# Energy Conservation Program: Test Procedures for Portable Air Conditioners

> Briefs, arguments, decisions, and more.

URL: https://www.frixlaw.com/law-library/documents/fr%3A2015-03589

## Record

- **Collection:** Federal Register
- **Document type:** Proposed Rule
- **Published:** February 25, 2015
- **Citation:** 80 FR 10212

## Text

DEPARTMENT OF ENERGY
10 CFR Parts 429 and 430
[Docket No. EERE-2014-BT-TP-0014]
RIN 1904-AD22
Energy Conservation Program: Test Procedures for Portable Air Conditioners

AGENCY:

Office of Energy Efficiency and Renewable Energy, Department of Energy.

ACTION:

Notice of proposed rulemaking.

SUMMARY:

The U.S. Department of Energy (DOE) proposes to establish test procedures for portable air conditioners (ACs) in accordance with the guidance and requirements set forth by the Energy Policy and Conservation Act to establish technologically feasible, economically justified energy conservation standards for products identified by specific criteria to provide national energy savings through improved energy efficiency. The proposed test procedures are based upon industry methods to determine energy consumption in active modes, off-cycle mode, standby modes, and off mode, with certain modifications to ensure the test procedures are repeatable and representative. The proposed test procedure would create a new appendix CC, which would be used to determine capacities and energy efficiency metrics that could be the basis for any future energy conservation standards for portable ACs. DOE also proposes adding a sampling plan and rounding requirements for portable ACs, necessary when certifying capacity and efficiency of a basic model.

DATES:

DOE will accept comments, data, and information regarding this notice of proposed rulemaking (NOPR) before and after the public meeting, but no later than May 11, 2015. See section V, “Public Participation,” for details.

DOE will hold a public meeting on Wednesday, March 18, 2015, from 9 a.m. to 12 p.m., in Washington, DC. The meeting will also be broadcast as a webinar. See section V, “Public Participation,” for webinar registration information, participant instructions, and information about the capabilities available to webinar participants.

ADDRESSES:

The public meeting will be held at the U.S. Department of Energy, Forrestal Building, Room 8E-089, 1000 Independence Avenue SW., Washington, DC 20585. To attend, please notify Ms. Brenda Edwards at (202) 586-2945. See section V Public Participation for additional meeting information.

Any comments submitted must identify the NOPR for Test Procedures for Portable Air Conditioners, and provide docket number EERE-2014-BT-TP-0014 and/or regulatory information number (RIN) number 1904-AD22. Comments may be submitted using any of the following methods:

1.
Federal eRulemaking Portal: www.regulations.gov
. Follow the instructions for submitting comments.

2.
Email: PortableAC2014TP0014@ee.doe.gov
. Include the docket number and/or RIN in the subject line of the message.

3.
Mail:
Ms. Brenda Edwards, U.S. Department of Energy, Building Technologies Program, Mailstop EE-5B, 1000 Independence Avenue SW., Washington, DC 20585-0121. If possible, please submit all items on a CD. It is not necessary to include printed copies.

4.
Hand Delivery/Courier:
Ms. Brenda Edwards, U.S. Department of Energy, Building Technologies Program, 950 L'Enfant Plaza, SW., Suite 600, Washington, DC 20024. Telephone: (202) 586-2945. If possible, please submit all items on a CD. It is not necessary to include printed copies.

For detailed instructions on submitting comments and additional information on the rulemaking process, see section V of this document (Public Participation).

Docket:
The docket, which includes
Federal Register
notices, public meeting attendee lists and transcripts, comments, and other supporting documents/materials, is available for review at regulations.gov. All documents in the docket are listed in the regulations.gov index. However, some documents listed in the index, such as those containing information that is exempt from public disclosure, may not be publicly available.

A link to the docket Web page can be found at:
http://www.regulations.gov/#!docketDetail;D=EERE-2014-BT-TP-0014
. This Web page will contain a link to the docket for this notice on the regulations.gov site. The regulations.gov Web page will contain simple instructions on how to access all documents, including public comments, in the docket. See section VII for information on how to submit comments through regulations.gov.

For further information on how to submit a comment, review other public comments and the docket, or participate in the public meeting, contact Ms. Brenda Edwards at (202) 586-2945 or by email:
Brenda.Edwards@ee.doe.gov
.

FOR FURTHER INFORMATION CONTACT:

Mr. Bryan Berringer, U.S. Department of Energy, Office of Building Technology Programs, Appliance Standards Division, 950 L'Enfant Plaza SW. Room 603, Washington, DC 20585-0121. Telephone: 202-586-0371. Email:
Bryan.Berringer@ee.doe.gov
.

Ms. Sarah Butler, U.S. Department of Energy, Office of the General Counsel, Mailstop GC-33, 1000 Independence Ave. SW., Washington, DC 20585-0121. Telephone: 202-586-1777; Email:
Sarah.Butler@hq.doe.gov
.

SUPPLEMENTARY INFORMATION:

DOE intends to incorporate by reference the following industry standards into 10 CFR part 430: Portable Air Conditioners AHAM PAC-1-2014, 2014.

Copies of AHAM PAC-1-2014 can be obtained from the Association of Home Appliance Manufacturers, 1111 19th Street NW., Suite 402, Washington, DC 20036, 202-872-5955, or by going to
http://www.aham.org/ht/d/ProductDetails/sku/PAC12009/from/714/pid/
.

Table of Contents

I. Authority and Background

A. General Test Procedure Rulemaking Process

B. Test Procedure for Portable Air Conditioners

II. Summary of the Notice of Proposed Rulemaking

III. Discussion

A. Products Covered by the Proposed Test Procedure

B. Determination, Classification, and Testing Provisions for Operational Modes

1. Active Modes

a. Cooling Mode

b. Heating Mode

2. Off-Cycle Mode

3. Standby Mode and Off Mode

a. Mode Definitions

b. Determination of Standby Mode and Off Mode Power Consumption

4. Combined Energy Efficiency Ratio

a. CEER Calculations

b. Mode Annual Operating Hours

C. Sampling Plan and Rounding Requirements

D. Compliance With Other Energy Policy and Conservation Act Requirements

1. Test Burden

2. Potential Incorporation of International Electrotechnical Commission Standard 62087

IV. Procedural Issues and Regulatory Review

A. Review Under Executive Order 12866

B. Review under the Regulatory Flexibility Act

C. Review Under the Paperwork Reduction Act of 1995

D. Review Under the National Environmental Policy Act of 1969

E. Review Under Executive Order 13132

F. Review Under Executive Order 12988

G. Review Under the Unfunded Mandates Reform Act of 1995

H. Review Under the Treasury and General Government Appropriations Act, 1999

I. Review Under Executive Order 12630

J. Review Under Treasury and General Government Appropriations Act, 2001

K. Review Under Executive Order 13211

L. Review Under Section 32 of the Federal Energy Administration Act of 1974

M. Description of Materials Incorporated by Reference

V. Public Participation

A. Attendance at Public Meeting

B. Procedure for Submitting Prepared General Statements for Distribution

C. Conduct of Public Meeting

D. Submission of Comments

E. Issues on Which DOE Seeks Comment

VI. Approval of the Office of the Secretary

I. Authority and Background

Title III of the Energy Policy and Conservation Act (EPCA), as amended (42 U.S.C. 6291,
et seq.
; “EPCA” or, “the Act”) sets forth various provisions designed to improve energy efficiency. Part A of title III of EPCA (42 U.S.C. 6291-6309) establishes the “Energy Conservation Program for Consumer Products Other Than Automobiles,” which covers consumer products and certain commercial products (hereinafter referred to as “covered products”).
1

EPCA authorizes DOE to establish technologically feasible, economically justified energy conservation standards for covered products or equipment that would be likely to result in significant national energy savings. (42 U.S.C. 6295(o)(2)(B)(i)(I)-(VII)) In addition to specifying a list of covered consumer and industrial products, EPCA contains provisions that enable the Secretary of Energy to classify additional types of consumer products as covered products. (42 U.S.C. 6292(a)(20)) For a given product to be classified as a covered product, the Secretary must determine that:

1
For editorial reasons, upon codification in the U.S. Code, Part B was re-designated Part A.

(1) Classifying the product as a covered product is necessary for the purposes of EPCA; and

(2) The average annual per-household energy use by products of each type is likely to exceed 100 kilowatt-hours (kWh) per year. (42 U.S.C. 6292(b)(1))

To prescribe an energy conservation standard pursuant to 42 U.S.C. 6295(o) and (p) for covered products added pursuant to 42 U.S.C. 6292(b)(1), the Secretary must also determine that:

(1) The average household energy use of the products has exceeded 150 kWh per household for a 12-month period;

(2) The aggregate 12-month energy use of the products has exceeded 4.2 terawatt-hours (TWh);

(3) Substantial improvement in energy efficiency is technologically feasible; and

(4) Application of a labeling rule under 42 U.S.C. 6294 is unlikely to be sufficient to induce manufacturers to produce, and consumers and other persons to purchase, covered products of such type (or class) that achieve the maximum energy efficiency that is technologically feasible and economically justified. (42 U.S.C. 6295(l)(1))

Under EPCA, the energy conservation program consists essentially of four parts: (1) Testing, (2) labeling, (3) Federal energy conservation standards, and (4) certification and enforcement procedures. The testing requirements consist of test procedures that manufacturers of covered products must use as the basis for: (1) Certifying to DOE that their products comply with the applicable energy conservation standards adopted under EPCA, and (2) making representations about the efficiency of those products. Similarly, DOE must use these test procedures to determine whether the products comply with any relevant standards promulgated under EPCA.

A. General Test Procedure Rulemaking Process

Under 42 U.S.C. 6293, EPCA sets forth the criteria and procedures DOE must follow when prescribing or amending test procedures for covered products. EPCA provides in relevant part that any test procedures prescribed or amended under this section shall be reasonably designed to produce test results that measure energy efficiency, energy use or estimated annual operating cost of a covered product during a representative average use cycle or period of use and shall not be unduly burdensome to conduct. (42 U.S.C. 6293(b)(3))

In addition, if DOE determines that a test procedure should be prescribed or amended, it must publish proposed test procedures and offer the public an opportunity to present oral and written comments on them. (42 U.S.C. 6293(b)(2))

B. Test Procedure for Portable Air Conditioners

There are currently no DOE test procedures or energy conservation standards for portable ACs. On July 5, 2013, DOE issued a notice of proposed determination (NOPD) of coverage (hereinafter referred to as the “July 2013 NOPD”), in which DOE announced that it tentatively determined that portable ACs meet the criteria under 42 U.S.C. 6292(b)(1) to be classified as a covered product. 78 FR 40403. DOE estimated that 973.7 thousand portable AC units were shipped in North America in 2012, with a projected growth to 1743.7 thousand units by 2018, representing nearly 80-percent growth in 6 years.
2

Id.
at 40404. In addition, DOE estimated the average per-household electricity consumption by portable ACs to be approximately 650 kWh per year.
Id.

2
Transparency Media Research, “Air Conditioning Systems Market—Global Scenario, Trends, Industry Analysis, Size, Share and Forecast, 2012-2018,” January 2013.

In response to the July 2013 NOPD, DOE received comments from interested parties on several topics regarding appropriate test procedures for portable ACs that DOE should consider if it issues a final determination classifying portable ACs as a covered product.

On May 9, 2014, DOE published in the
Federal Register
a notice of data availability (NODA) (hereinafter referred to as the “May 2014 NODA”), in which it agreed that a DOE test procedure for portable ACs would provide consistency and clarity for representations of energy use of these products. DOE evaluated available industry test procedures to determine whether such methodologies would be suitable for incorporation in a future DOE test procedure, should DOE determine to classify portable ACs as a covered product. DOE conducted testing on a range of portable ACs to determine typical cooling capacities and cooling energy efficiencies based on the existing industry test methods and other modified approaches for portable ACs. 79 FR 26639, 26640 (May 9, 2014).

As discussed above, DOE also recently initiated a separate rulemaking to consider establishing energy conservation standards for portable ACs. Any new standards would be based on the same efficiency metrics derived from the test procedure that DOE would adopt in a final rule in this rulemaking.

II. Summary of the Notice of Proposed Rulemaking

In this NOPR, DOE proposes to establish in Title 10 of the Code of Federal Regulations (CFR), section 430.2, the definition of portable AC that was initially proposed in the July 2013 NOPD, modified to distinguish from room ACs and dehumidifiers.

DOE also proposes to establish in 10 CFR part 430, subpart B, a test procedure for single-duct and dual-duct portable ACs that would provide an accurate representation of performance in active modes, standby modes, and off mode. Because spot cooler portable ACs do not provide net cooling to a conditioned space, DOE is not proposing test procedures for these products in this NOPR. The proposed active mode testing methodology would utilize the Association of Home

Appliance Manufacturers (AHAM) portable AC test procedure (AHAM PAC-1) to measure cooling capacity and cooling energy efficiency ratio (EER
cm
), with additional provisions to account for heat transferred to the indoor conditioned space from the case, ducts, and any infiltration air from unconditioned spaces. DOE also proposes to clarify for such active mode testing (1) test duct configuration; (2) instructions for condensate collection; (3) control settings for operating mode, fan speed, temperature set point, and louver oscillation; and (4) unit placement within the test chamber. DOE proposes to define this operating mode as “cooling mode” to distinguish it from other active modes, such as “heating mode.”

