Section 220
Section 220.60  Trailing
Cables
a)         Trailing cables; ampacity.
All trailing
cables shall meet the minimum requirements for construction and ampacity
provided in the Standards of the Insulated Power Cable Engineers Association – National
Electric Manufacturers Association in effect when such cables are purchased.
b)         Trailing cables; short-circuit, grounded phase protection, and
disconnecting devices.
Short-circuit
protection for trailing cable shall be provided by a circuit breaker or other
no less effective device of adequate current-interrupting capacity in each
ungrounded conductor.  One (1) breaker may protect multiple cables if the
amperage setting on the breaker is set to the lowest amperage setting of the
smallest circuit.  Disconnecting devices shall be installed in conjunction with
each circuit breaker and within three thousand (3,000) feet of each mobile
machine.  Such disconnecting devices used to connect power from trailing cables
shall be plainly marked and identified and such devices shall be equipped or
designed in such a manner that it can be determined by visual observation that
the power is disconnected.
c)         Short-circuit protection; ratings and settings of circuit
breakers.
Circuit
breakers providing short-circuit protection for trailing cables shall be set at
not more than eighty (80) percent of the short-circuit capability of the
system.  The maximum time for clearing a short circuit shall not exceed that
cable time current rating specified by the Insulated Power Cable Engineers
Association higher settings may be permitted by an authorized representative of
the Department when he has determined that higher settings are justified.
d)         Design of trailing cable for low and medium voltage three (3)
phase equipment
system.  The maximum time for clearing a short circuit shall not exceed that
cable time current rating specified by the Insulated Power Cable Engineers
Association higher settings may be permitted by an authorized representative of
the Department when he has determined that higher settings are justified.
d)         Design of trailing cable for low and medium voltage three (3)
phase equipment.
All trailing
cables supplying power to equipment from low and medium-voltage systems
purchased after effective date shall contain two (2) or more grounding
conductors having a total cross-sectional area of not less than one-half (½)
the power conductor and grounded metallic shields around each power conductor.
The metallic shielding shall meet the requirements for shielding provided by
the Standards of the Insulated Power Cable Engineers Association-National
Electrical Manufacturers Association for type SH or SHD portable power cables.
Such trailing cables shall include an insulated conductor for the ground
continuity check circuit except in circuits in which a no less effective device
for ground check monitoring approved by the Department is being utilized.
e)         Splicing of trailing cables.
1)         When splices in trailing cables are made, they shall be:
A)        Mechanically strong with adequate electrical conductivity,
B)        Effectively insulated and sealed so as to exclude moisture, and
C)        Vulcanized or otherwise made with suitable materials to provide
good bonding to the outer jacket.
2)         Splices made in trailing cables shall provide continuity of
all components including the grounded metallic shielding.
3)         Trailing cables or portable cables with exposed wires or
splices that heat or spark under load shall not be used.
f)         Securing of Trailing Cables to equipment.
Trailing cables shall be secured to machines in a manner to
protect the cables from damage and to prevent strain on the electrical
connections.
g)         Protection of trailing cables
g the grounded metallic shielding.
3)         Trailing cables or portable cables with exposed wires or
splices that heat or spark under load shall not be used.
f)         Securing of Trailing Cables to equipment.
Trailing cables shall be secured to machines in a manner to
protect the cables from damage and to prevent strain on the electrical
connections.
g)         Protection of trailing cables.
Trailing cables shall be adequately protected to prevent
damage by mobile equipment and placed to afford protection against rock slides
and other falling objects.  Surplus trailing cable to shovels, draglines,
drills, and similar equipment shall be stored on reels mounted on the equipment
or otherwise protected from mechanical damage.  Damaged outer jackets of
trailing cables shall be repaired to the same degree of protection as the
remainder of the cable.
h)         Breaking trailing cable and power cable connections.
1)         Plugs and connectors in trailing cables and power cables shall
not be connected or disconnected while the circuit is energized.
2)         No power cable or electric circuit supplying power in excess
of two hundred forty (240) volts will be energized or deenergized, hooked up or
unhooked except by a person qualified under Section 220.50(e) of this Part to
perform electrical work, or by a person trained to perform electrical work at
the direction of a qualified person.
3)         This requirement shall not be construed to include the
energizing or deenergizing of a simple "on-off"switch on standard
equipment, when such switch or equipment is located outside of any high-voltage
switch house.
i)          Trailing Cables; Movement.
Trailing cables shall not be moved with mobile equipment
unless cable slings, sleds, or equivalent protection is provided.
j)          Energized trailing cables, handling.
Energized trailing cables, where the phase-to-ground voltage
is one hundred fifty (150) volts or more, shall be handled only by persons
wearing protective gloves
h-voltage
switch house.
i)          Trailing Cables; Movement.
Trailing cables shall not be moved with mobile equipment
unless cable slings, sleds, or equivalent protection is provided.
j)          Energized trailing cables, handling.
Energized trailing cables, where the phase-to-ground voltage
is one hundred fifty (150) volts or more, shall be handled only by persons
wearing protective gloves.  Protective gloves must be worn while using
insulated hooks or tongs.
k)         Protective gloves; minimum requirements.
1)         Protective gloves worn while handling high-voltage trailing cables
shall be rated at least for the phase-to-ground voltage of the system and shall
be used and tested in accordance with the provisions of Section 220.80(aa),
(bb) and (cc).
2)         Protective gloves worn while handling low-voltage and
medium-voltage trailing cables shall be rated for a minimum of the
phase-to-ground voltage of the circuit.
3)         Protective gloves shall be inspected for defects before each
use. Protective gloves which contain defects shall not be used.

