# Entergy Texas, Inc.// Office of Public Utility Counsel and Public Utility Commission of Texas v. Public Utility Commission of Texas and Texas Industrial Energy Consumers// Office of Public Utility Counsel and Entergy Texas, Inc.

> Texas Court of Appeals, 3rd District (Austin) · June 2, 2015

URL: https://www.frixlaw.com/law-library/cases/4067257

## Case

- **Court:** Texas Court of Appeals, 3rd District (Austin)
- **Decided:** June 2, 2015
- **Precedential status:** Published
- **Opinion:** Opinion
- **Cited by:** 0 later opinions in the Frix Law Library

## Citator (automated)

- No negative treatment found by the automated citator. That is not the same as a confirmation that the case is good law; read the citing cases.
- Full citator and citing cases: https://www.frixlaw.com/law-library/cases/4067257

## Opinion text

ACCEPTED
03-14-00735-CV
5514728
THIRD COURT OF APPEALS
AUSTIN, TEXAS
6/2/2015 3:48:59 PM
JEFFREY D. KYLE
CLERK
No. 03-14-00735-CV

IN THE FILED IN
3rd COURT OF APPEALS
THIRD COURT OF APPEALS AUSTIN, TEXAS
AT AUSTIN, TEXAS 6/2/2015 3:48:59 PM
JEFFREY D. KYLE
Entergy Texas, Inc., et al., Clerk
Appellants

v.

Public Utility Commission of Texas, et al.,
Appellees

Appeal from the 353rd Judicial District Court, Travis County, Texas
The Honorable John K. Dietz, Judge Presiding
________________________________________________________________

ENTERGY TEXAS, INC.’S REPLY BRIEF
_________________________________________________________________

John F. Williams
State Bar No. 21554100
jwilliams@dwmrlaw.com
Marnie A. McCormick
State Bar No. 00794264
mmccormick@dwmrlaw.com
DUGGINS WREN MANN & ROMERO, LLP
600 Congress Ave., Ste. 1900 (78701)
P. O. Box 1149
Austin, Texas 78767-1149
(512) 744-9300
(512) 744-9399 fax

ATTORNEYS FOR APPELLANT
ENTERGY TEXAS, INC.

June 2015

ORAL ARGUMENT REQUESTED
TABLE OF CONTENTS

TABLE OF CONTENTS ........................................................................................... i

INDEX OF AUTHORITIES..................................................................................... ii

ARGUMENT AND AUTHORITIES ........................................................................1

I.  There is no evidence or legal justification for the Commission’s
disallowance of over $11 million associated with ETI’s unrecovered
Hurricane Rita reconstruction costs.................................................................1

A.  Nothing in PURA required the Commission to address
amortization of the regulatory asset in Docket No. 37744. ..................1

B.  There is no evidence that anyone intended ETI to begin
amortizing the regulatory asset upon the settlement of Docket
No. 37744. .............................................................................................3

II.  The Commission’s refusal to make any adjustment to ETI’s test-year
level of purchased capacity expense is arbitrary and capricious and
unsupported by substantial evidence. ..............................................................7

A.  The Commission misapplied the standard for adjustments to
test-year expenses. .................................................................................8

B.  The Commission’s refusal to make any adjustment to test-year
levels of capacity costs is not supported by substantial
evidence. ..............................................................................................11

III.  The Commission’s decision to set ETI’s transmission equalization
expense at the test-year level is unsupported by substantial evidence. .........16

CONCLUSION AND PRAYER .............................................................................18

CERTIFICATE OF COMPLIANCE .......................................................................19

CERTIFICATE OF SERVICE ................................................................................20

APPENDIX ..............................................................................................................22

i
INDEX OF AUTHORITIES

Cases
AEP Texas Central Co. v. Public Util. Comm’n of Tex.,
286 S.W.3d 450 (Tex. App. – Corpus Christi 2008, pet. denied) .........................4
Bowden v. Phillips Petroleum Co.,
247 S.W.3d 690 (Tex. 2008) ..................................................................................8
City of El Paso v. Public Util. Comm’n of Tex.,
883 S.W.2d 179 (Tex. 1994) ..................................................................................9
Commint Technical Services, Inc. v. Quickel,
314 S.W.3d 646 (Tex. App. – Houston [14th Dist.] 2010, no pet.) ........................4
Freedom Communications, Inc. v. Coronado,
372 S.W.3d 621 (Tex. 2012) ..................................................................................5
Hawkins v. Texas Co.,
209 S.W.2d 338 (Tex. 1948) ................................................................................18
Hendee v. Dewhurst,
228 S.W.3d 354 (Tex. App. -- Austin 2007, pet. denied) ......................................5
Katy Intern., Inc. v. Jinchun Jiang,
451 S.W.3d 74 (Tex. App. – Houston [14th Dist.] 2014, pet. requested) .............5
Office of Pub. Util. Counsel v. Public Util. Comm'n,
878 S.W.2d 598 (Tex. 1994) ..................................................................................5
Office of Pub. Util. Counsel v. Texas-New Mexico Power Co.,
344 S.W.3d 446 (Tex. App. – Austin 2011, pet. denied) ......................................4
Railroad Comm’n of Tex. v. High Plains Natural Gas Co.,
628 S.W.2d 753 (Tex. 1981) .................................................................................9
State of Texas’ Agencies & Institutions of Higher Learning v.
Public Util. Comm’n of Tex.,
450 S.W.3d 615 (Tex. App. – Austin 2014, pet. requested) .................................4
Suburban Util. Corp. v. Public Util. Comm’n of Tex.,
652 S.W.2d 358 (Tex. 1983) ....................................................................... 8, 9, 16
Texas Utils. Elec. Co. v. Public Util. Comm’n,
881 S.W.2d 387 (Tex. App. – Austin 1994),
rev’d on other grounds, 935 S.W.2d 109 (Tex. 1996) .................................. 15, 18

ii
Vickers v. State,
No. 06-14-00072-CR, 2015 WL 1882910, *6 n.11
(Tex. App. – Texarkana Apr. 27, 2015, no pet. h.) ................................................5
Woods v. William M. Mercer, Inc.,
769 S.W.2d 515 (Tex. 1988) ..................................................................................4
Statutes
Tex. Gov’t Code Ann. § 2001.174...................................................................... 8, 18
Tex. Util. Code Ann. § 11.001, et seq. ......................................................................1
Tex. Util. Code Ann. § 11.002 .................................................................................10
Tex. Util. Code Ann. § 36.051 ...................................................................................9
Tex. Util. Code Ann. § 39.459 ...............................................................................2, 3
Tex. Util. Code Ann. § 39.462 ...............................................................................2, 3
Rules
16 Tex. Admin. Code § 25.231 ........................................................................... 9, 10
Tex. R. Civ. P. 94 .......................................................................................................4
Tex. R. Evid. 201 .......................................................................................................5
Administrative	Cases
Application of Entergy Gulf States, Inc. for Determination of
Hurricane Reconstruction Costs, Docket No. 32907.............................................7
Application of Entergy Texas, Inc. for Authority to Change Rates and
Reconcile Fuel Costs, Docket No. 37744 .........................................................5, 6

iii
Appellant Entergy Texas, Inc. (“ETI”) respectfully submits this reply to the

appellees’ briefs of the Public Utility Commission of Texas (“the Commission” or

“PUCT”) and Texas Industrial Energy Consumers (“TIEC”).

ARGUMENT AND AUTHORITIES

I. There is no evidence or legal justification for the Commission’s
disallowance of over $11 million associated with ETI’s unrecovered
Hurricane Rita reconstruction costs.

ETI challenges the Commission’s decision to allow it to amortize only $15

million of its Hurricane Rita regulatory asset. That is about $11 million less than

ETI proved it is entitled to but has not recovered. The Commission, the only party

to address this issue in its response brief, does not present any persuasive argument

for upholding its decision.

A. Nothing in PURA1 required the Commission to address
amortization of the regulatory asset in Docket No. 37744.

One of the rationales the Commission gave in support of its decision was its

view that PURA section 39.459(c) required ETI’s unrecovered Hurricane Rita

reconstruction costs to be addressed in a previous case, Docket No. 37744.2 As

explained in ETI’s appellant’s brief, section 39.459(c) does not apply to the

situation at hand. That provision addresses what should happen when a utility

securitizes hurricane reconstruction costs and then recovers them a second time

1
See Tex. Util. Code Ann. § 11.001, et seq. (“Public Utility Regulatory Act” or “PURA”).
2
AR Part I, Binder 5, Item 185 (Proposal for Decision at 15 & 21-22); AR Part I, Binder 7, Item
244 (Order on Rehearing at 1).
1
from an insurance company. See Tex. Util. Code Ann. § 39.459(c). Here, neither

of those things happened. A different statute, PURA section 39.462(a), applies in

this situation. That provision authorizes a utility to seek unrecovered hurricane

reconstruction costs “in its next base rate proceeding or through any other

proceeding authorized by Subchapter C, Chapter 36.” Id. § 39.462(a) (emphasis

added). It is undisputed that this case is authorized by Chapter 36.

The Commission now tacitly acknowledges that section 39.462(a) applies,

but still argues that the issue was statutorily required to be addressed in Docket No.

37744.3 The Commission contends that even under section 39.462(a), it was

required to address the issue in Docket No. 37744 because that was the “next”

base-rate proceeding after ETI knew it would not receive the anticipated insurance

proceeds.4 That statute says no such thing. Indeed, section 39.462(a) broadly

authorizes the Commission to address the issue in “any” proceeding authorized by

Chapter 36. This reflects the legislature’s understanding of the fact that it is often

difficult or impossible for a utility to know when multiple, large insurance claims

or government grants will be paid in full. Under the plain language of PURA

section 39.462(a), the Commission had authority to address the issue in this case.

Moreover, the Commission is flat wrong that Docket No. 37744 was the first

base rate case after ETI “knew” what insurance proceeds it would recover. It is

3
PUCT’s Appellee’s Brief at 16-17.
4
See id. at 18.
2
true that ETI had not recovered these insurance proceeds when it initiated Docket

No. 37744. But it is undisputed that ETI ended up receiving another $5 million in

insurance proceeds after Docket No. 37744, and ETI adjusted its regulatory asset

to account for this fact.5 Even under the Commission’s erroneous interpretation

of PURA sections 39.459(c) and 39.462(a), then, the Commission was not limited

to addressing the issue of hurricane reconstruction costs in Docket No. 37744.

B. There is no evidence that anyone intended ETI to begin
amortizing the regulatory asset upon the settlement of
Docket No. 37744.

The second rationale the Commission gave for its order was its conclusion

that ETI did not disprove that the issue was resolved in Docket No. 37744.6 That

was not, however, ETI’s burden. ETI affirmatively established that it had not yet

included the unrecovered insurance proceeds in its rate base, or begun recovering

them, when it filed this case.7 Intervening parties responded by arguing that ETI

should already have either written off or begun amortizing the Hurricane Rita

regulatory asset upon the conclusion of Docket No. 37744.8 In other words,

intervenors argued that Docket No. 37744 barred ETI from seeking permission to

amortize the full amount of the asset in this rate case. Intervenors, not ETI, bore

5
AR Part II, Binder 37, ETI Exh. 46 (Considine Rebuttal at 18 of 55).
6
AR Part I, Binder 5, Item 185 (Proposal for Decision at 22); AR Part I, Binder 7, Item 244
(Order on Rehearing at 1).
7
AR Part II, Binder 32, ETI Exh. 8 (Considine Direct at 20).
8
E.g., AR Part II, Binder 40, Staff Exh. 1 (Givens Direct at 32-35); AR Part II, Binder 8, Cities
Exh. 2 (Garrett Direct at 11).
3
the burden of proof on this affirmative defense. E.g., Tex. R. Civ. P. 94; Woods v.

William M. Mercer, Inc., 769 S.W.2d 515, 517 (Tex. 1988); Commint Technical

Services, Inc. v. Quickel, 314 S.W.3d 646, 651 (Tex. App. – Houston [14th Dist.]

2010, no pet.).

Regardless of who bore the burden of proof, the Commission is bound to

interpret a settlement and an order adopting it in accordance with the rules of

contract interpretation. See AEP Texas Central Co. v. Public Util. Comm’n of Tex.,

286 S.W.3d 450, 464 (Tex. App. – Corpus Christi 2008, pet. denied). The

Commission cannot use the opportunity to interpret its prior order as a means to

amend it. E.g., Office of Public Util. Counsel v. Texas-New Mexico Power Co.,

344 S.W.3d 446, 452 (Tex. App. – Austin 2011, pet. denied). Under the rules of

contract interpretation, the primary duty of the Commission is to determine and

give effect to the parties’ intentions as expressed in the document. AEP Tex. Cent.

Co., 286 S.W.3d at 464.

The Docket No. 37744 order does not say anything about the Hurricane Rita

regulatory asset, and the Commission does not pretend that it does. Nor does the

Commission dispute that a utility must have a regulator’s authority to begin

recovering a regulatory asset. See, e.g., State of Texas’ Agencies & Institutions of

Higher Learning v. Public Util. Comm’n of Tex., 450 S.W.3d 615, 646 (Tex. App.

– Austin 2014, pet. requested) (recovery of regulatory asset is two-step process, the

4
second step being the authorization of a recovery mechanism). The Commission

nevertheless argues that the amortization of the Hurricane Rita regulatory asset

should have been “considered” approved in Docket No. 37744 because the order in

that case was “ambiguous,” and there is substantial evidence that no one in that

case disputed that ETI should get to recover the regulatory asset.