For those single-duct and dual-duct portable ACs that incorporate a heating function, DOE proposes additional testing methodology for measuring energy use in heating mode similar to the methodology proposed for the measurement of cooling capacity and EER
cm
, except that testing conditions would be specified that are representative of ambient conditions when portable ACs would be used for heating purposes. The proposed test procedure includes a measure of heating capacity and heating energy efficiency ratio (EER
hm
).

The proposed single-duct and dual-duct portable AC test procedure also includes a measure of energy use in off-cycle mode, which occurs when the ambient dry-bulb temperature reaches the setpoint. This may include operation of the fan either continuously or cyclically without activating the refrigeration (or heating) system, or periods in standby mode when the fan is not operating.

In this NOPR, DOE identifies and discusses all relevant low-power modes, including bucket-full mode, delay-start mode, inactive mode, and off mode. DOE also proposes definitions for inactive mode and off mode, and proposes test procedures to determine energy consumption representative of each of these low-power modes based on the procedures outlined in the standard published by the International Electrotechnical Commission (IEC), titled “Household electrical appliances—Measurement of standby power,” Publication 62301, Edition 2.0 (2011-01) (hereinafter referred to as “IEC Standard 62301”).

In addition, DOE proposes a combined energy efficiency ratio (CEER) metric to be used in reporting the overall energy efficiency of a single-duct and dual-duct portable AC. The CEER metric would represent energy use in all available operating modes. DOE also proposes to define a separate CEER metric for cooling mode that would also apply to units that include heating mode and would be a common metric used for comparison among portable ACs. DOE also proposes an EER metric to represent performance in cooling and heating modes that could be used to compare cooling and heating performance with other similar products.

Finally, DOE proposes adding a sampling plan and rounding requirements for portable ACs to a new section 10 CFR 429.62. These instructions are necessary when certifying capacity and efficiency of a basic model.

III. Discussion

A. Products Covered by the Proposed Test Procedure

A portable AC is a self-contained, refrigeration-based product that, similar to a room AC, removes latent and sensible heat from the ambient air in a single space such as a room. Similar to room ACs, portable ACs are standalone appliances designed to operate independently of any other air treatment devices, though they may also be used in conjunction with other pre-existing air treatment devices. However, unlike room ACs, portable ACs are not designed as a unit to be mounted in a window or through the wall. Portable ACs are placed in the conditioned space and may have flexible ducting, typically connected to a window to remove condenser outlet air from the conditioned space.

DOE is generally aware of 3 categories of portable ACs including single-duct models, dual-duct models, and spot coolers. Single-duct portable ACs utilize a single condenser exhaust duct to vent heated air to the unconditioned space. Other configurations include dual-duct, which intakes some or all condenser air from and exhausts to unconditioned space, and spot coolers, which have no ducting on the condenser side and may utilize small directional ducts on the evaporator exhaust. Spot coolers are often used in applications that require cooling in one localized zone and can tolerate exhaust heat outside of this zone.

In the July 2013 NOPD, DOE proposed to define “portable air conditioner” as:

A consumer product, other than a “packaged terminal air conditioner” which is powered by a single-phase electric current and which is an encased assembly designed as a portable unit that may rest on the floor or other elevated surface for the purpose of providing delivery of conditioned air to an enclosed space. It includes a prime source of refrigeration and may include means for ventilating and heating. 78 FR 40403, 40404 (July 5, 2013).

DOE maintained this proposed definition in the May 2014 NODA. In the July 2013 NOPD, DOE also stated that portable ACs are moveable units typically designed to provide 8,000 to 14,000 British thermal units per hour (Btu/h) of cooling capacity for a single room.
Id.

In response to the proposed definition, Pacific Gas and Electric Company, Southern California Gas Company, San Diego Gas and Electric, and Southern California Edison (hereinafter referred to as the “California Investor-Owned Utilities (IOUs)”) and Edison Electric Institute (EEI) stated that the requirement in the definition to be powered by a single-phase electric current may exclude some equipment designed for commercial applications. The California IOUs encouraged DOE to consider a large range of portable ACs, both residential and commercial, to ensure that all potential savings are examined and analyzed. In particular, the California IOUs recommended that DOE consider covering portable ACs with capacities above 14,000 Btu/h because there are units currently on the market with cooling capacities up to and above 65,000 Btu/h. (California IOUs, NOPD No. 5 at pp. 1-2;
3

EEI, NOPD No. 3 at p. 5) EEI also commented that DOE should consider revising the definition of “portable air conditioner” to ensure that three-phase electrical current units are covered, and to better reflect products that currently are on the market with and without heating capability. (EEI, NOPD No. 3 at p. 5)

3
A notation in the form “California IOUs, NOPD No. 5 at pp. 1-2” identifies a written comment: (1) Made by Pacific Gas and Electric Company, San Diego Gas and Electric Company, and Southern California Edison (“the California IOUs”); (2) recorded in document number 5 that is filed in the docket of the rulemaking for determination of coverage of portable air conditioners as a covered consumer product (Docket No. EERE-2013- BT-STD-0033) and available for review at
www.regulations.gov
; and (3) which appears on pages 1-2 of document number 5.

Oceanaire Inc. (Oceanaire) commented that according to the EPCA definition, commercial spot coolers (portable ACs that do not have ducting attached to the condenser) are not covered products. According to Oceanaire, commercial spot coolers are mainly used in the rental market where emergencies create a need for immediate and focused cooling systems, with example applications including food and cosmetics processing plants,

outdoor entertainment venues, and steel processing factories. Oceanaire noted that the cooling capacity of these rental units range between 1 and 5 tons (12,000 to 60,000 Btu/h), where actual performance is determined by a wide range of operating environments, which may include high and low temperatures, high humidity, and corrosive conditions that are not experienced in household applications. Further, Oceanaire noted that its commercial product construction is robust, comprising mainly 18 gauge and thicker steel cabinetry and support structures. (Oceanaire, No. 2 at pp. 1-2
4

)

4
A notation in the form “Oceanaire, No. 2 at pp. 1-2” identifies a written comment: (1) Made by Oceanaire, Inc. (Oceanaire); (2) recorded in document number 2 that is filed in the docket of the portable air conditioner test procedure rulemaking (Docket No. EERE-2014- BT-TP-0014) and available for review at
www.regulations.gov
; and (3) which appears on pages 1-2 of document number 2.

Portable ACs, most commonly in single-duct or dual-duct configuration, typically range in cooling capacity from 5,000 to 14,000 Btu/h when measured according to existing industry test methods. According to sizing charts provided by vendors, these portable ACs are intended to cool rooms of up to approximately 525 square feet in area,
5

are often heavier than 50 pounds, and so are designed with wheels to provide mobility from room to room. Spot coolers, a category of portable ACs under DOE's proposed definition, are typically intended for larger spaces and harsher applications. Most have cooling capacities greater than 14,000 Btu/h, when measured according to existing industry test methods, and are typically larger than single-duct and dual-duct portable ACs, often weighing more than 100 pounds. Because they are frequently moved from site to site, spot coolers are more rugged in construction, although they also have wheels to maintain portability. During interviews, manufacturers indicated that spot cooler shipments represent no more than approximately 1.5 percent of the total portable AC market in the United States, and that only about half of those shipments are for spot coolers with single-phase, 120-volt, and 60-Hertz power supply requirements (the power supply appropriate for consumer products). Additionally, manufacturers noted that the spot coolers typically incorporate more powerful and louder blowers, condensate collection without auto-evaporation, and larger case sizes than typical single-duct and dual-duct portable ACs. Manufacturer interviews confirmed that spot coolers are often rented on a seasonal or emergency basis, unlike other portable ACs, which are generally purchased for regular use on a seasonal or occasional basis. Based on these considerations, DOE is not considering a test procedure for spot coolers at this time even though DOE believes spot coolers would meet the proposed definition of portable AC if DOE finalizes the coverage determination as proposed.

5
For example:
www.air-n-water.com/portable-ac-size.htm
.

DOE recognizes that certain portable ACs also include options for operating as a dehumidifier and/or heater, with heating means provided by either an electric resistance heater or by modifying internal refrigerant flow to operate the unit as a heat pump. The dehumidification function may be achieved in some units by decreasing fan speeds, removing the condenser duct(s), and for some units, disabling the self-evaporative feature by draining the condensate before it reaches the condenser coils or deactivating the condensate slinger fan when the controls are set to dehumidification mode. In all of these cases, the air flow pattern and psychrometrics differ fundamentally from those of a dehumidifier, resulting in different energy efficiencies during dehumidification operation, even though both products may use a refrigeration system to remove moisture from the air.

DOE also recognizes that although room ACs and portable ACs share many of the same components that operate similarly to provide cooled air to a conditioned space, a portable AC, unlike a room AC, may be entirely located within the conditioned space so that some or all of the condenser air may be drawn from that space, and some heat from the refrigeration system and ducting is transferred to the conditioned space as well. These differences would lead to differing cooling mode energy efficiencies between room ACs and portable ACs, even if the products were to incorporate the same components. In addition, operation of the portable AC without activation of the refrigeration system may be more accurately characterized as “air circulation” rather than “ventilation” because the portable AC may be operated without drawing air from outside the conditioned space. Thus, DOE proposes to clarify in the definition of “portable air conditioner” that the primary function of the product is to provide cooled, conditioned air to the space in addition to other functions such as air circulation or heating, and that it is a product other than a room AC or dehumidifier. DOE also proposes to restructure the portable AC definition to align with both the room AC and dehumidifier definitions. In sum, DOE proposes to add to 10 CFR 430.2 the following definition for “portable air conditioner.”

An encased assembly, other than a “packaged terminal air conditioner,” “room air conditioner,” or “dehumidifier,” designed as a portable unit for delivering cooled, conditioned air to an enclosed space, that is powered by single-phase electric current, which may rest on the floor or other elevated surface. It includes a source of refrigeration and may include additional means for air circulation and heating.

Although this proposed definition differs from the definition presented in the July 2013 NOPD, DOE maintains its tentative determination that portable ACs qualify as a covered product under Part A of Title III of EPCA, as amended. A product may be added as a covered product, pursuant to 42 U.S.C. 6292(b)(1), if (1) classifying products of such type as covered products is necessary and appropriate to carry out the purposes of EPCA; and (2) the average per-household energy use by products of such type is likely to exceed 100 kWh (or its Btu equivalent) per year. As discussed in the July 2013 NOPD, DOE determined that portable ACs meet the first requirement because: Shipments are projected to increase 80 percent over a 6-year period from 2012 to 2017, coverage of portable ACs would allow for conservation of energy through labeling programs and the regulation of portable AC energy efficiency, and there is significant variation in the annual energy consumption of different portable AC models currently available on the market. 78 FR 40403, 40404 (July 5, 2013). For the second requirement, DOE determined that a typical portable AC uses approximately 650 kWh/year, well above the 100 kWh/year threshold. 78 FR 40403, 40404-40405 (July 5, 2013). The updated portable AC definition proposed in this NOPR only includes additional clarification to differentiate portable ACs from dehumidifiers and room ACs, it does not alter the intended scope of the definition. Accordingly, the determinations from the July 2013 NOPD remain valid for the revised proposed portable AC definition.

DOE also proposes to include in the new test procedure at appendix CC the following definitions for different portable AC configurations to clarify the testing provisions to be used to obtain representative results for cooling capacity, heating capacity (where applicable), and CEER:

“Single-duct portable air conditioner” means a portable air conditioner that

draws all of the condenser inlet air from the conditioned space without the means of a duct, and discharges the condenser outlet air outside the conditioned space through a single duct.

“Dual-duct portable air conditioner” means a portable air conditioner that draws some or all of the condenser inlet air from outside the conditioned space through a duct, and may draw additional condenser inlet air from the conditioned space. The condenser outlet air is discharged outside the conditioned space by means of a separate duct.

DOE is also proposing a definition for “spot cooler” as a portable air conditioner that draws condenser inlet air from and discharges condenser outlet air to the conditioned space, and draws evaporator inlet air from and discharges evaporator outlet air to a localized zone within the conditioned space. DOE is proposing such a definition in this NOPR to clarify that testing these products would not be required at this time, as discussed previously in this section.

DOE requests comment on these proposed definitions for portable ACs and their specific configurations, including the proposal that spot coolers not be addressed in this rulemaking.

B. Determination, Classification, and Testing Provisions for Operational Modes

1. Active Modes

Portable ACs are typically purchased by consumers to provide cooled air to a conditioned space, although certain models provide additional functions such as heating, dehumidification, and air circulation. Because room ACs and dehumidifiers share many of the same internal components and incorporate some of the same operating modes as portable ACs, DOE considered the mode definitions for these products to develop applicable mode definitions for portable ACs.

