# Transmission System Planning Performance Requirements for Extreme Weather

> Briefs, arguments, decisions, and more.

URL: https://www.frixlaw.com/law-library/documents/fr%3A2022-13471

## Record

- **Collection:** Federal Register
- **Document type:** Proposed Rule
- **Published:** June 27, 2022
- **Citation:** 87 FR 38020

## Text

DEPARTMENT OF ENERGY
Federal Energy Regulatory Commission
18 CFR Part 40
[Docket No. RM22-10-000]
Transmission System Planning Performance Requirements for Extreme Weather

AGENCY:

Federal Energy Regulatory Commission, Department of Energy.

ACTION:

Notice of proposed rulemaking.

SUMMARY:

The Federal Energy Regulatory Commission proposes to direct that the North American Electric Reliability Corporation, the Commission-certified Electric Reliability Organization, submit to the Commission modifications to Reliability Standard TPL-001-5.1 (Transmission System Planning Performance Requirements) within one year of the effective date of a final rule in this proceeding to address reliability concerns pertaining to transmission system planning for extreme heat and cold weather events that impact the reliable operations of the Bulk-Power

System. Specifically, we propose to direct NERC to develop modifications to Reliability Standard TPL-001-5.1 to require: development of benchmark planning cases based on information such as major prior extreme heat and cold weather events or future meteorological projections; planning for extreme heat and cold events using steady state and transient stability analyses expanded to cover a range of extreme weather scenarios including the expected resource mix's availability during extreme weather conditions, and including the broad area impacts of extreme weather; and corrective action plans that include mitigation for any instances where performance requirements for extreme heat and cold events are not met.

DATES:

Comments are due August 26, 2022.

ADDRESSES:

Comments, identified by docket number, may be filed in the following ways. Electronic filing through
https://www.ferc.gov,
is preferred.

•
Electronic Filing:
Documents must be filed in acceptable native applications and print-to-PDF, but not in scanned or picture format.

• For those unable to file electronically, comments may be filed by U.S. Postal Service mail or by hand (including courier) delivery.

○ Mail via U.S. Postal Service only: Addressed to: Federal Energy Regulatory Commission, Office of the Secretary, 888 First Street NE, Washington, DC 20426.

○ For delivery via any other carrier (including courier): Deliver to: Federal Energy Regulatory Commission, Office of the Secretary, 12225 Wilkins Avenue, Rockville, MD 20852.

FOR FURTHER INFORMATION CONTACT:

Mahmood Mirheydar (Technical Information), Office of Electric Reliability, Federal Energy Regulatory Commission, 888 First Street NE, Washington, DC 20426, (202) 502-8034,
mahmood.mirheydar@ferc.gov

Milena Yordanova (Legal Information), Office of the General Counsel, Federal Energy Regulatory Commission, 888 First Street NE, Washington, DC 20426, (202) 502-6194,
milena.yordanova@ferc.gov

SUPPLEMENTARY INFORMATION:

Table of Contents

Paragraph Nos.

I. Introduction
1

II. Background
8

A. Legal Authority
8

B. Climate Change, Extreme Weather, and Electric System Reliability Technical Conference
10

C. Overview of Technical Conference Comments
13

D. Cold Weather Reliability Standards
18

E. Reliability Standard TPL-001-4 (Transmission System Planning Performance Requirements)
20

III. The Need for Reform
24

A. Recent Events Show Changes in Weather Patterns Resulting in More Extreme Heat and Cold Weather Events
24

B. NERC Reliability Standards Do Not Require Planning To Minimize the Increasing Reliability Risks Associated With Anticipated Extreme Heat and Cold Weather Events
37

IV. Proposed Directives
47

A. Develop Benchmark Planning Cases Based on Major Prior Extreme Heat and Cold Weather Events
50

B. Transmission System Planning for Extreme Heat and Cold Weather Events
57

1. Steady State and Transient Stability Analyses
58

2. Transmission Planning Studies of Wide-Area Events
64

3. Study Concurrent Generator and Transmission Outages
68

4. Sensitivity Analysis
73

5. Modifications to the Traditional Planning Approach
75

6. Coordination Among Planning Coordinators and Transmission Planners and Sharing of Study Results
80

C. Implement a Corrective Action Plan If Performance Standards Are Not Met
83

D. Other Extreme Weather-Related Events and Issues
90

V. Information Collection Statement
94

VI. Environmental Assessment
96

VII. Regulatory Flexibility Act Certification
97

VIII. Comment Procedures
100

IX. Document Availability
103

I. Introduction

1. Pursuant to section 215(d)(5) of the Federal Power Act (FPA),
1

the Commission proposes to direct that the North American Electric Reliability Corporation (NERC), the Commission-certified Electric Reliability Organization (ERO), submit modifications to Reliability Standard TPL-001-5.1 (Transmission System Planning Performance Requirements)
2

that address concerns pertaining to transmission system planning for extreme heat or cold weather events that impact the reliable operation
3

of the Bulk-Power System.
4

1
16 U.S.C 824o(d)(5).

2

Transmission Planning Reliability Standard TPL-001-5,
Order No. 867, 85 FR 8155 (Feb. 13, 2020), 170 FERC ¶ 61,030, at P 1 (2020) (approving the proposed Reliability Standard TPL-001-5 and associated implementation plan).
N. Am. Elec. Reliability Corp.,
Docket No. RD20-8-000 (June 10, 2020) (delegated order) (approving Reliability Standard TPL-001-5.1). This NOPR refers to Reliability Standard TPL-001-5.1 to reflect that the currently effective version 4 of the Reliability Standard will be soon replaced by version 5.1 and any modifications proposed in the NOPR will apply only to TPL-001-5.1.

3
The FPA defines “Reliable Operation” as “operating the elements of the Bulk-Power System within equipment and electric system thermal, voltage, and stability limits so that instability, uncontrolled separation, or cascading failures of such system will not occur as a result of a sudden disturbance, including a cybersecurity incident, or unanticipated failure of system elements.” 16 U.S.C. 824o(a)(4).

4
The Bulk-Power System is defined in the FPA as “facilities and control systems necessary for operating an interconnected electric energy transmission network (or any portion thereof), and electric energy from generating facilities needed to maintain transmission system reliability. The term does not include facilities used in the local distribution of electric energy.”
Id.
824o(a)(1).

2. We take this action to address planning challenges associated with extreme heat and cold weather events, particularly those that occur during periods when the Bulk-Power System must meet unexpectedly high demand.
5

Extreme heat and cold weather events are occurring with greater frequency, and are projected to occur with even greater frequency in the future.
6

As such, the impact of concurrent failures of Bulk-Power System generators and transmission equipment and the potential for cascading outages
7

that may be caused by extreme heat and cold events should be studied and corrective actions should be identified and implemented.

5
Technical Conference June 1-2, 2021,
Climate Change, Extreme Weather, and Electric System Reliability,
Docket No. AD21-13-000 (June 1-2, 2021), June 1, 2021 Tr. 26: 3-7 (Derek Stenclik, Founding Partner, Telos Energy, Inc.), 31:7-8 (Judy Chang, Undersecretary of Energy, Massachusetts).

6
Environmental Protection Agency,
Climate Change Indicators: Weather and Climate
(May 12, 2021) (EPA Climate Change Indicators),
https://www.epa.gov/climate-indicators/weather-climate
(showing an upward trend in extreme heat and cold weather events).

7
NERC Glossary of Terms Used in Reliability Standards (Updated March 29, 2022) (NERC Glossary). NERC defines “cascading” as, “The uncontrolled successive loss of System Elements triggered by an incident at any location. Cascading results in widespread electric service interruption that cannot be restrained from sequentially spreading beyond an area predetermined by studies.”

3. At the Commission's June 1-2, 2021 technical conference on Climate Change, Extreme Weather, and Electric System Reliability, there was consensus among panelists that planners cannot simply project historical weather patterns forward to effectively forecast the future, since climate change has made the use of historical weather observations no longer representative of future conditions.
8

For example, extreme heat in summer in regions like the Pacific northwest and extreme cold in winter in regions like Texas has increased demand for electricity at times when historically demand has been low and such events will likely continue to present challenges in the future.
9

Therefore, transmission planners and planning coordinators need to reflect these new realities into their planning processes.
10

8
June 1, 2021 Tr. 30:2-3 (Chang), 31:12-18 (Lisa Barton, Executive Vice President/Chief Operating Officer, American Electric Power).

9
June 1, 2021 Tr. 31:1-6 (Chang); June 2, 2021 Tr. 72:8-10 (Amanda Frazier, Senior Vice President of Regulatory Policy, Vista Corp.); 9:1-5 (Wesley Yeomans, Vice President of Operations, New York Independent System Operator, Inc. (NYISO)) (noting that in New York the majority of the extreme conditions were cold weather related but that there can be heat waves in New York City, and more heat waves are expected).

10
June 1, 2021 Tr. 35:1-6 (Chang).
See also
US News,
Blackouts in US Northwest Due to Heat Wave, Deaths Reported
(June 29, 2021),
https://www.usnews.com/news/business/articles/2021-06-29/rolling-blackouts-for-parts-of-us-northwest-amid-heat-wave
; Judah Cohen et al.,
Linking Arctic Variability and Change With Extreme Winter Weather in the United States,
373 Sci. 1116, 1120 (2021),
https://www.science.org/doi/10.1126/science.abi9167
(a study connecting the 2021 extreme cold weather event in Texas and the South-central United States to global warming-induced weather anomalies that are likely to continue to produce severe winter storm events).

4. Since 2011, the country has experienced at least seven major extreme heat and cold weather events,
11

all of which put stress on the Bulk-Power System, and resulted in some degree of load shed, and in some cases nearly caused system collapse and uncontrolled blackouts, which were only avoided via the actions of system operators. Of these, the four most severe occurred in 2011, 2013, 2018, and 2021. The extreme weather conditions in the February 2011 Southwest Cold Weather Event resulted in the acumulative loss of approximately thirty thousand megawatts of generation resources, causing the Electric Reliability Council of Texas (ERCOT) to shed load to prevent widespread, uncontrolled blackouts throughout the entire ERCOT Interconnection. The September Midwest and Mid-Atlantic 2013 Heatwave Event lasted over three days and at its peak required a 5,791 MW reduction in load. The PJM Interconnection, L.L.C. (PJM) analysis during the event indicated a need for pre-contingency load shed to avoid post-contingency voltage collapse and a potential cascading outage.
12

During the January 2018 South Central Cold Weather Event in the Midwest, had the grid operator lost the single largest contingency of 1,163 MW, there could have been firm load shedding to maintain system stability. In February of 2021, the extensive cold in the South Central and Texas regions required a combined total of 23,418 MW of firm load shed to maintain Bulk-Power System reliability; it was the largest controlled load shedding event in U.S. history. During this 2021 Cold Weather Event, had frequency in Texas remained under its lowest point on February 15, 2021 for an additional five minutes, approximately 17,000 MW of additional generation would have tripped, potentially blacking out the entire ERCOT Interconnection. ERCOT shed firm load in order to maintain frequency to prevent a collapse of the system.
13

11
This NOPR references the following seven extreme heat and cold weather events experienced since 2011: (1) February 2011 Southwest Cold Weather Event; (2) September Midwest and Mid-Atlantic 2013 Heatwave Event; (3) January 2014 Polar Vortex Cold Weather Event; (4) January 2018 South Central Cold Weather Event; (5) August 2020 California Heatwave Event; (6) 2021 Cold Weather Event; (7) June 2021 the Pacific Northwest Heatwave Event. The naming of the events is based on the title of the associated reliability report for each event cited below.

12
PJM,
Technical Analysis of Operational Events and Market Impacts during the September 2013 Heat Wave,
at 13 (Dec. 23, 2013),
https://www.yumpu.com/en/document/read/40807126/20131223-technical-analysis-of-operational-events-and-market-impacts-during-the-september-2013-heat-wave.

13
FERC, NERC, Regional Entity Staff Report,
The February 2021 Cold Weather Outages in Texas, and the South-Central United States,
at 133 (Nov. 2021) (2021 Cold Weather Event Report).