## Nearby sections

- [62 Ill. Adm. Code 220.10 Section 220.10  Introduction and Definitions](https://www.frixlaw.com/law-library/statutes/STATE_IL_IAC_T62_P220_S220_10.md)
- [62 Ill. Adm. Code 220.20 Section 220.20  Surface Installations](https://www.frixlaw.com/law-library/statutes/STATE_IL_IAC_T62_P220_S220_20.md)
- [62 Ill. Adm. Code 220.30 Section 220.30  Thermal Dryers](https://www.frixlaw.com/law-library/statutes/STATE_IL_IAC_T62_P220_S220_30.md)
- [62 Ill. Adm. Code 220.40 Section 220.40  Safeguard For Mechanical Equipment](https://www.frixlaw.com/law-library/statutes/STATE_IL_IAC_T62_P220_S220_40.md)
- [62 Ill. Adm. Code 220.50 Section 220.50  Electrical Equipment-General](https://www.frixlaw.com/law-library/statutes/STATE_IL_IAC_T62_P220_S220_50.md)
- [62 Ill. Adm. Code 220.60 Section 220.60  Trailing Cables](https://www.frixlaw.com/law-library/statutes/STATE_IL_IAC_T62_P220_S220_60.md)
- [62 Ill. Adm. Code 220.70 Section 220.70  Grounding](https://www.frixlaw.com/law-library/statutes/STATE_IL_IAC_T62_P220_S220_70.md)
- [62 Ill. Adm. Code 220.80 Section 220.80  Surface High-Voltage Distribution](https://www.frixlaw.com/law-library/statutes/STATE_IL_IAC_T62_P220_S220_80.md)
- [62 Ill. Adm. Code 220.90 Section 220.90  Low and Medium-Voltage Alternating Current Circuits](https://www.frixlaw.com/law-library/statutes/STATE_IL_IAC_T62_P220_S220_90.md)
- [62 Ill. Adm. Code 220.100 Section 220.100  Ground Control](https://www.frixlaw.com/law-library/statutes/STATE_IL_IAC_T62_P220_S220_100.md)
- [62 Ill. Adm. Code 220.110 Section 220.110  Fire Protection](https://www.frixlaw.com/law-library/statutes/STATE_IL_IAC_T62_P220_S220_110.md)
- [62 Ill. Adm. Code 220.120 Section 220.120  Mine Maps](https://www.frixlaw.com/law-library/statutes/STATE_IL_IAC_T62_P220_S220_120.md)
- [62 Ill. Adm. Code 220.130 Section 220.130  Explosives and Blasting](https://www.frixlaw.com/law-library/statutes/STATE_IL_IAC_T62_P220_S220_130.md)
- [62 Ill. Adm. Code 220.140 Section 220.140  Man Hoisting](https://www.frixlaw.com/law-library/statutes/STATE_IL_IAC_T62_P220_S220_140.md)

---

Source: Frix Law Library, https://www.frixlaw.com/law-library/statutes/STATE_IL_IAC_T62_P220_S220_60. Check the current official text before relying on it. Not legal advice.