Appendix F of title 10, part 430, subpart B of the CFR defines “active mode” for room ACs as a mode in which the room AC is connected to a mains power source, has been activated and is performing the main function of cooling or heating the conditioned space, or circulating air through activation of its fan or blower, with or without energizing active air-cleaning components or devices such as ultraviolet (UV) radiation, electrostatic filters, ozone generators, or other air-cleaning devices. Appendix X within that same subpart of the CFR defines “active mode” for dehumidifiers as a mode in which a dehumidifier is connected to a mains power source, has been activated, and is performing the main functions of removing moisture from air by drawing moist air over a refrigerated coil using a fan, or circulating air through activation of the fan without activation of the refrigeration system.

Portable ACs provide the same main functions as room ACs: (1) Cooling with activation of the refrigeration system and blower or fan; (2) for certain models, heating by means of activation of a blower or fan and either the refrigeration system and a reverse-cycle solenoid valve or a resistance heater; or (3) air circulation by activating only the blower or fan. As with dehumidifiers, a portable AC evaporator may also experience frosting and may need to perform a defrost operation. DOE, therefore, proposes the following definition for portable AC active mode:

“Active mode” means a mode in which the portable air conditioner is connected to a mains power source, has been activated, and is performing the main functions of cooling or heating the conditioned space, circulating air through activation of its fan or blower without activation of the refrigeration system, or defrosting the refrigerant coil.

DOE proposes to designate active mode functions performed when the temperature setpoint is not yet reached as either “cooling mode” or “heating mode,” depending upon the user-selected function.

Portable ACs may also operate in “off-cycle mode,” during which the fan or blower may operate without activation of the refrigeration system after the temperature setpoint has been reached. Under these conditions, the fan may be operated to ensure that air is drawn over the thermostat to monitor ambient conditions, or for air circulation in the conditioned space. It is also possible that immediately following a period of cooling or heating, fan operation may be initiated to remove any remaining frost or moisture from the evaporator. Although the periods of fan operation would classify those periods of off-cycle mode as an active mode, DOE notes that the portable AC may also enter one or more periods of a standby mode during off-cycle mode, in which the fan or blower does not operate. Therefore, DOE proposes to define off-cycle mode to include all periods of fan operation and standby mode that occur when the temperature set point has been reached, and further proposes to measure the energy consumption during off-cycle mode according to methodology discussed in section III.B.2 of this NOPR.

Portable ACs may also operate in a consumer-selected mode during which the blower is operated with all other cooling or heating components disabled. The blower may operate cyclically or continuously to circulate air in the conditioned space. DOE refers to this consumer-selected, active mode as “air-circulation mode.” DOE does not currently have information on the usage of this consumer-initiated air circulation feature and, therefore is not proposing to measure energy usage during “air-circulation mode.” However, DOE seeks information on annual hours associated with this mode.

Some portable ACs also include a dehumidification or “dry” function. DOE learned through manufacturer interviews that portable AC operation in this mode is adjusted to maximize latent rather than sensible heat removal, typically by decreasing the evaporator fan or blower speed. Though not always specified in the user manual, when operating in dry mode, the installation may be modified to direct condenser exhaust into the conditioned space. In this case, a drain setup is necessary to remove condensate before it passes over the condenser to be re-evaporated into the condenser exhaust. Though the evaporator and condenser outlet air streams are not fully mixed, the net effect is minimal heating or cooling within the conditioned space and a reduction in relative humidity. DOE considered addressing dehumidification performance as part of this test procedure proposal, and determined that it is not technically feasible to combine dehumidification performance, in units of liters per kWh, with a cooling or heating performance, in units of Btu/Wh. Because dehumidification is not the primary mode of operation for portable ACs, DOE does not believe that the annual operating hours in dehumidification mode would be significant and would therefore not substantially impact a metric that considers the combined annual energy consumption of each operating mode. DOE's tentative conclusion is supported by a recent field study conducted by Burke,
et al.,
(hereinafter referred to as the Burke Portable AC Study), in which portable ACs were monitored over multiple summer months in 19 locations in New York and Pennsylvania.
6

No users in this study reported operating their portable AC in dehumidification mode. DOE also notes

that including dehumidification mode in a portable AC test procedure would significantly and disproportionately increase test burden. Therefore, DOE does not propose to include dehumidification mode as an operating mode to be addressed in a portable AC test procedure.

6
T. Burke,
et al.,
Using Field-Metered Data to Quantify Annual Energy Use of Portable Air Conditioners, Lawrence Berkeley National Laboratory, Report No. LBNL-6868E (December 2014). Available at:
www.osti.gov/scitech/servlets/purl/1166989
.

In summary, DOE proposes to include the following definitions in new appendix CC to clarify the types of portable AC operation within active mode:

“Cooling mode” means an active mode in which a portable air conditioner has activated the main cooling function according to the thermostat or temperature sensor signal, including activating the refrigeration system, or the fan or blower without activation of the refrigeration system.

“Heating mode” means an active mode in which a portable air conditioner has activated the main heating function according to the thermostat or temperature sensor signal, including activating a resistance heater, the refrigeration system with a reverse refrigerant flow valve, or the fan or blower without activation of the resistance heater or refrigeration system.

Further discussion of off-cycle mode, including a proposed definition, is included in section III.2 of this NOPR.

a. Cooling Mode

As discussed in the May 2014 NODA, DOE identified three industry test procedures that measure portable AC performance in cooling mode and that are applicable to products sold in North America:

(1) AHAM PAC-1-2009 “Portable Air Conditioners” (AHAM PAC-1-2009) specifies cooling mode testing conducted in accordance with American National Standards Institute (ANSI)/American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE) Standard 37-2005 “Methods of Testing for Rating Electrically Driven Unitary Air-Conditioning and Heat Pump Equipment” (ANSI/ASHRAE Standard 37-2005).
7

The metrics incorporated in AHAM PAC-1-2009 include capacity and energy efficiency ratio (EER) for the following configurations: Single-Duct, Dual-Duct, Spot Cooling, and Water Cooled Condenser.

7
ANSI/ASHRAE Standard 37 was updated in 2009. DOE reviewed the 2005 and 2009 versions and concluded there would be no measurable difference in portable air conditioner results obtained from each. Therefore, DOE utilized ANSI/ASHRAE Standard 37-2009 when testing according to AHAM PAC-1-2009.

(2) Canadian Standards Association (CSA) C370-2013 “Cooling Performance of Portable Air Conditioners” (CSA C370-2013) is harmonized with AHAM PAC-1-2009, and thus also incorporates testing provisions from ANSI/ASHRAE Standard 37-2009.

(3) ANSI/ASHRAE Standard 128-2011 “Method of Rating Unitary Spot Air Conditioners” (ANSI/ASHRAE Standard 128-2011) is adapted from the previous 2009 version of CSA C370. It too references ANSI/ASHRAE Standard 37-2009. The previous version of ANSI/ASHRAE Standard 128, published in 2001, is required by California regulations to be used to certify spot cooler performance for such products sold in that State. A key difference between ANSI/ASHRAE Standard 128-2011 and ANSI/ASHRAE Standard 128-2001 is that the older version specifies a higher indoor ambient testing temperature, which increases measured cooling capacity and EER. 79 FR 26639, 26640-26641 (May 9, 2014).

DOE found no significant differences that would produce varying results among the three test procedures. The aforementioned versions of the AHAM, CSA, and ASHRAE test procedures each measure cooling capacity and EER based on an air enthalpy approach that measures the airflow rate, dry-bulb temperature, and water vapor content of air at the inlet and outlet of the indoor (evaporator) side. In addition, for air-cooled portable ACs with cooling capacity less than 135,000 Btu/h, which include the products that are the subject of this NOPR, the indoor air enthalpy results must be validated by measuring cooling capacity by either an outdoor air enthalpy method or a compressor calibration method. As explained in the May 2014 NODA, DOE selected the outdoor air enthalpy method for its investigative testing to minimize test burden because it only requires additional metering components, similar to those used for the indoor air enthalpy method. DOE conducted initial testing according to AHAM PAC-1-2009 to establish baseline capacities and efficiencies of a preliminary sample of test units according to the existing industry test procedures. 79 FR 26639, 26641 (May 9, 2014).

To investigate the contribution of operational factors on the apparent reduction in cooling capacity observed for units in the field, DOE compared the results of AHAM PAC-1-2009 testing with the results of additional testing with a test room calorimeter approach based on ANSI/ASHRAE Standard 16-1983 (RA 99), “Method of Testing for Rating Room Air Conditioners and Packaged Terminal Air Conditioners” (ANSI/ASHRAE Standard 16-1983), with certain modifications to allow testing of portable ACs. The room calorimeter approach allowed DOE to determine the cooling capacity of a portable AC that accounts for any air infiltration effects and heat transfer to the conditioned space through gaps in the product case and seams in the duct connections, along with an associated EER. Values of these performance metrics measured accordingly may more accurately reflect real-world portable AC operation. In that test series, DOE also investigated cooling capacity and EER as a function of the infiltration air temperature for single-duct and dual-duct units, and the effect of condenser exhaust air entrainment at the intake for dual-duct portable ACs. DOE presented the results of this preliminary testing in the May 2014 NODA. 79 FR 26639, 26643-26648 (May 9, 2014).

Although AHAM PAC-1-2009, CSA C370-2013, and ANSI/ASHRAE Standard 128-2011, all reference the test setup and methodology from ANSI/ASHRAE Standard 37, AHAM PAC-1-2009 did not specify the particular sections in ANSI/ASHRAE Standard 37 that are to be used. However, AHAM recently published an updated version of its portable AC test procedure, AHAM PAC-1-2014, that references specific sections in ANSI/ASHRAE Standard 37 for equipment setup, cooling capacity determination, power input determination, data recording, and results reporting, consistent with the approach in CSA C370-2013 and ANSI/ASHRAE Standard 128-2011. These clarifications will likely improve testing reproducibility by eliminating different possible interpretations of the provisions to reference from ANSI/ASHRAE Standard 37. AHAM also slightly revised the evaporator inlet and condenser inlet temperatures for its standard rating conditions in AHAM PAC-1-2014, in order to harmonize with the temperatures specified in CSA C370-2013 and ANSI/ASHRAE Standard 128-2011. Conditions that had been specified as 80 degrees Fahrenheit (°F) dry-bulb temperature and 67 °F wet-bulb temperature were adjusted to 80.6 °F/66.2 °F, and conditions that had been specified as 95 °F/75 °F were adjusted to 95 °F/75.2 °F. DOE did not identify other substantive changes between the 2009 and 2014 versions of AHAM PAC-1 that would affect testing results.

For the May 2014 NODA, DOE conducted an initial round of performance testing on a preliminary sample of test units representative of products available at that time on the U.S. market. The test sample included a total of eight portable ACs (four single-duct, two dual-duct, and two spot coolers), covering a range of rated cooling capacities (8,000-13,500 Btu/h) and EERs (7.0-11.2 Btu per watt-hour (Btu/Wh)). Following publication of the May 2014 NODA, DOE performed additional testing on a larger set of test units. This second test sample included a total of eighteen portable ACs; thirteen

single-duct and 5 dual-duct
8

units, expanding the range of rated cooling capacities (5,000-14,000 Btu/h) and the maximum rated EER to 12.1 Btu/Wh. DOE did not include any spot coolers in the second test sample because it is not proposing testing provisions for them at this time for reasons discussed in section IIII.A of this NOPR.

8
One of the dual-duct units was shipped with a conversion kit to enable testing in single-duct configuration. DOE performed all tests on this “convertible” unit in both single-duct and dual-duct configurations.

Because DOE does not currently regulate portable ACs, manufacturers may advertise or market their products using any available test procedure. For those models that are included in the California Energy Commission (CEC) product database and that are sold in California, however, manufacturers must report cooling capacity and EER according to ANSI/ASHRAE Standard 128-2001. DOE notes that the cooling capacities and EERs obtained from using ANSI/ASHRAE Standard 128-2001 are higher than those obtained using the current ANSI/ASHRAE Standard 128-2011, primarily due to higher temperature evaporator inlet air in the 2001 version of the test procedure.
9

9
ANSI/ASHRAE Standard 128-2011 specifies 80.6 degrees °F dry-bulb temperature and 66.2 °F wet-bulb temperature for the standard rating conditions for the evaporator inlet of dual-duct portable ACs and both the evaporator and condenser inlets of single-duct units. It also specifies standard rating conditions of 95 °F dry-bulb temperature and 75.2 °F wet-bulb temperature for the condenser inlet side of dual-duct portable ACs and both the evaporator and condenser inlets of spot coolers. ANSI/ASHRAE Standard 128-2001 specifies 95 °F dry-bulb temperature and 83 °F wet-bulb temperature for the standard rating conditions for both the evaporator and condenser inlets of all portable ACs, including spot coolers.

Due to the consistent method of reporting performance required by the CEC, DOE selected units for its test sample largely from cooling capacities and EERs listed in the CEC product database. However, due to the difference in testing temperature, DOE expected that these values would differ from the cooling capacities and EERs that would be obtained using any of the three current industry test methods. For additional products not listed in the CEC product database, DOE utilized information from manufacturer literature to inform its selection.

The 24 test units
10

(comprising the samples from the May 2014 NODA testing and testing for this proposal) and their key features are presented in Table III.1, with cooling capacity expressed in Btu/h and EER expressed in Btu/Wh.