5. Given the reliability risks associated with extreme heat and cold weather events, including the potential for widespread blackouts, we believe it would be appropriate for planning of the transmission system to account for extreme heat and cold weather events' potential impact over wide geographical areas, and to consider the changing resource mix and associated planning assumptions. Reliability Standard TPL-001-4, the currently effective transmission system planning standard, was developed to establish transmission system planning performance requirements that ensure that the Bulk-Power System operates reliably over a broad spectrum of system conditions and following a wide range of probable contingencies. Reliability Standard TPL-001-4, and its successor, TPL-001-5.1, includes provisions for transmission planners and planning coordinators to study system performance under extreme events based on their experience. However, the current standards do not specifically require that a performance analysis be conducted for extreme heat and cold weather, despite the fact that such events have demonstrated a potential harm to reliable operations of the Bulk-Power System, thus leaving a gap in system planning.

6. To address this reliability gap, we propose to direct NERC to develop modifications to Reliability Standard TPL-001-5.1 to require: (1) development of benchmark planning cases based on information such as major prior extreme heat and cold weather events or future meteorological projections; (2) planning for extreme heat and cold events using steady state and transient stability analyses expanded to cover a range of extreme weather scenarios including the expected resource mix's availability during extreme heat and cold weather conditions, and including the broad area impacts of extreme heat and cold

weather; and (3) corrective action plans that include mitigation for any instances where performance requirements for extreme heat and cold events are not met. In proposing to direct NERC to modify Reliability Standard TPL-001-5.1, we are not proposing specific requirements. Instead, we identify concerns that we believe should be addressed. NERC may propose to develop new or modified Reliability Standards that address our concerns in an equally efficient and effective manner. However, NERC's proposal should explain how it addresses the Commission's concerns.
14

14

See e.g., Mandatory Reliability Standards for the Bulk-Power Sys.,
Order No. 693, 72 FR 16416 (Apr. 4, 2007), 118 FERC ¶ 61,218, at PP 186, 297,
order on reh'g,
Order No. 693-A, 120 FERC ¶ 61,053 (2007) (“where the Final Rule identifies a concern and offers a specific approach to address the concern, we will consider an equivalent alternative approach provided that the ERO demonstrates that the alternative will address the Commission's underlying concern or goal as efficiently and effectively as the Commission's proposal”);
Reliability Standards for Physical Sec. Measures,
146 FERC ¶ 61,166, at P 13 (2014).

7. We further propose to direct NERC to submit modifications to Reliability Standard TPL-001-5.1 within one year of the effective date of a final rule in this proceeding with compliance obligations for all proposed new or modified Reliability Standards beginning no later than 12 months from the date of Commission approval of the modified Reliability Standard. Finally, we invite comments on whether to also direct NERC to address in Reliability Standard TPL-001-5.1 other extreme weather-related events.

II. Background

A. Legal Authority

8. Section 215 of the FPA requires a Commission-certified ERO to develop mandatory and enforceable Reliability Standards, subject to Commission review and approval. Reliability Standards may be enforced by the ERO, subject to Commission oversight, or by the Commission independently.
15

Pursuant to section 215 of the FPA, the Commission established a process to select and certify an ERO,
16

and subsequently certified NERC.
17

15
16 U.S.C. 824o(e).

16

Rules Concerning Certification of the Elec. Reliability Org. & Procedures for the Establishment, Approval, & Enf't. of Elec. Reliability Standards,
Order No. 672, 71 FR 8662 (Feb. 17, 2006), 114 FERC ¶ 61,104,
order on reh'g,
Order No. 672-A, 71 FR 19814 (Apr. 18, 2006), 114 FERC ¶ 61,328 (2006).

17

N. Am. Elec. Reliability Corp.,
116 FERC ¶ 61,062,
order on reh'g and compliance,
117 FERC ¶ 61,126 (2006),
aff'd sub nom. Alcoa, Inc.
v.
FERC,
564 F.3d 1342 (D.C. Cir. 2009).

9. Pursuant to section 215(d)(5) of the FPA, the Commission has the authority, upon its own motion or upon complaint, to order the ERO to submit to the Commission a proposed Reliability Standard or a modification to a Reliability Standard that addresses a specific matter if the Commission considers such a new or modified Reliability Standard appropriate to carry out section 215 of the FPA.
18

Further, pursuant to § 39.5(g) of the Commission's regulations, the Commission may order a deadline by which the ERO must submit a proposed or modified Reliability Standard, when ordering the ERO to submit to the Commission a proposed Reliability Standard that addresses a specific matter.
19

18
16 U.S.C. 824o(d)(5).

19
18 CFR 39.5(g) (2021).

B. Climate Change, Extreme Weather, and Electric System Reliability Technical Conference

10. On March 5, 2021, the Commission announced that staff would hold a technical conference to discuss issues surrounding the threat to electric system reliability posed by climate change and extreme weather events.
20

The Commission sought to understand, among other things, whether further action from the Commission is needed to help achieve an electric system that can withstand, respond to, and recover from extreme weather events.
21

On March 15, 2021, the Commission invited comments on a range of issues related to Bulk-Power System reliability, including how extreme weather events (
e.g.,
hurricanes, extreme heat, extreme cold, drought, storms), have impacted the electric system and whether these events would require changes to the way generation, transmission, substation, or other facilities are designed, built, sited, and operated.
22

The Commission also inquired whether there are opportunities to improve the NERC Reliability Standards to address vulnerabilities to Bulk-Power System reliability due to climate change or extreme weather events in the areas of transmission planning, Bulk-Power System operations, Bulk-Power System maintenance, and emergency operations.
23

20

Climate Change, Extreme Weather, and Electric System Reliability,
Notice of Technical Conference, Docket No. AD21-13-000, at 1 (Mar. 5, 2021).

21

Id.
at 2.

22
Supplemental Notice of Technical Conference, Docket No. AD21-13-000, at 1, 3 (Mar. 15, 2021).

23

Id.
at 5.

11. On June 1 and 2, 2021, the Commission convened a staff-led technical conference on Climate Change, Extreme Weather, and Electric System Reliability focused on: (1) ways in which planning practices might evolve to achieve outcomes that reflect consumer needs for reliable electricity in the face of patterns of climate change and extreme weather events that diverge from historical trends; (2) best practices throughout the industry for assessing the risks posed by climate change and extreme weather and developing cost-effective mitigation; (3) ways in which existing operating practices may necessitate updated techniques and approaches in light of increasing instances of extreme weather and longer-term threats posed by climate change; (4) best practices for the recovery period following an extreme weather event; and (5) the role that coordination and cooperation across jurisdictions could play in planning, operations, and recovery practices to address climate change and extreme weather events.
24

24
Supplemental Notice of Technical Conference, Docket No. AD21-13-000, at 1, 3 (May 27, 2021) (attaching agenda).

12. Following the conference, the Commission invited comments on specific topics discussed at the conference, such as the possibility of: incorporating probabilistic methods into local transmission planning and/or regional transmission planning; coordinating transfers across the seams between Regional Transmission Organizations; the possibility of modifying transmission planning requirements established under Reliability Standard TPL-001 to better assess and mitigate the risk of extreme weather events and associated common mode failures; additional changes to the NERC Reliability Standards to address the risk of extreme weather events; and among other topics, whether target levels of interregional transfer capacity could help facilitate more effective development of interregional transmission projects to help ensure reliability and resilience during extreme weather events.
25

25
Notice Inviting Post-Technical Conference Comments, Docket No. AD21-13-000, at 3, 5 (Aug. 11, 2021).

C. Overview of Technical Conference Comments

13. Commenters submitted more than 50 sets of pre-conference and 20 post-conference comments on a wide range of issues, including the types of extreme weather events experienced,
26

and the range of mitigating measures that could be taken to address the specific risks of climate change in various regions of the country. Commenters expressed

concerns that the impacts of climate change are anticipated to affect the electric system in multiple, compounding, and synergistic ways.
27

Generally, industry experts agreed that extreme weather events are likely to become more severe and frequent in the future,
28

and acknowledged the challenges associated with planning for extreme events, including shifting scheduled maintenance, canceling or recalling transmission and generation assets from scheduled maintenance to meet demand under unexpected circumstances.
29

26

See, e.g.,
California Independent System Operator Corporation (CAISO) Pre-Conference Comments at 3.

27
Environmental Defense Fund and Columbia Law School's Sabin Center for Climate Change Law Pre-Conference Comments at 4.

28
CAISO Pre-Conference Comments at 1-3; California Public Utilities Commission Pre-Conference Comments at 4; Oregon Public Utilities Commission Pre-Conference Comments at 2-3; NYISO Pre-Conference Comments at 4.

29
June 2, 2021, Tr. at 21-23 (Wesley Yeomans, Vice President of Operations, NYISO).

14. Some commenters discussed potential changes to the NERC Reliability Standards to address planning and operational preparedness for energy adequacy risks,
30

contingencies related to extreme weather events, and wide-area transmission planning and development challenges,
31

among others. In addition, participants advocated for planning that reflects the new climate-change driven conditions, as the expected impacts of climate change “need to be baked into the rest of your planning and development activities.”
32

30
ISO-New England Inc. Pre-Conference Comments at 10.

31
Midcontinent Independent System Operator (MISO) Pre-Conference Comments at 4-5, 14-17.

32
June 1, 2021 Tr. 136:18-21 (Neil Millar, Vice President, Transmission Planning & Infrastructure Development, CAISO).

15. Pacific Gas and Electric Company states that Reliability Standard TPL-001-4 already requires transmission planners to evaluate extreme events, but could benefit from providing further clarity on the events to consider, as well as the extent to which investments can be made to the grid to mitigate the identified issues for the given event evaluated.
33

33
Pacific Gas and Electric Company Pre-Conference Comments at 19-20.

16. Post-conference comments also addressed more directly the potential reliability gaps in the existing set of Reliability Standards, including Reliability Standard TPL-001-4. For example, MISO argues that while current Commission-approved Reliability Standards provide for the assessment of the impacts of extreme events that may include climate-driven weather events, they do not include requirements to mitigate consequences from such events.
34

Similarly, PJM states that Reliability Standard TPL-001-4 should be modified to specifically account for extreme weather events by mandating regional extreme weather design standards for transmission and generation operating criteria.
35

CAISO also states that Reliability Standard TPL-001 may not serve as the best means to assess the threat and risk of extreme weather events.
36

34
MISO Post-Conference Comments at 20.

35
PJM Post-Conference Comments at 21.

36
CAISO Post-Conference Comments at 10.

17. NERC agrees that with proper planning, including consideration not only of historic temperature averages but also consideration of conditions during extreme weather events and the linkage between critical infrastructures, the risks associated with extreme weather and the changing resource mix can be mitigated.
37

NERC agrees that enhancements to the Reliability Standards could be beneficial. Some examples of potential enhancements include requiring reliability coordinators, balancing authorities, or planning coordinators to determine the temperature to which plants in their respective areas must weatherize; requiring reliability coordinators or balancing authorities to develop seasonal emergency energy management plans, to address conditions such as wildfires, extreme hot and cold temperatures, and severe storms (
i.e.,
hurricanes); requiring reliability coordinators to develop a rolling three week emergency energy management plan; and requiring balancing authorities to prepare a seasonal energy management plan based on regional extreme weather scenarios identified in NERC's seasonal assessments.
38

37
NERC Pre-Conference Comments at 6.

38

Id.
at 15-16; NERC Post-Conference Comments at 5-7 (explaining that additional modifications to the Reliability Standards may be appropriate as the resource mix is transformed to one that is more sensitive to severe weather conditions, as some types of severe weather events or conditions could result in the loss of a substantial amount of resources due to fuel concerns).

D. Cold Weather Reliability Standards

18. NERC and the Commission have begun to address the effects of extreme cold weather on generating units, specifically focusing on improved performance of generating units during cold weather conditions. On August 24, 2021, the Commission approved revised Reliability Standards to address some of the reliability risks posed by extreme cold weather.
39

Effective April 2023, those Reliability Standards will,
inter alia,
require generators to implement plans for cold weather preparedness and require the balancing authority, transmission operator, and reliability coordinator to plan and operate the grid reliably during cold weather conditions by requiring the exchange of certain information related to the generator's capability to operate under such conditions.
40

39

N. Am. Elec. Reliability Corp.,
176 FERC ¶ 61,119 (2021). The Commission approved proposed Reliability Standards EOP-011-2 (Emergency Preparedness and Operations); IRO-010-4 (Reliability Coordinator Data Specification and Collection); and TOP-003-5 (Operational Reliability Data) (collectively, the Cold Weather Reliability Standards).

40

Id.
P 3.

19. The proposed improvements to transmission planning discussed in this NOPR and the requirements in the Cold Weather Reliability Standards both work together to mitigate the reliability impact of extreme weather events, such as the 2021 Cold Weather Event in Texas and South-Central United States. To ensure reliability, transmission planning should be considered in the context of generators' performance and availability during extreme heat and cold events.