The Commission is correct that there is evidence in this case that no one in

Docket No. 37744 contested ETI’s right to recover the Hurricane Rita regulatory

asset at some point in time. However, there was a dispute in Docket No. 37744

about when and how ETI could recover the regulatory asset. Cities’ witness Jacob

Pous testified in Docket No. 37744 that ETI should not be able to amortize the

regulatory asset over a five-year period, and should credit the amount to its storm

reserve instead.9 No witness in this case testified about, much less controverted,

that fact. In short, no witness to this case said the parties to Docket No. 37744

agreed that ETI should begin amortizing the regulatory asset when the case was

9
See Application of Entergy Texas, Inc. for Authority to Change Rates and Reconcile Fuel Costs,
Docket No. 37744 (Pous Direct at 113). A certified copy of Mr. Pous’s testimony is attached to
this brief at Appendix A. ETI does not present this document in support of the truth of its
content. ETI presents the document only to establish that it was filed, and the nature of the
matter the witness discussed, in the prior docket. This document was filed with the Commission,
a state agency. It is publicly available, and its authenticity is readily verifiable. This Court can,
therefore, take judicial notice of the document for the limited purpose ETI presents it. Tex. R.
Evid. 201(b); Freedom Communications, Inc. v. Coronado, 372 S.W.3d 621, 623 (Tex. 2012);
Office of Pub. Util. Counsel v. Public Util. Comm'n, 878 S.W.2d 598, 600 (Tex. 1994); Vickers
v. State, No. 06-14-00072-CR, 2015 WL 1882910, *6 n.11 (Tex. App. – Texarkana Apr. 27,
2015, no pet. h.); Katy Intern., Inc. v. Jinchun Jiang, 451 S.W.3d 74, 94 n.20 (Tex. App. –
Houston [14th Dist.] 2014, pet. requested); Hendee v. Dewhurst, 228 S.W.3d 354, 377 n.30 (Tex.
App. -- Austin 2007, pet. denied).
5
settled. Nevertheless, the Commission concluded in this case that ETI should have

done that. There is no testimony supporting the Commission’s conclusion.

The only evidence in this case of what the parties intended when they settled

Docket No. 37744 is the settlement agreement itself. Though the settlement

agreement expressly mentioned several issues in the case, it said nothing about

ETI’s request to amortize the Hurricane Rita regulatory asset. The agreement

certainly gave no indication that the parties intended ETI to begin recovering the

regulatory asset immediately. The agreement did, however, say, “[e]xcept to the

extent that the Stipulation expressly governs a Signatory’s rights and obligations

for future periods, this Stipulation shall not be binding or precedential upon a

Signatory outside this docket, and Signatories retain their rights to pursue relief to

which they may be entitled in other proceedings.”10

Despite that language in the agreement, the Commission maintains that the

Mother Hubbard clause in the order adopting the settlement supports its decision in

this case.11 The order says that “any … requests for general or specific relief, if not

expressly granted in this order, are hereby denied.”12 It is undisputed that neither

10
Id. (Aug. 6, 2010 Stipulation and Settlement Agreement at 12) (emphasis added).
11
PUCT’s Appellee’s Brief at 21.
12
Application of Entergy Texas, Inc. for Authority to Change Rates and Reconcile Fuel Costs,
Docket No. 37744 (Dec. 13, 2010, Order at ¶ 15). Public filings in Commission dockets may be
accessed at the Commission’s interchange:
http://interchange.puc.texas.gov/WebApp/Interchange/application/dbapps/filings/pgSearch.asp
The “Control Number” for each case is its docket number.
6
the settlement agreement nor the order expressly granted ETI the authority to begin

amortizing the Hurricane Rita regulatory asset.13

In light of this language in the Docket No. 37744 order and the fact that

recovery of a regulatory asset requires express agency approval, it would have

been unreasonable for ETI to begin amortizing the asset upon the conclusion of

Docket No. 37744. The factual basis for the Commission’s contrary conclusion in

this case is not supported by substantial evidence. And there is no legal

justification – articulated in the Commission’s order or not – supporting what the

Commission did here. Because there is no evidence or law supporting the

Commission’s decision, it is not entitled to any deference and should be reversed.

II. The Commission’s refusal to make any adjustment to ETI’s test-year
level of purchased capacity expense is arbitrary and capricious and
unsupported by substantial evidence.

In its initial brief, ETI challenged the Commission’s refusal to include in

rates any of the increase in purchased capacity expense ETI proved it would incur

by the time rates went into effect. Neither the Commission nor TIEC presents any

13
The Attorney General makes a cryptic argument on page 21 of its brief, suggesting that ETI
cannot logically argue that “only one part of its request could have been approved” in Docket
No. 37744. See PUCT’s Appellee’s Brief at 21. ETI does not contend that the Commission
approved anything regarding the Hurricane Rita regulatory asset in Docket No. 37744. The
Commission approved ETI’s creation of the regulatory asset in Docket No. 32907 when it
recognized ETI’s future right to true-up its anticipated insurance recovery. See Application of
Entergy Gulf States, Inc. for Determination of Hurricane Reconstruction Costs, Docket No.
32907 (Dec. 1, 2006, Order at FOF 28). ETI sought approval of a recovery mechanism in
Docket No. 37744. ETI’s point here is that the Commission did not even mention the Hurricane
Rita regulatory asset, much less approve an amortization schedule for the asset, in its Docket No.
37744 order.
7
logical basis upon which to disallow the entire $30 million increase in expenses at

issue.

A. The Commission misapplied the standard for adjustments
to test-year expenses.

The Commission took the view that only ETI’s test-year level of purchased

capacity expense should be included in rates because acknowledging known and

measurable changes to test-year data is an “exception.”14 ETI challenged that view

as contrary to PURA and judicial precedent.

In response, the Commission and TIEC point out that the Commission may

exercise “discretion” in determining what changes to make to test-year levels of

expense. That does not mean, however, that the Commission has carte blanche to

do whatever it wants. Even when it exercises discretion, the Commission must

adhere to some guiding principles. See, e.g., Tex. Gov’t Code Ann. § 2001.174(2)

(agency order reversible for abuse of discretion); Bowden v. Phillips Petroleum

Co., 247 S.W.3d 690, 696 (Tex. 2008) (failure to adhere to any guiding principles

constitutes abuse of discretion).

One of those principles is that rates are set prospectively. E.g., Suburban

Util. Corp. v. Public Util. Comm’n of Tex., 652 S.W.2d 358, 366 (Tex. 1983).

Another is that a utility is entitled to a reasonable opportunity to recover all of the

14
AR Part I, Binder 7, Item 244 (Order on Rehearing at 1); AR Part I, Binder 5, Item 185
(Proposal for Decision at 108).
8
reasonable and necessary expenses it incurs when the rates are in effect. See Tex.

Util. Code Ann. § 36.051; Railroad Comm’n of Tex. v. High Plains Natural Gas

Co., 628 S.W.2d 753 (Tex. 1981). PURA provides no support for giving test-year

data more weight than rate-year data in the process of setting rates. PURA does

not even impose the test-year construct – that is a Commission-made ratemaking

convention. Compare Tex. Util. Code Ann. § 36.051 with 16 Tex. Admin. Code

§ 25.231(a). And the Texas Supreme Court has acknowledged that the goal of the

process is to make the test-year data as representative as possible of the cost

situation that is apt to prevail in the future, not the past. City of El Paso v. Public

Util. Comm’n of Tex., 883 S.W.2d 179, 188 (Tex. 1994). Costs that can be

anticipated with reasonable (not absolute) certainty should be included. See

Suburban Util. Corp., 652 S.W.2d at 362.

TIEC and the Commission acknowledge this is the standard. But they argue

the Commission’s order should be upheld because ETI could not predict its rate-

year costs with surgical precision. That cannot be a basis upon which to disallow

the entire adjustment. Without a crystal ball, it is impossible to know future costs

to the dollar. The Commission may not disregard compelling evidence of

substantial increases to test-year levels of expense simply because there may be

some level of uncertainty at the margin.

9
TIEC argues that projections of future expenses should be treated as

inherently suspect because there is a risk the projections will end up being too

high. TIEC fails to note that placing undue emphasis on test-year data imposes the

opposite risk – that rates will end up being too low. The Commission is charged

with setting rates that are just and reasonable for both consumers and utilities.

Tex. Util. Code Ann. § 11.002(a).

Contrary to TIEC’s assertions, ETI does not, in this appeal, seek to overturn

the Commission’s test-year approach to ratemaking. See 16 Tex. Admin. Code

§ 25.231(a). ETI simply seeks to hold the Commission to PURA’s basic guarantee

to utilities. To give effect to that guarantee, historical test-year data can only be

the starting place for setting rates. Because rates are set on a prospective basis,

evidence of known and measurable changes to test-year data must be given at least

equal weight to the test-year data itself. It cannot logically be treated with

suspicion or as an “exception” that is subject to a heightened proof requirement.

The Commission itself acknowledges this principle in other contexts. The

Commission made adjustments to other categories of ETI’s test-year expense, even

though those adjustments were based upon projections and estimates.15 If the

Commission is to allow post-test-year changes based upon projections in one

15
E.g., AR Part I, Binder 5, Item 185 (Proposal for Decision at 68 (short-term asset update), 163-
64 (payroll adjustments), & 182-86 (ad valorem tax rate update)).
10
situation, it must allow them in another. It is an abuse of discretion to apply

different standards in materially analogous circumstances.

B. The Commission’s refusal to make any adjustment to test-
year levels of capacity costs is not supported by substantial
evidence.

ETI showed that during the time rates would be in effect, it would incur over

$38 million annually above its test-year level of purchased capacity expense. ETI

showed that by procuring these third-party resources, it would save about $8

million annually in payments related to Entergy system resources. Accordingly,

ETI requested the Commission to include the net $30 million increase over its test-

year levels of purchased capacity expense in rates.

The Commission and TIEC argue the Commission was justified in denying

this request for several reasons. First, the Commission says ETI merely “believes”

its contracts will be in place during the rate year.16 But ETI proved that all the

third-party capacity contracts were executed before the hearing.17 Indeed, one of

them went into effect during the test year,18 and another went into effect five

months after the test-year end and several months before the hearing in this case.19

16
See PUCT’s Appellee’s Brief at 33.
17
E.g., AR Part IV, Binder 43, Vol. L (5/3/12 Tr. at 1942 & 1959) (Frontier contract); AR Part
II, Binder 35, ETI Exh. 34 (Cooper Direct at 17 of 25) (SRMPA contract); AR Part II, Binder 35,
ETI Exh. 34 (Cooper Direct at 16 of 25) (regarding Calpine contract).
18
AR Part IV, Binder 43, Vol. L (5/3/12 Tr. at 1942 & 1959) (regarding Frontier contract).
19
AR Part II, Binder 35, ETI Exh. 34 (Cooper Direct at 17 of 25) (regarding SRMPA contract).
11
The Commission and TIEC also argue that ETI simply “assumed” it would

have to pay for all the third-party resources it had contracted for. That is

affirmatively debunked by the record. ETI’s expectation that any adjustments for

poor performance under the Frontier contract would be minor was based upon its

past experience with the Frontier resource.20 ETI also proved that its agreement

with SRMPA was for “system capacity.”21 Even if one of SRMPA’s resources

were to falter, there is no evidence supporting the conclusion that SRMPA’s entire

system might become unavailable. ETI further proved that it had experience with

the Calpine resource, and that price deviations under that contract were “very, very

small” in ETI’s experience.22 ETI took its historical experience into account when

projecting future costs, and did not blindly assume what they would be under these

contracts.

The Commission and TIEC also contend that there are multiple “offsets”

that would negate any additional expense ETI will incur under the new third-party

purchased capacity contracts. As ETI pointed out in its appellant’s brief, none of

these offsets justifies a complete disallowance of ETI’s entire capital outlay for the

contracts at issue.

20
AR Part IV, Binder 43, Vol. F (4/26/12 Tr. at 705).
21
AR Part II, Binder 31, ETI Exh. 3A (SRMPA Power Contract) [Highly Sensitive].
22
AR Part IV, Binder 42, Vol. L (5/3/12 Tr. at 1942).
12
Both the Commission and TIEC contend that future load growth may offset

some of ETI’s increased purchased capacity expense. Even if the Commission

could properly consider future load growth in setting base rates, ETI made the

additional third-party capacity purchases to serve existing load,23 and existing

customers would recoup substantial savings from increased efficiencies and fuel

savings that would result from the purchases.24 Moreover, intervenors’ load

growth projections would not fully materialize until the rate year,25 but ETI began

incurring the additional purchased capacity costs during and shortly after the test

year. The prospect of load growth in ETI’s service area cannot logically offset the

immediate increase in purchased capacity expense at issue.

The Commission and TIEC also attempt to cast doubt upon ETI’s evidence

about how much the increased third-party capacity purchases enable ETI to avoid

in MSS-1 costs.26 But TIEC’s own witness admitted the inverse relationship

between the two categories of cost.27 Indeed, the record establishes that MSS-1

costs reached test-year lows during the last two months of the test year, when the

23
AR Part II, Binder 37 (ETI Exh. 47, Cooper Rebuttal at 5-7); see also AR Part II, Binder 37
(ETI Exh. 57, May Rebuttal at 13-15).
24
AR Part II, Binder 35 (ETI Exh. 34, Cooper Direct at 24 of 25).
25
AR Part IV, Binder 43, Vol. J (5/1/12 Tr. at 1299-1300) [Highly Sensitive].
26
As explained in ETI’s appellant’s brief, Schedule MSS-1 to the Entergy System Agreement
requires the various Entergy operating companies to make and receive payments according to
their relative share of total system capacity. See AR Part II, Binder 37, ETI Exh. 47 (Cooper
Rebuttal at 5-6).
27
AR Part II, Binder 41, TIEC Exh. 1 (Pollock Direct at 22, Table 1).
13
Frontier contract was stepped up.28 And another intervenor, Cities, adopted ETI’s

calculation of rate-year MSS-1 costs.29

Finally, the MSS-430 calculation is not a basis upon which to disallow all of

ETI’s increased third-party purchased capacity costs. The Commission itself

acknowledged that, save for costs associated with ETI’s contract with its Arkansas

affiliate, MSS-4 costs would remain “fairly stable” from the test year to the rate

year.31 Regarding the Arkansas contract (referred to by the parties as the Entergy

Arkansas, “EAI” or “EA” “WBL” contract), Cities’ and TIEC’s proposed

adjustments are not reasonably supported by the record. The evidence shows that

although the contract expired after the test year, ETI had extended the contract by

the time the hearing took place.32 Additionally, it is not reasonable to conclude

that if the Arkansas contract were not in place, ETI would not replace it with

another resource, since it is undisputed that ETI needed the capacity.33

In a nutshell, the Commission and TIEC argue that because there is “some

uncertainty” in these projections, it was inappropriate to make any adjustment. But

28
See AR Part II, Binder 9, Cities Exh. 6C (Nalepa Direct Attachment KJN-3 at 2) [Highly
Sensitive].
29
AR Part II, Binder 9, Cities Exh. 6C (Nalepa Direct at 17 [Highly Sensitive]).
30
As explained in ETI’s initial brief, Schedule MSS-4 to the Entergy System Agreement
contains a formula that sets the price of power purchased from specific units owned by other
Entergy operating companies. See AR Part II, Binder 36, ETI Exh. 39 (Cicio Direct at 24-26).
31
AR Part I, Binder 5, Item 185 (Proposal for Decision at 100); AR Part I, Binder 7, Item 244
(Order on Rehearing at 1).
32
AR Part IV, Binder 43, Vol. E (4/26/12 Tr. at 687-88 [Confidential]) .
33
See AR Part II, Binder 37 (ETI Exh. 47, Cooper Rebuttal at 15-16 of 21).
14
this Court long ago rejected the notion that when some of a utility’s proposal is

challenged, the entire proposal must be rejected unless the utility itself quantifies

the challenged piece. See Texas Utils. Elec. Co. v. Public Util. Comm’n, 881

S.W.2d 387, 404 (Tex. App. – Austin 1994), rev’d on other grounds, 935 S.W.2d

109 (Tex. 1996). This Court recognized that when the evidence conflicts about

how much of a proposal to include, it is the Commission’s job to sift through the

evidence and make the call. The Commission may not just throw its hands in the

air and refuse to address the issue simply because the utility’s evidence is contested

or because the issues are complex. See id. at 404-05.

