# 62 Ill. Adm. Code 220.70: Section 220.70 Grounding

> Illinois · Regulations · In force

URL: https://www.frixlaw.com/law-library/statutes/STATE_IL_IAC_T62_P220_S220_70

## Section

- **Citation:** 62 Ill. Adm. Code 220.70
- **Heading:** Section 220.70 Grounding
- **Jurisdiction:** Illinois
- **Kind:** Regulations
- **Status:** In force
- **Text as of:** August 14, 2026
- **Source:** Compiled text
- **Location:** Illinois Administrative Code / Title 62 MINING / CHAPTER I: DEPARTMENT OF NATURAL RESOURCES / Part 220 SURFACE INSTALLATION HEALTH AND SAFETY / Section 220.70 Grounding

## Text

Section 220
Section 220.70  Grounding
a)         Grounding, metallic shielding, armors, conduit enclosing power
conductors, metallic frames, casings, and other metallic enclosures of electric
equipment and circuits.
Metallic shieldings, armors, conduits enclosing power
conductors, metallic frames, casings, and other metallic enclosures of electric
equipment and circuits that can become "alive" through failure of
insulation or by contact with energized parts shall be grounded by methods
approved by an authorized representative of the Department.
b)         Approved grounding methods; three (3)-phase systems.
1)         Resistance Grounded Systems.  A grounding circuit consisting
of a grounding wire that meets the requirements of Section 220.70(f),
originating at the grounded side of the grounding resistor, shall extend along
with the power conductors and serve as the grounding conductor for all metallic
shielding, armors, conduit enclosing power conductors, metallic frames,
casings, and other metallic enclosures of electric equipment and circuits that
receive power from the circuit.  The grounding resistor shall be located at the
power source.  The grounded side of the grounding resistor shall be connected
to a low resistance ground field.
2)         Solidly Grounded Systems.  The grounded point of three
(3)-phase systems shall be grounded to a low resistance ground field and to the
cases of the source transformers.  A grounding circuit that meets the
requirements of Section 220.70(b)(1) shall originate at the grounded point of
the circuit and extend along with the power conductors and serve as a grounding
circuit for the frames, casings, and other metallic enclosures of all circuits
and equipment receiving power from that circuit.  The grounded point shall be
located at the power source
ce transformers.  A grounding circuit that meets the
requirements of Section 220.70(b)(1) shall originate at the grounded point of
the circuit and extend along with the power conductors and serve as a grounding
circuit for the frames, casings, and other metallic enclosures of all circuits
and equipment receiving power from that circuit.  The grounded point shall be
located at the power source.  In three (3)-phase, four (4)-wire systems in
which the neutral is a power conductor, the neutral shall also be grounded to a
low resistance ground field at the service entrance to building or at the
utilization locations.
3)         Ungrounded Systems.  A grounding circuit, consisting of a
grounding conductor that meets the requirements of Section 220.70(i) and
originating at the grounded case or frame of the power source, shall extend
along with the power conductors and serve as the grounding conductor for all
metallic casings and other metallic enclosures of electrical equipment and
circuits receiving power from that circuit.  The grounded case or frame of the
power source shall be connected to a low resistance ground field.
c)         Grounding method; single-phase system.
Single phase systems shall be grounded in such manner so that
the minimum amount of voltage will exist between the ungrounded conductors and
earth.  A conductor that meets the requirements of Section 220.70(i) shall
originate at the grounded point in the circuit and extend along with the power
conductors and serve as a grounding medium for the frames of all equipment
receiving power from that circuit and such conductor shall also be grounded to
a low resistance ground field at the service entrance or utilization points.
d)         Grounding methods; direct-current systems.
1)         Direct-current systems having one (1) grounded polarity.  In
direct-current systems having one polarity grounded to a low resistance ground
field the grounded feeder wire or track rail shall be approved grounding medium
conductor shall also be grounded to
a low resistance ground field at the service entrance or utilization points.
d)         Grounding methods; direct-current systems.
1)         Direct-current systems having one (1) grounded polarity.  In
direct-current systems having one polarity grounded to a low resistance ground
field the grounded feeder wire or track rail shall be approved grounding medium.
A grounding circuit meeting the requirements of Section 220.70(f) shall
originate at the grounded feeder wire or tract rail and extend along with the
power conductors and serve as a grounding conductor for the frames, casing, and
metallic enclosures of all circuits and equipment receiving power from that
credit.
2)         Direct current systems having a grounded neutral point.  The
grounded neutral point shall be the approved grounding medium.  A grounding
circuit meeting the requirements of Section 220.70(f) originate at the grounded
neutral point and extend along with the power conductors and serve as a
grounding conductor for the frames, casings, and metallic enclosures of all
circuits and equipment receiving power from that circuit.
3)         Ungrounded direct-current circuits.  In ungrounded
direct-current circuits the grounded frame or casing of the power source shall
be the approved grounding medium.  In the event the power source is a
direct-current generator, the frame of the generator power source is a direct-current
generator, the frame of the generator shall be connected to a low resistance
ground field.  A grounding circuit meeting the requirements of Section
220.70(f) shall originate at the grounded frame or casing of the power source
and extend along with the power conductors and serve as a grounding conductor
for the frames, casings, and metallic enclosures of all circuits and equipment
receiving power from that circuit.
e)         Low resistance ground field; interpretation
ground field.  A grounding circuit meeting the requirements of Section
220.70(f) shall originate at the grounded frame or casing of the power source
and extend along with the power conductors and serve as a grounding conductor
for the frames, casings, and metallic enclosures of all circuits and equipment
receiving power from that circuit.
e)         Low resistance ground field; interpretation.
1)         A low resistance ground field as referred to in Section 220.90
of this Part is interpreted to mean:  made electrodes, buried metallic piping
system, metal building framework, well or borehole casing, steel piling, and
other underground metal structures installed for purpose other than grounding
which have a resistance to ground of not more than five (5) OHMS.  Grounding
fields shall be measured at the time of installation and at least annually
thereafter to insure a sufficiently low resistance ground field has been
established and is being maintained and such measurements shall be recorded and
kept at the installation.
2)         An authorized representative of the Department may allow
higher resistance to ground values if an investigation has revealed that such
greater values of resistance will not pose a hazard to the miners.
f)         Grounding wires; capacity.
Where grounding wires are used to ground metallic shielding,
armors, conduits, frames, casings, and other metallic enclosures, such
grounding wires will be approved if:
1)         Where the power conductor used is No.  6 A.W.G., or larger,
the cross-sectional area of the grounding wire is at least one-half (½) the
cross-sectional area of the power conductor; or
2)         Where the power conductor used is less than No.  6 A.W.G., the
cross-sectional area of the grounding wire is equal to the cross-sectional area
of the power conductor.
g)         Protection other than grounding.
Methods other than grounding which provide no less effective
protection may be permitted by the Department or its authorized
representative
al area of the power conductor; or
2)         Where the power conductor used is less than No.  6 A.W.G., the
cross-sectional area of the grounding wire is equal to the cross-sectional area
of the power conductor.
g)         Protection other than grounding.
Methods other than grounding which provide no less effective
protection may be permitted by the Department or its authorized
representative.  Such methods shall not be used unless so approved.
h)         Grounding circuit; criteria.
The grounding circuit for equipment and conductor enclosures
shall:
1)         Be permanent and continuous;
2)         Have ample current-carrying capacity to conduct safely any
currents liable to be imposed on it; and
3)         Have impedance sufficiently low to facilitate the operation of
the ground overcurrent devices in the circuit during fault conditions.
i)          Approved grounding conductors.
Any of the following conductors when properly installed shall
be acceptable for grounding equipment to the ground field:
1)         A properly-sized copper or other corrosion-resistant conductor
which meets the requirements of Section 220.70(f);
2)         Rigid metal conduit;
3)         Electrical metallic tubing; and
4)         The structural metal frame of buildings.
j)          Use of grounding connectors.
If ground wires are attached to grounded power conductors,
separate clamps, suitable for such purpose, shall be used and installed to
provide a solid connection.
k)         Guy wire; grounding.
Guy wires from poles supporting power lines shall be securely
connected to the system ground or be provided with insulators installed near
the pole end.