E. Reliability Standard TPL-001-4 (Transmission System Planning Performance Requirements)

20. Transmission system planning refers to the evaluation of future transmission system performance and creation of corrective action plans that includes mitigation for extreme heat and cold events to remedy identified deficiencies.
41

The planning horizon associated with transmission system planning covers near term (one to five years), long-term (six to 10 years), and beyond.
42

41
NERC Glossary defines “Planning Assessment” as “documented evaluation of future Transmission System performance and Corrective Action Plans to remedy identified deficiencies.”

42

Id.

21. Reliability Standard TPL-001-4, applicable to planning coordinators and transmission planners, establishes minimum transmission system planning performance requirements within the identified planning horizon to plan a Bulk-Power System that will operate reliably over a broad spectrum of system conditions and follow a wide range of probable contingencies.
43

Under Reliability Standard TPL-001-4, and Reliability Standard TPL-001-5.1, Requirement R2, each transmission planner and planning coordinator must prepare an annual planning assessment of its portion of the Bulk-Power System based on current or qualified past studies, document its assumptions, and document the summarized results of the

steady state analyses, short circuit analyses, and stability analyses.
44

This planning assessment is required for both near-term and long-term transmission planning horizons.
45

43
Reliability Standard TPL-001-4, Purpose.

44
Reliability Standard TPL-001-4/5.1, Requirement 2. Further, steady-state analyses are a snapshot in time where load and system conditions (
e.g.,
generators, lines, facilities) are modeled as constant (not as changing over time). The analysis will either solve or diverge (not solved).
See
IEEE,
Transactions on Power Systems, Vol. 19, No. 2,
(May 2004) (power system stability is the ability of an electric power system, for a given initial operating condition, to regain a state of operating equilibrium after being subjected to a physical disturbance, with most system variables bounded so that practically the entire system remains intact);
see also,
Kundur, Prabha,
Power System Stability and Control,
McGraw Hill, at 26 (1994).

45

See
Reliability Standard TPL-001-4, Requirement 2.1 (Near-Term Transmission Planning Horizon) and Requirement R.2.2 (Long-Term Transmission Planning Horizon).

22. Requirements R3 and R4 of Reliability Standard TPL-001-4 require in part that planning coordinators and transmission planners conduct steady state and stability analyses of pre-specified extreme events and evaluate possible actions designed to reduce the likelihood or mitigate the consequences and adverse impacts of the event(s), if the analysis concludes that the pre-selected extreme events cause cascading outages.

23. Table 1 of Reliability Standard TPL-001-4 includes a list of examples of planning events for which specific studies may be required, generally, based on the entity's own evaluation that such an event could occur within its operating area. Section 3.a of Table-1, Steady State & Stability Performance Extreme Events, states that steady state analysis should be conducted for wide-area events affecting the transmission system based on system configuration and how it can be affected by events such as wildfires and severe weather (
e.g.,
hurricanes and tornadoes). In addition, section 3.b serves as a catch-all provision, stating that steady state analysis should be performed for “other events based upon operating experience that may result in wide-area disturbances.”

III. The Need for Reform

A. Recent Events Show Changes in Weather Patterns Resulting in More Extreme Heat and Cold Weather Events

24. Recent extreme weather-related events that spread across large portions of the country over the past decade demonstrate the challenges to transmission planning from extreme heat and cold weather patterns. Since 2011, the country has experienced at least seven major extreme heat and cold weather events; of these, four neared system collapse (2011, 2013, 2018, and 2021 extreme cold weather events) if the operators had not acted to shed load. The remaining three events (2014, 2020, 2021 extreme heat weather events) resulted in generation loss and varying degrees of load shedding.

25. These extreme heat and cold events demonstrate a risk to reliable operation of the Bulk-Power System. Below we discuss in detail how recent extreme cold and heat events have demonstrated such risks, including resource availability, limitations of the transmission system locally and over a wide area, and limitations of interregional transfer capabilities.

26. From February 1 to February 4, 2011, the southwest region of the United States experienced unusually cold and windy weather, referred to as the February 2011 Southwest Cold Weather Event. Low temperatures during the period were in the teens for five consecutive mornings and there were many sustained hours of below freezing temperatures throughout Texas and New Mexico. Low temperatures in Albuquerque, New Mexico ranged from 7 degrees Fahrenheit to minus seven degrees Fahrenheit over the period, compared to a normal range of 51 to 26 degrees Fahrenheit. Temperatures in Dallas, Texas ranged from 19 degrees to 14 degrees Fahrenheit, compared to a normal range of 60 to mid-to-upper 30s degrees Fahrenheit. Many cities in the region did not see temperatures above freezing until February 4, 2011. In addition, sustained high winds of over 20 mph produced severe wind chill factors. The extreme weather conditions resulted in the loss of a significant number of generators which occurred almost simultaneously, causing ERCOT to shed load to prevent widespread, uncontrolled blackouts throughout the entire ERCOT Interconnection.
46

As a result, approximately 4.4 million electric customers were affected over the course of the event.
47

46
FERC and NERC Staff Report,
Outages and Curtailments During the Southwest Cold Weather Event of February 1-5, 2011,
at 7 (Aug. 2011),
https://www.ferc.gov/sites/default/files/2020-05/ReportontheSouthwestColdWeatherEventfromFebruary2011Report.pdf.
Load shedding may be used to reduce an overload condition (such as when thermal limits on a transmission line are exceeded), to recover from an under-frequency condition, or to return voltage to a normal level.

47

Id.
at 1.

27. Two years later, the Midwest and mid-Atlantic experienced unseasonably hot weather from September 9 through September 11, 2013, which led to emergency conditions in the PJM service area. During this period, temperatures ranged from the upper 80s into the 90s Fahrenheit, which in some areas like Cleveland translated into conditions of over 20 degrees above normal.
48

As a result, demand for electricity reached an all-time high for September within PJM's footprint. Transmission owners tend to schedule maintenance outages during the fall and spring, increasing the risk of system stress during periods of weather-related high energy demand, such as occurred in September 2013. PJM implemented controlled outages in a few constrained areas to prevent uncontrolled blackouts over larger areas that could have affected many more customers.
49

In preparation for another day of unseasonably high use of electricity, on September 11, PJM called for voluntary demand response
50

across much of its service area, resulting in a 6,048 MW reduction in electricity demand, the largest amount of demand response PJM had ever received. During the entire event PJM shed 157 MW of load affecting approximately 45,000 customers.
51

48
PJM,
Technical Analysis of Operational Events and Market Impacts during the September 2013 Heat Wave,
at 7, Figure 1, RTO Temperatures (Dec. 23, 2013) (PJM Heat Wave Analysis),
https://www.yumpu.com/en/document/read/40807126/20131223-technical-analysis-of-operational-events-and-market-impacts-during-the-september-2013-heat-wave.

49

Id.
at 4.

50
Under demand response programs, retail customers volunteer and are paid to reduce their electricity use when requested.

51
PJM Heat Wave Analysis at 5.

28. Another extreme event occurred the following year, in early January 2014, when the Midwest, south central, and east coast regions of the country experienced an extreme cold weather event known as the polar vortex, referred to as the January 2014 Polar Vortex Cold Weather Event, where extreme cold resulted in temperatures 20 to 30 degrees Fahrenheit below normal.
52

Some areas faced days that were 35 degrees Fahrenheit or more below their normal temperatures. These extreme temperatures resulted in record high electrical demand on January 6 and again on January 7, 2014. During the January 2014 Polar Vortex Cold Weather Event, the cold weather increased demand for natural gas, which caused a significant amount of gas-fired generation to become unavailable due to unavailability of the non-firm gas purchases they relied on. The cold weather and issues from fuel combined for over 35,000 MW of generator outages during the height of the polar vortex

weather conditions.
53

By employing communication tools, interruptible load, demand-side management tools, and voltage reduction, balancing authorities and load serving entities were mostly able to maintain their operating reserve margins and serve firm load and only one balancing authority was required to shed 300 MW of firm load. Many outages, including a number of those in the southeastern United States, were the result of temperatures that fell below a plant's design basis.
54

52
NERC,
Polar Vortex Review
(Sept. 2014) (Polar Vortex Review),
https://www.nerc.com/pa/rrm/January%202014%20Polar%20Vortex%20Review/Polar_Vortex_Review_29_Sept_2014_Final.pdf.

53

Id.
at 4.

54

Id.
at iii.

29. Further, in mid-January 2018, a large area of the south-central region of the United States saw unusually cold weather, with temperatures dropping from about five degrees Fahrenheit to as much as 27 degrees Fahrenheit below the normal daily minimums. Texas, Louisiana, Arkansas, Oklahoma, Mississippi, Missouri, and other neighboring states were all affected by the extreme cold weather, which lasted from January 12 to January 19, 2018, known as the January 2018 South Central Cold Weather Event.
55

The reliability coordinators in MISO did not anticipate the numerous mitigation measures they would need to take to maintain Bulk-Power System reliability at the peak of the event (January 17, 2018), including transmission loading relief, transmission reconfiguration, and the need to be prepared to shed firm load in the event of an additional contingency in MISO South of 1,163 MW.
56

Although the system remained stable on January 17, 2018, this event represented a near miss of cascading outages.

55
FERC and NERC Staff Report,
The South Central United States Cold Weather Bulk Electric System Event of January 17, 2018,
at 6-8 (July 2019) (2018 Cold Weather Event Report),
https://www.nerc.com/pa/rrm/ea/Documents/South_Central_Cold_Weather_Event_FERC-NERC-Report_20190718.pdf.

56

Id.
at 12.

30. Two years later, the western United States suffered another intense and prolonged heatwave affecting many areas across the Western Interconnection during a five-day period from August 14 through August 19, 2020 (August 2020 California Heatwave Event). With temperatures between 15- and 30-degrees Fahrenheit above normal, many areas in the western parts of the country broke daily heat records. Some areas in the southwest posted record temperatures: Phoenix, Arizona reached a record 115 degrees Fahrenheit. Even cities located further north had similar temperature spikes, with Portland, Oregon, registering 102 degrees Fahrenheit. Because of these high temperatures, electricity demand in the Western Interconnection reached a record high on August 18, 2020.
57

On August 14 and 15, CAISO shed firm load to maintain the operating reserves needed to maintain the reliability and security of the Bulk-Power System. Several other entities reported being one contingency away from needing to shed load as well.
58

57
Western Electricity Coordinating Council,
August 2020 Heatwave Event Analysis Report,
at 1-2 (Mar. 19, 2021) (2020 Heat Event Report),
https://www.wecc.org/Reliability/August%202020%20Heatwave%20Event%20Report.pdf.

58

Id.
at 1.

31. More recently, in February 2021, Texas and the South-Central United States experienced the 2021 Cold Weather Event, the fourth cold-weather-related event in the last ten years to jeopardize Bulk-Power System reliability. Temperatures began to drop below freezing in Texas and the Southwest Power Pool, Inc. (SPP) region on February 8, 2021, but temperatures dropped even lower during the week of February 14, reaching their nadir on February 15 and 16, 2021. Daily low temperatures for February 15th were as much as 40 to 50 degrees lower than average daily minimum temperatures for that day. In addition to the arctic air, the cold front brought periods of freezing precipitation and snow to large parts of Texas and the South Central region, starting February 10, and extending into the week of February 14, 2021.
59

59
2021 Cold Weather Event Report at 9, 12-13.

32. This was the most devastating cold-weather-related event in the last 10 years to impact Bulk-Power System reliability, with a combined 23,418 MW of manual firm load shed, the largest controlled firm load shed event in U.S. history.
60

The unplanned generation outages that escalated during the event, 65,622 MW, were more than four times as large as the previous largest event, in 2011 (14,702 MW).
61

ERCOT faced the greatest challenge due to the magnitude of unplanned generating unit outages in its area, coupled with its limited ability to import power to help offset generation shortfalls. Notably, the entire ERCOT Interconnection has a maximum total import limitation of only 1,220 MW, which limited ERCOT's ability to import electricity to meet demand.
62

In Texas alone, this event resulted in more than 4.5 million people losing power, cost the Texas economy between $80 to $130 billion, and caused at least 210 deaths.
63

Had frequency in Texas remained under its lowest point for an additional five minutes during the peak of the event, approximately 17,000 MW of additional generation would have tripped, potentially blacking out the entire ERCOT Interconnection. In contrast to ERCOT, some regions, such as MISO and SPP, had the ability to import power from the east, where weather conditions were less severe, to make up for a large portion of their generation shortfalls during the event. For example, PJM was exporting an unprecedented amount of electricity into MISO and SPP, reaching over 15,700 MW of interregional transfers on February 15, 2021.
64

60

Id.
at 9.