10
DOE also tested two spot coolers for the May 2014 NODA. However, because DOE is not proposing testing provisions for these units at this time, the results for those units are not considered further in this analysis.

Table III.1—Portable AC Test Sample

Test unit
Duct type

Rated cooling
capacity

(
Btu/h
)

Rated EER (
Btu/Wh
)

SD1
1

Single
8,000
7.0

SD2
1

Single
9,500
9.6

SD3
1

Single
12,000
8.7

SD4
1

Single
13,000
9.7

SD5
Single
8,000
10.2

SD6
Single
14,000
8.9

SD7
Single
12,000
8.1

SD8
Single
9,000
9.2

SD9
Single
9,000
10.3

SD10
Single
10,000
9.5

SD11
Single
12,000
12.6

SD12
Single
10,000
8.8

SD13
Single
12,500

3
N/A

SD14
Single
12,000
10.0

SD15
Single
5,000
8.6

SD16
Single
11,000
9.2

SD17
Single
12,000

3
N/A

DD1
1

Dual
9,500
9.4

DD2
1

Dual
13,000
8.9

DD3
Dual
11,600
8.8

DD4
2

Dual
14,000

3
N/A

DD5
Dual
9,000
9.2

DD6
Dual
14,000
9.5

DD7
Dual
13,500
9.5

1
These units were tested and discussed in the May 2014 NODA. This table does not include the two spot coolers that were tested in support of the May 2014 NODA.

2
This test unit shipped with the capabilities of operating in both single-duct and dual-duct configuration. Therefore, it was tested according to both configurations.

3
No rated value was published in the CEC database or in manufacturer documentation.

Baseline Testing

DOE first performed testing in accordance with AHAM PAC-1-2009
11

to determine baseline performance according to industry standards. This baseline performance was then compared to performance measured according to modified or alternate test approaches to determine an optimal approach.

11
DOE's testing and analysis was completed prior to the publication of AHAM PAC-1-2014. Because, as discussed earlier, DOE concludes that the differences between the 2009 and 2014 versions of the test standard would not affect testing results substantively, DOE proposes a test procedure in this rule that would referenece certain provisions of the current versions of the standard (AHAM PAC-1-2014).

AHAM PAC-1-2009 requires two-chamber air enthalpy testing for single-duct and dual-duct units, and a single-chamber setup for spot coolers. For each ducted configuration, the portable AC and any associated ducting is located entirely within a chamber held at “indoor” standard rating conditions at the evaporator inlet of 80 °F dry-bulb temperature and 67 °F wet-bulb temperature, which correspond to 51-

percent relative humidity. For the condenser-side exhaust on single-duct and dual-duct units, the manufacturer-supplied or manufacturer-specified flexible ducting connects the unit under test to a separate test chamber maintained at “outdoor” standard rating conditions. The outdoor conditions specify 95 °F dry-bulb temperature and 75 °F wet-bulb temperature (40-percent relative humidity) at the condenser inlet for dual-duct units. The outdoor conditions for single-duct units, however, are not explicitly specified. AHAM PAC-1-2009 only requires that the condenser inlet conditions, which would be set by air intake from the indoor side chamber, be maintained at 80 °F dry-bulb temperature and 67 °F wet-bulb temperature. Because the single-duct condenser air is discharged to the outdoor side with no intake air from that location, DOE does not believe that the results obtained using AHAM PAC-1-2009 would be measurably affected by the conditions in the outdoor side chamber. Nonetheless, for consistency with the testing of dual-duct units, DOE chose to maintain the outdoor side conditions, measured near to the condenser exhaust but not close enough to be affected by that airflow, at 95 °F dry-bulb temperature and 75 °F wet-bulb temperature.

Section 6.1 of AHAM PAC-1-2009, “Method of Test,” instructs that the details of testing are as specified in ANSI/ASHRAE Standard 37-2005, but does not identify particular provisions to be used other than noting that references in Section 8.5.1 of ANSI/ASHRAE Standard 37-2005 refer to the indoor side (the cooling, or evaporator side) and the outdoor side (the heat rejection, or condenser, side) of the portable AC under test. DOE determined that additional relevant sections to incorporate would include those referring to test setup, test conduct, cooling capacity and power input determination, data recording, and test result reporting. The following paragraphs describe the equivalent clauses from ANSI/ASHRAE Standard 37-2009 that DOE decided were appropriate for conducting its baseline tests for both the May 2014 NODA and this proposal.

The test apparatus (
i.e.,
ducts, air flow-measurement nozzle, and additional instrumentation) were adjusted according to Section 8.6, “Additional Requirements for the Outdoor Air Enthalpy Method,” of ANSI/ASHRAE Standard 37-2009, which ensures that air flow rate and static pressure in the condenser exhaust air stream, and condenser inlet air stream for dual-duct units, are representative of actual installations. The test room conditioning apparatus and the units under test were then operated until steady-state performance was achieved according to the specified test tolerances in Section 8.7, “Test Procedure for Cooling Capacity Tests,” of ANSI/ASHRAE Standard 37-2009. Airflow rate, dry-bulb temperature, and water vapor content were recorded to evaluate cooling capacity at equal intervals that spanned 5 minutes or less until readings over one-half hour were within the same tolerances, as required by that section.

These collected data were then used to calculate total, sensible, and latent indoor cooling capacity based on the equations in Section 7.3.3, “Cooling Calculations,” of ANSI/ASHRAE Standard 37-2009. This section provides calculations to determine indoor cooling capacity based on both the indoor and outdoor air enthalpy methods. As described in Section 7.3.3.3 of ANSI/ASHRAE Standard 37-2009, the indoor air enthalpy cooling capacity calculation was adjusted for heat transferred from the surface of the duct(s) to the conditioned space. DOE estimated a convective heat transfer coefficient of 4 Btu/h per square foot per °F, based on a midpoint of values for forced convection and free convection as recommended by the test laboratory for this specific test and setup. Four thermocouples were placed in a grid on the surface of the condenser duct(s). The heat transfer was determined by multiplying the estimated heat transfer coefficient by the surface area of each component and by the average temperature difference between the duct surface and test chamber air.

Although AHAM PAC-1-2009 specifies in Section 5.1 that the evaporator circulating fan heat shall be included in the total cooling capacity by means of fan power measurement, DOE selected an alternate calculation that it concluded would provide a more accurate measure of overall heat transfer to the conditioned space. DOE estimated this heat transferred to the conditioned space by monitoring the temperature differential between the case surfaces and the indoor room, with measurements and calculations similar to those used for the ducts. This estimate was made by placing four thermocouples on each surface of the case and measuring the surface area to determine the total heat transfer through the case. This approach directly estimates the heating contribution of all internal components within the case to the cooling capacity, while making no assumption regarding whether the heat from individual components is transferred to the cooling or heat rejection side.

Based on the provisions discussed above, DOE used the following equation when calculating the cooling capacity and EER for portable ACs according to AHAM PAC-1-2009:

Cooling Capacity
=
Q
indoor
−
Q
duct
−
Q
case

Where:

Q
indoor
is the evaporator air enthalpy cooling capacity, in Btu/h, as calculated according to Section 7.3.3.1 of ANSI/ASHRAE 37-2009.

Q
duct
is the heat transferred from the condenser exhaust duct (and condenser inlet duct for dual-duct units) to the conditioned space, in Btu/h, as calculated according to Section 7.3.3.3 of ANSI/ASHRAE 37-2009.

Q
case
is the heat transferred from the portable AC case to the conditioned space, in Btu/h, also calculated using the methodology in 7.3.3.3 of ANSI/ASHRAE 37-2009, but using temperature measurements located on the case surfaces rather than the ducts.

From the calculated evaporator air enthalpy cooling capacity, DOE determined the associated EER consistent with the definitions in Sections 3.8 and 3.9 and ratings requirements in Sections 5.3 and 5.4 of AHAM PAC-1-2009. Table III.2 shows the results of the baseline testing for all test units according to AHAM PAC-1-2009, including results from testing for the May 2014 NODA and this proposal.

Table III.2—Baseline Test Results

Test unit
Duct type

Cooling capacity (
Btu/h
)

EER (
Btu/Wh
)

SD1
Single
5,850
6.8

SD2
Single
6,600
7.4

SD3
Single
10,950
7.5

SD4
Single
9,500
6.6

SD5
Single
5,600
8.3

SD6
Single
10,250
8.0

SD7
Single
8,550
6.4

SD8
Single
6,750
5.9

SD9
Single
6,700
6.9

SD10
Single
8,100
8.1

SD11
Single
5,700
5.7

SD12
Single
8,050
7.3

SD13
Single
10,350
8.6

SD14
Single
9,250
8.1

SD15
Single
4,250
8.2

SD16
Single
8,200
7.3

SD17
Single
5,800
6.8

SD18
1

Single
7,200
5.4

DD1
Dual
8,600
7.4

DD2
Dual
7,200
5.5

DD3
Dual
5,950
4.8

DD4
1

Dual
5,900
4.1

DD5
Dual
5,250
5.3

DD6
Dual
7,450
6.0

DD7
Dual
7,300
5.7

1
This test unit shipped with the capabilities of operating in both single-duct and dual-duct configuration. Therefore, it was tested according to both configurations.

Calorimeter Method Testing

For the May 2014 NODA and this proposal, DOE further investigated heat transfer effects not currently captured in available portable AC test procedures, through additional testing according to the room calorimeter approach described in the May 2014 NODA. 79 FR 26639, 26644 (May 9, 2014). This approach, adapted from ANSI/ASHRAE Standard 16-1983, used two test chambers, one maintained at the indoor conditions and the other adjusted to maintain the outdoor conditions as specified below. The portable AC under test was located within the indoor test room with the condenser duct(s) interfacing with the outdoor test room by means of the manufacturer-supplied or manufacturer-recommended mounting fixture, unless otherwise noted. Infiltration air from the outdoor chamber at 95 °F dry-bulb and 75 °F wet-bulb (40-percent relative humidity) was introduced by means of a pressure-equalizing device to the indoor chamber, which was maintained at 80 °F dry-bulb and 67 °F wet-bulb (51-percent relative humidity). The pressure-equalizing device maintained a static pressure differential of less than 0.005 inches of water between the chambers, as specified in Section 4.2.3 of ANSI/ASHRAE Standard 16-1983.

DOE measured all energy consumed by the indoor chamber components to maintain the required ambient conditions while the portable AC under test operated continuously at its maximum fan speed during a 1-hour stable period following a period of no less than 1 hour with stabilized conditions. All heating and cooling contributions to the indoor chamber were summed, including: Chamber cooling, heat transferred through the chamber wall, air-circulation fans, dehumidifiers, humidifiers, and scales. The net indoor chamber cooling was recorded as the portable AC's cooling capacity. This approach encompasses all cooling and heating effects generated by the portable AC, including air infiltration effects that are not captured or estimated by the air enthalpy approach.

The test units were installed with the manufacturer-provided ducting, duct attachment collar, and mounting fixture. This test approach included the impacts of heat transfer from the ducts and air leaks in the duct connections and mounting fixture, in addition to heat leakage through the case and infiltration air. Table III.3 shows the measured net cooling capacities and EER values for all units tested according to the calorimeter approach when the infiltration air dry-bulb temperature was 95 °F. Also included are the results for the rated and baseline values. Figure III.1 also presents the comparison of baseline and calorimeter testing results.

Table III.3—Rated, Baseline, and Calorimeter Results

Test unit

Cooling capacity (
Btu/h
)

Rated
Baseline
Calorimeter

EER (
Btu/Wh
)

Rated
Baseline
Calorimeter

SD1
8,000
5,850
-450
7.0
6.8
-0.5

SD2
9,500
6,600
-650
9.6
7.4
-0.7

SD3
12,000
10,950
3,500
8.7
7.5
2.3

SD4
13,000
9,500
1,850
9.7
6.6
1.3

SD5
8,000
5,600
150
10.2
8.3
0.2

SD6
14,000
10,250
3,000
8.9
8.0
2.3

SD7
12,000
8,550
2,850
8.1
6.4
2.1

SD8
9,000
6,750
900
9.2
5.9
0.8

SD9
9,000
6,700
1,050
10.3
6.9
1.1

SD10
10,000
8,100
1,900
9.5
8.1
1.9

SD11
12,000
5,700
1,100
12.6
5.7
1.1

SD12
10,000
8,050
1,600
8.8
7.3
1.5

SD13
12,500
10,350
3,900

1
N/A

8.6
3.2

SD14
12,000
9,250
2,300
10.0
8.1
2.0

SD15
5,000
4,250
-2,450
8.6
8.2
-4.7

SD16
11,000
8,200
1,700
9.2
7.3
1.5

SD17
12,000
5,800
-650

1
N/A

6.8
-0.7

SD18
2

14,000
7,200
850

1
N/A

5.4
0.6

DD1
9,500
8,600
3,400
9.4
7.4
2.9

DD2
13,000
7,200
3,450
8.9
5.5
2.6

DD3
11,600
5,950
3,100
8.8
4.8
2.5

DD4
2

14,000
5,900
2,400

1
N/A

4.1
1.7

DD5
9,000
5,250
2,700
9.2
5.3
2.8

DD6
14,000
7,450
2,800
9.5
6.0
2.2

DD7
13,500
7,300
4,000
9.5
5.7
3.0

1
No rated value was published in the CEC database or on manufacturer documentation.

2
This test unit shipped with the capabilities of operating in both single-duct and dual-duct configuration. Therefore, it was tested according to both configurations.