TIEC cites the testimony of witnesses who recommended that the

Commission adopt a level of purchased capacity expense below the test-year level,

and suggests this testimony alone supports the Commission’s decision.34 But each

piece of testimony TIEC cites is based upon multiple “offsets” to ETI’s increased

level of expense. Each of these proposed offsets are flawed, as explained in ETI’s

appellant’s brief and above. Moreover, even assuming arguendo one of the offsets

were sustainable, no single offset justifies the entire disallowance. For both these

reasons, it is not reasonable to conclude from the evidence in this record that none

of ETI’s $30 million increase in third-party capacity costs were known and

measurable. The Commission did not even suggest that any single finding justifies

34
See TIEC’s Appellee’s Brief at 33.
15
the entire disallowance, or how much of the disallowance is attributed to each of its

findings. Therefore, if this Court determines that any of the Commission’s

findings are unsupported by substantial evidence, it must reverse the whole

disallowance and remand to the Commission for further consideration.

III. The Commission’s decision to set ETI’s transmission equalization
expense at the test-year level is unsupported by substantial evidence.

ETI challenges the Commission’s decision to set ETI’s MSS-2 (that is,

transmission equalization) expense at the test-year level for two reasons. First, the

Commission misapplied the “known and measurable” ratemaking standard, as it

did in setting ETI’s purchased capacity costs. Second, the Commission’s decision

is not supported by substantial evidence. The Commission and TIEC filed

responses. They devote their entire argument on this issue to attacking ETI’s

evidence supporting its request to include its rate-year level, rather than test-year

level, of MSS-2 expense in rates.

The issue before the Court, however, is whether there is substantial evidence

supporting the Commission’s conclusion that the test-year MSS-2 expense was the

level the utility “anticipated with reasonable certainty.” Suburban Util. Corp., 652

S.W.2d at 362. Clearly, this is not the case; there is no evidence that the test year

level allowed by the Commission is adequate or representative of the expense the

utility will incur when rates are in effect. All the evidence is to the contrary.

16
As ETI noted in its initial brief, no witness testified that the test-year level of

expense was a fair or reasonable representation of what ETI would incur under

Schedule MSS-2 when these rates would be in effect. Though they proposed

different levels of increase, every witness testifying on this issue – including ETI’s,

TIEC’s, and Cities’ – recognized that the test-year amount of MSS-2 expense was

too small and should be updated based on more recent, actual payment

information. 35 Moreover, ETI established that the actual, historical level of MSS-2

expense it incurred, in every month from the end of the test year to the time of the

hearing, pointed to a substantially increasing, known and measurable level of

expense. 36 TIEC now wholly ignores its own witness’s testimony on this issue,

choosing instead to focus exclusively on its criticisms of ETI’s evidence. Even

assuming arguendo that there is reasonable disagreement about ETI’s proposed

rate-year level of MSS-2 expense, the record conclusively establishes that the test-

year level is not adequate. In this circumstance, the Commission may not blindly

adhere to its test-year convention. There is literally no evidence to support the

Commission’s decision.

The Commission is bound to consider all the record evidence and reach a

conclusion that is reasonably supported by it. See Hawkins v. Texas Co., 209
35
AR Part IV, Binder 43, Vol. C (4/25/12 Tr. at 452-53); AR Part IV, Binder 43, Vol. F (4/27/12
Tr. at 738, 760, 763, 780, & 783-84); AR Part II, Binder 41, TIEC Exh. 1 (Pollock Direct at 32-
33); AR Part II, Binder 8, Cities Exh. 4B (Goins Direct, Errata No. 3 at 9 [Highly Sensitive]);
AR Part II, Binder 8, Cities Exh. 4 (Goins Direct at 22).
36
AR Part II, Binder 9, Cities Exh. 29 (Response of ETI to Cities RFI-5-1).
17
S.W.2d 338, 339-40 (Tex. 1948); Texas Utils. Elec. Co., 881 S.W.2d at 404. The

APA confirms this principle, requiring a court to reverse the agency if its decision

is “not reasonably supported by substantial evidence considering the reliable and

probative evidence in the record as a whole.” Tex. Gov’t Code Ann.

§ 2001.174(2)(E) (emphasis added). Because the Commission’s decision is not

supported by any evidence, much less reasonably supported by the evidence, the

Court must reverse it.

CONCLUSION AND PRAYER

For all these reasons, Entergy Texas, Inc. respectfully requests this Court

reverse the district court’s judgment insofar as it affirms the Public Utility

Commission’s order in the respects discussed above. ETI requests the Court

remand the case to the Commission for further proceedings consistent with the

Court’s decision. Entergy Texas, Inc. further requests its costs of court and any

other relief to which it may show itself justly entitled.

18
Respectfully submitted,

/s/ Marnie A. McCormick
John F. Williams
State Bar No. 21554100
Marnie A. McCormick
State Bar No. 00794264
mmccormick@dwmrlaw.com
DUGGINS WREN MANN & ROMERO, LLP
P. O. Box 1149
Austin, Texas 78767-1149
(512) 744-9300
(512) 744-9399 fax

ATTORNEYS FOR APPELLANT
ENTERGY TEXAS, INC.

CERTIFICATE OF COMPLIANCE

I certify that this document contains 4,727 words in the portions of the
document that are subject to the word limits of Texas Rule of Appellate Procedure
9.4(i), as measured by the undersigned’s word-processing software.

/s/ Marnie A. McCormick
Marnie A. McCormick

19
CERTIFICATE OF SERVICE

The undersigned counsel certifies that the foregoing document was
electronically filed with the Clerk of the Court using the electronic case filing
system of the Court, and that a true and correct copy was served on the following
lead counsel for all parties via electronic service on the 2nd day of June, 2015:

Elizabeth R. B. Sterling
Environmental Protection Division
Office of the Attorney General
P. O. Box 12548 (MC 066)
Austin TX 78711-2548
Counsel for Appellee Public Utility Commission of Texas

Rex D. VanMiddlesworth
Benjamin Hallmark
Thompson Knight LLP
98 San Jacinto Blvd., Ste. 1900
Austin TX 78701
Counsel for Intervenor Texas Industrial Energy Consumers

Susan M. Kelley (retired)37
Administrative Law Division
Office of the Attorney General
P. O. Box 12548
Austin TX 78711-2548
Counsel for Intervenor State Agencies

Sara Ferris
Office of Public Utility Counsel
1701 N. Congress Ave., Ste. 9-180
P. O. Box 12397
Austin TX 78711-2397
Counsel for Intervenor Office of Public Utility Counsel

37
State Agencies have not yet appeared or designated a new lead counsel in this appeal.
20
Daniel J. Lawton
LAWTON LAW FIRM PC
12600 Hill Country Blvd., Ste. R-275
Austin TX 78738
Counsel for Cities of Anahuac, et al.

/s/ Marnie A. McCormick
Marnie A. McCormick

21
APPENDIX

A. Certified copy of Direct Testimony of J. Pous in PUCT Docket No. 37744

22
APPENDIX A
SOAH DOCKET NO. XXX-XX-XXXX
PUC DOCKET NO. 37744

'I II

APPLICATION OF ENTERGY TEXAS, § BEFORE THE STATE OFFICE
INC. FOR AUTHORITY TO CHANGE § OF
RATES AND RECONCILE FUEL COSTS § ADMINISTRATIVE HEARINGS

Ii

DIRECT TESTIMONY AND EXIDBITS

OF

JACOBPOUS

ON BEHALF OF
I

CERTAIN CITIES SERVED BY ENTERGY TEXAS, INC.

CBRTIPIBD TO BS ATRUE AND CORRSCT
COPY OF THE OIUOINAL ON FH..E WITH THE
PUBLIC UTILITY COMMISSION OF TEXAS
JUNE9,2010
c~~'~.

:*t:3';•
Diversified Utility Consultants Inc.
1912 West Anderson Lane, Suite 202
Austin, TX 78757
Record copY
·-
UL \ 3 'l.0\6
Cities Exhibit , 'K.'f
·-·
,I '
TABLE OF CONTENTS

SECTION I: INTRODUCTION .................................................................................................... 1

SECTION II: DEPRECIATION ..................................................................................................... 7

1. General ........................................................................................................................................ 7

2. Production Life ........................................................................................................................... 11

A. General ................................................................................................................................... 11

B. Basis for Retirement Dates ..................................................................................................... 14

C. Recommendation .................................................................................................................... 21

3. Production Interim Retirements .................................................................................................. 22

4. Production Net Salvage ............................................................................................................... 26

5. Mass Property Life .................................................................................................................. 38

A. Introduction ........................................................................................................................... 38

B. Account Specific Adjustments .............................................................................................. 43

6. Mass Property Net Salvage ......................................................................................................... 71

7. ELG vs. ALG Calculation Procedure ......................................................................................... 76

8. Remaining Life Method .............................................................................................................. 86

SECTION III: FULLY ACCRUED DEPRECIATION ................................................................. 89

SECTION IV: SGSF CAPITAL RECOVERY .............................................................................. 93

SECTIONV: STORM INSURANCE RESERVE ...................................................................... 102

1. General .................................................................................................................................... I 02

2. Storm Reserve Deficit ............................................................................................................. 105

3. Target Reserve ........................................................................................................................ 114

4. Annual Expected Losses ......................................................................................................... 117

I 5. Minimum Storm Reserve Threshold ....................................................................................... 120

SECTION VI: CASH WORKING CAPITAL ................................................................................. 123
I I
1. Introduction ............................................................................................................................. 123

2. General .................................................................................................................................... 125

3. Revenue Lag ............................................................................................................................. 127

A. Meter Reading To Billing ................................................................................................... 127

B. Billing-To-Payment Revenue Lag ...................................................................................... 130

C. Customer Float .................................................................................................................... 135

4. Expense Leads .......................................................................................................................... 136

A. Payroll .................................................................................................................................. 136

B. FAS 106 .............................................................................................................................. 139

C. Entergy Services Inc. ("ESI") Expense Lead ..................................................................... 141

D. Other O&M Expense Lead ................................................................................................. 142

SECTION VII: RIVER BEND DECOMMISSIONING REVENUE REQUIREMENT .............. 144

SECTION VIII: RIVER BEND DEPRECIATION RATES ........................................................... 149

2
ACRONYMS:

2008 Study 2008 Gannett Fleming Depreciation Study
AICPA American Institute of Certified Public Accountants
ALG Average Life Group
APFD Accumulated Provision for Depreciation
ASL Average Service Life
CIS Consumer Information Systems
Company Entergy Texas, Inc.
Commission Public Utility Commission of Texas
CPI Consumer Price Index
ewe Cash Working Capital
DUCI Diversified Utility Consultants, Inc
EIA U.S. Energy Information Administration
EAi Entergy Arkansas, Inc.
EGSL Entergy Gulf States Louisiana
ELG Equal Life Group
ESI Entergy Services, Inc.
ETI Entergy Texas, Inc.
FERC Federal Energy Regulatory Commission
FPL Florida Power & Light Company
FPSC Florida Public Service Commission
MPSC Michigan Public Service Commission
NARUC National Association of Regulatory Utility Commissioners
NIMB "not in my backyard" syndrome
NPC Nevada Power Company
NPSC Nevada Public Service Commission
NRC Nuclear Regulatory Commission
O&M Operation & Maintenance
occ Oklahoma Corporation Commission
OLT Observed Life Table
PSO Public Service of Oklahoma
PUC Public Utility Commission of Texas
RCT Railroad Commission of Texas

1
Reserve Accumulated Provision for Depreciation
SGSF Spindletop Gas Storage Facility
SGT Sabine Gas Transportation Company
SRP Strategic Resource Plan
SWEPCO Southwest Electric Power Company
USOA FERC Uniform System of Accounts

2
Docket No. 37744

APPLICATION OF ENTERGY TEXAS § BEFORE THE
INC. FOR AUTHORITY TO CHANGE § PUBLIC UTILITY
RATES & RECONCILE FUEL COSTS § COMMISSION OF TEXAS