61

Id.

62

Id.
at 127 n.197.

63

Id.
at 10.

64
PJM Post-Conference Comments at 17-18; 2021 Cold Weather Event Report at 229 n. 355. Interregional transfer capability allows an entity in one region with available energy to assist one or more entities in another region that is experiencing an energy shortfall due to the extreme weather event.

33. Finally, in June 2021 the Pacific Northwest experienced another record-breaking heat wave, referred to as June 2021 the Pacific Northwest Heatwave. During the event, Seattle set an all-time record high temperature of 104 degrees Fahrenheit on June 27, 2021, while Portland had two back-to-back all-time records, on June 26 and 27, 2021, where temperatures reached 108- and 112-degrees Fahrenheit, respectively.
65

While such events are still rare in today's climate, researchers believe such events are likely to become more common in the future.
66

65
Climate Signals,
Northwest Pacific Heat Wave June 2021
(Oct. 2021),
https://www.climatesignals.org/events/northwest-pacific-heat-wave-june-2021#/more.

66
Sjoukje Y. Philip, Sarah F. Kew et al
., Rapid attribution analysis of the extraordinary heatwave on the Pacific Coast of the US and Canada
(June 2021), at 19
9, https://www.worldweatherattribution.org/wp-content/uploads/NW-US-extreme-heat-2021-scientific-report-WWA.pdf.

34. While these wide-area extreme events may not occur every year, their frequency and magnitude are expected to increase. NOAA's data and analyses show an increasing trend in extreme heat and cold events,
67

and the U.S. Environmental Protection Agency climate change indicators also show upward trends in heatwave frequency, duration, and intensity.
68

NOAA states that climate change is also driving more compound events, which are multiple extreme events occurring simultaneously or successively, such as concurrent heat waves and droughts,

and more extreme heat conditions in cities.
69

67
NOAA website,
Climate Data Online
(NOAA website, Climate Data Online),
https://www.ncdc.noaa.gov/cdo-web/.

68
EPA Climate Change Indicators.

69
NOAA website, Climate Data Online.

35. With respect to extreme cold, NOAA explains that accelerated arctic warming is likely contributing to the increasing frequency of Arctic polar vortex-stretching events that deliver extreme cold to the United States and Canada, including the winter 2021 Texas cold wave.
70

NOAA climate data indicates that the occurrence of significant cold weather events is trending higher nationwide.
71

70
NOAA, Climate Program Office,
Research Links Extreme Cold Weather in the United States to Arctic Warming, https://cpo.noaa.gov/Interagency-Programs/NIHHIS/ArtMID/6409/ArticleID/2369/Research-Links-Extreme-Cold-Weather-in-the-United-States-to-Arctic-Warming?msclkid=f9ad03bcc7c911ecba22ebf3e1ead5d9.

71
NOAA website, Climate Data Online.

36. As discussed, the recent extreme heat and cold events have had a significant impact on the reliability of the Bulk-Power System. However, the potential impact of widespread extreme heat and cold events on the reliability of the Bulk-Power System can be modeled and studied in advance as part of near-term and long-term transmission system planning. Transmission planners could use the studies to develop transmission system operational strategies or corrective action plans with mitigation that could be deployed prior to and in preparation for extreme heat and cold events. Examples of such corrective action plans include planning for additional contingency reserves or implementing new energy efficiency programs to decrease load,
72

planning for additional interregional transfer capability, transmission switching/reconfiguration, or adjusting transmission and generation maintenance outages based on longer-lead forecasts. Therefore, given the urgency of addressing the negative impact of extreme weather on the reliability of the Bulk-Power System, the proposed directives to NERC in this NOPR aim to improve system planning specifically for extreme heat and cold weather events.

72
Contingency reserves would only contribute to a corrective action plan to the extent that they are expected to perform during the applicable modeled extreme weather event(s) and thereby contribute to meeting the applicable performance criteria. Accordingly, if for instance, extreme cold is anticipated to cause fuel unavailability for the applicable area, a corrective action plan would need to account for such limitations.

B. NERC Reliability Standards Do Not Require Planning To Minimize the Increasing Reliability Risks Associated With Anticipated Extreme Heat and Cold Weather Events

37. The currently effective Reliability Standard TPL-001-4 and the to-be-effective TPL-001-5.1, Requirements R3 and R4 require steady state and stability analyses to be performed for extreme events “listed in Table 1 that are expected to produce more severe system impacts.” Table 1, Steady State & Stability Performance Extreme Events, under the Steady State analysis, sections 3.a.iii and 3.a.iv lists wildfires and severe weather (
e.g.,
hurricanes and tornadoes) as potential events that could be studied. However, neither Requirements R3 or R4, nor the associated Table 1 specifically require steady state analyses for extreme heat and cold conditions to be completed as part of the transmission planner's or planning coordinator's planning assessment. Finally, Table 1, provisions 2.f (stability) and 3.b (steady state), require the responsible entities to study events based on operating experience that may result in a wide-area disturbance, but they do not specify the study of extreme heat or cold conditions.

38. System planning measures alone will not eliminate the reliability risk associated with extreme heat and cold events. However, system planning will limit the impact of such events and reduce the risk to the reliability of the Bulk-Power System, which prior events demonstrate is significant.

39. The country experienced wide-spread cold weather events in 2011, 2014, 2018, and 2021. With the exception of the January 2018 South Central Cold Weather Event, planned and unplanned generating unit outages caused energy emergencies and triggered the need for firm load shed. As evidenced by the last cold weather event in 2021, where generation loss and loss of load were the most extreme, it becomes increasingly more important to consider changes in transmission planning. Although during the January 2018 South Central Cold Weather Event the system remained stable, the 2018 Cold Weather Event Report addressing this specific event recommended that MISO and other reliability coordinators perform voltage stability analyses when under similarly constrained conditions, benchmark planning and operations models against actual events that strained the system, perform periodic impact studies to identify which elements in the adjacent reliability coordinators' systems have the most impact on their own systems, and perform drills with entities involved in load shedding to prepare to execute load-shedding for maintaining reserves while at the same time alleviating severe transmission conditions.
73

73
2018 Cold Weather Event Report at 12-13.

40. Having the necessary data and performing modeling in advance of extreme cold temperatures could allow transmission planners and operators to assess the potential impact of an event to identify corrective actions that could be taken well in advance of the event. Such action could include ensuring generators have winterized their equipment, scheduling fewer planned outages of generating units and transmission lines, and endeavoring to maintain transmission ties intact to: (1) permit maximum transfers to an area experiencing a deficiency in generation; (2) minimize the possibility of cascading outages; and (3) assist in restoring operation to normal.
74

While these corrective action plans may not fully mitigate the potential impact of these events, they could minimize the impact and reduce system restoration time.

74
ERCOT,
Nodal Operating Guide,
at 137 (Jan. 1, 2022),
https://www.ercot.com/files/docs/2021/12/21/Nodal%20Operating%20Guide.pdf.

41. Past experience can inform how steady state and stability analyses should model transmission and generator outages, including availability of wind, natural gas, and other resources sensitive to extreme cold conditions. For example, the February 2021 cold weather-related outages in Texas and the south-central United States caused 4,125 outages/derates of generating units (
i.e.,
approximately 456 GW during event in total event area). Of the total generation losses, 59% were gas-fired generating units due to fuel issues
75

and a pipeline equipment failure, and 27% were wind generation due to blade icing.
76

75
Fuel issues included 87% natural gas fuel supply issues (decreased natural gas production, terms and conditions of natural gas commodity and transportation contracts, low pipeline pressure and other issues) and 13% other fuel issues.

76
2021 Cold Weather Event Report at 163.

42. While heat events have different planning challenges, they also present a serious risk to the Bulk-Power System and often require operators to shed load to maintain system stability. The recent extreme heat events resulted in a variety of reliability issues such as controlled rolling blackouts and transmission congestion. During the August 2020 California Heatwave Event, wind production was low during the evenings, and solar generation was declining during the peak demand hours, leading to reserve shortages.

Similar to Texas, California relies on wind and solar generation to meet normal peak day demand, but wind and solar generation were largely unavailable. Steady state and stability analyses of study cases modeled to reflect past extreme conditions as well as modeling of availability of generation resources during extreme heat conditions in the planning process could have better prepared the transmission operators for such conditions.

43. Past extreme heat and cold events discussed above demonstrate the importance of assessing resource and reserve requirements under extreme heat and cold weather conditions. Developing and using extreme heat and cold weather scenarios in planning analyses will help to identify the potential risks that extreme events may pose to the Bulk-Power System. Based on the risks identified, appropriate mitigations or corrective action plans such as requiring additional reserves and transfer capability can be developed and deployed to address the risks and specify what should be planned for the longer term to ensure the availability of electricity in real time.

44. NERC recognizes that extreme events present a reliability risk and there are opportunities to improve the transmission planning processes. Following the 2021 extreme cold weather event, NERC issued a level 2 NERC Alert to industry on cold weather preparations for extreme weather events with five recommendations to assist reliability coordinators, balancing authorities, transmission operators, and generator owners in preparing for the winter season. NERC's level 2 Alerts recommend but do not mandate registered entities to take specific actions.
77

The Alert recommended seasonal operating plans for the upcoming winter season, which would include plans to utilize additional transmission capacity, consideration of the import capability of the system and resource availability constraints on external systems, and load forecasting practices that consider extreme events, among other recommendations.
78

The NERC Alert did not include any recommendations concerning long-term transmission planning.

77
NERC,
About Alerts, https://www.nerc.com/pa/rrm/bpsa/Pages/About-Alerts.aspx.

78
NERC,
Alert R-2021-08-18-01 Extreme Cold Weather Events
(Aug. 18, 2021),
https://www.nerc.com/pa/rrm/bpsa/Alerts%20DL/NERC%20Alert%20R-2021-08-18-01%20Extreme%20Cold%20Weather%20Events.pdf.

45. In addition, in 2021 NERC formed the Energy Reliability Assessment Task Force (ERATF) to assess risks associated with unassured energy supplies, including the inconsistent output from variable renewable energy resources, fuel location, and volatility in forecasted load, which can result in insufficient amounts of energy on the system to serve electrical demand.
79

The ERATF uses resource adequacy models to address energy availability concerns related to the operations planning horizon (
i.e.,
one day to one year) and near-term planning horizon (
i.e.,
one to five years).
80

In December of 2021, the ERATF prepared a draft Standard Authorization Request (SAR) and based on the comments to the SAR, two SARs were created: a planning SAR and an operations/operations planning SAR, aiming to create or modify NERC Reliability Standards across the operations/operational planning time horizon and the planning time horizon. To discuss this latest update with industry members, NERC held an informational Webinar on May 19, 2022, and the two SARs were scheduled for committee consideration on June 8, 2022.
81

79
NERC,
Energy Reliability Assessment Task Force website,
(ERAFT website),
https://www.nerc.com/comm/RSTC/Pages/ERATF.aspx#:~:text=%E2%80%8B%E2%80%8B%E2%80%8B%E2%80%8B%E2%80%8B,insufficient%20amounts%20of%20energy%20on.

80
NERC Post-Technical Conference Comments at 7.

81
NERC,
Informational Webinar: Industry Webinar Energy Reliability Assessment Task Force Update on the Revised SARs
(May 19, 2022),
https://www.nerc.com/pa/RAPA/Lists/RAPA/DispForm.aspx?ID=480
; NERC,
Reliability and Security Technical Committee Meeting Agenda,
SAR Draft.

46. While these ongoing efforts by NERC and industry members are intended to improve system reliability, they do not directly address the gap in transmission planning related to extreme heat and cold weather. NERC acknowledges that heat and cold events have effects on the grid but at this time has not determined that modifications to TPL-001-5.1 are needed to address extreme weather events.
82

82
NERC,
2021 ERO Reliability Risk Priorities Report,
Risk Profile 2, at 26 (July 2021),
https://www.nerc.com/comm/RISC/Documents/RISC%20ERO%20Priorities%20Report_Final_RISC_Approved_July_8_2021_Board_Submitted_Copy.pdf; see also
NERC Post-Conference Comments at 5 (referencing Reliability Standard TPL-001-4, NERC states that “[w]ith respect to extreme weather more generally, NERC staff will continue to examine the Reliability Standards to determine if other modifications are needed.”).