## Nearby sections

- [62 Ill. Adm. Code 220.10 Section 220.10  Introduction and Definitions](https://www.frixlaw.com/law-library/statutes/STATE_IL_IAC_T62_P220_S220_10.md)
- [62 Ill. Adm. Code 220.20 Section 220.20  Surface Installations](https://www.frixlaw.com/law-library/statutes/STATE_IL_IAC_T62_P220_S220_20.md)
- [62 Ill. Adm. Code 220.30 Section 220.30  Thermal Dryers](https://www.frixlaw.com/law-library/statutes/STATE_IL_IAC_T62_P220_S220_30.md)
- [62 Ill. Adm. Code 220.40 Section 220.40  Safeguard For Mechanical Equipment](https://www.frixlaw.com/law-library/statutes/STATE_IL_IAC_T62_P220_S220_40.md)
- [62 Ill. Adm. Code 220.50 Section 220.50  Electrical Equipment-General](https://www.frixlaw.com/law-library/statutes/STATE_IL_IAC_T62_P220_S220_50.md)
- [62 Ill. Adm. Code 220.60 Section 220.60  Trailing Cables](https://www.frixlaw.com/law-library/statutes/STATE_IL_IAC_T62_P220_S220_60.md)
- [62 Ill. Adm. Code 220.70 Section 220.70  Grounding](https://www.frixlaw.com/law-library/statutes/STATE_IL_IAC_T62_P220_S220_70.md)
- [62 Ill. Adm. Code 220.80 Section 220.80  Surface High-Voltage Distribution](https://www.frixlaw.com/law-library/statutes/STATE_IL_IAC_T62_P220_S220_80.md)
- [62 Ill. Adm. Code 220.90 Section 220.90  Low and Medium-Voltage Alternating Current Circuits](https://www.frixlaw.com/law-library/statutes/STATE_IL_IAC_T62_P220_S220_90.md)
- [62 Ill. Adm. Code 220.100 Section 220.100  Ground Control](https://www.frixlaw.com/law-library/statutes/STATE_IL_IAC_T62_P220_S220_100.md)
- [62 Ill. Adm. Code 220.110 Section 220.110  Fire Protection](https://www.frixlaw.com/law-library/statutes/STATE_IL_IAC_T62_P220_S220_110.md)
- [62 Ill. Adm. Code 220.120 Section 220.120  Mine Maps](https://www.frixlaw.com/law-library/statutes/STATE_IL_IAC_T62_P220_S220_120.md)
- [62 Ill. Adm. Code 220.130 Section 220.130  Explosives and Blasting](https://www.frixlaw.com/law-library/statutes/STATE_IL_IAC_T62_P220_S220_130.md)
- [62 Ill. Adm. Code 220.140 Section 220.140  Man Hoisting](https://www.frixlaw.com/law-library/statutes/STATE_IL_IAC_T62_P220_S220_140.md)

---

Source: Frix Law Library, https://www.frixlaw.com/law-library/statutes/STATE_IL_IAC_T62_P220_S220_70. Check the current official text before relying on it. Not legal advice.