SECTION I: INTRODUCTION

1 Q. PLEASE STATE YOUR NAME AND BUSINESS?
2 A. My name is Jacob Pous and my business address is 1912 W. Anderson Lane, Suite 202,
3 Austin, Texas 78757.
4
5 Q. WHAT IS YOUR OCCUPATION?
6 A. I am a principal in the firm of Diversified Utility Consultants, Inc. ("DUCI"). A copy of
7 my qualifications appears as Appendix A.
8
9 Q. HAVE YOU PREVIOUSLY TESTIFIED IN PUBLIC UTILITY PROCEEDINGS?
10 A. Yes. Appendix A also includes a list of proceedings in which I have previously presented
11 testimony. In addition, I have been involved in numerous utility rate proceedings that
12 resulted in settlements before testimony was filed. In total, I have participated in well
13 over 400 utility rate proceedings in the United States and Canada.
14
15 Q. WHAT IS YOUR PROFESSIONAL BACKGROUND?
16 A. I am a registered professional engineer. I am registered to practice as a Professional
17 Engineer in the State of Texas, as well as numerous other states.
18
19 Q. ON WHOSE BEHALF ARE YOU TESTIFYING IN THIS PROCEEDING?
20 A. I am testifying on behalf of the cities of Anahuac, Beaumont, Bridge City, Cleveland,
21 Conroe, Houston, Huntsville, Montgomery, Navasota, Oak Ridge North, Pine Forest,
22 Pinehurst, Port Arthur, Port Neches, Groves, Nederland, Orange, Rose City, Shenandoah,

I 1

I
1 Silsbee, Sour Lake, Splendora, Vidor, and West Orange ("Cities") served by the Entergy
2 Texas, Inc. ("Company" or "ETI").
3
4 Q. WHAT IS THE PURPOSE OF YOUR TESTIMONY?
5 A. The purpose of my testimony is to address certain adjustments that are required to ETI's
6 requested rate increase filed before the Public Utility Commission of Texas
7 ("Commission" or "PUC"). I have provided Cities' witness Mr. Garrett with my
8 recommendations in order that they will be incorporated into the Cities' total revenue
9 requirement presentation.
10
11 Q. PLEASE BRIEFLY SUMMARIZE YOUR TESTIMONY.
12 A. The following is a brief summary of each of the major areas I address herein.
13
14 • Production Plant Life Spans. The Company proposes to retire almost all of its
15 gas-fired generation on June 30, 2025, for purposes of calculating depreciation
16 rates in this case as set forth in the 2008 Gannett Fleming depreciation study
17 ("2008 Study"). The proposed retirement year is earlier than and inconsistent with
18 the Company's internal planning for system resources. The Company's proposed
19 depreciation life spans assumes a retirement date that is also artificially short in
20 comparison to the life expectancy by the industry as well as the Company's own
21 resource planning division. I recommend establishing minimum life spans for the
22 Company's gas-fired generating facilities at the later of the year 2029 or when
23 such units reach 65 years of age. The standalone impact of this recommendation is
24 a reduction in depreciation expense of $11. 7 million based on plant in service as
25 of December 31, 2008.
26
27 • Interim Retirements. In spite of this Commission's previous rulings and
28 precedent regarding exclusion of interim retirements in the calculation of
29 production plant depreciation rates, the Company still proposes interim
30 retirements in its calculation. The Company's witness, Mr. Spanos attempts to
31 distinguish the Commission precedent by relying on an incorrect premise that the
32 Company's interim retirement analysis is based on a historical perspective, and
33 the Commission's precedent is applicable to a future perspective. This is a
34 distinction without a difference, because the Company applies the result of its
35 historical calculations to projected future results. Therefore, the Company's
36 witness's attempt to distinguish the Company's request from previous
37 Commission decisions is incorrect. The impact of upholding the Commission's
38 long standing precedent against interim retirements results in an approximate $4.6
39 million reduction in depreciation expense based on plant as of December 31,
40 2008.

2
1
2 • Production Plant Net Salvage. The Company proposes negative net salvage
3 values ranging from a negative 15% to a negative 32% for its gas and coal-fired
4 generations. The Company's coal-fired proposal isbased on an undocumented,
5 unsupported and inappropriate regression analysis associated with a database for
6 which the Company's depreciation witness has no first-hand knowledge. The
7 Company does not have a regression or any mathematical model to estimate net
8 salvage for gas-fired generation, but rather assumes it is approximately 80% of
9 the coal-fired value. Therefore, assuming the 80% factor to be correct, any
10 inaccuracies in the coal regression analysis would carry over to the Company's
11 projected net salvage for gas-fired generation. As a second step to the Company's
12 unsupported net salvage analysis, Mr. Spanos escalates the estimated demolition
13 costs as of the end of 2008 into the future for as many as 35 years and
14 recommends s that current customers pay with current dollars for future inflated
15 costs. These aspects of the Company's analysis are neither credible nor
16 reasonable. Therefore, in consideration of significant increases in scrap metal
17 prices that have occurred in the last 5 years and the potential sale of used
18 equipment, a zero (0) level of net salvage for production plant is recommended.
19 On a standalone basis this recommendation results in a reduction of
20 approximately $11. 7 million in depreciation expense based on plant as of
21 December 31, 2008.
22
23 • Mass Propertv Life Analysis. There are numerous problems with the Company's
24 proposed life-curve combination for the various mass property accounts
25 (transmission, distribution and general plant). First and foremost, the Company's
26 life analysis includes the impact of hurricane activity as typical, ongoing events.
27 This has resulted in certain accounts having life expectations shorter than
28 basically all other utilities in the industry. In addition, the Company's consultant
29 recognizes that there is a "significant portion" of the survivor curve to which the
30 curve-fitting process should be geared; however he has failed to properly
31 implement such criteria. Finally, the Company has failed to provide reasonable or
32 adequate support for its various positions. Modifications to 16 of the Company's
33 proposals results in a standalone impact of a $11.1 million reduction to annual
34 depreciation expense based on plant as of December 31, 2008.
35
I 36
37
• Mass Property Net Salvage. The Company's analysis relies only on the most
recent 5 years of data. This compares to a 16-year database employed by the same
consultant in the current El Paso Electric Company case before this Commission.
l 38
39
40
Without any indication in the testimony, depreciation study or workpapers, is the
fact that the limited five years of data is not even maintained by account, yet it is

I 41
42
presented by account based on an initially unidentified data manipulation.
Another fatal flaw in the Company's proposals is that there are the effects of
several major hurricanes reflected in the 5-year historical database. Thus, the data
43

! 44
45
46
relied upon by the Company to propose net salvage parameters are significantly
skewed to more negative levels than would reasonably be expected. Given the
significant problems with the Company's presentation and database in this case,

I 3

I
1 retaining the existing levels of net salvage by account is recommended. On a
2 standalone basis this recommendation results in a $10.6 million reduction in
3 annual depreciation expense based on plant in service as of December 31, 2008.
4
5 • Calculation Procedure. The Company proposes to use the Equal Life Group
6 ("ELG") calculation procedure. The ELG procedure is not a conservative capital
7 recovery method and in fact represents an accelerated procedure when compared
8 to the industry standard Average Life Group ("ALO") calculation procedure. The
9 ELG procedure is inaccurate in all instances, except in the improbable scenario
10 that future annual retirements for up to 100 years into the future can be precisely
11 estimated. In reality, ETI cannot predict future annual retirement levels with any
12 degree of accuracy, even for as little as a 5-year period. Relying on the ALO
13 procedure, a straight line, non-accelerated procedure, results in a standalone
14 reduction to annual depreciation expense of $19.3 million based on plant as of
15 December 31, 2009.
16
17 • Combined Impact of Depreciation Adjustments. The combined impact of the
18 various depreciation adjustments is not simply the summation of the individual
19 standalone impacts. If life, net salvage, or calculation procedure proposals are
20 modified within the same account, they are interactive with each other. As set
21 forth on Schedule (JP-1 ), the combined impact of the various adjustments results
22 in a $57 million reduction in depreciation expense based on plant in service as of
23 December 31, 2008.
24
25 • Fully Accrued Depreciation. The Company admits that it unilaterally changed
26 the Commission approved depreciation rates when it ceased booking depreciation
27 expense for three accounts. The Company does not have the authority to
28 unilaterally change a depreciation rate previously approved by the Commission.
29 Reversal of the Company's inappropriate actions results in a $6.2 million decrease
30 in rate base and a $1.5 million credit amortization expense associated with a four-
31 year amortization period.
32
33 • Spindletop Gas Storage Facilitv l"SGSF"). Since the Company's last fully
34 litigated rate proceeding, the Company has exercised an option to purchase the
35 SGSF facilities for $1. Due to the unique situation of ownership, operation and
36 cost recovery, customers have significantly overpaid depreciation expense and are
37 now entitled to appropriate net salvage treatment and correction of the
38 intergenerational inequity that has transpired. Amortizing the excess depreciation
39 reserve over a 4-year period and recognition of Company-established net salvage
40 expectations results in a $5.5 million reduction to revenue requirements
41 associated with this unique investment. However, given Cities' witness Mr.
42 Nalepa's recommendation relating to the SGSF, only $1.2 million of my
43 recommendation associated with the recognition of net salvage is required, when
44 Mr. Nalepa's position is adopted.
45

4
1 • Storm Insurance Reserve. The Company has overstated revenue requirements in
2 the calculation of its insurance reserve request. The Company performs a flawed
3 Monte Carlo simulation. The Company has skewed its results to the high side
4 based on the inclusion of inappropriate costs and charges to the insurance reserve.
5 ETI also inappropriately attempts to segregate certain hurricane securitization cost
6 from the reserve. Removing certain inappropriate charges to the Company's
7 insurance reserve and performing a more realistic projection of future storm cost
8 accruals results in a $7. 7 million reduction to the Company's storm reserve annual
9 accrual and a $45.9 million reduction to rate base. In addition, I recommend an
IO increase in the current $50,000 storm insurance threshold limit to $500,000.
11
12 • Cash Working Capital ("CWC"). The Company overstates and incorrectly
13 calculates the Company's CWC requirements. In particular, the Company relies
14 on an inconsistent implementation of service period between revenues and
15 expenses. There are numerous other flaws associated with the Company's
16 approach to CWC that require correction. Based on my various recommendations,
17 the standalone impact of the corrected lead-lag analysis for the measurement of
18 ewe requirements would result in an incremental $43.7 million reduction to rate
19 base and an approximate corresponding $5. 7 million reduction to revenue
20 requirements.
21
22 • River Bend Decommissioning. The Company seeks approval from this
23 Commission for its proposed level of decommissioning expense associated with
24 the River Bend plant that is now owned by ETI's Louisiana affiliate Entergy Gulf
25 States Louisiana ("EGSL"). Cities' witness Mr. Brazell testifies that the
26 Commission does not have the authority to set a decommissioning revenue
27 requirement for River Bend given EGSL' s ownership of the plant. The
28 Company's proposal is based on a 40-year life span for River Bend, rather than
29 the more appropriate and realistic 60-year life expectancy. Therefore, if the
30 Commission were to determine the proper decommissioning revenue requirement
31 for Texas retail customers, I recommend that a 60-year life span be employed. In
32 addition, the beginning balances in the decommissioning funds are understated in
33 the Company's presentation and would need to be corrected. The standalone
34 impact of these adjustments eliminates the need for Texas retail customers to
35 contribute any additional amounts to the decommissioning trust funds. Therefore,
l 36
37
my recommendation results in a $2.8 million reduction to proposed annual
decommissioning revenue requirements.
38
39 • River Bend Depreciation. Cities' witness Mr. Brazell presents the position that
40 the Commission does not have the authority to set depreciation rates for River
41 Bend. However, the Company has requested that the Commission do just that.
42 Unfortunately, the Company's presentation reflects a 40-year service life for
43 River Bend. It should be noted that the Company relies on a 60-year life for
44 River Bend in the Louisiana jurisdiction and agreed to a 60-year life in Docket
45 No. 34800, a settled proceeding. While the Company has not yet received
46 permission from the Nuclear Regulatory Commission (''NRC") for such license

5
1 extension, it must be noted that not a single license application for the 20-year life
2 extension has been denied by the NRC. Therefore, if the Commission does elect
3 to establish a depreciation rate for River Bend, it should do so based on the 20-
4 year life extension and with no interim retirements reflected therein.
5
6 Q. IS THERE A CONCERN THAT NEEDS TO BE ADDRESSED AT THE
7 BEGINNING OF YOUR TESTIMONY?
8 A. Yes, in the area of depreciation and capital recovery a utility can present aggressive,
9 middle of the road, or conservative parameters given the subjectivity required in
10 performing any future depreciation or capital recovery estimate. After review of the
11 Company's depreciation presentation, it is clear that the Company's position in this case
12 is one of the most aggressive presentations realistically possible. The Company's
13 approach results in an extremely excessive level of depreciation expense, rapid return of
14 capital investment to shareholders, which in my estimation, is unreasonable and an
15 unnecessary burden for current customers.
16
17 Q. DO THE PROPOSED DEPRECIATION PARAMETERS CONTINUE THE
18 CORPORATE PLAN THAT PUSHES AGGRESSIVE DEPRECIATION
19 PRACTICES?
20 A. Yes. While utilities have become more sophisticated in the last several decades when it
21 comes to spelling out their corporate plans, this Company continues its predecessor's
22 Corporate Plan, which under the heading of Long-Range Corporate Objectives, stated the
23 following: "Push accounting/depreciation judgments aggressively where possible." 1
24 (Emphasis added).
25
26 Q. CAN YOU PROVIDE SPECIFIC EXAMPLES THAT DEMONSTRATE ETl'S
27 CONTINUATION OF THE PREVIOUSLY STATED AGGRESSIVE
28 DEPRECIATION PRACTICES?
29 A. Yes. First and foremost is the Company's decision to utilize the ELG calculation
30 procedure. Reliance on the ELG procedure in light of identifiable "anomalies" that result
31 from the analyses of the underlying data is flawed and can no longer be relied upon to

1
Gulf States Utilities Corporate Plan 1980-1984 item l(c).

6
I predict with some degree of certainty how mortality patterns might look in the future.
2 The anomalies in the analyses are due, at least in part, to problems with the data,
3 including potential problems associated with the jurisdictional separation of ETI and
4 EGSL. Indeed, the combination of the underlying data problems with the fact that the
5 ELG procedure is the most accelerated book depreciation calculation procedure that can
6 be proposed in a rate proceeding, can only result in a magnified distortion of the capital
7 recovery process compared to the industry standard ALG calculation procedure.
8
9 Next, in the area of production plant net salvage, Mr. Spanos not only relied upon an
I0 unsubstantiated regression analysis that produces excessively negative values, but then
11 proposed a unique escalation calculation. The Company, through Mr. Spanos' testimony,
12 proposes to charge current customers, who would have to pay with current dollars, for
13 costs that have been escalated, without discounting costs back to the present, for as many
14 as 35 years into the future. Such approach is illogical and unrealistic.
15
16 While there are other actions taken by Mr. Spanos that further push his and the
17 Company's aggressive depreciation goals, the above examples more than establish the
18 nature of the Company's presentation.