IV. Proposed Directives

47. We preliminarily find that a reliability gap exists in Reliability Standard TPL-001-5.1 with respect to a lack of a long-term planning requirement for extreme heat and cold weather events. Accordingly, pursuant to section 215(d)(5) of the FPA, we propose to direct that NERC develop modifications to Reliability Standard TPL-001-5.1 to require: (1) development of benchmark planning cases based on information such as major prior extreme heat and cold weather events or future meteorological projections;
83

(2) planning for extreme heat and cold events using steady state and transient stability analyses expanded to consider a range of extreme heat and cold weather scenarios (
i.e.,
sensitivities to be applied to the benchmark base case(s)), including the expected resource mix's availability during extreme heat and cold weather conditions, and including the broad area impacts of extreme heat and cold weather; and (3) corrective action plans that include mitigation for any instances where performance requirements for extreme heat and cold events are not met. We further elaborate on the substance of these proposed directives below. In proposing to direct NERC to develop modifications to Reliability Standard TPL-001-5.1, we are not proposing specific requirements; we are identifying concerns that we believe should be addressed. NERC may propose to develop new or modified Reliability Standards that address these concerns in an equally efficient and effective manner as the requirements proposed in this paragraph; however, NERC must explain how its proposal addresses the Commission's concerns.
84

83
For instance, a benchmark event could be constructed based on data from a major prior extreme heat or cold event, with adjustments if necessary to account for the fact that future meteorological projections may estimate that similar events in the future are likely to be more extreme.

84
Order No. 693, 118 FERC ¶ 61,218 at P 186;
Reliability Standards for Physical Sec. Measures,
146 FERC ¶ 61,166 at P 13.

48. We further propose to direct NERC to submit modifications to Reliability Standard TPL-001-5.1 within one year of the effective date of a final rule in this proceeding with compliance obligations for all proposed new or modified Reliability Standards beginning no later than 12 months from the date of Commission approval of the modified Reliability Standard. Finally, we invite comments on whether to also direct NERC to address in Reliability Standard TPL-001-5.1 other extreme weather-related events.

49. Below we provide additional context for these three proposed directives and describe reliability concerns and potential options for

consideration that we believe would address these concerns.

A. Develop Benchmark Planning Cases Based on Major Prior Extreme Heat and Cold Weather Events

50. As part of its revisions to Reliability Standard TPL-001-5.1, we are proposing to direct that NERC develop requirements that address the types of extreme heat and cold scenarios the responsible entities are required to study. Reliability Standard TPL-001-5.1 does not require any specific approach to studying extreme heat and cold events and we are concerned that, without specific requirements describing the types of heat and cold scenarios that entities must study, the standard may not provide a significant improvement upon the status quo.

51. To accomplish this, the modified Reliability Standard developed by NERC should include benchmark events that responsible entities must study, as well as guidelines regarding which range of sensitivities must be applied to these benchmark event scenarios. Such benchmark events should be based on prior events (
e.g.,
February 2011 Southwest Cold Weather Event, January 2014 Polar Vortex Cold Weather Event) and/or constructed based on meteorological projections, as described above. In addition to providing valuable case study information to be applied to possible comparable future events, these events will also serve as a basis for effectively using assets and resources. Once developed, the results of the benchmark events studies could be applied to determine the limitations of the transmission system locally and over a wide-area, and to understand resource availability and potential firm load shedding requirements under stressed conditions.

52. While extreme weather risks may vary from region to region and change over time, it is important that transmission planners and planning coordinators likely to be impacted by the same types of extreme weather events use consistent benchmark events. In determining an appropriate benchmark event, NERC should consider approaches to provide a uniform framework while still recognizing regional differences. For example, NERC could define benchmark events around a projected frequency (
e.g.,
1-in-50-year event) or probability distribution (95th percentile event),

53. We propose to provide NERC with flexibility in defining one or more appropriate benchmark events. For example, one approach could be for NERC to develop the common benchmark event or events through the standards development process and include the relevant parameters of the benchmark event or events in the modified reliability standard. Another approach could be to include in the modified standard the primary features of the benchmark event or events (
e.g.,
the expected occurrence such as one-in-50 years) while designating another set of entities, such as the Regional Entities, reliability coordinators, or even NERC itself, as responsible for periodically updating key aspects of the benchmark events based on the most up-to-date data. Such a method for developing benchmark events and scenarios could establish a common design basis across the industry while still recognizing regional differences in climate and weather patterns. We seek comment on whether, and to what extent, it may be appropriate to allow designated entities to periodically update key aspects of the benchmark events.

54. As discussed further below, establishing one or more benchmark events should form the basis for sensitivity analysis, which provide better visibility into the actual system conditions during extreme heat and cold. For example, sensitivity analysis could include analysis of simultaneously varying generation dispatch (
e.g.,
wind, solar, natural gas, and other fuel generation availability), system transfers, and load, which have been observed during prior extreme heat and cold events.

55. In addition to establishing requirements that address the extreme heat and cold scenarios that responsible entities are required to study, NERC could also establish measures of system performance (stability, voltage, thermal limits, etc.) to determine whether the responsible entities must implement a corrective action plan. Performance requirements are a corollary to study requirements—without clear performance requirements, the obligations on responsible entities to mitigate issues with system performance may be unclear. Moreover, performance requirements are an integral part of the existing Reliability Standard TPL-001-5.1.
85

Accordingly, NERC should incorporate performance requirements for extreme heat and cold conditions when modifying TPL-001-5.1.

85

See
Reliability Standard TPL-001-5.1 (Transmission System Planning Performance Requirements), Requirements R1 through R8.

56. In establishing any proposed performance requirements, NERC should seek to prevent system instability, uncontrolled separation, and cascading outages. While load shedding could still occur during extreme heat and cold events to prevent instability, uncontrolled separation, and cascading, it should be minimized as much as possible. Developing benchmark events and associated corrective actions to be deployed prior to and during the event, would result in better system performance in real time.

B. Transmission System Planning for Extreme Heat and Cold Weather Events

57. As discussed above, we propose to direct that NERC develop modifications to Reliability Standard TPL-001-5.1 to require planning for extreme heat and cold events using steady state and transient stability analyses expanded to consider a range of extreme heat and cold weather scenarios including the expected resource mix's availability during extreme heat and cold weather conditions, and including the broad area impacts of extreme heat and cold weather. In this section, we discuss six topics which NERC would be required to address in a modified Reliability Standard pursuant to the proposed directive: (1) steady state and transient stability analysis; (2) transmission planning studies of wide area issues; (3) concurrent generator and transmission outages; (4) sensitivity analysis; (5) consideration of modifications to the traditional planning approach; and (6) coordination among planning coordinators and transmission planners and sharing of results. We note that a range of methods/approaches could satisfy the Commission's directive with regard to issues (3) through (6). NERC would retain flexibility with regard to
how
to address these topics, so long as it incorporates them into its proposed solution. To better inform our directive to NERC in the final rule, we invite comments on these matters.

1. Steady State and Transient Stability Analyses

58. To maintain and improve the reliability of the Bulk-Power System, it is important to conduct both steady state and stability analyses for extreme heat and cold events as part of transmission planning studies. As discussed above, steady state and stability analyses of study cases modeled to reflect past and forecasted extreme heat and cold conditions would better prepare transmission operators for such conditions. Further, this approach is consistent with Reliability Standard TPL-001-5.1, which requires both steady state and stability analyses for extreme events identified in Table 1 of the Standard. Performing these studies in the long-term planning horizon time frame (
i.e.,
five to 10 years) will provide an adequate lead time for entities to

develop and implement corrective action plans to reduce the likelihood or mitigate the consequences and adverse impacts of such events.

59. A steady-state analysis or assessment is based on a snapshot in time where bulk-electric system facilities such as generators, transmission lines, transformers, etc. are modeled as fixed and load is modeled as a constant. The steady state analysis assesses the ability of the system to deliver electricity to load within the ratings and constraints of generators and transmission lines. It also includes a contingency analysis to predict electrical system conditions when elements are removed from the base case.
86

86
NERC,
Compliance Implementation Guidance Real-time Assessment Quality of Analysis,
at 3 (May 2019),
https://www.nerc.com/pa/comp/guidance/EROEndorsedImplementationGuidance/TOP-010-1(i)%2520R3%2520and%2520IRO-018-1(i)%2520R2%2520-%2520RTA%2520Quality%2520of%2520Analysis%2520(OC).pdf.

60. Transient stability or dynamic studies add to the steady state analyses simulate the time-varying characteristics of the system during a disturbance that occurs during an extreme heat or cold weather event. They are time-domain analyses that assess angular stability, voltage stability, and frequency excursions.
87

Transient angular stability is the ability of interconnected synchronous machines of a power system to remain in synchronism after being subjected to a disturbance (
i.e.,
fault, sudden loss of load, and generation tripping).
88

Transient voltage stability refers to the ability of a power system to maintain steady voltages at all buses in the system after being subjected to a disturbance.
89

87
Indian Institute of Technology Patna,
Power System Dynamics and Control,
at 1, (Power System Dynamics),
https://www.iitp.ac.in/~siva/2022/ee549/Introduction_Power_System_Stability.pdf.

88

Id.
at 3.

89

Id.
at 15.

61. While we recognize dynamic studies can be more resource intensive to perform, we believe that the consideration of both types of studies is important to understand the potential impacts of extreme heat and cold weather events. We believe the consideration of dynamic studies is particularly important given the changing resource mix and the need to understand the dynamic behavior of both traditional generators as well as variable energy resources (VER) (mainly wind and photovoltaic solar).

62. To that end, we seek comments on whether planning coordinators and transmission planners should include contingencies based on their planning area and perform both steady state and transient stability (dynamic) analyses using extreme heat and cold cases. We are inviting comments on the following topics regarding planning for extreme heat and cold weather conditions: (1) the set of contingencies planning coordinators and transmission planners must consider; (2) required analyses to ensure system stability, frequency excursion and angular deviations caused as a result of near simultaneous outages or common mode failures of VERs; and (3) the role of demand response under such scenarios.

63. Finally, we emphasize the continued importance of ensuring that entities responsible for performing assessments under TPL-001-5.1 are able to obtain the necessary data. Currently, the data for steady-state, dynamic, and short circuit modeling can be obtained pursuant to Reliability Standard MOD-32-1, Requirement 1 (Data for Power System Modeling and Analysis), which is referenced in Reliability Standard TPL-001-5.1. Specifically, Reliability Standard MOD-32-1 allows planning coordinators and transmission planners to request data from the generator owners and transmission owners, which are obligated to provide the specified data.
90

Consistent with the existing standards, we believe it is important for NERC to ensure that registered entities responsible for performing studies of extreme weather are able to access the data necessary to complete such studies. Accordingly, we seek comment on whether the existing Reliability Standards are sufficient to ensure that responsible entities performing studies of extreme heat and cold weather conditions have the necessary data, or whether the Commission should direct additional changes pursuant to FPA 215(d)(5) to address that issue.

90
Reliability Standard MOD-032-1, Requirements R1 and R2.

2. Transmission Planning Studies of Wide-Area Events

64. As discussed above, our proposed directive would include modifications to TPL-001-5.1 to require transmission planning studies that consider the broad area impacts of extreme heat and cold weather. The effects of extreme weather events on the reliable operation of the Bulk-Power System can be widespread, potentially causing simultaneous loss of generation and increased transmission constraints within and across regions. The studies required by TPL-001-5.1, however, have traditionally focused on local planning and typically do not address the issues caused by wide-area extreme heat and cold weather events on a regional or interconnection scale.
91

91
June 1, 2021 Tr. 153: 2-9. (Frederick Heinle, Assistant People's Counsel, Office of the People's Counsel for the District of Columbia).

65. Reliability Standard TPL-001-5.1 does not contemplate the consideration of impacts from wide-area events
92

that may impact multiple planning coordinators simultaneously; in contrast, TPL-001-5.1 only requires identifying and evaluating selected wide-area events resulting from conditions such as loss of a large gas pipeline into a region or multiple regions that have significant gas-fired generation, and does not specify studying potential issues resulting from extreme heat and cold.
93

92
Reliability Standard TPL-001-5.1, Table 1, Steady State & Stability Performance Extreme Events, uses the term “wide area events” to refer to such things as loss of two generating stations resulting from conditions including severe weather or wildfires, distinguishing such events from “local area events” affecting the transmission system, which may involve the isolated loss of a transmission tower, substation, or generating station.