EP25FE15.000

Figure III.1 demonstrates that there is little correlation between EER and cooling capacity for the baseline results when the effects of air infiltration and heat losses are not accounted for. When such effects are included, the values of both EER and cooling capacity are reduced for a given test unit, but the data evidence a clear relationship between EER and cooling capacity. Figure III.1 also demonstrates that the net cooling of portable ACs may be significantly lower than an air enthalpy measurement would suggest, due to the effects of infiltration air. Thus, DOE determined that the existing representations of capacity and EER, which are based on air enthalpy methods, are likely to be inconsistent and may not represent true portable AC performance. Further, the varying differences between the calorimeter and baseline results indicate that varying infiltration air flow rates and heat losses would preclude a fixed translation factor that could be applied to the results of an air enthalpy measurement to account for the impact of these effects. For these reasons, DOE determined that a DOE test procedure for portable ACs that includes a measure of infiltration air effects and heat losses would provide consistency and clarity for representation of capacity and energy use for these products. Specific proposals for such a test procedure are discussed in the following sections.

i. General Test Approach

As discussed in the previous section, the results from baseline testing according to AHAM PAC-1-2009 and investigative testing according to the calorimeter approach suggest that the calorimeter approach most accurately represents portable AC performance by accounting for the effects of air infiltration and heat losses.

DOE considered comments received in response to the initial baseline and calorimeter approach results presented in the May 2014 NODA. Appliance Standards Awareness Project, Alliance to Save Energy, American Council for an Energy-Efficient Economy, Consumers Union, Natural Resources Defense Council, and Northwest Energy Efficiency Alliance (hereinafter referred to as the “Joint Commenters”) and the California IOUs observed that the current industry test procedures do not capture the effects of infiltration air and duct heat loss and leakage, which would lead to an overestimation of portable AC

performance in real-world settings. In addition, according to the Joint Commenters, the current industry test procedures do not provide an accurate relative ranking of portable AC units, such that single-duct units appear to be more efficient than dual-duct units. Therefore, the Joint Commenters and the California IOUs urged DOE to adopt a test procedure for portable ACs based on the calorimeter approach, which would align with the current test procedures for room ACs and would better reflect real-world cooling capacities and EERs of both single-duct and dual-duct configurations. The California IOUs commented that because portable ACs can be used as a substitute for room ACs, they support the adoption of a test procedure for portable ACs that would allow consumers to make realistic comparisons of capacity and efficiency between comparable product types. (California IOUs, No. 5 at pp. 2-3; Joint Commenters, No. 6 at pp. 1-2)

AHAM supports the incorporation by reference of AHAM PAC-1-2014, which is harmonized with CSA C370-2013, in a DOE test procedure for portable ACs. AHAM indicated that AHAM PAC-1-2014 best measures representative performance for each portable AC configuration, in comparison to other approaches. AHAM commented that, unlike other air conditioning products, portable ACs are intended to be easily relocated from one room to another and therefore the compressor and condenser are both inside the conditioned room, as opposed to a room AC, where the compressor and condenser are outside the room. Because a portable AC does not operate in between the conditioned and unconditioned space as room ACs do, and instead is located solely in the conditioned space, AHAM believes that the calorimeter approach, intended for room ACs, may not be as representative as the enthalpy approach for portable ACs. AHAM also commented that ANSI/ASHRAE 128-2011 instructs that it is not to be used for portable ACs with cooling capacities less than 65,000 Btu/h, and ANSI/AHAM 128-2001 does not address all portable AC configurations. AHAM noted that Canada may promulgate portable AC standards using CSA C370-2013, and stated that North American harmonization will provide consistency and clarity for regulated parties and consumers in both countries. (AHAM, No. 4 at p. 2) AHAM acknowledged the differences between rated values and baseline test results obtained using AHAM PAC-1-2009, and stated that a conversion factor between rated values and results obtained using its recommended test procedure, AHAM PAC-1-2014, is not feasible due to the wide range of differences between these values. (AHAM, No. 4 at p. 3)

De' Longhi Appliances s.r.l. (De' Longhi) indicated that the air enthalpy method and a calorimeter method with no air infiltration would ensure levels of reproducibility and repeatability required for regulated products. Further, De' Longhi stated that AHAM PAC-1-2009 and CSA C370-2013 are more suitable for representing performance of all the categories of portable ACs. (De' Longhi, No. 3 at p. 5)

AHAM and De' Longhi also stated that the calorimeter approach is much more burdensome than the air enthalpy approach, requiring more expensive test equipment and longer test times. AHAM believes that adoption of the calorimeter method for testing portable ACs would also require many laboratories to build new test facilities because portable ACs are not currently tested using a calorimeter approach, representing a significant burden. AHAM is also concerned that there are few third-party test laboratories that have the capability to test using a calorimeter approach, which would impact choice and availability for testing. Therefore, AHAM urged DOE to adopt the test approach of AHAM PAC-1-2014 to produce representative test results that are not unduly burdensome to conduct. (AHAM, No. 4 at p. 4) De' Longhi stated that the test burden associated with a test method should be proportionate to the amount of energy consumed by a certain product category. According to De' Longhi, because portable ACs are a small fraction of the air conditioning market with a unique usage pattern, being operated generally for short period of time, the test burden should be minimized. De' Longhi commented that the calorimeter method would result in an unreasonably large burden for this product category, and therefore, the air enthalpy method is preferable due to the higher availability of testing apparatus and lower cost of testing. (De' Longhi, No. 3 at p. 3)

The results presented in Table III.3 and displayed in Figure III.1 demonstrate that the calorimeter method provides a measure of net portable AC cooling capacity and EER across different product configurations and varying air infiltration rates that is comparable to the performance trends obtained according to AHAM PAC-1-2009. However, DOE found in its testing that, although equipment setup is simpler for the calorimeter approach as based on ANSI/ASHRAE Standard 16 requirements, maintaining the conditions in a calorimeter chamber can be difficult, particularly at higher test unit cooling capacities. In those cases, additional climate control components may be necessary, all of which must be monitored to measure the heat transfer to and from the indoor side test room. These additional components may include air circulating fans to ensure conditions are uniform throughout the test room, humidifiers and dehumidifiers to maintain the necessary relative humidity, and scales to measure the evaporated or condensed moisture during testing. Incorporating the heating and cooling effects from each of these components proved to be complex, with potential uncertainties in the net cooling capacity accumulating with each additional component. After considering the burdens and complexity of the calorimeter approach, DOE determined the air enthalpy approach provided in AHAM PAC-1-2009 and AHAM PAC-1-2014 to be a less burdensome approach. Although AHAM PAC-1-2014 requires comprehensive instrumentation to monitor air stream enthalpies and specific measures to ensure that this instrumentation has no impact on performance, it also provides a straight-forward calculation for determining indoor-side cooling based on a well-defined set of variables. Many of the instruments required for the air enthalpy approach, as specified in ANSI/ASHRAE Standard 37, are used in testing central ACs and heat pumps, and ANSI/ASHRAE Standard 37 is also referenced in the DOE test procedure to determine energy consumption of furnace fans. Thus, DOE believes that many commercial laboratories have the capability to perform the air enthalpy test, while few laboratories in the United States have the test chamber and instrumentation required to test according to the calorimeter approach. In addition, the air enthalpy approach, as specified in ANSI/ASHRAE Standard 37 with additional guidance in AHAM PAC-1-2014, is specifically applicable for testing portable ACs, while the calorimeter approach requires modifications from the room AC test procedure specified in ANSI/ASHRAE 16 to accommodate portable ACs.

Therefore, if DOE determines that portable ACs are covered products and establishes a test procedure for them, DOE proposes that AHAM PAC-1-2014 be the basis of the DOE test procedure to ensure that multiple labs are capable of performing the test, to minimize added test burden, and to align with current industry practices. However, as described in the remaining subsections of section III.1.a, DOE believes that additional provisions and clarifications

would be necessary to incorporate AHAM PAC-1-2014 into a DOE portable AC test procedure.

ii. Infiltration Air Effects and Cooling Capacity

Infiltration from outside the conditioned space in which the portable AC is located occurs due to the negative pressure induced as condenser air is exhausted to the outdoor space. Although this effect is most pronounced for single-duct units, which draw all of their condenser air from within the conditioned space, dual-duct units also draw a portion of their condenser air from the conditioned space. In its testing, DOE estimated the infiltration air flow rate as equal to the condenser exhaust flow rate to the outdoor chamber minus any condenser intake flow rate from the outdoor chamber because it had determined that air leakage from the outdoor chamber to locations other than the indoor chamber was negligible.

For a single-duct unit, the air balance equation results in the infiltration air flow rate being equal to the condenser exhaust air flow rate. For dual-duct units, the condenser exhaust duct flow rate may be higher than the inlet duct flow rate. This is due to some intake air being drawn from the indoor chamber via louvers or leakage through the case, duct connections, or between the evaporator and condenser sections. Table III.4 presents the estimated infiltration air flow rates for the full test sample.

Table III.4—Infiltration Air Flow Rate

Test unit

Condenser outlet air flow rate
(CFM)

Condenser inlet air flow rate
(CFM) *

Net infiltration air flow rate
(CFM)

SD1
268.03

268.03

SD2
262.59

262.59

SD3
285.45

285.45

SD4
254.30

254.30

SD5
217.77

217.77

SD6
228.43

228.43

SD7
221.83

221.83

SD8
224.61

224.61

SD9
229.09

229.09

SD10
220.80

220.80

SD11
175.07

175.07

SD12
237.37

237.37

SD13
247.39

247.39

SD14
262.52

262.52

SD15
278.89

278.89

SD16
250.69

250.69

SD17
249.37

249.37

SD18
246.48

246.48

Average of Single-Duct

242.26

DD1
271.85
170.79
101.06

DD2
214.83
128.05
86.78

DD3
234.87
146.29
88.58

DD4
251.67
126.60
125.07

DD5
207.85
113.15
94.71

DD6
272.43
76.61
195.82

DD7
244.47
107.49
136.99

Average of Dual-Duct

118.43

* Condenser inlet air flow rate is only applicable for dual-duct units.

As discussed in the May 2014 NODA, DOE investigated various infiltration air temperatures. In its initial calorimeter tests, DOE maintained the outdoor test chamber conditions at 95 °F dry-bulb temperature and 75 °F wet-bulb temperature, which would be representative of outdoor air being drawn directly into the conditioned space to replace any condenser inlet air from that same conditioned space. However, it is possible that some or all of the replacement air is drawn from a location other than the outdoors directly, such as a basement, attic, garage, or a space that is conditioned by other equipment. Because varying infiltration air temperature would have a significant impact on cooling capacity and EER, DOE performed additional testing over a range of dry-bulb temperatures for the infiltration air that spanned 78 °F to 95 °F, all at the 40-percent relative humidity specified at the 95 °F condition. 79 FR 26639, 26646 (May 9, 2014).

In response to the May 2014 NODA, the Joint Commenters and California IOUs stated that the current industry standard outdoor air conditions (95 °F dry-bulb temperature and 75 °F wet-bulb temperature) are appropriate for infiltration air. (Joint Commenters, No. 6 at p. 3; California IOUs, No. 5 at p. 3) The Joint Commenters added that although some or all of the infiltration air may be drawn from a location other than the outdoors directly, such as a basement, attic, garage, or a space that is conditioned by other equipment, all infiltration air is ultimately coming from the outdoors and adding heat to the home where the portable AC is installed. (Joint Commenters, No. 6 at p. 3)

AHAM stated that in the field, there is a mixture of indoor and outdoor air, and infiltration air will be at different temperature and humidity levels in every home, due to varying home designs. Therefore, AHAM does not

believe there is an “average” condition that DOE could select to replicate in a test procedure condition and would not support an approach that utilizes existing test procedures with numerical adjustments for infiltration air. (AHAM, No. 4 at p. 5) De' Longhi concurred, stating that the effect of air infiltration would be complex to standardize. De' Longhi commented that air infiltration flow pathways are determined by the path of minimum air flow resistance, and therefore it is not possible to determine the amount of infiltration air that originates from adjacent indoor rooms versus from outdoors. De' Longhi believes that in most situations, unconditioned outdoor air is just a small portion of the total infiltration air. Accordingly, De' Longhi stated that the standard outdoor air conditions of 95 °F dry-bulb temperature and 75 °F wet-bulb temperature are not representative of the infiltration air temperatures. De' Longhi suggested that if DOE determines to include portable ACs as a covered product, the heat transfer effects of infiltration air should not be taken into account in a DOE test procedure. (De' Longhi, No. 3 at p. 4)

DOE agrees that, as for all covered products, real-world installations experience varying ambient conditions. The test procedure must thus consider the most representative operation in selecting appropriate specifications for those conditions. Recognizing that in some cases the infiltration air enters the conditioned space directly from outdoors, and that any air infiltrating from other conditioned spaces likely also originated from outdoors before being conditioned by other cooling equipment, DOE concludes that 95 °F dry-bulb temperature and 75 °F wet-bulb temperature is most representative for infiltration air conditions, in accordance with the outdoor conditions specified in AHAM PAC-1-2014, and proposes to specify these conditions in the portable AC test procedure. Such conditions would also produce comparable results for single-duct and dual-duct configurations.