19 SECTION II: DEPRECIATION

20 1. General
21

I 22

23
Q.
A.
WHAT IS DEPRECIATION?

There are two commonly cited definitions of depreciation. The first comes from the

I 24
25
Federal Energy Regulatory Commission's ("FERC") Uniform System of Accounts
("USOA"): 2

l 26 'Depreciation', as applied to depreciable plant, means the loss in service
27 value not restored by current maintenance, incurred in connection with

I 28 the consumption or prospective retirement of electric plant in the course

2
Title 18 Code of Federal Regulations Part 101.

7
1 of service from causes which are known to be in current operation and
2 against which the utility is not protected by insurance. Among the causes
3 to be given consideration are wear and tear, decay, action of the
4 elements, inadequacy, obsolescence, changes in the art, changes in
5 demand and requirements of public authorities.

6 The second definition, from the American Institute of Certified Public Accountants
7 ("AICPA"), is similar:

8 Depreciation accounting is a system of accounting which aims to
9 distribute the cost or other basic value of tangible capital assets, less
10 salvage (if any) over the estimated useful life of the unit (which may be a
11 group of assets) in a systematic and rational manner. It is a process of
12 a/location, not of valuation. Depreciation for the year is a portion of the
13 total charge under such a system that is allocated to the year. Although
14 the allocation may properly take into account occurrences during the
15 year, it is not intended to be a measurement of the effect of all such
16 occurrences.

17 Q. WHAT ARE THE TWO GENERAL FORMULAS USED IN DETE RMINING
18 DEPRECIATION RATES?

19 A. The whole life and the remaining life technique are the most commonly used formulas.
20 The whole life technique is as follows: 3

Depreciation Rate (%) = [ Original Cost - Net Salvage
Average Service Life
Original Cost
J
21 The remaining life technique for calculating depreciation rates is as follows:

22

~ J
Original Cost - Reserve - Net Salvage
Depreoiation Rate (%) [ Remaining Life
Original Cost

3
A theoretical depreciation reserve calculation is developed and compared to the actual accumulated provision
for depreciation in conjunction with the whole life technique. If the differential is significant, an
amortization of the differential for some period of time may be recommended.

8
1 The two formulas should equal each other when the difference between the theoretical
2 reserve and the actual Accumulated Provision for Depreciation ("APFD" or "reserve")
3 are recovered over the remaining life of the investment under the whole life formula.
4
5 Q. ARE THERE ADDITIONAL CONSIDERATIONS IN DEPRECIATION BEYOND
6 THE DEFINITIONS?
7 A. Yes. The definitions provide only a general outline of the overall utility depreciation
8 concept. In order to arrive at a depreciation-related revenue requirement in a rate
9 proceeding, a depreciation system must be established.
10
11 Q. WHAT IS A DEPRECIATION SYSTEM?
12 A. A depreciation system constitutes the method, procedure, and technique employed in the
13 development of depreciation rates.
14
15 Q. BRIEFLY DESCRIBE WHAT IS MEANT BY "METHOD".
16 A. Method identifies whether a straight-line, liberalized, compound interest, or other type of
17 calculation is being performed. The straight-line method is normally employed for utility
18 depreciation proceedings.
19
20 Q. BRIEFLY DESCRIBE WHAT IS MEANT BY "PROCEDURE".
21 A. Procedure identifies a calculation approach or grouping. For example, procedures can
22 reflect the grouping of only a single item, items by vintage (year of addition), items by
23 broad group or total grouping, and equal life groupings. The vast majority of utilities and

I 24
25
regulatory authorities use the ALG procedure.

I 26
27
Q.
A.
PLEASE BRIEFLY DESCRIBE WHAT IS MEANT BY "TECHNIQUES".
There are two main categories of techniques with various sub-groupings: the whole life

I 28
29
technique and the remaining life technique. The whole life technique simply reflects
calculation of a depreciation rate based on the whole life (e.g., a ten-year life would

I 30
31
imply a ten percent depreciation rate over the life of a plant). The remaining life
technique recognizes that depreciation is a forecast or estimation process that is never

9
1 precisely accurate and requires true-ups in order to recover only 100% of what a utility is
2 entitled to over the entire life of the investment. Therefore, as time passes, the remaining
3 life technique attempts to recover the remaining unrecovered balance over the remaining
4 life or other period. Most utilities rely on a remaining life technique in utility rate matters.
5
6 Q. DO THE METHODS, PROCEDURES, AND TECHNIQUES INTERACT WITH
7 ONE ANOTHER?
8 A. Yes. Different depreciation rates will result depending on what combination of method,
9 procedure and technique is employed. Differences will occur even when beginning with
10 the same average service life and net salvage values.
11
12 Q. WHAT IS NET SALVAGE?
13 A. Net salvage is the value obtained from retired property (the gross salvage) less the cost of
14 removal. Net salvage can be either positive in cases where gross salvage exceeds cost of
15 removal, or negative in cases where cost of removal is greater than gross salvage.
16
17 Q. HOW DOES NET SALVAGE IMPACT THE CALCULATION OF
18 DEPRECIATION?
19 A. The intent of the depreciation process is to allow the Company to recover 100% of
20 investment less net salvage. Therefore, if net salvage is a positive 10%, then the utility
21 should only recover 90% of its investment through annual depreciation charges, under the
22 theory that it will recover the remaining 10% through net salvage at the time the asset
23 retires (e.g., 90% + 10% = 100%). Alternatively, if net salvage is a negative 10%, then
24 the utility should be allowed to recover 110% of its investment through annual
25 depreciation charges so that the negative 10% net salvage that is expected to occur at the
26 end of the property's life will still leave the utility whole (e.g., 110% - 10% = 100%).
27
28 Q. WHAT ARE THE KEY ELEMENTS OF THE DEPRECIATION FORMULA AT
29 ISSUE IN TIDS PROCEEDING?
30 A. All parameters in the previously noted formula are at issue. The establishment of life and
31 net salvage parameters are a function of the analyses performed, the interpretation of the

10
1 data, the judgment and experience of the analys~ and other relevant information. In
2 addition, the remaining life calculation is at issue given that Mr. Spanos of Gannett
3 Fleming performs a different remaining life calculation than every other utility that does
4 not retain Gannett Fleming that I have dealt with over the past 37 years, including this
5 Company. This remaining life calculation produces theoretically impossible results.
6 Finally, the calculation procedure is a major issue in this case, as ETI does not rely on the
7 industry standard ALG procedure.

8 2. Production Life

9 A. General
10
11 Q. WHAT IS THE ISSUE IN TlllS PORTION OF YOUR TESTIMONY?
12 A. This portion of my testimony addresses the appropriate life spans for the Company's
13 various generating units. In particular, I will address what appears to be a practice of
14 understating the life span for generating units. I recommend longer life spans for the
15 Company's gas-fired generating units.
16
17 Q. WHAT IS A LIFE SPAN FOR A GENERATING UNIT?
18 A. A life span for a generating unit sets the period during which it is expected to be in
19 service prior to being retired. For example, if a generating unit was placed into service on
20 January 1, 1980 and had a 60-year estimated life span it would have a projected
21 retirement date of December 31, 2040. It should be noted that a generating unit that is
22 placed in peaking or standby service is still in service and not retired.
I 23
24 Q. PLEASE EXPLAIN THE SIGNIFICANCE OF SETTING AN APPROPRIATE
~ 25 LIFESPAN.
26 A. In determining the depreciation rate, and thus depreciation expense for a generating unit,
I 27 it is necessary to establish the period over which customers are expected to receive
28 benefits and in return pay for such benefits. This process complies with the standard
f 29 regulatory "matching principle." As previously noted, the depreciation formula includes

I 11

I
1 the original cost less net salvage less the APFD, all divided by the remaining life. Thus, if
2 the life spans, and the related remaining life, are set at too short a period, current
3 customers overpay and vice versa. Failure to set a proper estimated retirement date for a
4 generating unit creates intergenerational inequities and fails to comply with the
5 "matching principle" of ratemaking.
6
7 Q. ARE THE RETIREMENT DATES FOR GENERATING UNITS KNOWN WITH
8 CERTAINTY?
9 A. Not for most units. Even for nuclear units that must operate within the period of a license
10 granted by the NRC, we now know that the initial estimate of a 40-year life span has been
11 or will be expanded to 60-years. Indeed, in ETI's last case, Docket No. 34800, the life
12 span for River Bend was extended for ratemaking purposes to 60 years. 4
13
14 Q. WHEN SETTING THE LIFE SPAN FOR A GENERATING UNIT, IS IT
15 APPROPRIATE TO LIMIT THE TIME FRAME TO THE INITIAL ESTIMATED
16 PERIOD CORRESPONDING TO WHEN MAJOR CAPITAL ADDITIONS MAY
17 BE REQUIRED IN ORDER TO KEEP THE UNIT IN SERVICE?
18 A. No, even though ETI and its depreciation consultant, Mr. Spanos, attempt to rely on such
19 a concept to artificially limit the current estimate of life span for units. Indeed, it is
20 questionable whether even the Company really believes such less than credible argument
21 given the sizeable capital additions it had to make in the early stages of service life for its
22 gas fired units. 5 In recognition of these sizeable capital additions that were necessary to
23 keep the units operating, ETI did not attempt to limit the life spans in its earlier
24 depreciation studies to the date of the expected capital additions.

4
PUC Docket No. 34800 Final Order FOF 34.
s Exhibit JJS-1pages209-252.

12
1 Q. WHY IS IT INAPPROPRIATE TO ARTIFICIALLY LIMIT THE LIFE SPAN OF
2 A GENERATING UNIT BASED ON UNCERTAINTY AS TO WHETHER
3 FUTURE CAPITAL ADDITIONS WILL BE MADE?
4 A. It is inappropriate to implement such depreciation judgment because it assumes that
5 utilities will act differently in the future than they have acted in the past without the
6 benefit of specific factors that would warrant such a change. Generating units are very
7 capital-intensive items. Economic theory recognizes that it is normally expected that
8 capital expenditures and normal maintenance expense will not only be made, but
9 encouraged as necessary, to keep a large capital intensive facility in operation for as long
10 as economically practical. This has been the Company's practice as it applies to actual
11 operation of its units.
12
13 An analogy would be associated with the purchase of a home. A new home can easily be
14 expected to last well over 50 years. However, a major capital expenditure for a new roof
15 may be required after 15 to 20 years. No reasonable person would set the life expectancy
16 of the house at 20 years because the decision has not been made regarding an expected
17 major expenditure 20 years in the future. The same can be said about limiting the
18 expected initial life expectancy of a house to even 30 or 40 years when the second
19 replacement of a roof can be expected. The issue becomes at what point would one
20 expect external forces such as a change in character of the neighborhood or other events
21 to change, for it to warrant the abandonment of the house. As long as the best use of the
22 house is as a dwelling and it is economically cost effective to make repairs and
23 replacements, the initial life should not be set artificially short due to potential
24 uncertainties surrounding future major capital additions.
I 25

I 26
27
Q. DOES THE COMPANY'S PRODUCTION PLANT DEPRECIATION EXPENSE
REPRESENT A SIGNIFICANT REVENUE REQUIREMENT?

I 28
29
A. Yes. The Company's 2008 Study identifies over $783 million of investment and proposes
$28.4 million in depreciation expense for annual Steam Production plant (Accounts 310-
316). 6 This level of depreciation expense is unnecessary and only arises as a result of the
l 30

6
2008 Study at Exhibit JJS-1 page 52.
I 13
I Company's witness's aggressive "depreciation judgment" for reflecting life spans,
2 corresponding interim retirements, and net salvage values.

3 B. Basis for Retirement Dates
4
5 Q. WHAT TESTIMONY DID THE COMPANY SPECIFICALLY PROVIDE IN
6 SUPPORT OF THE PROPOSED LIFE SPANS FOR ITS VARIOUS
7 GENERATING UNITS?
8 A. The Company provided the testimony of Mr. Spanos. The entire basis for this significant
9 parameter is set forth at pages 19 and 20 of Mr. Spanos' direct testimony where he states:
10
11 The bases for the probable retirement years are life spans for each facility
12 that are based on judgment and incorporate consideration of the age, use.
13 size. nature of construction. management outlook, and typical life spans
14 experienced and used by other electric utilities for similar facilities. Many
15 of the life spans result in probable retirement years that are many years in
16 the future, but included as part of ETI' s resource plan. As a result, the
17 retirements of these facilities are not yet subject to specific management
18 plans. At the appropriate time, detailed studies of the economics of
19 rehabilitation and continued use or retirement of the facility will be
20 performed and the results incorporated in the estimation of the facility's
21 life span. (Emphasis added).
22
23 Q. DID THE COMPANY ADD ANY ADDITIONAL INFORMATION REGARDING
24 THE BASIS FOR THE LIFE SPANS OF ITS UNITS IN THE 2008
25 DEPRECIATION STUDY?
26 A. While the 2008 Study added the following statements, such verbiage fails to provide any
27 additional meaningful basis for the Company's proposed life spans:
28
29 The life span estimates for power generating stations were the result of
30 considering experienced life spans of similar generating units, the age of
31 surviving units, general operating characteristics of the units, major
32 refurbishing, and discussion with management personnel concerning the
33 probable long-term outlook for the units. Final decisions as to date of
34 retirement will be determined by management on a unit by unit basis. 7
35 (Emphasis added).

7
2008 Study at Exhibit JJS-1 page 35.