93
Reliability Standard TPL-001-5.1, Table 1, Steady State & Stability Performance Extreme Events, Section 3(a)(i).

66. Failure to study the wide-area impact of extreme heat or extreme cold weather conditions when an entity conducts transmission planning, could result in reliability issues that simultaneously affect multiple regions to remain undetected in the long-term planning horizon. This, in turn, could lead to otherwise avoidable situations where the system is one contingency away from voltage collapse and uncontrolled blackouts.

67. Based on prior events, we preliminarily find that it is appropriate that the study criteria for extreme heat and cold events include a consideration of wide-area conditions affecting neighboring regions and their impact on one planning area's ability to rely on the resources of another region during the weather event. To identify opportunities for improved wide-area planning studies and coordination, we seek comment on: (1) whether wide-area planning studies should be defined geographically or electrically; (2) which entities should oversee and coordinate the wide-area planning models and studies (
e.g.,
reliability coordinators, regional planning groups); (3) which entities should have responsibility to address the results of the studies, and how they should communicate those results among transmission planners; and (4) how to develop corrective action plans that mitigate issues that require corrective action by, and coordination among, multiple transmission owners.

3. Study Concurrent Generator and Transmission Outages

68. Concurrent outages occur nearly simultaneously in different planning areas due to the same extreme weather events, such as the unplanned generator outages associated with the major extreme heat and cold events discussed above. Generation resources that are sensitive to severe weather conditions may cease operation during extreme heat and cold events, thus contributing to wide-area concurrent outages. In addition, the performance of power transformers, transmission lines, and other equipment degrades under extreme heat and may have to come out of service. Extreme heat could lead to significant derating, reduced lifetime, and even possible failures of power transformers, while extreme cold could lead to at least temporary facility transmission outages.
94

94
MIT News,
Preventing the Next Blackout
(Dec. 5, 2017),
https://news.mit.edu/2017/mit-study-climate-change-effects-large-transformers-1205; see also
IEEE Standard C57.91-2011, Table 2; IEEE Standard C57.91-2011, Table 3; 2021 Cold Weather Event Report at 95.

69. Therefore, modeling the loss of these generators and transmission equipment during extreme heat and cold weather events would allow planners to determine the effects of potential concurrent transmission and generator outages and study the feasibility (
i.e.,
availability and deliverability) of external generation resources that could possibly be imported to serve load during such events, thereby minimizing the potential impact of extreme heat and cold events on customers.
95

Modeling concurrent generator and transmission outages would also allow planners to better identify appropriate solutions to be incorporated into corrective action plans.

95
The Cold Weather Reliability Standards referenced
supra
take effect in April 2023, and are expected to improve generating unit performance and help alleviate some of the unsustainable levels of generation outages seen during extreme events. Improved transmission planning alone cannot overcome the challenges associated with generator outages during extreme events. Therefore, both the Cold Weather Reliability Standards and this proposal to improve transmission planning are necessary for the Bulk Power System to perform reliably in the face of future extreme weather events.

70. Extreme cold effects on generators vary by generator type, cooling systems, and fuel sources.
96

Transmission planners commonly assume that the failures of individual generators are independent. This understanding, however, is inconsistent with documented historical events, that show multiple coincident outages due to the same cause. For instance, the 2021 extreme cold event demonstrated the limitations of such an assumption. Between February 8 and February 20, 2021, approximately 44% of generator outages were caused by freezing issues, 31% by fuel issues related to extreme cold weather, and another 21% were caused by mechanical/electrical failures related to cold weather.
97

Meanwhile, wind turbine generators were the second largest share of individual generating units after gas-fired generators that suffered freezing issues in the southern part of SPP and Texas, as temperatures dropped well below zero degrees Fahrenheit.
98

Transmission facilities were also affected in the short-term, as transmission operators managed to return them into service.
99

Likewise, the 2018 Cold Weather Event Report revealed that there is a high correlation between generator outages and cold temperatures, indicating that as temperatures decrease, unplanned generator outages and derates increase.
100

96
Polar Vortex Review at 12.

97
2021 Cold Weather Event Report at 15-16.

98

Id.
at 75.

99

Id.
at 95.

100
2018 Cold Weather Event Report at 80.

71. Similarly, extreme heat impacts on generators vary by generator type, and the common implication is a reduction in the overall generation capacity throughout the wide area affected by the heat event.
101

Generally, extreme heat poses more of a threat to the functioning of a solar panel than extreme cold. As temperatures increase above 77 degrees Fahrenheit, which is a standard test condition, solar panels generate less voltage and become less efficient,
102

producing less power for a given amount of solar energy depending on the solar panel temperature coefficient.
103

For example, during the 2020 heat event in California, wind and solar generation were largely unavailable.
104

While extreme cold temperatures on clear days would not negatively impact energy output. Also, solar panels are built to be waterproof to protect the electronic components against heavy rain and to withstand hailstorms. However, snow,
105

ice accumulation, or cloud cover that commonly accompany extreme cold weather could prevent the panels from receiving as much sunlight, which would limit their power production and efficiency.

101
Department of Energy,
U.S. Energy Sector Vulnerabilities to Climate Change and Extreme Weather, Department of Energy,
at 19-22 (July 11, 2013),
https://www.energy.gov/sites/default/files/2013/07/f2/20130716-Energy%20Sector%20Vulnerabilities%20Report.pdf
(listing the impacts of increased ambient air temperature on the various types of generators).

102
IEEEXplore, International Conference on Current Trends in Computer, Electrical, Electronics and Communication (ICCTCEEC-2017),
Effect of Temperature on Performance of Solar Panels—Analysis, https://ieeexplore.ieee.org/stamp/stamp.jsp?tp=&arnumber=8455109.

103
Temperature coefficient describes the percentage of power output that is lost by a specific solar panel as the temperature rises above 77 degrees Fahrenheit.

104
2020 Heat Event Report at 11.

105
A recent study by Sandia National Labs identified snow events as causing the largest performance reductions at solar facilities.
See
Nicole D. Jackson & Thushara Gunda,
Evaluation of Extreme Weather Impacts on Utility-Scale Photovoltaic Plant Performance in the United States,
302, Applied Energy, 1:7 (2021),
https://www.researchgate.net/publication/353944206_Evaluation_of_extreme_weather_impacts_on_utility-scale_photovoltaic_plant_performance_in_the_United_States.

72. Requiring transmission planners and planning coordinators to study concurrent generator and transmission failures under extreme heat and cold events is one way to address the reliability gap. Accounting for concurrent outages in planning studies would provide a more realistic assessment of system conditions (
i.e.,
updated conditions based on historic benchmarked performance) during potential extreme heat and cold events and will help better assess the probability of potential occurrences of cascading outages, uncontrolled separation, or instability. Transmission planners and planning coordinators could also model the derating and possible loss of wind and solar generators, as well as natural gas generators sensitive to extreme heat and cold conditions. To identify the scope of these planning studies, we are seeking comments on: (1) the assumptions (
e.g.,
weather forecast, load forecast, transmission voltage levels, generator types, multi-day low wind, solar event, etc.) used in modeling of concurrent outages due to extreme heat and cold weather events; (2) what assumptions should be included when performing modeling and planning for generators sensitive to extreme heat and cold; (3) how the impact of loss of generators sensitive to extreme heat and cold should be factored into long-term planning; (4) the extent of neighboring systems' or planning areas' outages that should be modeled in transmission planning studies; and (5) whether a certain threshold of penetration of wind, solar generation, and natural gas generators should trigger additional analyses.

4. Sensitivity Analysis

73. As part of its revisions to TPL-001-5.1, NERC should establish a requirement for sensitivity analysis for

transmission planners and planning coordinators to consider system models and sensitivity cases when assessing extreme heat and extreme cold weather. A sensitivity case is a variation from the base case that helps a transmission planner to determine if the results are sensitive to changes in the inputs. Reliability Standard TPL-001-5.1, Requirement R2.1.4 requires that sensitivity power flow cases be used to demonstrate the impact of changes to the basic assumptions used in the models for system peak load or system off-peak load. These changes include, among other things, conditions that vary with temperature; specifically, load, generation, and system transfers.
106

While requiring the variation of one of the specified conditions to demonstrate a measurable change, it does not require the simultaneous variation of load, generation and transfers necessary to model conditions that reflect extreme heat or cold weather conditions, thus potentially causing major reliability issues (
i.e.,
widespread outages, cascading, etc.) to remain overlooked and undetected in the planning horizon. To model the effect of extreme heat or cold weather, demand probability scenario cases (90/10, 80/20, 50/50),
107

generators that are affected by these events (
i.e.,
wind tripping off, solar dropping off, gas plants not operational due to gas restrictions/freeze-offs, etc.), and transfer levels need to be defined and modeled in sensitivity analyses.

106
To effectively model the Bulk-Power System, transmission planners need make assumptions that create scenarios that are valid, realistic, and defendable.
See
North American Transmission Forum, TPL-001-4 Reference Document, at 8-9 (Aug. 2, 2021),
https://www.natf.net/docs/natf/documents/resources/planning-and-modeling/natf-tpl-001-4-reference-document.pdf.
Specifically, appropriate assumptions and corresponding model adjustments need to be made regarding load (demand), generation (particularly that of renewables), and transfers (power flows between regions or zones).
See
National Renewable Energy Laboratory,
Report: The Evolving Role of Extreme Weather Events in the U.S. Power System with High Levels of Variable Renewable Energy
(Dec. 2021),
https://www.nrel.gov/docs/fy22osti/78394.pdf.

107
Demand scenario cases are given designations based on the percent probability the actual system's peak demand for the period under study will be above or below certain level. For example, for a 90/10 case, the system demand is modeled at a level that there is a 90% probability the actual system demand will be below that level and a 10% probability that the actual system demand will be above that level. Other designations follow similarly using different percentages.

74. Therefore, we seek comment on: (1) requiring transmission planners and planning coordinators to assess reliability in the planning horizon for sensitivity cases in which multiple inputs,
e.g.,
load and generator failures, change simultaneously during extreme heat and cold events; and (2) the range of factors and the number of sensitivity cases that should be considered to ensure reliable planning.

5. Modifications to the Traditional Planning Approach

75. In modifying TPL-001-5.1, we propose to direct NERC to consider planning methods and techniques that diverge from past Reliability Standard requirements.
108

Reliability Standard TPL-001-5.1 is based on a deterministic approach, which uses planned contingencies and definite performance criteria to study system response to various conditions. This approach yields accurate planning when the power supply is highly dispatchable, weather is predictable, and near-record peak demand is reached only a few days a year.
109

However, the current planning approach applied in Reliability Standard TPL-001-5.1 likely is not sufficient to accurately characterize the reliability risk from extreme heat and cold weather given the high degree of uncertainty inherent in predicting severe weather and its impact on generation resources, transmission, and load.

108
We are not making a proposed finding at this time that modifications to the traditional planning approach are necessary to properly plan for extreme weather. Nonetheless, there is sufficient concern such that we believe NERC should consider alternative approaches when developing a new or modified Reliability Standard in response to a final rule in this proceeding.

109
June 1, 2021 Tr. 31 (Barton).

76. An alternative to the deterministic approach is to use probabilistic approaches in transmission planning. Probabilistic transmission planning captures random uncertainties in power system planning, including those in load forecasting, generator performance, and failures of system equipment. The probabilistic method is not intended to replace the deterministic criterion but adds one more dimension to enhance the transmission planning process.
110

110
IEEE Explore,
Probabilistic Planning of Transmission Systems: Why, How and an Actual Example,
at 1 (July 2008),
https://ieeexplore.ieee.org/document/4596093.

77. NERC has recognized the need to incorporate probabilistic approaches into planning activities. For example, NERC's Probabilistic Assessment Working Group develops probabilistic analysis that contributes to NERC's Long-Term Reliability Assessment every other year. NERC is also investigating the development of probabilistic methods to study resource adequacy, energy sufficiency, and transmission adequacy for reliable delivery in composite reliability studies as well as to develop enhanced reliability metrics.
111

111
NERC Post-Technical Conference Comments 3.

78. Therefore, to ensure reliable planning and operations in response to extreme heat and cold events, we believe that a new or modified approach may be beneficial to capture these events during the planning process. The new approach could include elements of both deterministic and probabilistic approaches to assess reliability outcomes. For example, the January 2018 South Central Cold Weather Event in the South Central part of the country was a near-miss where MISO would have been required to perform firm load shed if its next-worst contingency occurred (
i.e.,
outage of 1,163 MW generation in MISO South). The load shed would have been needed to alleviate low voltages at many locations that would have been significantly below their limits due to the failure of almost 200 generating units. Including scenarios in the planning process in which generator failures are probabilistically evaluated could result in a planning approach better prepared to ensure reliable outcomes compared to the existing planning requirements under Reliability Standard TPL-001-5.1.