DOE also developed methodology for the May 2014 NODA that would adjust the results obtained from an air enthalpy method to account for the total heat added to the room by the infiltration air. The infiltration air mass flow rate of dry air would be calculated as:

EP25FE15.001

Where:

m

sd
is the dry air mass flow rate of infiltration air for a single-duct unit, in pounds per minute (lb/m).

m

dd
is the dry air mass flow rate of infiltration air for a dual-duct unit, in lb/m.

V
co
is the volumetric flow rate of the condenser outlet air, in cubic feet per minute (cfm).

V
ci
is the volumetric flow rate of the condenser inlet air, in cfm.

ρ
co
is the density of the condenser inlet air, in pounds mass per cubic feet (lb
m
/ft
3
).

ρ
ci
is the density of the condenser inlet air, in lb
m
/ft
3
.

ω
co
is the humidity ratio of condenser outlet air, in pounds mass of water vapor per pounds mass of dry air (lb
w
/lb
da
).

ω
ci
is the humidity ratio of condenser inlet air, in lb
w
/lb
da
.

The sensible heat contribution of the infiltration air would be calculated as follows:

EP25FE15.002

Where:

Q
s
is the sensible heat added to the room by infiltration air, in Btu/h;

m

is the dry air mass flow rate of infiltration air for a single-duct or dual-dual duct unit, in lb/m;

c
p_da
is the specific heat of dry air, 0.24 Btu/lb
m
- °F.

c
p_wv
is the specific heat of water vapor, 0.444 Btu/lb
m
- °F.

ω
ia
is the humidity ratio of the infiltration air, 0.0141 lb
w
/lb
da
.

ω
ei
is the humidity ratio of the evaporator inlet air, in lb
w
/lb
da
.

60 is the conversion factor from minutes to hours.

T
ei
is the indoor chamber dry-bulb temperature measured at the evaporator inlet, in °F.

T
ia
is the infiltration air dry-bulb temperature, 95 °F.

DOE used the following equation for the latent heat contribution of the infiltration air:

EP25FE15.003

Where:

Q
l
is the latent heat added to the room by infiltration air, in Btu/h.

m

is the mass flow rate of infiltration air for a single-duct or dual-dual duct unit, in lb/m.

ω
ia
is the humidity ratio of the infiltration air, 0.0141 lb
w
/lb
da
.

ω
ei
is the humidity ratio of the evaporator inlet air, in lb
w
/lb
da
.

H
fg
is the latent heat of vaporization for water vapor, 1061 Btu/lb
m
.

60 is the conversion factor from minutes to hours.

The total heat contribution of the infiltration air is the sum of the sensible and latent heat.

Q
infiltration
=
Q
s
+
Q
l

Where:

Q
infiltration
is the total infiltration air heat, in Btu/h.

Q
s
is the sensible heat added to the room by infiltration air, in Btu/h.

Q
l
is the latent heat added to the room by infiltration air, in Btu/h.

Table III.5 displays the cooling capacity as determined by the baseline air enthalpy testing approach of AHAM PAC-1-2009, and the modified air enthalpy approach that subtracts the estimated infiltration air heat input from the cooling capacity measurement.

Table III.5—Modified Air Enthalpy Performance

Test unit

Cooling capacity (
Btu/h
)

Baseline
Modified AHAM

EER
cm
(
Btu/Wh
)

Baseline
Modified AHAM

SD1
5,850
−900
6.8
−1.0

SD2
6,600
200
7.4
0.2

SD3
10,950
4,050
7.5
2.8

SD4
9,500
4,000
6.6
2.8

SD5
5,600
400
8.3
0.6

SD6
10,250
4,750
8.0
3.7

SD7
8,550
3,500
6.4
2.6

SD8
6,750
1,500
5.9
1.3

SD9
6,700
1,150
6.9
1.2

SD10
8,100
2,750
8.1
2.7

SD11
5,700
1,350
5.7
1.4

SD12
8,050
2,250
7.3
2.0

SD13
10,350
4,450
8.6
3.7

SD14
9,250
2,800
8.1
2.4

SD15
4,250
−2,900
8.2
−5.6

SD16
8,200
2,200
7.3
2.0

SD17
5,800
−850
6.8
−1.0

SD18
7,200
1,300
5.4
1.0

DD1
8,600
6,550
7.4
5.6

DD2
7,200
5,500
5.5
4.2

DD3
5,950
4,150
4.8
3.4

DD4
5,900
3,100
4.1
2.2

DD5
5,250
3,200
5.3
3.2

DD6
7,450
2,800
6.0
2.2

DD7
7,300
4,200
5.7
3.3

The data above show the significant reduction in cooling capacity and EER
cm
caused by infiltration air heat input, which is greater for single-duct units than for dual-duct units. For three of the single-duct units, the impacts of infiltration air were so great that they produced net heating in the conditioned space, as indicated by the negative cooling capacity values.

In response to this approach, which was presented in the May 2014 NODA, the Joint Commenters stated that this modified air enthalpy testing approach is not a suitable alternative to the proposed calorimeter approach. According to the Joint Commenters, the alternate testing approach would provide a significant improvement over the current industry test procedures by addressing the impact of infiltration air with a numerical adjustment, but the alternate testing approach fails to capture additional impacts on portable AC performance such as leakage through gaps in the ducts and duct connections and heat transfer through the ducts. The Joint Commenters expressed concern that DOE found no consistent difference between the calorimeter approach and the alternate test approach, and therefore believe the alternate test approach would not necessarily provide a good indication of real-world portable AC performance. Although the alternate testing approach may represent a lower testing burden compared to the calorimeter approach, the Joint Commenters reminded DOE that the current room AC test procedure is based on a calorimeter approach, and stated that the calorimeter approach is also appropriate for portable ACs. (Joint Commenters, No. 6 at p. 3)

DOE recognizes that the modified air enthalpy approach and calorimeter approach both greatly reduce the cooling capacity and EER
cm
when compared with the results from AHAM PAC-1-2014 and other current industry-accepted test procedures that do not address infiltration air. Based on the data presented above and comments received from interested parties and manufacturer interviews, DOE believes that any portable AC test procedure must include the heat transfer effects of infiltration air, in addition to the effects of duct and case heat transfer, discussed later in this NOPR. DOE also recognizes that the results produced by the calorimeter and modified air enthalpy approaches do not align. However, as discussed earlier in this section, DOE found it difficult to maintain the test chamber conditions for the calorimeter approach, particularly for higher-capacity portable ACs. Due to significant infiltration of air at conditions substantially different than the required indoor-side test chamber conditions, additional air conditioning equipment is required to maintain the indoor-side test chamber conditions, all of which must be accounted for in determining the net heating or cooling effect in the test chamber. DOE believes the cumulative uncertainty related to incorporating the heating and cooling effects from each of these components may have been significant enough to have resulted in the inconsistency between the calorimeter and modified air enthalpy approaches. The modified air enthalpy approach accounts for the major heating and cooling effects of the portable AC with direct measurements of the product air streams and temperature measurements of the case and ducts. Therefore, DOE is confident in the accuracy of the results from this test approach.

Based on the significant heat input from infiltration air seen from testing, DOE determined that applying such a numerical adjustment for infiltration air to the results of testing with AHAM PAC-1-2014 would accurately reflect portable AC performance. Therefore, DOE proposes the adjusted cooling capacity be determined as follows:

Adjusted Cooling Capacity = Capacity
cm
−
Q
infiltration
−
Q
misc

Where:

Capacity
cm
is the cooling capacity as determined in accordance with AHAM PAC-1-2014.

Q
infiltration
is the sum of sensible (Q
s
) and latent (Q
l
) heat transfer from infiltration air, as calculated above.

Q
misc
is the impact of other heat transfer effects, discussed in the following sections.

iii. Test Conditions

AHAM PAC-1-2014 requires two-chamber air enthalpy testing in which the “indoor” standard rating conditions are maintained at the evaporator inlet of 80.6 °F dry-bulb temperature and 66.2

°F wet-bulb temperature, which correspond to approximately 46-percent relative humidity. For single-duct units, the condenser inlet conditions are the same as the evaporator inlet. For dual-duct units, the outdoor conditions, as monitored at the interface between the condenser inlet duct and outdoor test room, must be maintained at 95 °F dry-bulb temperature and 75.2 °F wet-bulb temperature (40-percent relative humidity). Because these conditions are close to those required by the DOE room air conditioner test procedure (80 °F dry-bulb temperature and 67 °F wet-bulb temperature on the indoor side, and 95 °F dry-bulb temperature and 75 °F wet-bulb temperature on the outdoor side), test results obtained for portable ACs under the proposed test procedure would be comparable to those for room ACs, which would allow consumers to directly compare these product types. Therefore, DOE proposes to utilize the following ambient conditions presented in

Table III.6 below, based on those test conditions specified in Table 3, “Standard Rating Conditions,” of AHAM PAC-1-2014. The test configurations in

Table III.6 refer to the test configurations referenced in Table 2 of AHAM PAC-1-2014, with Test Configuration 3 applicable to dual-duct portable ACs and Test Configuration 5 applicable to single-duct portable ACs.

Table III.6—Standard Rating Conditions—Cooling Mode

Test configuration
Evaporator inlet air, °F (°C)
Dry bulb
Wet bulb
Condenser inlet air, °F (°C)
Dry bulb
Wet bulb

3
80.6 (27)
66.2 (19)
95.0 (35)
75.2 (24)

5
80.6 (27)
66.2 (19)
80.6 (27)
66.2 (19)

For single-duct units, AHAM PAC-1-2014 specifies identical evaporator and condenser inlet conditions, with the same allowable tolerances on the dry-bulb and wet-bulb temperatures. Depending upon the airflow and unit configuration, the evaporator and condenser inlet may be directly adjacent to one another or on opposite faces of the test unit case. Thus, although both evaporator and condenser inlets intake air from the same conditioned space, it is possible that the two inlet air conditions may not simultaneously meet the requirements in AHAM PAC-1-2014 due to slight non-homogeneity in the test chamber, even if one or the other inlet is within tolerance.

Table 2b in Section 8.7 of ANSI/ASHRAE Standard 37-2009, referenced by AHAM PAC-1-2014, specifies that both condenser inlet and evaporator inlet dry-bulb temperatures must be maintained within a range of 2.0 °F and an average within 0.5 °F of the nominal values. However, test chambers may experience varying levels of homogeneity in test conditions and test laboratories may differently prioritize maintaining conditions at either the condenser inlet or evaporator inlet. Therefore, to ensure repeatability and reproducibility, DOE proposes in this NOPR to specify a more stringent tolerance for the evaporator inlet dry-bulb that is consistent with the evaporator inlet wet-bulb temperature tolerance, within a range of 1.0 °F with an average difference of 0.3 °F. The condenser inlet dry-bulb temperature would be maintained within the test tolerance as specified in Table 2b of ANSI/ASHRAE Standard 37-2009. This tolerance modification will ensure that all test laboratories employ the same approach in testing, to first maintain the evaporator inlet test conditions and then ensure that condenser inlet conditions satisfy the tolerance requirements.

As discussed in the May 2014 NODA, portable AC manufacturers typically provide a single mounting fixture for dual-duct units that houses both the condenser inlet and exhaust ducts to minimize installation time and optimize the use of window space. However, this approach typically positions the condenser inlet and exhaust directly adjacent to one another. During operation when installed in the field, short-circuiting may occur between some of the condenser exhaust air and the outdoor ambient air. DOE investigated the effects of potential condenser inlet and exhaust mixing and results indicated that there was minimal mixing between the condenser exhaust and inlet air flows. 79 FR 26639, 26648 (May 9, 2014).

In response to the May 2014 NODA, De' Longhi commented that the condenser inlet and exhaust mixing only has a minimal influence as reported by DOE results. (De' Longhi, No. 3 at p. 4) AHAM agreed with DOE's conclusion that condenser exhaust air and inlet air mixing in dual-duct units need not be addressed or measured in a portable AC test procedure. (AHAM, No. 4 at p. 5)

iv. Duct Heat Transfer and Leakage

In response to the May 2014 NODA, the California IOUs commented that it is unclear if there is a standard test set-up in regards to length of ducting and distance from the portable AC to the outdoor chamber. They suggested that DOE should address alignment of the portable AC and the associated ducting, in relation to the outdoor chamber, including distance, duct length, duct insulation, and duct configuration (
e.g.,
inclusion of bends). (California IOUs, No. 5 at p. 3) Section 7.3.7 and Figure 2 of AHAM PAC-1-2014 address the required ducting arrangement and specifies the duct height, duct length, and spacing of the test unit in relation to the chamber walls. Additionally, duct insulation and unit placement are further discussed in this section and section III.B.1.a.viii of this NOPR.