14
1 Q. WHAT SPECIFIC ITEM OF INFORMATION HAS THE COMPANY
2 PROVIDED IN SUPPORT OF ITS "JUDGMENT" IN ESTABLISIDNG THE
3 LIFE SPANS FOR ITS GENERATING UNITS REFLECTING
4 "CONSIDERATION OF THE AGE" OR "USE, SIZE, NATURE OF
5 CONSTRUCTION" OF ITS UNITS?
6 A. The Company has provided no information that would support its proposal for a life span
7 as short as 46 years for Sabine 5. In fact, Sabine Units 1 and 2, which are much smaller
8 and dispatched less than Sabine 5, have already reached ages in excess of 46 years. Thus,
9 judgment in conjunction with consideration of age or physical characteristics of the units
10 should have caused the Company to propose longer life spans than it has.
11
12 Q. WHAT SPECIFIC ITEM OF INFORMATION HAS THE COMPANY
13 PROVIDED IN SUPPORT OF ITS "JUDGMENT" IN ESTABLISIDNG THE
14 LIFE SPANS FOR ITS GENERATING UNITS REFLECTING "MANAGEMENT
15 OUTLOOK"?
16 A. The Company has provided no information that would support its proposals. In fact, the
17 timing horizon of the Company's Strategic Resource Plan ("SRP") is through 2028. 8 The
18 SRP planning horizon exceeds the retirement dates for all of the Company's gas-fired
19 units, yet such plan relies on the continued operation of all such units to meet future
20 loads. Thus, even the Company's current management "outlook" refutes the judgment
21 employed by Mr. Spanos in the 2008 Study.
22
23 Q. WHAT SPECIFIC ITEM OF INFORMATION HAS THE COMPANY

I 24
25
PROVIDED IN SUPPORT OF ITS "JUDGMENT" IN ESTABLISIDNG THE
LIFE SPANS FOR ITS GENERATING UNITS REFLECTING "TYPICAL LIFE

~
26 SPANS EXPERIENCED AND USED BY OTHER UTILITIES OF SIMILAR
27 FACILITIES"?

I 28
29
A. The Company has provided no information. However, through discovery, it was
determined that Gannett Fleming has supported a range of life spans for gas-fired units

I 30 that is so wide that it would allow for a selection of about any value, even ones

8
Response to Rose City 1-36 Attachments.

15
l approaching 70 years. I submit that Gannett Fleming's life span range for gas-fired units
2 is so large that it defies any credibility that might have been assigned to it in the
3 "judgmental" process claimed by Mr. Spanos.
4
5 Q. DOES MR. SPANOS' TESTIMONY PROVIDE SUFFICIENT EXPLANATION
6 AND JUSTIFICATION TO SUPPORT THE COMPANY'S PROPOSED LIFE
7 SPANS FOR ITS GENERATING FACILITIES?
8 A. No.
9
10 Q. DID THE COMPANY PROVIDE ANY ADDITIONAL INFORMATION JN
11 RESPONSE TO DISCOVERY?
12 A. Yes. Mr. Spanos provided his site visit notes that reference limited additional information
13 such as:
14
15 • System maintenance good;
16 • Control upgrades;
17 • Monthly vibration program, performance tests; and
18 • Boiler exam and maintenance every year. 9
19
20 Q. DO THESE ADDITIONAL STATEMENTS CONTAINED IN MR. SPANOS' SITE
21 VISIT NOTES PROVIDE SUFFICIENT SUPPORT FOR THE COMPANY'S
22 LIFE SPAN PROPOSALS?
23 A. No. These statements represent the type of statements one would expect relating to a
24 dynamic situation requiring decisions whether to retire units or continue to expend funds
25 to permit continued operation. In fact, it is quite clear from these comments and other
26 information in the 2008 Study that the Company has historically decided, and currently is
27 deciding, to make necessary capital expenditures to keep its units in operation long after
28 the claimed initial design life. The Company has faced the decision whether to retire
29 these units or spend funds to keep them in operating condition beyond initial expectations
30 and in each instance has decided that it is economically appropriate and efficient to do
31 what all other utilities have been doing: maximize the life of a capital-intensive asset.

9
Response to Rose City 1-15 Attachment.

16
1 There is more support for longer life spans in Mr. Spanos' notes than there is for the
2 artificially short life spans being proposed.
3
4 Q. DID MR. SPANOS PROVIDE ANY ADDITIONAL INFORMATION
5 REGARDING ms PROPOSED LIFE SPANS DURING ms DEPOSITION?
6 A. Yes. Mr. Spanos stated that the life spans corresponded with the best estimate of the
7 likelihood of assets being either taken out of service (i.e. retired), or the date of expected
8 major capital additions in the future made to change the functionality of the asset. 10 He
9 also admits that the proposed retirement in his study does not necessarily relate to when
10 the units would be shut down. 11 These two statements taken together default to a position
11 that the probable retirement dates in Mr. Spanos' study are the unsubstantiated date Mr.
12 Spanos assumes the Company may make major capital additions to change the
13 functionality of the units.
14
15 Q. IS THERE ANYTHING IN THE USOA THAT DEFINES OR TIES THE
16 SERVICE PERIOD FOR A GENERATING UNIT TO AN ASSUMED DATE
17 WHEN A UTILITY MIGHT MAKE A MAJOR CAPITAL ADDITION THAT
18 CHANGES THE FUNCTIONALITY OF AN ASSET?
19 A. Absolutely not.
20
21 Q. DID MR. SPANOS OR THE COMPANY PROVIDE A SINGLE DOCUMENT
22 THAT DEMONSTRATES THE PROPOSED RETIREMENT DATES ARE THE
23 COMPANY'S BEST ESTIMATE OF WHEN A UNIT WILL RETIRE?

I 24
25
A. No. In fact, as previously discussed, the documents presented by the Company now
demonstrate that assumed retirements prior to 2029 are not the current best estimate of

~ 26 the Company.

~
I 10
Deposition of Mr. Spanos on April 20, 2010 at TR 39.
Id.
I
II

17

!
1 Q. DID MR. SPANOS PROVIDE A SINGLE DOCUMENT OR ITEM OF
2 EVIDENCE THAT IT IS APPROPRIATE TO TIE THE PROPOSED
3 RETIREMENT DATE TO A CONCEPT OF WHEN MAJOR CAPITAL
4 EXPENDITURES MIGHT OCCUR?
5 A. No, Mr. Spanos' concept is a backdoor approach to recognizing interim additions,
6 something the PUC and other regulators do not permit.
7
8 Q. WHAT ARE INTERIM ADDITIONS?
9 A. Interim additions are theoretical future dollars of investment or capital additions in plant
10 to be added to existing facility of the Company. Such additions are not the dollars of
11 investment currently in service. Rather, they are .estimated dollars for replacement of
12 certain existing facilities or for additions of new facilities to an existing generating
13 facility in the future.
14
15 Q. ARE INTERIM ADDITIONS APPROPRIATE FOR DEPRECIATION
16 PURPOSES?
17 A. No. Interim additions are inappropriate since they reflect the estimation of potential
18 additions to plant-in-service that currently do not exist and are not used and useful in
19 providing service. Interim additions may never actually occur or may occur at a much
20 different date or amount than initially assumed.
21
22 Q. IN THE RATEMAKING PROCESS, ARE INTERIM ADDITIONS EVER
23 APPROPRIATE FOR DEPRECIATION PURPOSES?
24 A. No. Interim additions are appropriate only after they occur. Once such expenditures
25 occur, and the plant becomes used and useful in providing service, it is appropriate to
26 incorporate the plant investment into a depreciation study. Under this approach, the
27 Company is not deprived of a return of its investments associated with interim additions.
28 Moreover, customers are not inappropriately charged for unknown plant that is not used
29 and useful in providing service to them at the time the depreciation rates are developed.

18
1 Q. WHAT SOURCE SUPPORTS YOUR POSITION THAT ESTIMATED INTERIM
2 ADDITIONS SHOULD NOT BE REFLECTED IN THE DEPRECIATION
3 CALCULATION?
4 A. The National Association of Regulatory Utility Commissioners (''NARUC") 1968
5 publication entitled Public Utility Depreciation Practices describes, on pages 133 and
6 134, how interim additions are treated. It states the following:

7 Appropriate computations must be made for such interim retirements, but
8 interim additions are not considered in the depreciation computation until
9 they are actually made.
10 It is possible to estimate the probable future retirements and additions to a
11 particular piece ofproperty and thus arrive at a single depreciation rate
12 applicable over the entire life of the property. This is an unsatisfactory
13 practice inasmuch as considerable speculations would be required to
14 make such an estimate on future additions. In any event. this is not
15 necessary inasmuch as the depreciation accrual can be adjusted in future
16 years as additions are made. (Emphasis added).
17
18 The 1996 NARUC depreciation publication reaffirms this concept. 12
19

20 Q. HAS THE FERC RENDERED A DECISION ON THE CONCEPT OF
21 INTERIM ADDITIONS?

22 A. Yes. The FERC reviewed and ruled on this issue in its Opinion No. 165, a
23 Commonwealth Edison Company case. 13 In that case, Commonwealth Edison had
24 proposed taking into account budgeted future interim additions and stated that without the
25 inclusion of the budgeted interim additions, there would be a violation of the matching

I 26
27
principle (i.e. revenues collected corresponding to the expenses incurred). In Opinion
No. 165, the FERC clearly rejected recognition of interim additions:

I 28
29
... we reject its [Edison 'sj claim that this will leave some costs
unrecovered after the plant is retired. Such a result might occur if
30 Commonwealth would fail to adjust its depreciation rates from time to
I 31
32
time, taking into account up-to-date information on changes in plant
balances, estimated remaining life, salvage and removal cost experience,
33 and accumulated provision for depreciation to date. However,
I 12
Page 142 states" ... interim additions are not considered in the depreciation base or rate until they occur."
13
23 FERC paragraph 61,219 (1983)

19
1 Commonwealth not only is free to make such adjustments to its
2 depreciation rates, but is obligated to do so to assure that as near as
3 possible the service value of electric plant is fully recovered during its
4 useful life. For all these reasons, we find no basis to approve
5 Commonwealth's depreciation methodology. 14
6
7 Q. IS THERE A NEED TO SPECULATE ON THE COMPANY'S FUTURE
8 INTERIM ADDITIONS?

9 A. No. The Company will have the opportunity to recover actual additions to plant from
10 customers once they occur.
11
12 Q. ARE OTHER UTILITIES FACED WITH THE SAME CONCERNS RELATING
13 TO THE DECISION TO REPAIR OR REPLACE WORN OR BROKEN
14 COMPONENTS VERSUS RETIRE A UNIT?
15 A. Yes, and the trend in the industry has been to project even longer life spans. In fact, in a
16 recent case here in Texas, Southwest Electric Power Company ("SWEPCO") filed for life
17 spans longer than ETI has for comparable units. 15 A listing of comparable size and age of
18 generating units between SWEPCO and ETI, along with the life spans filed by both
19 utilities is set forth in the table below:
20
21 COMPARABLE UNITS

Size Year Life Size Year Life
ETIUnit (MW) Installed Span SWEPCOUnit
0::
Q)
a.
:::>
(f)

70

60
0.5 8.5 16.5 24.5 32.5 40.5 48.5
4.5 12.5 20.5 28.5 36.5 44.5 52.5
AGE (YEARS)
Actual 52R2.5 __..,_ 45R2.5

I In addition, the Company's historical data reflects retirement activity associated with
2 recent hurricanes, thus resulting in an artificially short life indication even based on the
3 Company's actuarial analysis. Next, a review of Mr. Spanos' industry database indicates
4 that a longer ASL is warranted than the 45-year value he proposed. In fact, the mean,
5 median and mode for his industry database all exceed 45 years, even when taking into
6 account some unusually low values associated with cooperatives or old studies reflected
7 in that database. 64 Mr. Spanos' notes also support something longer than a 45-year ASL.
8 For example, Mr. Spanos' notes associated with substations specifically state "about 50

64
Response to Rose City 1-1 7 Attachment.

46

I
years. " 65 Indeed, the notes further identify the Company has a policy of cradle to grave
2 accounting for its transformers, which should have indicated a longer ASL compared to
3 the industry average since many utilities actually retire transformers when they move
4 such equipment from one location to another. In addition, while Mr. Spanos' notes
5 indicate that there is an expectation for a shorter lives in the future for transformers, this
6 is an argument that has been utilized in the industry for the past 20 or 30 years, yet the
7 industry has demonstrated increasing life expectancy for substation equipment as more
8 empirical data has been obtained. Therefore, the 52-year ASL is more indicative of the
9 Company's actual experience, better reflects industry expectations, and is more
10 representative of the type of equipment in the account.
11
12 Q. WHAT IS THE IMPACT OF YOUR RECOMMENDATION?
13 A. My recommendation of a 52-year ASL on a standalone basis results in a $1,462,347
14 reduction to depreciation expense based on plant in service as of December 31, 2008.
15
16 Account354
17
18 Q. WHAT DOES THE COMPANY PROPOSE FOR ACCOUNT 354 -
19 TRANSMISSION TOWERS?
20 A. The Company proposes a 50-S4 life-curve combination. 66
21
22 Q. WHAT IS THE COMPANY'S BASIS FOR ITS PROPOSAL?
23 A. This is an account where the historical data is not relied upon and Mr. Spanos reverts to

I 24
25
his generalized statement referring to judgment and other information.

26 Q. DO YOU AGREE WITH THE COMPANY'S PROPOSAL?
27 A. No. I recommend a 63-S4 life-curve combination.

I
I 65
Response to Rose City 1-15 Addendum page 46.
66
Exhibit JJS-1 page 52.