79. One option to modify the existing planning approach would be to expand the required deterministic studies to include probabilistically developed scenarios. Therefore, we seek comments on industry's experience and opinion on combining or layering probabilistic and deterministic approaches when planning for extreme heat and cold weather conditions in the context of Reliability Standard TPL-001-5.1. Specifically, we seek comments on the use of the proposed hybrid planning approach and: (1) the assumptions from the deterministic and probabilistic approaches that should be applied to study extreme heat and cold weather events; (2) the potential planning challenges from combining the two planning approaches; (3) the costs associated with adjustments to the currently applied deterministic approach; (4) the implementation period necessary for proposed changes; and (5) the reliability benefits that could result.

6. Coordination Among Planning Coordinators and Transmission Planners and Sharing of Study Results

80. Reliability Standard TPL-001-5.1 cross-refences Reliability Standard MOD-032-1 (Data for Power System Modeling and Analysis), which establishes consistent modeling data requirements and reporting procedures

for development of planning horizon cases necessary to support analysis of the reliability of the interconnected transmission system. Reliability Standard MOD-032-1 ensures adequate means of data collection for transmission planning. It requires each balancing authority, generator owner, load serving entity, resource planner, transmission owner, and transmission service provider to provide steady-state, dynamic, and short circuit modeling data to its transmission planner(s) and planning coordinator(s). The modeling data is then shared pursuant to the data requirements and reporting procedures developed by the transmission planner and planning coordinator as set forth in Reliability Standard TPL-001-5.1, Requirement R1.

81. While balancing authorities and other entities must share system information and study results with their transmission and planning coordinator pursuant to Reliability Standards MOD-032-1 and TPL-001-5.1 as described above, there is no required sharing of such information—or required coordination—among planning coordinators and transmission planners with transmission operators, transmission owners, and generator owners, thus limiting the benefits of additional modeling. Sharing system information and study results and enhancing coordination among these entities for extreme heat and cold weather events could result in more representative planning models by better: (1) integrating and including operations concerns (
e.g.,
lessons learned from past issues including corrective actions and projected outcomes from these actions, evolving issues concerning extreme heat/cold) in planning models; and (2) conveying reliability concerns from planning studies (
e.g.,
potential widespread cascading, islanding, significant loss of load, blackout, etc.) as they pertain to extreme heat or cold.

82. Therefore, as part of its revisions, NERC should require system information and study results sharing, and coordination among planning coordinators and transmission planners with transmission operators, transmission owners, and generator owners for extreme heat and cold weather events. To better understand the benefits of the suggested actions, we are inviting comments on: (1) the parameters and timing of coordination and sharing; (2) specific protocols that may need to be established for efficient coordination practices; and (3) potential impediments to the proposed coordination efforts.

C. Implement a Corrective Action Plan If Performance Standards Are Not Met

83. Pursuant to FPA 215(d)(5), we propose to direct NERC to modify Reliability Standard TPL-001-5.1 to require corrective action plans that include mitigation for any instances where performance requirements for extreme heat and cold events are not met. Under the currently effective Reliability Standard TPL-001-4, planning coordinators and transmission planners are required to evaluate possible actions to reduce the likelihood or mitigate the consequences of extreme events but are not obligated to develop corrective action plans. Specifically, if such events are found to cause cascading outages, they need only be evaluated for possible actions designed to reduce their likelihood or mitigate their consequences and adverse impacts.
112

Accordingly, because of their potential severity, we believe that extreme heat and cold weather events should require evaluation and the development and implementation of corrective action plans to help protect against system instability, uncontrolled separation, or cascading failures as a result of a sudden disturbance or unanticipated failure of system elements.

112
Reliability Standard TPL-001-4, Requirements R3.3.5 and R4.4.5 require computer simulation analyses of extreme events listed in Table 1 of the standard (some listed are examples and are not definitive), and if the analysis concludes there is Cascading caused by the occurrence of extreme events, an evaluation of possible actions designed to reduce the likelihood or mitigate the consequences and adverse impacts of the event(s) shall be conducted.

84. Consistent with the existing requirements of TPL-001-5.1, we believe it is appropriate to provide responsible entities with the flexibility to determine the best actions to include in their corrective action plan to remedy any identified deficiencies in performance. Examples of actions that could be included in a corrective action plan are planning for additional contingency reserves or implementing new energy efficiency programs to decrease load, increasing intra- and inter-regional transfer capabilities, transmission switching, or adjusting transmission and generation maintenance outages based on longer-lead forecasts. Well planned mitigation and corrective actions that account for some of these contingencies will minimize loss of load and improve resilience during extreme heat and cold weather events.

85. In particular, increases in interregional transfer capability could be considered as one option to address potential reliability issues during extreme weather events. Such transfer capability would allow an entity in one region with available energy to assist one or more entities in another region that is experiencing an energy shortfall due to the extreme weather event. Increasing interregional transfer capability may be a particularly robust option for planning entities attempting to mitigate the risks associated with concurrent generator outages over a wide area.
113

113
In this NOPR we refer to interregional transfer capability strictly in the context of improving the reliability of the Bulk-Power System through improved transmission system planning and associated modifications to NERC's Reliability Standards. As such, our proposals here are distinct from the requirements for interregional coordination and cost allocation for public utility transmission providers.
See Transmission Planning and Cost Allocation by Transmission Owning and Operating Public Utilities,
Order No. 1000, 76 FR 49842 (Aug. 11, 2011), 136 FERC ¶ 61,051 (2011),
order on reh'g,
Order No. 1000-A, 77 FR 32184 (May 31, 2012), 139 FERC ¶ 61,132,
order on reh'g and clarification,
Order No. 1000-B, 77 FR 64890 (Oct. 24, 2012), 141 FERC ¶ 61,044 (2012),
aff'd sub nom. S.C. Pub. Serv. Auth.
v.
FERC,
762 F.3d 41 (D.C. Cir. 2014).

86. Recent events have shown that interregional transfer capability can be critical to maintaining reliability during extreme weather events. For example, during the 2021 Cold Weather Event in Texas and the South Central United States, SPP and MISO imported power from other balancing authorities to make up for their increasing load levels and generation shortfalls, because the eastern part of the Eastern Interconnection did not have the same arctic weather conditions. Specifically, MISO was able to import large amounts of power from neighbors to the east (
e.g.,
PJM), and SPP was able to transfer some of that power through MISO into its region. Those east-to-west transfers into MISO peaked at nearly 13,000 MW.
114

PJM had additional energy available to be transferred but could not facilitate the transfer due to internal congestion in neighboring systems.
115

114
2021 Cold Weather Event Report at 15.

115
PJM Post-Conference Comments at 19-20.

87. Recent events have also shown that the loss of interregional transfer capability can have significant implications for system reliability during extreme weather events. For instance, during the August 2020 California Heatwave Event, there was a reduction in the transfer capability through the Northwest AC Intertie by as much as 1,250 MW due to another extreme weather event that occurred earlier in 2020 which damaged transmission facilities in the northwest part of the Western Interconnection. The transfer capability of the intertie linking

Canadian and U.S. power systems was also reduced by up to 750 MW due to other planned maintenance outages, further limiting the ability to transfer energy from the north to the load centers in the south.
116

116
2020 Heat Event Report at 6.

88. Thus, we believe that there may be potential benefits in better incorporating interregional transfer capability into corrective action plans, where warranted and encourage NERC to consider establishing requirements that appropriately recognize the value of interregional transfer capability.

89. To ensure corrective action plans are developed and implemented in a timely fashion, we invite comments on the timeframe for developing such corrective action plans and sharing of the corrective actions with other interconnected planning entities.

D. Other Extreme Weather-Related Events and Issues

90. While the focus of this NOPR is on extreme heat and cold weather events, we recognize that long-term drought, particularly when occurring in conjunction with high temperatures, could also pose a serious risk to Bulk-Power System reliability over a wide geographical area.
117

In particular, we are concerned that drought may cause or contribute to conditions that affect reliable operation of transmission systems such as transmission outages, reduced plant efficiency, and reduced generation capacity.

117
DOE,
Impacts of Long-term Drought on Power Systems in the U.S. Southwest,
at 5,
https://www.energy.gov/sites/prod/files/Impacts%20of%20Long-term%20Drought%20on%20Power%20Systems%20in%20the%20US%20Southwest%20%E2%80%93%20July%202012.pdf.

91. Some examples of recorded events of reduced power production from drought were seen in the Midwest in 2007 forcing nuclear and coal-fired plants to shut down and curtail operations and along the Mississippi River in 2006, which affected nuclear plants in Illinois and Minnesota.
118

According to a study conducted by NOAA's drought task force, climate change has intensified the drought conditions gripping the Southwestern United States, the region's most severe on record, with precipitation at the lowest 20-month level documented since 1895.
119

The study indicates that the drought that emerged in early 2020 in California, Nevada and the “Four Corners” states of Arizona, Utah, Colorado and New Mexico has led to unprecedented water shortages in reservoirs across the region, while exacerbating devastating western wildfires over the past two years.
120

118

Id.
at 6.

119
NOAA,
Assessment Report the 2020-2021 Southwestern U.S. Drought,
at 6,
https://cpo.noaa.gov/MAPP/DTF4SWReport.

120
Reuters,
Southwest U.S. Drought, Worst in a Century, Linked by NOAA to Climate Change
(Sept. 21, 2021),
https://www.reuters.com/business/environment/southwest-us-drought-worst-century-linked-by-noaa-climate-change-2021-09-21/#:~:text=The%20drought%20emerged%20in%20early,two%20years%2C%20the%20report%20noted.

In addition, NERC's 2022 Summer Reliability Assessment concludes that in 2022 drought threatens wide areas of North America, mainly in the western United States and Texas, resulting in challenges to area electricity supplies.
121

121
NERC,
2022 Summer Reliability Assessment,
at 5 (May 2022),
https://www.nerc.com/pa/RAPA/ra/Reliability%20Assessments%20DL/NERC_SRA_2022.pdf.

92. Therefore, we seek comments on whether drought should be included along with extreme heat and cold weather events within the scope of Reliability Standard TPL-001-5.1 system planning requirements. These comments will assist the Commission in determining whether the final rule should direct that NERC further modify Reliability Standard TPL-001-5.1 to require transmission planners to conduct transmission planning assessments of the effects of drought conditions on transmission system operations.

93. Finally, we invite comments on whether other extreme weather events with significant impact on the reliability of the Bulk-Power System (
e.g.,
tornadoes, hurricanes) could also be considered and modeled in the future to improve system performance during these events.

V. Information Collection Statement

94. The information collection requirements contained in this Notice of Proposed Rulemaking are subject to review by the Office of Management and Budget (OMB) under section 3507(d) of the Paperwork Reduction Act of 1995.
122

OMB's regulations require approval of certain information collection requirements imposed by agency rules.
123

Upon approval of a collection of information, OMB will assign an OMB control number and expiration date. Respondents subject to the filing requirements of this rule will not be penalized for failing to respond to this collection of information unless the collection of information displays a valid OMB control number.

122
44 U.S.C. 3507(d).

123
5 CFR 1320.11.

95. The proposal to direct NERC modify existing Reliability Standard TPL-001 (Transmission System Planning Performance Requirements), is covered by, and already included in, the existing OMB-approved information collection FERC-725 (Certification of Electric Reliability Organization; Procedures for Electric Reliability Standards; OMB Control No. 1902-0225),under Reliability Standards Development.
124

The reporting requirements in FERC-725 include the ERO's overall responsibility for developing Reliability Standards, such as the TPL-001 Reliability, which is designed to ensure the BES will operate reliably over a broad spectrum of system conditions and following a wide range of probable contingencies.
125

The Commission will submit to OMB a request for a non-substantive revision of FERC-725 in connection with this NOPR.

124
Reliability Standards Development as described in FERC-725 covers standards development initiated by NERC, the Regional Entities, and industry, as well as standards the Commission may direct NERC to develop or modify.

125
Reliability Standard TPL-001-4, Purpose.

VI. Environmental Assessment

96. The Commission is required to prepare an Environmental Assessment or an Environmental Impact Statement for any action that may have a significant adverse effect on the human environment.
126

The Commission has categorically excluded certain actions from this requirement as not having a significant effect on the human environment. Included in the exclusion are rules that are clarifying, corrective, or procedural or that do not substantially change the effect of the regulations being amended.
127

The actions proposed here fall within this categorical exclusion in the Commission's regulations.