DOE also received comments from AHAM and De' Longhi expressing concern about including in a portable AC test procedure the effects of heat loss through minimally insulated ducts. They commented that there is no standardized method to account for such heat loss and that incorporating duct heat loss and leakage would impact test reproducibility and repeatability. AHAM stated that the approach DOE used in its investigative testing for estimating duct heat transfer is overly complicated and unnecessary. Accordingly, AHAM and De' Longhi suggested that the DOE test procedure should not address these factors. (AHAM, No. 4 at pp. 3-4; De' Longhi, No. 3 at p. 3)

As discussed in the May 2014 NODA, DOE investigated cooling performance impacts of uninsulated ducts and any air leakage at the duct connections or mounting fixtures. To quantify the heat transfer to the conditioned space through the minimally insulated condenser duct(s) and from any leaks at the duct connections or mounting fixture, DOE repeated the calorimeter testing with insulation surrounding the condenser ducts to benchmark results without this heat transfer for the initial

four single-duct and two dual-duct test units. DOE used insulation having a nominal R value of 6 (in units of hours-°F-square feet per Btu), with seams around the duct, adapter, and mounting bracket sealed with tape to minimize air leakage. To determine duct losses and air leakage effects, DOE compared results from these tests to the results from the initial calorimeter approach tests with no insulation. DOE found that uninsulated ducts and leaks in duct connections contribute anywhere from 460 to 1,300 Btu/h, which correlate to percentages of uninsulated cooling capacity that range from 18 to 199 percent. 79 FR 26639, 26645 (May 9, 2014). Therefore, DOE determined that duct heat losses and air leakage are non-negligible effects, and that duct configurations during the DOE test must be representative of actual usage. In addition, DOE notes that Section 7.3.3 of AHAM PAC-1-2014 states that “the portable AC shall be tested with clean filters in place as supplied by the manufacturer. Other equipment recommended as part of the air conditioner shall be in place, as well.” DOE proposes, therefore, that all ducting components (
e.g.,
duct, duct connections, and mounting bracket) as supplied by the manufacturer would be used for determining performance and would be installed in accordance with the manufacturer instructions. No additional sealing or insulation would be applied.

Section 7.3.3.3 of ANSI/ASHRAE Standard 37, as referenced by AHAM PAC-1-2014, specifies that the indoor cooling capacity shall be adjusted for heat transferred from the surface of ducts to the conditioned space. DOE recognizes that additional guidance may be necessary to determine such an adjustment, and for this reason proposes to account for heat transferred from the duct surface to the conditioned space in a portable AC test procedure methodology.

DOE proposes that four equally spaced thermocouples be adhered to the side of the entire length of the condenser exhaust duct for single-duct units and to each of the condenser inlet and exhaust ducts for dual-duct units. To ensure accurate heat transfer estimates, DOE proposes that temperature measurements would be required to have an accuracy to within ±0.5 °F. DOE proposes to average the four surface temperatures measurements to obtain T
duct
for each duct. DOE further proposes that a convection heat transfer coefficient of 4 Btu/h per square foot per °F be used, based on an average of values for forced convection and free convection. The surface area of each duct would be calculated as follows:

A
duct_j
= π × d
j
× L
j

Where:

d
j
is the outer duct diameter of duct “j”.

L
j
is the extended length of duct “j” while under test.

j represents the condenser exhaust duct and, for dual-duct units, condenser inlet duct.

Heat transferred from the surface of the duct(s) to the indoor conditioned space while operating in cooling mode shall be calculated as follows:

Q
duct_cm
= Σ
j
{
h
×
A
duct_j
× (
T
duct_j
−
T
ei
)}

Where:

Q
duct_cm
is the total heat transferred from the duct(s) to the indoor conditioned space in cooling mode.

h is the convection coefficient, 4 Btu/h per square foot per °F.

A
duct_j
is the surface area of duct “j”, in square feet.

T
duct_j
is the average surface temperature for duct “j”, in °F.

j represents the condenser exhaust duct and, for dual-duct units, condenser inlet duct.

T
ei
is the average evaporator inlet dry-bulb temperature, in °F.

v. Case Heat Transfer

As discussed previously in section III.B.1.a, DOE baseline testing incorporated a case heat transfer calculation, similar to that required to determine the heat transfer from the duct to the conditioned space in ANSI/AHAM Standard 37-2009, in lieu of the evaporator circulating fan heat measurement specified in AHAM PAC-1-2014. To determine case heat transfer, DOE placed four thermocouples on each face of the case to calculate average surface temperatures throughout the cooling mode test period. Table III.7 shows the average surface temperatures during the baseline testing for all single-duct and dual-duct test units.

Table III.7—Cooling Mode Case Surface Temperatures

Test unit
Average surface temperature during AHAM test (°F)
Top
Front
Right
Back
Left
Bottom
Average

SD1
79.4
81.6
81.5
81.3
81.9
84.2
81.7

SD2
79.6
79.0
80.9
89.2
91.5
88.5
84.8

SD3
76.6
82.3
80.0
82.3
84.9
83.0
81.5

SD4
73.0
85.3
92.2
82.9
82.7
84.8
83.5

SD5
77.9
81.3
82.3
83.6
82.4
89.8
82.9

SD6
72.8
80.5
78.5
81.7
81.9
86.0
80.2

SD7
73.2
82.8
82.7
81.4
78.2
87.7
81.0

SD8
88.6
79.7
84.2
91.2
87.8
77.3
84.8

SD9
78.2
85.0
77.8
86.0
80.5
93.3
83.5

SD10
76.8
91.4
84.3
84.5
85.0
97.4
86.6

SD11
79.8
87.7
85.4
84.5
87.6
90.6
85.9

SD12
72.7
82.2
80.8
81.8
80.3
81.2
79.8

SD13
72.8
79.7
81.1
81.8
82.2
83.7
80.2

SD14
75.6
78.9
79.2
84.1
81.5
81.8
80.2

SD15
79.9
83.7
81.1
81.4
85.9
80.6
82.1

SD16
75.5
88.1
88.1
80.3
81.7
84.5
83.0

SD17
80.3
80.0
83.4
94.9
91.0
95.1
87.4

SD18
76.4
78.8
79.1
81.4
78.9
87.2
80.3

DD1
75.1
78.0
80.2
82.7
80.5
81.4
79.7

DD2
80.8
75.9
80.6
86.7
81.0
87.7
82.1

DD3
76.7
80.2
80.7
86.4
81.8
81.4
81.2

DD4
78.2
79.8
80.3
85.2
79.9
89.2
82.1

DD5
75.7
77.0
82.2
84.6
83.2
85.1
81.3

DD6
76.7
78.3
81.0
85.1
79.0
78.1
79.7

DD7
74.4
83.3
79.6
88.0
76.9
80.3
80.4

Average
77.1
81.6
81.9
84.5
82.7
85.6

As shown in Table III.7, surface temperature varies significantly among different case surfaces of a given test unit during cooling mode, and that variation is a function of the particular test unit. For example, temperatures on test unit SD1 ranged from a top surface temperature of 79.4 °F to a bottom side temperature of 84.2 °F, a range of 4.8 °F, while test unit SD10 had a top surface temperature of 76.8 °F and a bottom side temperature of 97.4 °F, a range of 20.7 °F. Because each surface on a given test unit has a unique surface area and average surface temperature, DOE proposes that the heat transfer from the case to the ambient indoor space be calculated individually for each surface.

In response to the same methodology proposed in the May 2014 NODA, AHAM commented that this approach for estimating case heat transfer is overly complicated and unnecessary. AHAM believes that the approach in AHAM PAC-1-2014, which directly measures the evaporator circulating fan heat, is easier and simpler. AHAM also stated that DOE's method would introduce unnecessary variation in test results. (AHAM, No. 4 at p. 3)

DOE acknowledges that the proposed case heat transfer approach would require additional instrumentation. However, DOE believes that the testing burden imposed by the use of multiple thermocouples to measure surface temperatures is likely outweighed by the benefit of addressing the heat transfer effects of all internal heating components. In contrast, AHAM PAC-1-2014 only considers the evaporator fan heat, which is just one of the components that generates heat internally. Further, the proposed surface temperature approach would provide a direct measure of the overall heat transfer of heat-contributing components within the case to the room, without assuming the proportion of heat transferred to either the cooling or heat rejection side.

Therefore, DOE proposes in this NOPR that cooling mode testing include case surface heat transfer measured by means of four evenly spaced thermocouples placed on each case surface. The thermocouples would be positioned such that the case surface, when divided into quadrants, contains at least one thermocouple in each quadrant. If even spacing would result in a thermocouple being placed on an air inlet or exhaust grille, the thermocouple would be placed adjacent to the inlet or exhaust grille, maintaining the even spacing as closely as possible. To ensure accurate heat transfer estimates, DOE proposes to specify that temperature measurements be accurate to within ±0.5 °F. DOE further proposes to average the four surface temperatures measurements on each side to obtain T
case
for that side.

The surface area of each case side, A
case
, would be calculated as the product of the two primary surface dimensions, as follows:

A
case_k
= D
1_k
× D
2_k

Where:

D
1
and D
2
are the two primary dimensions of the case side “k” exposed to ambient air.

k represents the case sides including, front, back, right, left, top, and bottom.

Heat transferred from all case sides to the indoor conditioned space would be calculated according to the following:

Q
case_cm
= Σ
k
{
h
×
A
case_k
× (
T
case_k
−
T
ei
)}

Where:

Q
case_cm
is the total heat transferred from all case sides to the indoor conditioned space in cooling mode.

h is the convection coefficient, 4 Btu/h per square foot per °F.

k represents the case sides including: front, back, right, left, top, and bottom.

A
case_k
is the surface area of case side “k”, in square feet.

T
case_k
is the average surface temperature of case side “k”, in °F.

T
ei
is the average evaporator inlet air dry-bulb temperature, in °F.

vi. Condensate Collection

Many portable ACs include a feature to re-evaporate the condensate and remove it from the indoor space through the condenser exhaust air stream. This feature is performed by slinging or directing condensate that collects and drips off of the evaporator on to one or multiple condenser coil surfaces. All units in DOE's test sample included this feature. In the event that the condensate collection rate exceeds the removal rate of the auto-evaporation feature and the internal condensate collection bucket fills, all of the units provide a drain option to remove the collected condensate. Portable ACs typically ship with this drain sealed with a temporary plug, although a consumer-supplied drain line may also be installed. Manufacturer setup instructions typically do not specify that a drain line be installed during normal operation, relying primarily instead on the auto-evaporative condensate removal feature.

In response to the May 2014 NODA, the California IOUs confirmed DOE's research and indicated that there are different methods of handling condensate. Units may include an internal reservoir with a fill sensor to interrupt operation until the reservoir is emptied, a heater to re-evaporate the water into the exhaust air stream, or slingers that pass the condensate over the condenser to re-evaporate condensate and improve heat transfer. The California IOUs recommended that DOE address the different means of condensate handling. (California IOUs, No. 5 at p. 4) DOE agrees that a portable AC test procedure should recognize various methods of condensate removal to ensure comparable results among units with different condensate removal approaches.

DOE's investigative testing was conducted with a drain line attached to simplify condensate draining if necessary, but the line was elevated to simulate testing with the drain plug in place. Nonetheless, DOE observed that the auto-evaporation feature was effective for all test units under testing conditions so that no unit cycled off due to a full condensate bucket. Therefore, DOE proposes that the portable AC under test be set up in accordance with manufacturer instructions. If an auto-evaporative feature is provided along with a condensate drain, and the drain setup is unspecified, the drain plug would remain in place as shipped and no means of condensate removal would be installed for the duration of cooling mode testing. If the internal bucket fills during testing, the test would be invalid and halted, the drain plug would be removed, means would be provided to drain the condensate from the unit, and the test would be started from the beginning.

Section 7.1.2 of AHAM PAC-1-2014 contains provisions for portable ACs that incorporate condensate pumps that cycle to dispose condensate collected by the unit. DOE found through market

research and by investigating units in its test sample that units that include a condensate pump typically include an auto-evaporative feature. However, the activation of the condensate pump may differ in different operating modes. For example, one unit in DOE's sample activated the condensate pump only in heating mode, with condensate removed solely via auto-evaporation in cooling mode. DOE did not observe any units in its test sample that depended upon only a condensate pump for removing condensate during cooling mode.