47
1 Q. WHAT IS THE BASIS FOR YOUR RECOMMENDATION?
2 A. First, while the historical data provides an extremely short "stub curve", it does provide
3 an indication for a long ASL given the very limited level of retirement activity that has
4 transpired during over 50 years of data. 67 In addition, Mr. Spanos' industry database
5 indicates a mean, median and mode of 63, 65 and 65 years, respectively. 68 Indeed, the
6 industry data that would have formed possibly a major portion of Mr. Spanos'
7 'judgment" indicates that the use of a 50-year or lower ASL is very limited. Therefore,
8 all indications of available data indicate that a value in the mid 60-year range is by far
9 superior to the Company's proposed 50-year ASL. Moreover, the Company proposed a
10 55-year ASL for Account 355 - Transmission Poles. On a predominant basis, the
11 industry recognizes that transmission towers have longer expected ASLs than do
12 transmission poles. In this case, Mr. Spanos also failed to take this relationship into his
13 judgmental decision making process.
14
15 Q. WHAT IS THE IMPACT OF YOUR RECOMMENDATION?
16 A. My recommendation of a 63-year ASL on a standalone basis results in a $110,162
17 reduction to depreciation expense based on plant as of December 31, 2008.
18
19 Account 355
20
21 Q. WHAT DOES THE COMPANY PROPOSE FOR ACCOUNT 355 -
22 TRANSMISSION POLES AND FIXTURES?
23 A. The Company proposes a 55-R3 life-curve combination. 69
24
25 Q. WHAT IS THE COMPANY'S BASIS FOR ITS PROPOSAL?
26 A. This is another account where Mr. Spanos claims to have relied on the statistical actuarial
27 results. 70

67
Exhibit JJS-1pages99 and 100.
68
Response to Rose City 1-17 Attachment.
69
Exhibit JJS-1page52.
70
Exhibit JJS-1 page 33.

48
1 Q. DO YOU AGREE WITH THE COMPANY'S PROPOSAL?
2 A. No. The Company's proposal is artificially short; therefore, I recommend a 59-R2.5 life-
3 curve combination.
4
5 Q. WHAT IS THE BASIS FOR YOUR RECOMMENDATION?
6 A. As shown in the graph below, my recommendation results in a better fit to the OLT in the
7 significant portion of the curve that Mr. Spanos referenced in his testimony. Indeed, Mr.
8 Spanos sacrificed a better fitting relationship during periods beginning around age 8 years
9 in order to strive for a better match during the age intervals of approximately 25 years
10 through 35 years. The problem with Mr. Spanos' election to discount the earlier portion
11 of the curve in an effort to match a later portion of the curve sacrifices exposures in the
12 $40-$70 million range for better fitting exposures in the $15-$40 million range. 71 As can
13 be seen in the graph be]ow, my recommendation is a superior fit during the first
14 approximate 24 years of age.

I

71
Exhibit JJS-1pages104-105.

49
ENTERGY TEXAS
355 - TRANSMISSION POLES AND FIXlURES (1954)

100

90
en
a:::
0
>
-
c::
Q)
....
(.)

~ Q)
0...
::::>
en 80

70
0.5 8.5 16.5 24.5 32 .5 40.5 48.5
4.5 12.5 20.5 28.5 36.5 44.5 52.5
AGE (YEARS)
Actual 59R2. 5 __..._ 55R3

1 In addition, Mr. Spanos' notes indicate that new poles are steel and concrete, thus
2 indicating a longer life expectancy in the future than reflected in the historical data,
3 which reflects a higher level of wood poles. While Mr. Spanos reflected such information
4 in his notes, he apparently failed to take that into consideration in his undocumented
5 decision making process. 72 Otherwise, he would have proposed a longer ASL. Thus, from
6 a curve-fitting process, and taking into account the limited additional information
7 provided by the Company, a longer ASL than the 55-year life proposed by the Company
8 is warranted. Analysis of historical data and supplemental information better supports a
9 59-year ASL.

72
Response to Rose City 1-15 Addendum at page 46.

50

I
1
2 Q. WHAT IS THE IMPACT OF YOUR RECOMMENDATION?
3 A. My recommendation for a 59-year ASL on a standalone basis results in a $1,080,733
4 reduction to depreciation expense based on plant in service as of December 31, 2008.
5
6 Account 356
7
8 Q. WHAT DOES THE COMPANY PROPOSE FOR ACCOUNT 356 -
9 TRANSMISSION OVERHEAD CONDUCTORS?
10 A. The Company proposes a 53-R2.5 life-curve combination. 73
11
12 Q. WHAT IS THE COMPANY'S BASIS FOR ITS PROPOSAL?
13 A. For this account, the Company relies on Mr. Spanos' claim relating to a good to excellent
14 indication from the statistical analyses. 74
I 15
16 Q. DO YOU AGREE WITH THE COMPANY'S PROPOSAL?
I 17 A. No. The Company's proposal understates the realistic ASL for this account. Therefore, I
18 recommend a 55-year ASL with a corresponding R2.5 Iowa Survivor Curve. As shown in
19 the graph below, both Mr. Spanos' proposal and my recommendation are both good fits
20 of the data for approximately the first 27 years of age. At that point the Company's
21 proposal begins to deviate from the OLT until approximately 35 years of age and
22 understates the expected ASL. Thus, both curves are good fits through the most
23 significant portion of the curve, but the longer ASL continues the good fit through most

I 24
25
of the remaining portion of the OLT including portions of the curve that are still
significant. Another consideration for a somewhat longer ASL is that to the extent any

I 26
27
retirement activity associated with major hurricanes that occurred in recent periods is
reflected in the Company's data, it would understate the expected ASL for the remaining

l 28
29
investment. Therefore, a modest increase from what the Company has proposed in the
expected ASL is warranted at this time.

73
Exhibit JJS-1 page 52.
74
Id., at page 33.

51
ENTERGY TEXAS
356 - TRANSMISSION OVERHEAD CONDUCTORS AND DEVICES (1954)

100

90
C/)
a:
0
...c:
> Q)
,_
0 80
>
a:
Q)
a..
::>
C/)

70

60
0.5 8.5 16.5 24.5 32.5 40.5 48.5
4.5 12.5 20.5 28 .5 36 .5 44.5 52.5
AGE (YEARS)
Actual __..._ 55R2. 5 -6--- 53R2. 5

1 Q. WHAT IS THE IMP ACT OF YOUR RECOMMENDATION?
2 A. My recommendation for a 55-year ASL results in a $210,829 reduction to the Company' s
3 annual depreciation expense based on plant in service as ofDecember 31, 2008.

4 Accounf 360
5
6 Q. WHAT DOES THE COMPANY PROPOSE FOR ACCOUNT 360 -
7 DISTRIBUTION LAND RIGHTS?
8 A. The Company proposes a 55-R4 life-curve combination. 75

75
Exhibit JJS-1 page 51.

52
I Q. WHAT IS THE COMPANY'S BASIS FOR ITS PROPOSAL?
2 A. Given that there have been no retirement activity reflected in the Company's historical
3 database, this is an account where the Company relied on judgment and other undefined
4 parameters.
5
6 Q. DO YOU AGREE WITH THE COMPANY'S PROPOSAL?
7 A. No. The same situation as discussed for Account 350 - Transmission Land Rights also
8 pertains to Distribution Land Rights. The Company's selection would have land rights
9 retiring long before the end of a single life cycle is reached for various other distribution
10 accounts. Thus, on its face, the Company's proposal is illogical. Therefore, I recommend
11 a 85-R4 life-curve combination, taking into account land rights must exist for at least one
12 complete life cycle relating to the investment that resides upon it. As time passes this
13 estimate will have to be expanded in recognition that retirements will not occur as
14 additional new plant is placed on the same land rights and that new investment must also
15 complete its life cycle.
16
17 Q. WHAT IS THE IMPACT OF YOUR RECOMMENDATION?
18 A. My recommendation for an 85-year ASL results in a $120,195 reduction in depreciation
19 expense based on plant as of December 31, 2008.
20
21 Account 362
22
23 Q. WHAT DOES THE COMPANY PROPOSE FOR ACCOUNT 362 -

I 24
25 A.
DISTRIBUTION STATION EQUIPMENT?
The Company proposes a 40-Rl.5 life-curve combination. 76

I 26
27 Q. WHAT IS THE COMPANY'S BASIS FOR ITS PROPOSAL?

I 28
29
A. This is an account where the Company relied on what appeared to be a good to excellent
statistical indication from its statistical analysis of historical data. 77

76
Exhibit JJS-1page53.
77
Id., at page 34.

53
1 Q. DO YOU AGREE WITH THE COMPANY'S PROPOSAL?
2 A. No. The Company's proposed ASL is too short for the investment in this account.
3 Therefore, I am recommending a 47-Rl life-curve combination.
4
5 Q. WHAT IS THE BASIS FOR YOUR RECOMMENDATION?
6 A. A review of the historical OLT identifies two significant retirement periods that appear to
7 be out of line. In particular, the Company experienced its second highest retirement level
8 during the age interval of zero (0) to 0.5 year. 78 It is unusual to have such significant
9 levels of infant mortality in comparison to older aged equipment. Indeed, the vast
IO majority of this infant mortality incurred in 1954. 79 No other infant mortality of this
11 magnitude has transpired in the subsequent 54 years. Therefore, proper judgment should
12 have recognized this event as an outlier and normalized it in the database. The reality is
13 that utilities, absent unusual events, are not expected to purchase and install equipment
14 that is expected to fail immediately upon installation to any great extent. Thus, the
15 Company's historical OLT reflects an artificial reduction at an early time frame given
16 that such data is being used as a predictive tool for future expectations.

17 The largest level of retirement activity during any age interval occurred beginning at age
18 interval 6.5 years. 80 This annual level of retirement activity is approximately ten times the
19 level of retirement activity in the age intervals immediately preceding or following.
20 Again, this is the type of activity that should have caused an analyst to question the
21 validity of the resulting OLT as a basis for projecting future expectation for the remaining
22 investment. Indeed, this single age bracket yielded the highest retirement ratio through
23 the first 70 years of age.81 The impact of this single age bracket produced an atypical and
24 noticeable decline in the OLT as set forth in the graph in the Company's depreciation
25 study. 82 Events of this magnitude warrant further investigation, yet Mr. Spanos'
26 testimony, exhibits, workpapers and site visit notes make no reference to any specifics
27 regarding this retirement activity. Based upon further investigation it has been determined

78
Exhibit JJS-1 page 126.
79
Response to Rose City 13-7.
80
Exhibit JJS-1page126.
81
Id., at pages 126-127.
82
Id., at page 125.

54

I
I that $4.8 million of the $5.4 million was a retirement during age interval 6.5 years and
2 relevant to a 8MVA stored magnetic energy superconductor unit located at a substation.
3 The Company could not provide any support for why a retirement of this magnitude for
4 this type of equipment is expected to reoccur on a similar basis in the future. 83 Therefore,
5 the impact of what is a single, but large, unusual event should have been normalized in
6 the Company's analysis. Indeed, Mr. Spanos, who claims constant reliance on judgment,
7 apparently failed to even recognize that his own database of other utilities would have
8 indicated that his proposed 40-year ASL for this account was well below the mean,
9 median or mode for his industry range. 84 This discrepancy between ETI and the industry
10 should have resulted in this transaction being adjusted prior to the curve fitting process
11 had proper judgment been employed.
12
13 As set forth in the graph below, I have normalized only the outlier at the 6.5 age
14 interval. 85 As can be seen, my recommended 46-SO life-curve combination is a superior
15 or equal fit to all data points when compared to Mr. Spanos' proposal. Moreover, my
16 recommendation better matches Mr. Spanos' industry data and is consistent with the
17 cradle to grave type accounting employed by the Company for transformers and other
18 major equipment at substations, as identified in Mr. Spanos' site visit notes. 86 My
19 recommendation is conservative given the fact that the curve matching process still
20 incorporates atypical hurricane activity that should have also been normalized.

I
I
I
83
Response to Rose City 1-2 13-18.
84
Response to Rose City 1-16 Attachment even prior to the elimination of obvious outliers in Mr. Spanos' own
database.

' as Reflects 1979-2008 Experience band to address infant mortality issue.
86
Response to Rose City 1-15 Addendwn at pages 46 and 48.

55
ENTERGY TEXAS
362 - DISTRIBUTION STATION EQUIPMENT (Normafized)
100

90

en
g-
a:: 80
c::
Q)
0
>
a:: a.
~
Q)

::::> 70
en

60 I
50
0.5 8.5 16.5 24.5 32.5 40.5 48.5 56.5 64.5
4.5 12.5 20.5 28 .5 36.5 44.5 52.5 60.5

AGE (YEARS)
Actual 46R1.5 __..__ 40R1.5

1 Q. WHAT IS THE IMPACT OF YOUR RECOMMENDATION?
2 A. My recommended 46-year ASL results in a $783,405 reduction to annual depreciation
3 expense based on plant as of December 31, 2008.

Account 365
4
5
I
6
7
Q. WHAT DOES THE
DISTRIBUTION OVERHEAD CONDUCTORS?
COMPANY PROPOSE FOR ACCOUNT 365 -
I
8 A. The Company proposes a 36-R0.5 life-curve combination. 87
1
87
Exhibit JJS-1page53.

56
I
2 Q. WHAT IS THE COMPANY'S BASIS FOR ITS PROPOSAL?
3 A. This is an account where the Company relied heavily on the results of its statistical
4 analysis. 88
5
6 Q. DO YOU AGREE WITH THE COMPANY'S PROPOSAL?
7 A. No. The Company's proposal is artificially short. Therefore, I recommend a 39-S-0.5 life-
8 curve combination. The Company's historical data included $2.8 million of unusual
9 retirement activity in the age interval 0.5 that occurred in 2008, the year in which
10 Hurricane Ike hit. 89 The retirement activity at age intervals 0.5 is significantly greater
11 than any other time frame and is atypical in nature. Therefore, at a minimum, the OLT
12 would need to be normalized for such activity. As shown in the graph below, my life-
13 curve combination is a better match to the historical data minimally for the first 30 years,
14 and then again beginning at approximately 44 years of age. If the remaining retirements
15 associated with recent hurricane activity were also removed from the data, it would raise
16 the OLT and make my recommendation even a better fit than set forth in the graph
17 below.

I
I
I

' 88
89
Id., at page 34.
Response to Rose City 13-11.

57
ENTERGY TEXAS
365- DISTRIBUTION OVERHEAD CONDUCTORS & DEVICES (Normalized)

100
:-..
90
~~ ~
80
~
70 ~~
Cl)
0:: ~
~
..,
.+J
0 cQ) 60
> e
6;
::::>
Cl)
Q)
a.. 50

40

30
' .....

