# S.C. Code Regs. 8-1103: S.C. Code Regs. 8-1103. NEC Article 210.8(A) Dwelling Units

> South Carolina · Regulations · In force

URL: https://www.frixlaw.com/law-library/statutes/STATE_SC_CODEREGS_8_1103

## Section

- **Citation:** S.C. Code Regs. 8-1103
- **Heading:** S.C. Code Regs. 8-1103. NEC Article 210.8(A) Dwelling Units
- **Jurisdiction:** South Carolina
- **Kind:** Regulations
- **Status:** In force
- **Text as of:** August 14, 2026
- **Source:** Compiled text
- **Location:** South Carolina Code of Regulations / Chapter 8 BUILDING CODES COUNCIL / S.C. Code Regs. 8-1103

## Text

All 125-volt receptacles installed in the locations specified in 210.8(A)(1) through (A)(11) and supplied by single-phase branch circuits rated 150 volts or less to ground shall have ground-fault circuit-interrupter protection for personnel.

(1) Bathrooms.

(2) Garages and also accessory buildings that have a floor located at or below grade level not intended as habitable rooms and limited to storage areas, work areas, and areas of similar use.

(3) Outdoors.

Exception to (3): Receptacles that are not readily accessible and are supplied by a branch circuit dedicated to electric snow-melting, deicing, or pipeline and vessel heating equipment shall be permitted to be installed in accordance with 426.28 or 427.22, as applicable.

(4) Crawl spaces — at or below grade level.

(5) Basements

Exception No. 1 to (5): A receptacle supplying only a permanently installed fire alarm or burglar alarm system shall not be required to have ground-fault circuit-interrupter protection.

Exception No. 2 to (5): Receptacles in walk-out basements are excluded from this requirement.

Receptacles installed under the exception to 210.8(A)(5) shall not be considered as meeting the requirements of 210.52(G).

(6) Kitchens — where the receptacles are installed to serve the countertop surfaces.

(7) Sinks — where receptacles are installed within 1.8 m (6 ft) from the top inside edge of the bowl of the sink.

(8) Boathouses.

(9) Bathtubs or shower stalls — where receptacles are installed within 1.8 m (6 ft) of the outside edge of the bathtub or shower stall.
he requirements of 210.52(G).

(6) Kitchens — where the receptacles are installed to serve the countertop surfaces.

(7) Sinks — where receptacles are installed within 1.8 m (6 ft) from the top inside edge of the bowl of the sink.

(8) Boathouses.

(9) Bathtubs or shower stalls — where receptacles are installed within 1.8 m (6 ft) of the outside edge of the bathtub or shower stall.

(10) Laundry areas.

Exception to (1) through (3), (5) through (8), and (10): Listed locking support and mounting receptacles utilized in combination with compatible attachment fittings installed for the purpose of serving a ceiling luminaire or ceiling fan shall not be required to be ground-fault circuit-interrupter protected. If a general-purpose convenience receptacle is integral to the ceiling luminaire or ceiling fan, GFCI protection shall be provided.

(11) Indoor damp and wet locations.

## Nearby sections

- [S.C. Code Regs. 8-105 S.C. Code Regs. 8-105. Definitions](https://www.frixlaw.com/law-library/statutes/STATE_SC_CODEREGS_8_105.md)
- [S.C. Code Regs. 8-110 S.C. Code Regs. 8-110. Registration Required](https://www.frixlaw.com/law-library/statutes/STATE_SC_CODEREGS_8_110.md)
- [S.C. Code Regs. 8-115 S.C. Code Regs. 8-115. Classifications and Qualifications for Registration](https://www.frixlaw.com/law-library/statutes/STATE_SC_CODEREGS_8_115.md)
- [S.C. Code Regs. 8-120 S.C. Code Regs. 8-120. Requirements for Provisional Certification](https://www.frixlaw.com/law-library/statutes/STATE_SC_CODEREGS_8_120.md)
- [S.C. Code Regs. 8-135 S.C. Code Regs. 8-135. Requirements for Special Inspector Registration for Engineer-In-Training](https://www.frixlaw.com/law-library/statutes/STATE_SC_CODEREGS_8_135.md)
- [S.C. Code Regs. 8-140 S.C. Code Regs. 8-140. Renewal](https://www.frixlaw.com/law-library/statutes/STATE_SC_CODEREGS_8_140.md)
- [S.C. Code Regs. 8-145 S.C. Code Regs. 8-145. Fees](https://www.frixlaw.com/law-library/statutes/STATE_SC_CODEREGS_8_145.md)
- [S.C. Code Regs. 8-150 S.C. Code Regs. 8-150. Continuing Education](https://www.frixlaw.com/law-library/statutes/STATE_SC_CODEREGS_8_150.md)
- [S.C. Code Regs. 8-160 S.C. Code Regs. 8-160. Comity](https://www.frixlaw.com/law-library/statutes/STATE_SC_CODEREGS_8_160.md)
- [S.C. Code Regs. 8-165 S.C. Code Regs. 8-165. Conflict of Interest](https://www.frixlaw.com/law-library/statutes/STATE_SC_CODEREGS_8_165.md)
- [S.C. Code Regs. 8-170 S.C. Code Regs. 8-170. Grounds for Disciplinary Action or Denial](https://www.frixlaw.com/law-library/statutes/STATE_SC_CODEREGS_8_170.md)
- [S.C. Code Regs. 8-175 S.C. Code Regs. 8-175. Investigations and Hearings](https://www.frixlaw.com/law-library/statutes/STATE_SC_CODEREGS_8_175.md)
- [S.C. Code Regs. 8-180 S.C. Code Regs. 8-180. Appeal From Action of Council](https://www.frixlaw.com/law-library/statutes/STATE_SC_CODEREGS_8_180.md)
- [S.C. Code Regs. 8-185 S.C. Code Regs. 8-185. Registration Replacement](https://www.frixlaw.com/law-library/statutes/STATE_SC_CODEREGS_8_185.md)

---

Source: Frix Law Library, https://www.frixlaw.com/law-library/statutes/STATE_SC_CODEREGS_8_1103. Check the current official text before relying on it. Not legal advice.