 296-46B / Section 296-46B-110

## Text

003 Examination, identification, installation, use, and listing (product certification) of equipment.
(1) Listed electrical conduit can only be installed and used in accordance with its listing (i.e., as an electrical raceway for electrical conductors). If used as a sleeve for electrical conductors or other listed electrical conduits, the installation of a listed electrical conduit will be assumed to be for use as an electrical raceway and must be installed as allowed by chapter 19.28 RCW and this chapter (e.g., owner exemption, electrical contractor, etc.).
EXCEPTION:
Electrical nonmetallic elbow fittings may be connected to piping other than electrical conduit for the purposes of enclosing mechanical piping systems provided the elbows are distinctively marked to indicate their use as nonelectrical fittings prior to installation. For underground installations outside of buildings, elbows used for purposes other than electrical must be substantially painted to match the color of piping to which they are connected.
011 Deteriorating agents.
(2) Electrical equipment and wiring that has been submerged or exposed to water must comply with the following:
(a) All breakers, fuses, controllers, receptacles, lighting switches/dimmers, electric heaters, and any sealed device/equipment (e.g., relays, contactors, etc.) must be replaced.
(b) All other electrical equipment (e.g., wiring, breaker panelboards, disconnect switches, switchgear, motor control centers, boiler controls, HVAC/R equipment, electric motors, transformers, appliances, water heaters, and similar appliances) must be replaced or reconditioned by the original manufacturer or by its approved representative.
022 Identification of disconnecting means.
st be replaced.
(b) All other electrical equipment (e.g., wiring, breaker panelboards, disconnect switches, switchgear, motor control centers, boiler controls, HVAC/R equipment, electric motors, transformers, appliances, water heaters, and similar appliances) must be replaced or reconditioned by the original manufacturer or by its approved representative.
022 Identification of disconnecting means.
(3) For the purposes of legibly marking a disconnecting means, as required in NEC 110.22, an identification plate is required unless the disconnect is a circuit breaker/fused switch installed within a panelboard and the circuit breaker/fused switch is identified by a panelboard schedule. In other than dwelling units, the identification plate must include the identification designation of the circuit source panelboard that supplies the disconnecting means.
030 Over 1,000 volts - General.
(4) Each cable operating at over 1,000 volts and installed on customer-owned systems must be legibly marked in a permanent manner at each termination point and at each point the cable is accessible. The required marking must use phase designation, operating voltage, and circuit number if applicable.

## Nearby sections

- [WAC 296-46B-010 WAC 296-46B-010. General](https://www.frixlaw.com/law-library/statutes/STATE_WA_ADC_296_46B_010.md)
- [WAC 296-46B-100 WAC 296-46B-100. General definitions](https://www.frixlaw.com/law-library/statutes/STATE_WA_ADC_296_46B_100.md)
- [WAC 296-46B-110 WAC 296-46B-110. General requirements for electrical installations](https://www.frixlaw.com/law-library/statutes/STATE_WA_ADC_296_46B_110.md)
- [WAC 296-46B-210 WAC 296-46B-210. Branch circuits not over 1,000 volts ac, 1,500 volts dc nominal](https://www.frixlaw.com/law-library/statutes/STATE_WA_ADC_296_46B_210.md)
- [WAC 296-46B-215 WAC 296-46B-215. Feeders](https://www.frixlaw.com/law-library/statutes/STATE_WA_ADC_296_46B_215.md)
- [WAC 296-46B-220 WAC 296-46B-220. Branch circuit, feeder, and service calculations](https://www.frixlaw.com/law-library/statutes/STATE_WA_ADC_296_46B_220.md)
- [WAC 296-46B-225 WAC 296-46B-225. Outside branch circuits and feeders](https://www.frixlaw.com/law-library/statutes/STATE_WA_ADC_296_46B_225.md)
- [WAC 296-46B-230 WAC 296-46B-230. Services](https://www.frixlaw.com/law-library/statutes/STATE_WA_ADC_296_46B_230.md)
- [WAC 296-46B-235 WAC 296-46B-235. Branch circuits, feeders, and services over 1,000 volts ac, 1,500 volts dc nominal](https://www.frixlaw.com/law-library/statutes/STATE_WA_ADC_296_46B_235.md)
- [WAC 296-46B-240 WAC 296-46B-240. Overcurrent protection](https://www.frixlaw.com/law-library/statutes/STATE_WA_ADC_296_46B_240.md)
- [WAC 296-46B-250 WAC 296-46B-250. Grounding and bonding](https://www.frixlaw.com/law-library/statutes/STATE_WA_ADC_296_46B_250.md)
- [WAC 296-46B-300 WAC 296-46B-300. General requirements for wiring methods and materials](https://www.frixlaw.com/law-library/statutes/STATE_WA_ADC_296_46B_300.md)
- [WAC 296-46B-314 WAC 296-46B-314. Outlet, device, pull, and junction boxes; conduit bodies; fittings; and handhole enclosures](https://www.frixlaw.com/law-library/statutes/STATE_WA_ADC_296_46B_314.md)
- [WAC 296-46B-334 WAC 296-46B-334. Nonmetallic-sheathed cable](https://www.frixlaw.com/law-library/statutes/STATE_WA_ADC_296_46B_334.md)

---