Section 6.3.3 of AHAM PAC-1-2014 states that “. . . equipment recommended as part of the air conditioner shall be in place.” Therefore, DOE proposes that portable AC cooling mode testing would be performed in accordance with manufacturer installation and setup instructions, unless otherwise specified in the DOE test procedure. In addition, where available and as instructed by the manufacturer, DOE proposes that the auto-evaporation feature would be utilized for condensate removal during cooling mode testing. If no auto-evaporative feature is available, the gravity drain would be used. If no auto-evaporative feature or gravity drain is available, or if the manufacturer specifies the use of an included condensate pump during cooling mode operation, then DOE proposes that the portable AC would be tested with the condensate pump enabled. For these units, DOE also proposes to require the use of Section 7.1.2 of AHAM PAC-1-2014 if the pump cycles on and off.

vii. Control Settings

Portable ACs typically incorporate electronic controls that allow selection of the fan speed during cooling or heating mode. The highest fan speed will produce the most rapid rate of cooling or heating, while the lower fan speeds may be provided to reduce noise. Section 7.3.1 of AHAM PAC-1-2014 states that all adjustable settings, including fan speed, shall be set to achieve maximum capacity. Although the fan speed setting is clearly specified, it is not clear what setting should be selected for the cooling or heating setpoint. Many portable ACs have controls that allow consumers to select a target temperature, for example by setting the desired temperature or by adjusting a dial to a more or less cool setting. When the cooling setpoint temperature is lower than the ambient temperature, or higher than the ambient temperature in heating mode, the portable AC will operate continuously. AHAM PAC-1-2014 requires that the test chamber be maintained at 80.6 °F throughout the cooling mode test period, during which the unit must operate continuously, but does not specify a particular cooling setpoint temperature. To ensure that the test unit does not enter off-cycle mode, the test operator must select a control setting that corresponds to a temperature lower than 80.6 °F, particularly because no portable ACs in DOE's test sample included a “continuous on” setting. Because DOE acknowledges the potential for a unit to operate differently when cooling controls are set to different target temperatures below 80.6 °F, DOE proposes during cooling mode testing that the fan be set at the maximum speed if the fan speed is user adjustable and the temperature controls be set to the lowest available value. Similarly, as discussed in section III.B.1.b.i, DOE proposes during heating mode testing that the fan be set at the maximum speed if the fan speed is user adjustable and the temperature controls be set to the highest available value. These settings would likely best represent the settings that a consumer would select to achieve the primary function of the portable AC, which is to cool or heat the desired space as quickly as possible and then to maintain these conditions.

A number of test units in DOE's test sample included the option to oscillate the evaporator exhaust louvers to help circulate air throughout the conditioned space. Although AHAM PAC-1-2014 does not directly address louver oscillation, Section 7.3.1 of AHAM PAC-1-2014 states that all adjustable setting such as louvers, fan speed, and special functions must be set for maximum capacity. Accordingly, if there is a setting that automatically opens and closes the louvers, this feature would be disabled for the entirety of the rating test period, and the louvers would be opened to allow maximum capacity. If there is a manual setting to control louver direction and opening size, in accordance with section 7.3.1 of AHAM PAC-1-2014, the louvers shall be fully open to provide maximum airflow and capacity, and be positioned parallel to the air flow. However, this provision does not address an oscillating louver function that maintains constant and maximum louver exhaust area while redirecting the evaporator exhaust air flow. DOE does note, though, that AHAM PAC-1-2014 requires a constant external static pressure that is consistent with typical operation. The static pressure is initially affected by the test instrumentation that is placed over the evaporator exhaust grille to capture and measure the air flow rate, temperature, and humidity, such that a variable speed fan is required to adjust the external static pressure to ensure it is representative of normal operation. If the louvers were oscillating during the test period, the external static pressure measured at the evaporator exhaust would vary cyclically and thus the test would no longer be compliant with the required conditions. Also, oscillating louvers may interfere with the temperature and humidity instrumentation and possibly dislodge them, which could impact the measured performance and the integrity of the test procedure. In addition, DOE lacks information on the percentage of time that this feature is selected among those units equipped with oscillating louvers. Therefore, to provide comparable testing results in cooling mode for products with and without a louver oscillation feature, DOE proposes that portable AC cooling mode testing be conducted with any louver oscillation feature disabled. If the feature is included but there is no option to disable it, testing shall proceed with the louver oscillation enabled, without altering the unit construction or programming. DOE requests feedback on the proposal to disable louver oscillation where available and to maximize louver opening, either manually or by disabling an automatic feature.

viii. Test Unit Placement

Section 8.1.3 of ANSI/ASHRAE Standard 37 states that the outdoor condition test room must be of sufficient volume and circulate air in a manner that does not change the normal air-circulation patterns of the unit under test. Specifically, the dimensions of the room must be sufficient to ensure that the distance from any room surface to any equipment surface where air is discharged is not less than 6 feet and the distance to all other equipment surfaces must be no less than 3 feet. However, no comparable requirements are specified for the indoor test room. When tested according to AHAM PAC-1-2014 and ANSI/ASHRAE Standard 37, a portable AC is set up entirely within the indoor condition test room with the evaporator exhaust connected to instrumentation and ducted away from the test unit, and the condenser exhaust ducted with instrumentation to the outdoor test room. In that case, the requirements in Section 8.1.3 of ASNI/ASHRAE Standard 37 are not applicable, as no part of the case is within the outdoor condition test room. Instead, the portable AC is placed in the indoor condition test room, where walls and other obstructions may impede air flow

for the evaporator inlet for all configurations, and the condenser inlet for single-duct units. Therefore, to ensure performance is as repeatable and representative as possible, DOE concludes that the same distance requirements included in Section 8.1.3 of ANSI/ASHARE Standard 37 would be applicable to the indoor condition test room when testing portable ACs. DOE proposes that for all portable AC configurations, there must be no less than 6 feet from the evaporator inlet to any chamber wall surfaces, and for single-duct units, there must be no less than 6 feet from the condenser inlet surface to any other wall surface. Additionally, there must be no less than 3 feet between the other surfaces of the portable AC with no air inlet or exhaust (other than the bottom of the unit) and any wall surfaces.

ix. Electrical Supply

Section 7.3.2 of AHAM PAC-1-2014 does not require a specific test voltage, but rather states that the nameplate voltage shall be used. DOE notes that its dehumidifier test procedure requires a test voltage of either 115 or 230 volts (V), and these voltages would be comparable to those required for portable ACs, which are similar consumer products. To maintain repeatability and reproducibility for portable AC testing, DOE proposes that for active mode testing, the input standard voltage would be maintained at 115 V ±1 percent. DOE also proposes that the electrical supply be set to the nameplate listed rated frequency, maintained within ±1 percent.

b. Heating Mode

In response to the May 2014 NODA, DOE received a comment from the California IOUs suggesting that any future DOE test procedure for portable ACs include a measure of heating mode energy consumption. They stated that about 25 percent of models for sale at a major home improvement retailer include a heating function, and all of these models were marketed as a portable AC. The California IOUs suggested that DOE should ensure that the scope of a proposed test procedure that covers any products marketed as a portable AC also include testing the product's heating performance. (California IOUs, No. 5 at pp. 3-4)

DOE is aware that certain portable ACs, including some of the units in DOE's test sample, incorporate a heating function in addition to cooling and air-circulation modes. During teardowns, DOE found that there are two primary approaches to implement a heating function for portable ACs. The first, and most common, is a reverse-cycle heat pump, which requires a four-way reversing solenoid valve in the refrigerant loop that reroutes the refrigerant flow and converts the cooling air conditioning system to a heat pump. The second type of heating that DOE observed during teardowns was a resistance heater installed adjacent to the evaporator and in line with the evaporator exhaust air stream.

In consideration of the comment received and DOE's market and teardown observations, DOE conducted additional research to determine whether it could incorporate appropriate test methodology to measure heating mode energy consumption in a DOE portable AC test procedure.

i. General Test Approach

ANSI/ASHRAE Standard 37, the basis for DOE's proposed air enthalpy cooling mode test procedure, is intended for heat pump equipment in addition to air conditioning equipment. Section 1.1 of ANSI/ASHRAE Standard 37 states that the purpose of the standard is, in addition to determining cooling capacity of air conditioning equipment, providing methods to determine cooling and heating capacities of heat pump equipment. DOE reviewed ANSI/ASHRAE Standard 37 and determined that the same test chamber and instrumentation requirements and capacity calculations would apply to portable AC heating mode testing as for the proposed cooling mode testing. Further, as with the cooling mode test, the unit configurations included in AHAM PAC-1-2014 would be applicable to a heating mode test. Therefore, DOE proposes that the test unit be set up for a heating mode energy consumption test in accordance with the unit and duct setup requirements of AHAM PAC-1-2014, including those in Table 2 and Figure 1 of that standard. DOE also proposes to specify the same test requirements as for cooling mode, including infiltration air, duct heat transfer, case heat transfer, control settings, and test unit placement, discussed in the subsections of section III.B.1.a of this NOPR. However, DOE proposes that the temperature setpoint for heating mode be at the highest available temperature setting to ensure continuous operation.

ii. Ambient Test Conditions

ANSI/ASHRAE Standard 37 specifies the test setup, instrumentation, and test conduct, but does not specify the ambient test conditions for testing. For cooling mode, AHAM PAC-1-2014 provides the ambient test conditions for testing. To determine appropriate test conditions for a heating mode test, DOE reviewed ANSI/Air-Conditioning, Heating, and Refrigeration Institute (AHRI) 210/240—2008, “Performance Rating of Unitary Air-Conditioning and Air-Source Heat Pump Equipment” (ANSI/AHRI 210/240), which provides test conditions for determining performance of ACs and heat pumps. Table 4 of Section 6.1.4.2 of ANSI/AHRI 210/240 provides three test conditions in heating mode for a heat pump with a single-speed compressor and a fixed-speed indoor fan. The indoor air temperatures are the same for all three tests, 70 °F dry-bulb and 60 °F wet-bulb. For the outdoor air inlet temperatures, the high-temperature test, “H1,” requires 47 °F dry-bulb and 43 °F wet-bulb, while the frost accumulation test, “H2,” requires 35 °F dry-bulb and 33 °F wet-bulb, and the low-temperature test, “H3,” specifies 17 °F dry-bulb and 15 °F wet bulb.

DOE believes that the test conditions for H1 are the most representative of typical heating mode use for portable ACs, which are likely used as supplemental or low-capacity heaters when a central heating system is not necessary or operating. Therefore, DOE proposes the following ambient air test conditions as shown in Table III.8 below, with the test configurations referring to the test configurations referenced in Table 2 of AHAM PAC-1-2014. Test Configuration 3 is applicable to dual-duct portable ACs, and Test Configuration 5 is applicable to single-duct portable ACs. DOE notes that the terms “Evaporator” and “Condenser” refer to the heat exchanger configuration in cooling mode, not the reverse-cycle heating mode. This terminology maintains consistency with the cooling mode test conditions specification and would still be applicable for portable ACs that incorporate a resistance heater.

Table III.8—Standard Rating Conditions—Heating Mode

Test configuration
Evaporator inlet air, °F (°C)
Dry LBulb
Wet LBulb
Condenser inlet air, °F (°C)
Dry bulb
Wet bulb

3
70.0 (21.1)
60.0 (15.6)
47.0 (8.33)
43.0 (6.11)

5
70.0 (21.1)
60.0 (15.6)
70.0 (21.1)
60.0 (15.6)

iii. Adjusted Heating Capacity Calculation

Under the proposed heating mode testing conditions, DOE expects that the calculations provided by AHAM PAC-1-2014 would result in negative cooling (
i.e.,
heating) capacity values because the outdoor side temperature is lower than the indoor side temperature. Therefore, DOE proposes to multiply the resulting capacity by −1 to produce a positive value that would represent the amount of heating produced rather than cooling. Further, because heat transfer from the ducts and the case to the room would decrease the net heating in the conditioned space, these negative heating values must be added to the heating capacity in the adjusted capacity calculation. For the infiltration air heat transfer, the lower temperature of the infiltration air compared to the evaporator inlet temperature results in a negative temperature differential in the heat transfer calculation, which would result in a negative value for the heat contribution to the conditioned space. Thus, the infiltration air provides net cooling, and the resulting negative value would also be added to the heating capacity to obtain the adjusted heating capacity (AHC) in the heating mode, expressed in Btu/h, according to the following:

AHC
=
Capacity
hm
+
Q
duct_hm
+
Q
case_hm
+
Q
infiltration_hm

Where:

Capacity
hm
is the heating capacity measured in section 4.1.2 of this appendix.

Q
duct_hm
is the duct heat transfer while operating in heating mode, measured in section 4.1.2 of this appendix.

Q
case_hm
is the case heat transfer while operating in heating mode, measured in section 4.1.2 of this appendix.

Q
infiltration_hm
is the infiltration air heat transfer while operating in heating mode, measured in section 4.1.2 of this appendix.

2. Off-Cycle Mode

Certain portable ACs maintain blower operation without activation of the compressor after the temperature setpoint has been reached, rather than entering standby mode or off mode, or may operate with a combination of periods of blower operation and standby mode after reaching the setpoint. The fan-only operation may be intended to draw air over the internal thermostat to monitor ambient conditions, or may occur immediately following a period of cooling mode to defrost and dry the evaporator coil (or the condenser coil when operating in reverse-cycle heating mode). The blower may operate continuously, or may cycle on and off intermittently. In addition, some units allow the consumer to select operation of the blower continuously for air circulation purposes, without activation of the refrigeration system.

The existing industry portable AC test procedures do not presently contain provisions to measure energy use during this fan-only operation. However, DOE recently proposed a method for determining fan-only mode energy use in DOE's test procedure for dehumidifiers based on existing methodologies for measuring power consumption in

[Text truncated at 120,000 characters. The full text is on the page linked above.]

---

Source: Frix Law Library, https://www.frixlaw.com/law-library/documents/fr%3A2015-03589. Public record. Not legal advice.