126

Regulations Implementing the National Environmental Policy Act of 1969,
Order No. 486, 52 FR 47897 (Dec. 17, 1987), FERC Stats. & Regs., ¶ 30,783 (1987) (cross-referenced at 41 FERC ¶ 61,284).

127
18 CFR 380.4(a)(2)(ii) (2021).

VII. Regulatory Flexibility Act Certification

97. The Regulatory Flexibility Act of 1980 (RFA)
128

generally requires a description and analysis of proposed rules that will have significant economic impact on a substantial number of small entities.

128
5 U.S.C. 601-612.

98. We are proposing only to direct NERC, the Commission-certified ERO, to develop modified Reliability Standards that require enhanced long-term system transmission planning designed to prepare for extreme heat and cold

weather conditions.
129

Therefore, this Notice of Proposed Rulemaking will not have a significant or substantial impact on entities other than NERC. Consequently, the Commission certifies that this Notice of Proposed Rulemaking will not have a significant economic impact on a substantial number of small entities.

129

Cf. Cyber Sec. Incident Reporting Reliability Standards,
Notice of Proposed Rulemaking, 82 FR 61499 (Dec. 28, 2017), 161 FERC ¶ 61,291 (2017) (proposing to direct NERC to develop and submit modifications to the NERC Reliability Standards to improve mandatory reporting of Cyber Security Incidents, including incidents that might facilitate subsequent efforts to harm the reliable operation of the BES);
Internal Network Sec. Monitoring for High and Medium Impact Bulk Elec. Sys. Cyber Sys.,
178 FERC ¶ 61,038 (2020) (proposing to direct NERC to new or modified Reliability Standards that require internal network security monitoring within a trusted Critical Infrastructure Protection networked environment for high and medium impact Bulk Electric System Cyber Systems).

99. Any Reliability Standards proposed by NERC in compliance with this rulemaking will be considered by the Commission in future proceedings. As part of any future proceedings, the Commission will make determinations pertaining to the Regulatory Flexibility Act based on the content of the Reliability Standards proposed by NERC.

VIII. Comment Procedures

100. The Commission invites interested persons to submit comments on the matters and issues proposed in this notice to be adopted, including any related matters or alternative proposals that commenters may wish to discuss. Comments are due August 26, 2022. Comments must refer to Docket No. RM22-3-000, and must include the commenter's name, the organization they represent, if applicable, and address in their comments. All comments will be placed in the Commission's public files and may be viewed, printed, or downloaded remotely as described in the Document Availability section below. Commenters on this proposal are not required to serve copies of their comments on other commenters.

101. The Commission encourages comments to be filed electronically via the eFiling link on the Commission's website at
http://www.ferc.gov.
The Commission accepts most standard word processing formats. Documents created electronically using word processing software must be filed in native applications or print-to-PDF format and not in a scanned format. Commenters filing electronically do not need to make a paper filing.

102. Commenters that are not able to file comments electronically may file an original of their comment by USPS mail or by courier-or other delivery services. For submission sent via USPS only, filings should be mailed to: Federal Energy Regulatory Commission, Office of the Secretary, 888 First Street NE, Washington, DC 20426. Submission of filings other than by USPS should be delivered to: Federal Energy Regulatory Commission, 12225 Wilkins Avenue, Rockville, MD 20852.

IX. Document Availability

103. In addition to publishing the full text of this document in the
Federal Register
, the Commission provides all interested persons an opportunity to view and/or print the contents of this document via the internet through the Commission's Home Page (
http://www.ferc.gov
). At this time, the Commission has suspended access to the Commission's Public Reference Room due to the President's March 13, 2020 proclamation declaring a National Emergency concerning the Novel Coronavirus Disease (COVID-19).

104. From the Commission's Home Page on the internet, this information is available on eLibrary. The full text of this document is available on eLibrary in PDF and Microsoft Word format for viewing, printing, and/or downloading. To access this document in eLibrary, type the docket number excluding the last three digits of this document in the docket number field.

105. User assistance is available for eLibrary and the Commission's website during normal business hours from the Commission's Online Support at (202) 502-6652 (toll free at 1-866-208-3676) or email at
ferconlinesupport@ferc.gov,
or the Public Reference Room at (202) 502-8371, TTY (202)502-8659. Email the Public Reference Room at
public.referenceroom@ferc.gov.

By direction of the Commission. Commissioner Danly is concurring with a separate statement attached. Commissioner Clements is concurring with a separate statement attached. Commissioner Phillips is concurring with a separate statement attached.

Issued: June 16, 2022.
Debbie-Anne A. Reese,
Deputy Secretary.

UNITED STATES OF AMERICA

FEDERAL ENERGY REGULATORY COMMISSION

Transmission System Planning Performance Requirements for Extreme Weather

Docket No. RM22-10-000

(Issued June 16, 2022)

DANLY, Commissioner,
concurring:

1. I concur in today's notice of proposed rulemaking directing the North American Electric Reliability Corporation (NERC) to submit modifications to Reliability Standard TPL-001-5.1 to address reliability concerns related to transmission system planning.
130

It will take over two years, at a minimum, from this notice of proposed rulemaking (NOPR) to the ultimate implementation of any such changes. Reliability Standard development is neither swift nor agile, and this NOPR will not, indeed cannot, timely address the projected risk of widespread blackouts this summer,
131

nor can they be in place quickly enough to address future summer and winter reliability challenges over the next couple of years. Yet, I agree it is an important (albeit small) step to establish mandatory and enforceable compliance obligations to promote proactive planning for weather-related events.

130

Transmission Sys. Planning Performance Requirements for Extreme Weather,
179 FERC ¶ 61,195 (2022).

131
Chairman Glick says that I am “prone to hyperbole” when I warn that blackouts are the likely outcome of the majority's misguided policies to prop up renewables at the expense of competitive markets and existing fossil resources. Rich Heidorn Jr.,
Summer Forecasts Spark Warnings of `Reliability Crisis' at FERC,
RTO Insider (May 19, 2022),
https://www.rtoinsider.com/articles/30170-summer-forecasts-spark-warnings-reliability-crisis-ferc.
Chairman Glick appears to be confusing “hyperbole” with “reality.” California and Texas have already experienced blackouts. Over two-thirds of the nation faces “elevated [reliability] risk” this summer. Ethan Howland,
FERC commissioners respond to elevated power outage risks across two-thirds of US, Utility Dive
(May 20, 2022),
https://www.utilitydive.com/news/ferc-nerc-power-outage-risks-summer-drought/624111/
(“At its monthly meeting Thursday, Federal Energy Regulatory Commission members dissected the North American Electric Reliability Corp.'s warning that roughly two-thirds of the United States faces [sic] heightened risks of power outages this summer.”).

2. The NOPR makes use of, indeed bases our action upon, an ever-growing narrative: reliability challenges arise primarily from weather-related events.
132

But even if one were to grant that certain parts of the United States were experiencing statistically unusual weather when compared to historical baselines, that has
absolutely nothing
to do with whether the markets and regulated utilities are procuring

sufficient generation of the correct type to ensure resource adequacy and system reliability. We cannot blame our problems on the weather. The problem is federal and state policies which, by mandate or subsidy, spur the development of
weather dependent
generation resources at the expense of the dispatchable resources needed for system stability and resource adequacy. This is seen in particularly stark terms in our markets in which subsidies, combined with failed market design, warp price signals. This destroys the incentives required to ensure the orderly entry, exit, and retention of the necessary quantities of the necessary types of generation. The thinner and thinner margins that result render the Bulk-Power System more and more susceptible to the caprices of weather. We have been warned by credible sources on the matter: NERC,
133

the RTOs,
134

and Commission staff.
135

132

See
Chairman Glick (
@RichGlickFERC
), Twitter (May 19, 2022, 11:13 a.m.),
https://twitter.com/RichGlickFERC/status/1527306459263881223?s=20&t=3a4C-1cac3nmFkjZyvoUDA
(“Extreme weather may be the single most important factor impacting #grid #reliability & the impacts of expected heat, drought, wildfires, hurricanes, & other events—all pose a big threat. Keeping eye on West, ERCOT, & parts of MISO this summer.”); Benjamin Mullin,
Climate Change is Straining California's Energy System, Officials Say,
N.Y. Times (May 6, 2022),
https://www.nytimes.com/2022/05/06/business/energy-environment/california-electricity-shortage.html.

133

See generally
North American Electric Reliability Corp.,
2022 Summer Reliability Assessment
(May 2022),
https://www.nerc.com/pa/RAPA/ra/Reliability%20Assessments %20DL/NERC_SRA_2022.pdf.
In addition, NERC has warned that system operators in areas of significant amounts of solar photovoltaic (PV) resources should be aware of the potential for resource loss events during grid disturbances.
Id.
at 6. NERC has further warned that “[i]ndustry experience with unexpected tripping of [Bulk-Power System]-connected solar PV generation units can be traced back to the 2016 Blue Cut fire in California, and similar events have occurred as recently as Summer 2021. A common thread with these events is the lack of inverter-based resource (IBR) ride-through capability causing a minor system disturbance to become a major disturbance. The latest disturbance report reinforces that improvements to NERC Reliability Standards are needed to address systemic issues with IBRs.”
Id.
NERC also explains that “because the electrical output of variable energy resources (
e.g.,
wind, solar) depends on weather conditions, on-peak capacity contributions are less than nameplate capacity.”
Id.
at 45.

134

See, e.g.,
California Independent System Operator Corp.,
2022 Summer Loads and Resources Assessment
(May 18, 2022),
http://www.caiso.com/Documents/2022-Summer-Loads-and-Resources-Assessment.pdf;
Midcontinent Independent System Operator (MISO),
Lack of Firm generation may necessitate increased reliance on imports and use of emergency procedures to maintain reliability
(Apr. 28, 2022),
https://www.misoenergy.org/about/media-center/miso-projects-risk-of-insufficient-firm-generation-resources-to-cover-peak-load-in-summer-months/;
PJM Interconnection, L.L.C. (PJM),
Energy Transition in PJM: Frameworks for Analysis
(Dec. 15, 2021),
https://pjm.com/-/media/committees-groups/committees/mrc/2021/20211215/20211215-item-09-energy-transition-in-pjm-whitepaper.ashx
(addressing renewable integration).

135

See Staff Presentation on 2022 Summer Energy Market and Reliability Assessment
(AD06-3-000), FERC, at slide 9 (May 19, 2022),
https://www.ferc.gov/news-events/news/presentation-report-2022-summer-energy-market-and-reliability-assessment
(identifying the Western U.S., Texas, MISO and Southwest Power Pool as “[p]arts of North America are at elevated or high risk of energy shortfalls during peak summer conditions”) (emphasis in original);
id.
at slide 10 (In MISO, “[g]eneration capacity declined 2.3% since 2021 resulting in [a] lower reserve margin” and the “[n]orth and central areas [are] at risk of reserve shortfall in extreme temperatures, high generation outages, or low wind” with “[s]ome risk of insufficient operating reserves at normal peak demand.”).

3. As more nuclear
136

and coal plants
137

—with their high capacity factors and onsite fuel—announce early retirements, the dispatchable resources that remain are predominantly natural gas generators. Backstopping weather-dependent resources with gas generators, largely dependent on just-in-time delivery of gas, raises its own set of reliability concerns, particularly in areas—like New England—with inadequate pipeline infrastructure. On top of this, the Commission has delayed the processing of pipeline certificates and cast a chill over the pipeline industry with its “draft policy statements”
138

and orders throwing the finality of fully litigated certificates into doubt.
139

Under pressure to reduce emissions at all costs, pipelines have moved to electrify compressor stations, furthering an unhealthy co-dependency between the gas and electric systems. And the efforts of politically motivated financial institutions to cut fossil fuel producers' access to capital has added to the current supply crunch.
140

Yet, we are led to believe that extreme weather is supposed to be the culprit for the nation's looming reliability woes. Not so.

136
U.S. Energy Information Administration,
U.S. nuclear electricity generation continues to decline as more reactors retire
(Apr. 8, 2022),
https://www.eia.gov/todayinenergy/detail.php?id=51978.

137
Ethan Howland,
Coal plant owners seek to shut 3.2 GW in PJM in face of economic, regulatory and market pressures,
Utility Dive (Mar. 22, 2022),
https://www.utilitydive.com/news/coal-plant-owners-seek

[Text truncated at 120,000 characters. The full text is on the page linked above.]

---