~

~ ~

20
~~ a_

~
10 111 111 111 111 Ill 111 Ill 111 111 111 111 111 111 111 ~~ JUI 111 111 111

0.5 8.5 16.5 24.5 32.5 40 .5 48.5 56 .5 64.5
4.5 12.5 20.5 28.5 36.5 44.5 52.5 60.5

AGE (YEARS)

I Actual - - - 398-0.5 ___._ 36R0.5
I
1 Other considerations supporting a longer ASL are the fact that the only item of
2 information referenced by Mr. Spanos in his site notes was that if poles go down,
3 conductors may not be damaged and thus still in use. 90 All else equal, this would imply
4 that an ASL for conductors should be approximately as long as poles, if not longer. It
5 should be noted that my 39-year ASL recommended for conductors is one year shorter
6 than what Mr. Spanos has recommended for poles. Finally, a review of Mr. Spanos'
7 industry data would indicate that even a 39-year ASL is on the shorter side of life
8 expectancy. Thus, in conjunction with my life recommendation, the Commission should
9 also order the Company to perform a detailed analysis to normalize the impacts of major
1O hurricanes that occurred in the 2005 through 2008 era for use in the next depreciation
90
Response to Rose City 1-15 Addendum at page 49.

58
1 study. Overall, my recommended 39-year ASL is conservative, considering actual
2 historical data even before normalization for all hurricane activity.
3
4 Q. WHAT IS THE IMPACT OF YOUR RECOMMENDATION?
5 A. My recommendation for 39-year ASL results in a $1,103,876 reduction in depreciation
6 expense based on plant as of December 31, 2008.
7
8 Account 366
9
IO Q. WHAT DOES THE COMPANY PROPOSE FOR ACCOUNT 366 -
11 DISTRIBUTION UNDERGROUND CONDUIT?
12 A. The Company proposes a 50-R2 life-curve combination. 91
13
14 Q. WHAT IS THE COMPANY'S BASIS FOR ITS PROPOSAL?
15 A. This is an account where the Company did not rely on the statistical analysis it
16 performed, but rather relied on unidentified judgment and other factors. 92
17
18 Q. DO YOU AGREE WITH THE COMPANY'S PROPOSAL?
19 A. No. First, it must be noted that the existing ASL for this account is 60 years. Thus, the
20 Company is proposing a 10-year reduction based on undefined judgment. A review of the
21 data indicates unusually high levels of retirement activity at low age intervals, without
22 any explanation. 93 Substantial amounts of these early age retirements are associated with
23 underground plastic conduit and pads for transformers. These are not the type of

I 24
25
investments that one would normally anticipate retiring at early ages, absent unusual
circumstances. Moreover, industry experience would indicate that even a 50-year ASL is
26 artificially short. Indeed, Mr. Spanos' industry data, which is skewed with several very
94
27 short lives, still yields mean, median and mode values of approximately 55-60 years.
28 There is no logical explanation or documentation presented by the Company that

91
Exhibit JJS-1 page 53.
92
Id., at page 34.
93
Response to Rose City 13-12 through 13-15.
94
Response to Rose City 1-17.

59
1 warrants a reduction from the existing 60-R3 life-curve combination. Therefore, I
2 recommend retention of the existing ASL, which is more in line with the type of
3 investment reflected in this account.
4
5 Q. WHAT IS THE IMP ACT OF YOUR RECOMMENDATION?
6 A. My recommended 60-year ASL results in a $182,339 reduction to depreciation expense
7 based on plant as of December 31, 2008.
8
9 Account 368
10
11 Q. WHAT DOES THE COMPANY PROPOSE FOR ACCOUNT 368 -
12 DISTRIBUTION LINE TRANSFORMERS?
13 A. The Company proposes a 29-SO life-curve combination.95
14
15 Q. WHAT IS THE COMPANY'S BASIS FOR ITS PROPOSAL?
16 A. For this account the Company relied on what it believed to be a good or excellent
17 statistical fit for the historical data. 96
18 Q. DO YOU AGREE WITH THE COMPANY'S PROPOSAL?
19 A. No. The Company's proposal results in one of the shortest ASLs for any utility in the
20 industry. Therefore, at a minimum, I recommend increasing the ASL to 32 years with a
21 corresponding L0.5 Iowa Survivor Curve.
22
23 Q. WHAT IS THE BASIS FOR YOUR RECOMMENDATION?
24 A. First, a 31-L0.5 life-curve combination represents as good a fit to the OLT as does the
25 Company's proposal. Indeed, given the type of investment and other considerations, a 31-
26 L0.5 life-curve combination is a more realistic expectation for the investment in this
27 account. However, some of the other items of information exist that require some
28 additional level of increase in ASL. Those other items of information are the existing
29 ASL, the impact of hurricane related retirements, and industry information. The existing

95
Exhibit JJS-1 page 53.
96
Id., at page 34.

60
1 ASL for this account is 39 years, thus the Company is proposing a value 10 years shorter
2 than the existing level. Even if this was a reasonable prediction, which it is not, a degree
3 of gradualism may be warranted.
4

5 More significant to the concept for a longer ASL than proposed by the Company is the
6 fact that the Company has included significant retirement activity associated with
7 hurricane-related recent events. Normalization of the data to remove hurricane activity
8 would result in raising the OLT from its current position, thus resulting in a longer ASL.
9 Indeed, just removing the 2008 retirement activity for ages 0.5 year through 5.5 years,
10 corresponding to just the 2002-2007 vintage additions, increases the "head" or top
11 portion of the survivor curve by approximately 0.6 of a percentage point. This level of
12 increase is meaningful.
13
14 In addition, Mr. Spanos states in his site visit notes that the Company has historically
15 overloaded its line transformers. This is not a typical practice for an extended period of
16 time and thus, future life expectancy should be longer than that experienced historically. 97
17 Yet another consideration is the fact that Mr. Spanos' industry database indicates that a
18 29-year ASL would be basically at the extreme low end of the industry range. Even
19 retaining the unusually low values in Mr. Spanos' database, the mean, median and mode
20 would all be in the upper 30 to 40 year range, or more in line with the existing ASL.
21
22 Some minimal increase in the ASL above the 31-year ASL (that is as good a fit to the
23 historical data as is the Company's proposal) is warranted in light of industry data, the
24 Company's inappropriate historical actions of overloading transformers, the existing
25 ASL, and the inclusion of hurricane activity in the historical data. Therefore, I am

I 26
27
recommending a minimal incremental increase of one additional year as a conservative
estimate in favor of the Company. I further recommend that the Commission order the

I 28
29
Company to demonstrate the prudence of its continued operation of transformers above
maximum ratings, or that it is no longer performing such unusual activity, by the time it
30 files its next depreciation study.

97
Response to Rose City 1-15 Addendum at page 49.

61
1 Q. WHAT IS THE IMPACT OF YOUR RECOMMENDATION?
2 A. My recommendation for a 32-L0.5 life-curve combination results in a $1,478,940
3 reduction to depreciation expense based on plant in service as of December 31, 2008.
4
5 Account 369
6
7 Q. WHAT DOES THE COMPANY PROPOSE FOR ACCOUNT 369 -
8 DISTRIBUTION SERVICES?
9 A. The Company proposes a 27-U life-curve combination for both underground and
10 overhead services. 98
11
12 Q. WHAT IS THE COMPANY'S BASIS FOR ITS PROPOSAL?
13 A. This is one of the accounts where Mr. Spanos relied extensively on his actuarial analysis
14 for his proposal. 99

15 Q. DO YOU AGREE WITH THE COMPANY'S PROPOSAL?
16 A. No. A 29-year ASL represents basically the shortest ASL in Mr. Spanos' industry
17 database of approximately 60 values. The only few values that are lower correspond to a
18 Canadian utility, a cooperative and a utility that has not had its proposed ASL tested in a
19 fully litigated proceeding. 100 Moreover, the historical data relied upon by Mr. Spanos
20 incorporates the impact of recent severe hurricane activity, which helps produce the
21 proposed artificially short ASL.
22
23 Q. WHAT DO YOU RECOMMEND?
A.
24
25
I recommend a very conservative estimate of a 31-year ASL with an R3 Iowa Survivor
Curve. Initial review of Mr. Spanos' proposal raises concern from not only the short ASL
I
26 standpoint, but also from the standpoint of the unusual "L4" dispersion pattern. Mr.
27 Spanos' database of other utilities indicates a 40-45 year ASL is indicative of average

98
Exhibit JJS-1 page 53.
99
Id., at page 34.
100
Response to Rose City 1-17.

62

J
1 industry expectations. 101 In other words, the industry indicates a longer ASL than the
2 existing 36-year level, definitely not a reduction to the 27-year level as proposed by the
3 Company. Next, review of Mr. Spanos' industry database further raises concern
4 regarding the proposed "L4" Iowa Survivor Curve. In this existence, Mr. Spanos'
5 judgment relating to what he has observed from the industry and the type of plant in this
6 account should have resulted in further investigation. Indeed, not a single other industry
7 value relies on "L4" dispersion, or for that matter any "L" pattem. 102
8
9 Another consideration that is not addressed by Mr. Spanos is the movement towards more
10 underground rather than overhead services. As reaffirmed by Mr. Spanos' industry
11 database, underground services are generally expected to have a longer ASL than
12 overhead services. l03 The percent investment in underground services has grown faster
13 than for overhead services in the last I 5 years. 104 This fact should have also indicated a
14 longer ASL. Finally, the fact that the Company's data includes hurricane related
15 retirements further demonstrates that a longer ASL than indicated by the OLT is
16 appropriate.
17
18 In order to remain conservative, I am recommending splitting the difference between the
19 existing 36-year ASL and the 27-year ASL proposed by the Company, which yields a 31-
20 year ASL. Such a value still leaves the Company at the very low end of the industry
21 range, well below industry averages, and the existing ASL. I also recommended a "R3"
22 Iowa Survivor Curve, which corresponds to the most frequently used curve in Mr.
23 Spanos' database. In conjunction with my ASL recommendation, I further request that

I 24
25
the Commission order the Company to provide a detailed analysis as to why its historical
database gives indications of artificially short ASLs and what portion of such lower ASLs

I 26 is due to the inclusion of recent hurricane related activity.

101 Id.
r 102 Id.
103 Id.
104

I Exhibit JJS-1 pages 289-291.

63
1 Q. WHAT IS THE IMPACT OF YOUR RECOMMENDATION?
2 A. My recommendation for a 31-R3 life-curve combination results in a $1,159,669 reduction
3 to depreciation expense based on plant as of December 31, 2008.
4
5 Account 390
6
7 Q. WHAT DOES THE COMPANY PROPOSE FOR ACCOUNT 390 - GENERAL
8 PLANT STRUCTURES AND IMPROVEMENTS?
9 A. The Company proposes a 44-R2.5 life-curve combination. 105
10
11 Q. WHAT IS THE COMPANY'S BASIS FOR ITS PROPOSAL?
12 A. The Company relies on the results of its statistical actuarial analysis for this account. 106
13
14 Q. DO YOU AGREE WITH THE COMPANY'S PROPOSAL?
15 A. No. This is an account that requires special investigation. This account varies throughout
16 the industry because some utilities only rent facilities and have leasehold improvements
17 reflected in this account, while other utilities own the actual structure including the
18 interior components as well as roofs and other systems. The life expectancy for leasehold
19 improvements is much shorter than the life expectancy of an entire office building or
20 warehouse that is owned rather than leased. ETI owns most of its buildings. 107
21
22 Q. WHAT DO YOU RECOMMEND?
23 A. I recommend a 53-R2 life-curve combination as a conservative value. First, it must be
24 noted that a dramatic decline in the OLT as set forth on Exhibit JJS-1 page 176 is a result
25 of an internal decision by the Company to retire, for accounting purposes only, a portion
26 of its corporate headquarters. The investment in that building was subsequently
27 transferred to non-utility plant. In other words, the facility was not actually retired, but
28 reflects an accounting transaction between the regulated and non-regulated portions of

105
Exhibit JJS-1page53.
106
Id., at page 34.
107
Response to Rose City 1-41.

64
l the Company's business. 108 This type of transaction is atypical and should not negatively
2 affect current customers through the depreciation process. Relying on the remainder of
3 the OLT, but eliminating this unusual transaction, would require a substantial increase in
4 ASL.
5
6 In addition, the majority of the investment in this account is associated with office
7 buildings and other structures that the Company owns rather than leases. 109 Office
8 structures, warehouses and similar facilities can normally have life expectancies
9 approaching 75 to 100 years or more. Taking into account that the investments still
10 require a replacement of air conditioning systems, roofs and others components would
11 reduce the dollar-weighted ASL. Mr. Spanos' industry database indicates numerous
12 ASLs for investment in this account that still exceed 50 and even 60 years. In addition,
13 Mr. Spanos' site visit notes state that buildings are generally "concrete slab with steel
14 structures on top."uo Steel buildings on concrete slabs can easily be expected to achieve
15 50 or even 60 years on a dollar-weighted basis. Therefore, my recommended 53-year
16 ASL is conservative in favor of the Company.
17
18 Q. WHAT IS THE IMPACT OF YOUR RECOMMENDATION?
19 A. My recommended 53-R2 life-curve combination results in a $299,763 reduction to
20 depreciation expense based on plant as of December 31, 2008.
21
22 Account 391.2
23
24 Q. WHAT DOES THE COMPANY PROPOSE FOR ACCOUNT 391.2 - GENERAL
25 INFORMATION SYSTEMS?
26 A. The Company proposes a 5-SQ life-curve combination, or a 5-year amortization
27 period. 111

I 108
109
110
Response to Rose City 13-18.
Response to Rose City 1-41.
Response to Rose City 1-15 Addendum at page 149.
111
Exhibit JJS-1 page 53.

65
I Q. WHAT IS THE COMPANY'S BASIS FOR ITS PROPOSAL?
2 A. Mr. Spanos establishes the amortization period based on the anticipated life of the asset
3 over which benefits will be realized. u 2 The amortization period is based on ''judgment
4 which incorporates a consideration of the period during which the assets will render most
5 of their service, the amortization period and service lives used by other utilities and the
6 service life estimates previously used for the asset

[Text truncated at 120,000 characters. The full text is on the page linked above.]

---

Source: Frix Law Library, https://www.frixlaw.com/law-library/cases/4067257. Public record. Not legal advice.
